Final Narrative.pdf

PDF 357 KB Posted

Attached to
Y1DZ--589A4-21-700 EHRM Infrastructure Upgrades Construction Columbia, MO
Solicitation number
36C77622R0069
Issued by

About this file

This scope of work document outlines the requirements for an EHRM Infrastructure Upgrades Construction project at the Harry S. Truman Memorial Veterans Hospital in Columbia, Missouri. The contractor will provide all labor, materials, tools, equipment, and project management to upgrade the facilities' electric, HVAC, fiber, and IT network infrastructure to support a new Electronic Health Record Modernization system. Key work includes electrical panel upgrades, HVAC and communication infrastructure renovations, expansion of telecom and server rooms, installation of redundant fiber backbone between buildings, and replacement of legacy cabling with Category 6A. Environmental considerations like phasing of work and maintaining hospital operations are noted. The Department of Veterans Affairs Technology Acquisition Center in Austin is the contracting agency.

This file also includes a basis of design narrative describing technical requirements for fire protection, plumbing, mechanical, electrical, and security systems. Standards and guidelines are outlined for these building systems along with demolition and new construction scope. The level of detail in specifications and drawings will supersede information in this scope of work document.

View the file

Other files

File Type Posted
Answers to Technical Questions 7-15-22.pdf PDF
36C77622R0069 0007 Amendment 0007 7-15-22.pdf PDF
TERRACON ASBESTOS SURVEY Final Report-NESHAP Survey Report_updated as removed.pdf PDF
36C77622R0069 0006 Amendment 0006 7-7-2022.pdf PDF
Answers_Clarifications to Technical Questions 7-7-22.pdf PDF
Attachment A _Roof Plans_Site Layout.pdf PDF
Answers to Technical Questions 6-29-22.pdf PDF
36C77622R0069 0005 Amendment 0005 6-29-2022.pdf PDF
36C77622R0069 0004 Amendment 0004 6-27-2022.pdf PDF
36C77622R0069 0003 - Amendment 0003 - 6-22-2022.pdf PDF
36C77622R0069 0002 - Amendment 0002 - 6-16-2022.pdf PDF
Construction Wage Rates - Boone County - 5-27-22.pdf PDF
Site Visit Sign-In-Sheet 6-9-22.pdf PDF
36C77622R0069 0001 - Amendment 0001 - 6-9-22.pdf PDF
Attachment C - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Final Drawings_Part3.pdf PDF
Construction Wage Rates - Boone County - 4-22-22.pdf PDF
Attachment A - PPQ.docx DOCX document
Final Specifications-Vol 1_Rev2 - 3-28-22.pdf PDF
Attachment D - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment B - VHA Suppl. Contract Rqmnts for Combatting COVID-19 Updated 12-14-2021.pdf PDF
Final Specifications-Vol 2_Rev2 - 3-28-22.pdf PDF
Final Drawings_Part6.pdf PDF
Final Drawings_Part7.pdf PDF
Final Drawings_Part2.pdf PDF
Final Drawings_Part1.pdf PDF
36C77622R0069 Columbia EHRM Infra - 5-19-22.pdf PDF
Final Drawings_Part9.pdf PDF
Final Drawings_Part8.pdf PDF
Final Drawings_Part4.pdf PDF
Final Drawings_Part5.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HARRY S. TRUMAN MEMORIAL VETERAN’S HOSPITAL EHRM INFRASTRUCTURE UPGRADES

PROJECT #589A4-21-700

COLUMBIA, MO

1 | P a g e

Project 589A4-21-700

EHRM Infrastructure Upgrades – Columbia, MO

Construction Project Scope of Work

1. General Intent: Contractor shall completely prepare site for building operations, including demolition and removal of existing structures and furnish labor and materials and perform work as required by drawings and specifications.

2. Statement of Work: Contractor will provide all labor and material to facilitate a construction project to upgrade the facilities electric, HVAC, Fiber, and IT network to allow for the new Electronic Health Record Modernization (EHRM) system. The scope of this project includes but not limited to the following IT network infrastructure improvements: Electrical (electrical panel upgrade, power (normal, emergency)), Bonding, UPS, Building Management System interfaces, upgrades to existing HVAC, reconfiguration, expansion and renovation of existing space (demo, new construction, finishes), communication infrastructure (new data outlets, patch panels, upgrade to Cat 6A cable) in building as necessary, physical security upgrades, upgrade fiber infrastructure backbone campus wide within buildings and between buildings, install diversified path to data center for WAN, hazard material abatement. New redundant fiber installation from service provider entering westside of hospital and between data closets. Project buildings include: Buildings 1, 2, 14, 15, 22 and site.

