Final Drawings_Part2.pdf

PDF 18 MB Posted

Attached to
Y1DZ--589A4-21-700 EHRM Infrastructure Upgrades Construction Columbia, MO
Solicitation number
36C77622R0069
Issued by

About this file

This document provides details for a federal contract opportunity to complete EHRM Infrastructure Upgrades Construction work. The solicitation number is 36C77622R0069 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The contractor will be required to provide all labor, project management, materials, tools, supplies, and equipment as required by drawings and specifications to complete the necessary work for the EHRM Infrastructure Upgrades Construction project located in Columbia, MO. The related file referenced is the Final Drawings_Part2.pdf, but its content was not listed.

View the file

Other files

File Type Posted
Answers to Technical Questions 7-15-22.pdf PDF
36C77622R0069 0007 Amendment 0007 7-15-22.pdf PDF
TERRACON ASBESTOS SURVEY Final Report-NESHAP Survey Report_updated as removed.pdf PDF
36C77622R0069 0006 Amendment 0006 7-7-2022.pdf PDF
Answers_Clarifications to Technical Questions 7-7-22.pdf PDF
Attachment A _Roof Plans_Site Layout.pdf PDF
Answers to Technical Questions 6-29-22