3. Phasing: Medical Center must maintain operation 24 hours/day 7 days/week. Any service interruption must be scheduled and coordinated with COR ensuring no lapses in operation occur. It is the Contractor’s responsibility to develop a work plan and schedule detailing, at a minimum, procedures to be employed, equipment/materials to be used, interim life safety measures, and a schedule defining work duration with milestone subtasks.

4. Basis of Design Development Narrative (Technology / Low Voltage):

1. Overview

1.1. The Truman VA Medical Center is considered a Mission Critical Center.

1.2. The buildings included in the scope of the survey are Bldgs. 1, 2, 14, 15, and 22.

1.2.1. Building 1 is the main hospital.

1.2.2. Building 2 is the new Community Living Center and will be the diverse point of entry for services; the Second Entrance Room (ER).

1.2.3. Building 14 is the warehouse, which is contiguous to Building 1.

1.2.4. Building 15 is a Butler Building, which is being converted to a training room and will house a new TR for Building 22.

1.2.5. Building 22 is the engineering and administrative office. The building is modular type construction and is detached from Building 1.

1.3. The OIT Infrastructure Standard for Telecommunications Spaces, V3.1 is the basis of design including design alerts.

1.3.1. HEFP SOCAMES 6 Design Alert 1

1.3.2. SOCAMES 6 Design Alert 2

1.3.3. SOCAMES 6 Design Alert 3

1.3.4. HEFP SEP Design Alert 4

2 | P a g e

1.3.5. HEFP SEP Design Alert 5

1.3.6. HEFP SEP Design Alert 6

2. Data Center

2.1. The data center, a.k.a. Data Room or Main Computer Room, consists of a single row of cabinets mounted on raised floor. UPS systems and technician work areas are also housed in the Data Room.

2.1.1. The existing cabinets number approximately fourteen.

2.1.2. Four of the cabinets house network switches and fiber optic cable terminations.

2.1.3. Additional cabinets shall be required to house the new, diverse, redundant fiber backbone.

2.1.4. The new data center design will follow as closely as possible to the OIT standard for small data centers.

2.1.5. The existing data center, room D216, will be expanded into and take over room D209, to accommodate the additional racks needed for the diverse, redundant fiber optic backbone and UPS power.

2.1.6. Redundant fiber optic cable will be routed through overhead, 24” cable tray.

2.1.7. Analog circuits will be provided from PBX Room D208.

2.1.7.1. A Cat.5E, 100-pair cable will be routed through overhead cable tray to Cabinet #2 from the PBX room.

2.1.7.2. The cable will be terminated on two (2) Cat.5E, 48-port, patch panels at each end using 1-pair per each port.

2.1.8. Cabinets will be replaced with white cabinets configured in two rows aligned in a single column due to the long and narrow space.

2.1.8.1. Cabinets used as the basis of design are the following:

2.1.8.1.1. 24” wide cabinet; Chatsworth PN: FF1N-113C-E42-B

2.1.8.1.2. 40” wide cabinet; Chatsworth PN: NF8N-113N-C42-1

2.1.9. Cabinets will be fitted with vertical cable management fingers, air dams, sealing kits, cable grommets and brushes that are compatible with the Chatsworth cabinet.

2.1.10. Temperature and humidity will be monitored with sensors mounted in the cabinets using a remote infrastructure management system. The system controller will be connected to the existing BAS system using the MODBUS protocol or as directed by the COR.

2.1.10.1. The following components are used as the basis of design.

2.1.10.1.1. Chatsworth RIM-1000

2.1.10.1.2. Temperature sensor; Chatsworth PN: 60111-001

2.1.10.1.3. Temp/humidity sensor; Chatsworth PN: 60111-004

3. Entrance Room

3.1. There is currently one entrance room (ER) and point of demarcation for the incoming telecommunications services, located in Building 1, Basement Level, Room A060. Services enter from the north east portion of the property.

3.2. A new Community Living Center (CLC) is currently under construction on the northwest corner of the property.

3.2.1. Room K007 will become a second ER.

3.2.2. Telecommunication services will enter from the northwest portion of the property.

4. Telecom Rooms (TR)

4.1. Site Survey - The design team conducted a site survey of the four buildings and TRs.

3 | P a g e

4.1.1. According to the survey, TRs are not in compliance with the EHRM requirements.

Variances shall be required for TRs that cannot be expanded or practically relocated.

4.1.2. TRs do not stack vertically.

4.1.3. New or expanded TRs shall be required to provide the space required by the VA, OIT standards.

4.1.4. The design team used the VA Infrastructure Standard for Telecommunication Spaces, Version 3.1, dated July1, 2021 for this survey.

4.2. TR Fittings

4.2.1. Based on input received from the local OIT angled, high density, 1U, 48-place patch panels. Angled high density patch panels are the basis of design.

4.2.1.1. 48-place, 1U Patch Panel – Panduit, CPPA48HDWBLY

4.2.2. Based on input from the local OIT the high capacity, 2U, horizontal cable managers. High capacity, 2U horizontal cable managers shall be used as the basis of design.

4.2.2.1. High capacity, 2U – Panduit PEHF2

4.2.3. Based on observation of existing fire wall penetrations the Specified Technologies, EZ- Path system shall be used as the basis of design where fire stopping is required. The kits provide the device, wall plates, and labels. Series 33 and Series 22 may be substituted where necessary.

4.2.3.1. EZ Path Series 44+ kit, Specified Technologies, EZDP44S2

4.2.4. The existing 2-post racks will be replaced by channel racks. The Mighty Mo channel rack will be the basis of design.

4.2.4.1. Ortronics-Legrand, OR-MM2073038-W

4.3. Wall Field Equipment

4.3.1. Wall field equipment is to be left in place, unless otherwise note.

4.3.2. Telecommunications Bonding & Grounding – shall be installed according to TIA-607-D.

TIA-607-D shall be used as the basis of design.

5. Backbone Fiber Optic Cable

5.1. The existing fiber optic backbone consists of 62.5/125 and 50/125 multimode, OM-1, fiber optic cables are routed from the Bldg. 1 Data Room to each TR in Bldg. 1 and 14.

5.2. New fiber optic backbone for Side A and Side B shall be installed in phases. 50/125, OM4 multi mode and 9/125 OS2 single mode, OFNP, pre-terminated fiber optic trunk cable assemblies and MPO/LC cassettes shall be used as the basis of design.

5.2.1. Fiber optic trunk cable assembly, 24-strand, 50/125, OM4 multi mode, Method A, OFNP, Leviton FT-FM024LL(NNN)F36C36CY-NNAS; (NNN = length in feet)

5.2.2. Fiber optic cassette, 24-fiber, OM4 multi mode, MTP to shuttered Duplex-LC, Leviton

42LSM2-21C

5.2.3. Fiber optic cable, 24-strand, 9/125, OS2 single mode, Method A, OFNP, Leviton FT-

AW2024LL(NNN)F36B36BY-NNAS; (NNN = length in feet)

5.2.4. Fiber optic cassette, 24-fiber, OS2 single mode, MTP to shuttered Duplex-LC, Leviton

U2LSM2-21C

5.2.5. Fiber optic, flat, patch panel, accepts up to eight (8), HDX MTP cassettes, Leviton HDX1U-

F96

5.2.6. Fiber optic patch cable, 2-fiber, OM4, Standard A-B, LC to LC, aqua, Leviton PCF-

M3PD1RR-(NNN)0MAB; (NNN = length in feet)

5.2.7. Fiber optic patch cable, 2-fiber, OS2, Standard A-B, LC to LC, yellow, Leviton PCF-S2PD1RR-

(NNN)0MAB; (NNN = length in feet)

5.3. New Bldg. 1 pathways using existing multipurpose closets on floors to be cable chase for Size A.

4 | P a g e

5.3.1. Side A backbone to be phased in advance of Side B.

5.3.2. Where necessary, new core holes and sleeves shall be installed. The Contractor shall X-ray the floor and submit the results to the COR for approval prior to core drilling the floor.

5.3.3. Floor sleeves shall be an enclosed, fire rated pathway, 4”, rated for 100% fill. Where multiple sleeves are required, a floor frame or slot frame shall be used. The EZ Path Fire Rated Pathway shall be used as the basis of design.

5.3.3.1. EZ Path 44+, Specified Technologies, EZDP144FKS2

5.3.3.2. Floor frame, Specified Technologies, EZDG444S2

5.4. Existing pathways can be reused as Side A following demolition of the existing cabling.

5.4.1. Wire mesh type cable tray shall be installed to replace cable tray that does not have adequate capacity; maximum capacity at installation is 50% fill. Wire mesh, basket type cable tray shall have 4” sides, unless otherwise noted, and be ASTM coated. The Mono Systems wire mesh cable tray shall be used as the basis of design.

5.4.1.1. Straight section, 118” x XX” wide, Mono Systems TMX-4-118-XX

5.4.1.2. Tee fitting, Mono Systems TM4-HT-XX

5.4.1.3. Cross fitting, Mono Systems TM4-HC-XX

5.4.1.4. Horizontal bend fitting, Mono Systems TM4-HEXX-XX-RAD

5.4.1.5. Mono-mesh, strut trapeze, Mono Systems MM-P-TRPX

5.4.1.6. Speed splice, Mono Systems MM-CPL-SS

5.4.1.7. Conduit to tray adapter, Mono Systems TM-CTA-X

5.4.2. Media types shall not share the same cable tray. Cable trays shall have six (6) inches clearance between cablet trays.

5.4.3. Cable trays shall be joined using toolless joining kits.

5.4.4. Cable trays sections shall be bonded to one another and to the Supplemental Bonding

Network in accordance with TIA-607-D.

5.4.5. Existing cable trays that penetrate through a fire wall shall be fitted with an approved fire stop system. Cable tray penetrations shall be retrofitted with a device rated to 100% fill.

5.4.5.1. EZ Path 12” Cable Tray Retrofit Device, Specified Technologies EZCTR612

5.4.5.2. EZ Path 18” Cable Tray Retrofit Device, Specified Technologies EZCTR618

5.5. Non-continuous cable supports, J-hooks, may be used or re-used in places that cannot accommodate a cable tray.

5.5.1. New J-hooks shall have an integrated retaining clip.

5.5.1.1. J-hook, steel, 4”x3”, Monosystems, H-433-S

5.5.1.2. J-hook, steel, 2”x3”, Monosystems, H-433-S

5.6. Fiber backbone to Bldg. 15, which will serve Bldg. 22, shall require a variance.

5.6.1. Bldg. 15 is a Butler Building that is being repurposed to be a training facility with two rooms and a “Data Room” (TR) to serve Buildings 15 and 22. The two buildings are not attached.

5.6.2. The fiber backbone shall be extended from the Bldg. 1 Data Room to the Bldg. 15 TR utilizing existing pathway for Side A and through the Pipe Basement for Side B.

5.7. There is an existing 50/125, multimode, OM-4/5, fiber optic backbone that serves the patient services, such as Guest Wireless. This network is to be left in place.

6. Network Cabling

6.1. Legacy Category 5 and 5E cables, modular jacks, patch panels, and patch cables are to be replaced with Category 6A cables, modular jacks, patch panels, and patch cables. Panduit Category 6A cable and connectivity shall be used as the basis of design.

6.1.1. Category 6A Indoor Cable (CMP) - PUP6AHD04XX-G

5 | P a g e

6.1.2. Category 6A Indoor/Outdoor Cable - PUO6AS04BL-G

6.1.3. Category 6A Modular Jack – Panduit CJ6X88TGXX

6.1.4. Category 6A Modular Patch Panel – Panduit CPP48FMWBLY

6.1.5. Category 6A Patch Cables – Panduit UTP28X(L)(XX)

6.1.6. Faceplates, Single Gang, 3-place – Panduit CFPL3IXX

6.2. Existing Category 6 cable shall be left in place.

6.2.1. In a work area outlet, where a Category 6 jack shares a faceplate with a jack that is to be replaced, then the Category 6 jack shall be replaced with a matching jack.

6.2.2. Category 6 Modular Jack – Panduit, CJ688TGXX.

7. Voice Cables

7.1. Existing voice cables shall be left in place.

7.2. In a work area outlet, where a voice jack shares a faceplate with a network jack, then the voice jack shall be replaced with a Category 5e or better. Panduit connectivity shall be used as the basis of design.

7.2.1. Category 5E Modular Jack – Panduit, CJ5E88TGXX.

8. Special Conditions

8.1. Building 22/Building 15

8.1.1. Building 22 is a temporary type building and does not have a TR or TR cabinet as defined in the OIT Standards. Based on information from the local engineering staff, the TR in Building 15 will be used as the TR for Building 22 and Building 15.

8.1.2. Category 6A, horizontal cable shall be shielded, gel-filled, outside plant cable. Panduit –

PFO6X04BL-CEG

8.1.3. Category 6A shielded modular jacks shall be used to terminate the horizontal cable.

Panduit – CJS6X88TGY

8.1.4. Horizontal Category 6A cables shall be surge protected.

8.1.4.1. Work area outlet – Ditek DTK-110C6A

8.1.4.2. Telecom Room, rack mount, 24-port – Ditek DTK-RM24NETS

9. Other Low Voltage Systems

9.1. Other low voltage systems that use common pathways, such as existing cable trays and J-hooks, may need to be relocated or removed during installation. The Contractor may need to relocate wall mounted low voltage equipment as noted on the plans. The Contractor shall coordinate with the COR before beginning work in these effected areas.

9.1.1. Unless otherwise noted, low voltage systems not included in this scope of work include but may not be limited to the following.

9.1.1.1. Building automation controls

9.1.1.2. Electronic Security Systems

9.1.1.3. CATV

9.1.1.4. Distributed antenna system

9.1.1.5. Duress/personal safety systems

9.1.1.6. Guest/Patient systems

9.1.1.7. Infant protection systems

9.1.1.8. Nurse call

9.1.1.9. Paging or emergency evacuation systems

9.1.1.10. Patient wandering system

9.1.1.11. RTLS system

9.1.1.12. Voice telephone system

6 | P a g e

5. Basis of Design Development Narrative (Fire / Plumbing / Mechanical / Electrical / Security):

DIVISION 21 FIRE PROTECTION

1. GENERAL

A. The following design development narrative describes the requirements for the fire suppression systems for the EHRM Infrastructure Upgrades project at the Harry S. Truman Memorial Veterans Hospital based on our understanding of the project scope and applicable codes, criteria, and regulatory standards.

2. DESIGN STANDARDS, CRITERIA AND APPLICABLE CODES

A. VA OIT - Infrastructure Standard for Telecommunications Spaces, Version 3.1 B. VA Fire Protection Design Manual Version 8 June 1, 2021 C. 2019 National Fire Protection Code -NFPA 13, 2020 NFPA 75, and 2018 NFPA 2001 D. 2018 International Building Code (IBC)

3. DEMOLITION SCOPE

A. All existing piping wet fire suppression piping and sprinkler heads shall be reworked or removed as required to provide each new Tele Room with a code compliant system.

B. Where rooms are expanded to provide adequate space for equipment. cables, etc. sprinkler protection shall be reworked to provide a code compliant system within the new expanded area as well as immediately outside the expanded space.

C. Where openings have been created in walls and floors, openings shall be sealed. Openings in fire rated walls shall be provided with sleeves and openings shall be sealed with fire rated sealants.

D. Data Room D216 shall be provided with a new clean agent system above and below the raised floors if provided. Space for the new clean agent cylinders and release mechanism/controller shall be required.

E. Data Room D216, the existing wet sprinkler systems shall be reworked as to provide the room a separate control valve and flow switch for the room.

4. NEW SCOPE

A. All existing piping wet fire suppression piping and sprinkler heads shall be reworked or removed as required to provide each new Tele Room with a code compliant system.

B. Where rooms are expanded to provide adequate space for equipment. cables, etc. sprinkler protection shall be reworked to provide a code compliant system within the new expanded area as well as immediately outside the expanded space.

C. Data Room D216 shall be provided with a new clean agent system above and below the raised floors if provided. Space for the new clean agent cylinders and release mechanism/controller shall be required.

D. Data Room D216, the existing wet sprinkler systems shall be re-worked as to provide the room a separate control valve and flow switch for the room. Where openings have been created in walls and floors, openings shall be sealed. Openings in fire rated walls shall be provided with sleeves and openings shall be sealed with fire rated sealants.

7 | P a g e

DIVISION 22 PLUMBING

A. The following design development narrative describes the plumbing requirements for the EHRM Infrastructure Upgrades project at the Harry S. Truman Memorial Veterans Hospital based on our understanding of the project scope and applicable codes, criteria, and regulatory standards.

2. DESIGN STANDARDS AND APPLICABLE CODES

B. ASHRAE 90.1

C. VA Plumbing Design Manual D. International Plumbing Code E. (ASPE) American Society of Plumbing Engineers F. International Building Code (IBC)

A. All existing piping water piping shall be verified in each new Tele Room and Data/Server Room.

Determination whether the piping can be routed outside the new rooms. Where piping can be moved shall be routed outside the room and reconnected to existing. If piping cannot be moved drip pans and water sensors shall be installed to protection the room.

B. Where opens in fire rated walls have been created, the opens shall be sealed with appropriate sleeves and fire rated sealants.

A. Where it has been determined that the water piping within Tele Room and/or DATA/Server

Rooms can be re-routed outside, piping shall be cut re-routed and reconnected to existing piping. Insulation shall be installed on new piping and existing insulation that has been disturbed shall be replaced. Insulation shall meet ASHRAE 90.1. Existing piping that was re-routed shall be removed, including hangers and holes sealed.

B. Where opens in fire rated walls have been created, the opens shall be sealed with appropriate sleeves and fire rated sealants.

C. Data Equipment Room D216 shall be provided with new floor drain and water sensors below the raised floor. Floor drain shall be directly connected to a sanitary/waste pipe. Floor drain shall be provided with an electronic trap primer and deep seal trap.

DIVISION 23 MECHANICAL

A. The following design development narrative describes the mechanical system requirements for the EHRM Infrastructure Upgrades project at the Harry S. Truman Memorial Veterans Hospital based on our understanding of the project scope and applicable codes, criteria, and regulatory standards.

8 | P a g e

2. DESIGN CONDITIONS AND APPLICABLE CODES

B. VA HVAC Design Manual

C. ASHRAE 62.1, 2016

D. ASHRAE 90.1, 2013

E. Outdoor Design Conditions:

1. Summer: 94.7°F db / 75.7°F wb

2. Winter: 2.9°F

F. Indoor Design Conditions: 72°F (41°F to 95°F). 8% RH to 80% RH

A. All existing ductwork and piping that is just passing above the new TR space is to remain and will not be re-routed.

B. All variable air volume (VAV) units serving existing TR rooms will remain.

C. Room D216: Demolish computer room units (PAC-1 & 2), roof mounted condensing units, refrigerant piping, and associated ductwork in the space.

A. Install new split-system(s) for each new TR room. Locate condensing units on the roof of the building, unless noted otherwise on the drawings. Each split-system to be sized at 5kW (17,000 btu/hr) per IT rack in each TR room.

1. TR rooms with existing split DX systems will have the existing system removed and replaced with a larger system to comply with the current heat load requirements. (Rms C316, D198, E326)

2. Rooms with existing VAV terminal units will keep these units to operate as back-up to the new split DX system. (Rms 650, A060, A153A, A306A, C105, C358C, G050, G141)

3. Rooms with no existing cooling will be designed with a new split DX system only. (Rms 551, A213, E006, E139, E203)

B. Route refrigerant piping as shown on drawings. Install piping per specification 232300 and manufacturer’s recommendations.

C. Route condensate piping as shown on drawings to nearest existing TR condensate drain piping or nearby janitor’s sink.

D. All existing to remain piping shall have a catch pan below it to prevent water from dripping on the TR equipment. The catch pan shall have a drain connection that ties into the condensate drain. A water detector shall also be installed for each catch pan and tie into the BMS to notify the owner if a leak should occur.

E. Split-system indoor unit to be provided with temperature control modules. Wall mounted thermostat shall be provided with adjustable temperature set point and a start-stop switch.

F. Room D216:

1. Install (2) new, larger air conditioning units. The existing units are top discharge units that

9 | P a g e duct air to the server room. The new units will be up flow and the ductwork will be updated to supply air to the cold isle and return air from the hot isle. This room’s classification, per the OIT V3.1, requires that the HVAC systems have N+1 redundancy.

Therefore, two air conditioning units shall be in operation at a time, and one will be stand-

by. The BAS shall alternate primary and redundant units monthly. (3) three new condensing units will also be installed on the roof in the same location as the existing units.

G. All TR rooms will be designed to have rack temperature sensors.

H. All TR rooms will be designed to have a space humidity sensor used to monitor space humidity.

The TR rooms will not have the ability to actively control space humidity.

DIVISION 26 ELECTRICAL

A. The following design development narrative describes the mechanical system requirements for the

EHRM Infrastructure Upgrades project at Cincinnati and Ft. Thomas VA campuses based on our understanding of the project scope and applicable codes, criteria, and regulatory standards.

A. The electrical system will be in accordance with the following standards and design guidelines.

The specific requirements of these standards are not included in this document.

1. Infrastructure Standard for Telecommunication Spaces Version 3 (current revision).

2. NFPA 70 - National Electrical Code – 2020

3. NFPA 72 - National Fire Alarm and Signaling Code – 2019

4. NFPA 101 – Life Safety Code - 2018

5. NFPA 75 – Standard for the Fire Protection of Information Technology

Equipment - 2020

6. IESNA Illuminating Engineering Society of North American

7. International Building Code (IBC), 2018

8. National Electrical Manufacture’s Association (NEMA)

9. Federal Guidelines Institute Guidelines for the Design and Construction of

Healthcare Facilities

10. ASHRAE 90.1 Energy Standard for Buildings Except Low-Rise Residential Buildings

(IESNA Cosponsored) 2013

11. All applicable Federal, State, City and Local Codes, Regulations, Ordinances, Publications and Manuals

A. All the existing lights, devices and switches will be removed from the existing TR rooms. The existing circuits will be modified to be fed from the new panelboards withing the space.

Circuits transitioning through the space to devices not within the TR, will be modified and maintained as required for renovation.

10 | P a g e

A. Electrical Panel:

1. Each room will be provided with an emergency critical power panelboard and normal power panelboard.

a. The emergency panelboard source is from a critical power automatic transformer switch (ATS) feed by a level 1 EPS parallel generator system.

1) TR rooms that serve the hospital areas will be classified as critical equipment and the generator source will be from the critical generator branch.

b. The normal panelboard source is from the normal utility source distribution.

c. TR rooms that do not serve hospital areas will be feed from an available EPS generator branch.

d. The normal source for the normal panelboard and emergency panelboard will be from two different panelboard, switchboard, or switchgear.

e. The TR panelboards neutral bus will be sized 200% of current carrying bus.

f. The neutral conductor to all new TR panels from upstream panels will be up sized by one conductor size.

g. The TR panels will be 120/208/3ph/4w panels. The panel will be sized per the electrical demand.

h. Each panel in TR will be provide with main bus remote meter and remote surge protection device.

B. Lighting:

1. Each room will be provided with suspended LED 4000k, 80CRI+, strip fixture.

2. Light level will be an average of 40FC at 30”.

3. Ceiling mounted dual technology occupancy sensors will control lighting in the TR spaces.

Lighting will be turned on manually and turn off manually or automatic within 15 minutes of all occupants leaving the room or space.

C. TR Electrical Devices:

1. Receptacles, and power connections will be provided to meet the requirements of

Infrastructure Standard for Telecommunications Spaces. These devices will be circuited to the panel in the space. The neutral will be up sided by 1 size from panel to rack connection

(OIT 4.2.4).

a. 1 Rack PDU will be provided with one 20-amp 4w+G twist lock receptacle from the two panels in the room.

b. 2 Rack PDU will be provided with one 30-amp 4w+G twist lock receptacle from the two panels in the room.

c. 3 Rack PDU will be provided with one 60-amp 4w+G junction box with wipe to

PDU, from the two panels in the room.

d. When the room has more than 3 Racks, the above configurations will be used.

11 | P a g e

e. Each wall, in TR, will be provided with two duplex per wall (Legend sheet 2)

D. Server Room:

1. Server will have two 80KW UPS. The UPS is sized to maximize the existing 225-amp track busway. One UPS will be feed from the Critical branch and the other will be on the normal Branch. Both UPS will have a bypass switch.

2. The (3) CRAC units and associated condenser unit will be feed from the Equipment Branch.

3. One of the above (3) CRAC unit and associated condenser will be feed from a double throw switch so the unit could be powered from normal branch or equipment branch. The CRAC unit is located with in the server room. The double throw switch CRAC unit will shut down with EPO activations.

4. The existing 225-amp track busway will be reused to extend the new track busway. The existing 225-amp track busway was installed in late 2021. The two track busways will be feed from the UPS’s. One track busway will be feed from the critical UPS and the other track busway will be feed from the normal UPS.

a. The track busway will be provided with a L21-20R plug unit. Each rack will be provided with (1) plug unit from normal branch track busway and (1) plug unit from the critical branch track busway.

5. The server room will have (2) 100 amp 120/208v/3ph/4w panels. One on critical branch and the other on normal branch. These panels are for miscellaneous loads, lights, dry agent and EPO power.

6. The room will be provided with (2) emergency power off button (EPO) systems. Each system will have one button per door entering the space.

a. One EPO system will shut down the normal UPS, Normal 120v panel, and normal power side of the double through CRAC unit in the server room.

b. Other EPO system will shut down the critical UPS, critical 120v panel, and equipment power side of the double through CRAC unit in the server room.

7. Lights in server room will be controlled by an occupancy sensor. The sensor will turn the lights auto 30% on and auto off. The room will have manual 100% on during normal operations. The lights will turn on full bright during critical power branch power lose.

E. Fire Alarm (NFPA 72)

1. TR Rooms:

a. TR rooms that feed Hospital will be provided with smoke detection devices.

b. TR rooms with sprinkler pipe, will be provided with tamper and flow switches as required.

c. Fire alarm will monitor the activation of TR rooms when they have a clean agent suppression system. Currently, no TR rooms have or will have a clean agent system.

12 | P a g e

2. Server rooms (rating 2 and 3)

a. Server rooms will be provided with smoke detection devices.

1) Smoke detector will be provided above ceiling or below floor when the spaces are used for air flow.

b. Server room will be provided with tamper and flow switch for sprinkler system.

c. Fire alarm will monitor the activation of Server room clean agent suppression.

3. All new fire alarm wiring shall be class B and installed in conduit, assuming existing alarm structure is fire alarm wiring is class B

F. Other Electrical Items:

1. 120v circuit will be provided from the critical power panel for door security.

2. The mechanical equipment that services the TR space will be feed from the emergency critical power panelboard.

Distribution Equipment, and Branch Circuit Panelboards

A. The distribution panelboards and branch circuit panelboards will have copper phase, neutral and ground buses. Load centers will not be allowed and multi-section, such as double-section, panelboards will not be allowed. The maximum number of circuit breakers in a panelboard will not exceed 42. The neutral bus in each panelboard will be 200% fully rated and have an adequate number of terminals to accept one neutral conductor termination for each branch circuit. All circuit breakers will be bolt-on type and fully rated for the available short circuit fault current. Circuit breakers will be thermal-magnetic, except that fully adjustable electronic-trip circuit breakers will be used when necessary for fault and overcurrent coordination.

B. New transformers will have copper windings and be K13 rated.

C. See one-line diagram for a general system arrangement.

D. Each TR minimum panelboard requirement will be two dedicated electrical branch circuit breaker panelboards, 120/208v, 3-phase, 100 ampere main shunt trip circuit breaker, with 48 spaces.

Loads will include, but limited to, convenience receptacles, rack receptacles, HVAC (including split systems).

E. Distribution Equipment and Branch Panelboards with a significant number of nonlinear loads will have the neutral sized for the larger of either 1.73 times the phase conductor or one size larger than the phase conductor. The neutral feeding these panels will be counted as current carrying conductors.

Surge Protection Devices

A. Externally mounted Type 1 or Type 2 surge protective devices will be provided at the main distribution panelboard and as necessary, at panelboards serving electrically sensitive equipment.

13 | P a g e

Metering

A. Panelboards in TR rooms will be provided with meter.

B. Meters will be provided monitor load side of each existing ATS.

C. All meters will be monitored by the mechanical BAS system for kWH, Peak VA, and instantaneous VA.

Grounding and Bonding

A. The existing electrical system is grounded in accordance with the National Electrical Code.

B. An equipment grounding conductor will be routed with branch circuit and feeder conductors and bonded to a ground bus or ground lug at each end and in all pull boxes and cabinets.

Wiring Devices and Branch Circuits

A. Wiring devices and branch circuits will be provided for all equipment and areas as required in the scope of work. The convenience outlets will be heavy-duty specification grade, 20 ampere, 125 volt rated duplex devices, except where heavy duty hospital grade is required by NFPA requirements.

Wiring and Raceways

A. All wiring (120 volts and above) will consist of individual conductors run in raceway. All conductors will be copper. Conductor insulation will THHN-THWN or XHHW-2, as required for the application, with a minimum size of #12 AWG except for control wiring which may be #14 AWG and special systems such as public address will be minimum size as required by the respective manufacturer and other conditions such as voltage drop.

B. All interior conduits will be EMT and no smaller than ½-inch in diameter.

C. Flexible metal conduit will only be used for light fixture whips and connections to motors and other vibrating equipment; lengths will not exceed six feet. Liquid tight flexible metal conduit will be employed were exposed to moisture or outdoors. Flexible metal cables, including AC and MC cables, are prohibited.

D. All interior electrical equipment will be NEMA 1 construction.

DIVISION 28 SECURITY

A. The following design development narrative describes the security system requirements for the EHRM Infrastructure Upgrades project at Harry S. Truman Memorial Veteran’s Hospital campus based on our understanding of the project scope and applicable codes, criteria, and regulatory standards.

A. The security system will be in accordance with the following standards and design guidelines.

The specific requirements of these standards are not included in this document.

14 | P a g e

1. Infrastructure Standard for Telecommunication Spaces Version 3 (current revision).

2. NFPA 70 - National Electrical Code (NEC) - 2020

3. NFPA 72 - National Fire Alarm and Signaling Code – 2019

4. NFPA 101 – Life Safety Code - 2018

5. NFPA 75 – Standard for the Fire Protection of Information Technology

Equipment - 2020

6. International Building Code (IBC), 2018

7. Federal Guidelines Institute Guidelines for the Design and Construction of

Healthcare Facilities

8. All applicable Federal, State, City and Local Codes, Regulations, Ordinances, Publications and Manuals

A. All existing access control card readers on walls scheduled for demolition are to be removed back to source.

B. Any security lapse created by the removal of existing card readers is to be identified, and a security mitigation plan is to be implemented in order to maintain proper security within OIT spaces at all times.

A. Access Control:

1. Card readers to be placed at main entrance of all TRs and Server Rooms. Existing card readers shall remain in place unless otherwise noted. Access control system is an extension of the existing system. Door hardware to be coordinated with the architect.

Card Readers

A. Card readers shall be compatible with existing installed headend throughout the facility and be approved by owner prior to procurement.

Wiring and Raceways

A. Wiring shall be in accordance with NEC article 760, Specification Section 28 13 00, ACCESS CONTROL, and as recommended by the manufacturer of the access control system. All wires shall be color coded. Number and size of conductors shall be as recommended by the access control system manufacturer.

B. Any access control system wiring that extends outside of a building shall have additional power surge protection to protect equipment from physical damage and false signals due to lightning, voltage and current induced transients. Protection devices shall be shown on the submittal drawings and shall be UL listed or in accordance with written manufacturer's requirements.

C. All interior conduits will be EMT and no smaller than 3/4-inch in diameter.

Truman VA (Harry S. Truman Memorial Veterans’ Hospital)

800 Hospital Drive

Columbia, MO 65201

The above paragraphs constitute a basic outline of the work to be accomplished and in no way comprises all the details for construction of this project. Drawings and Specifications will supersede SOW / Narrative.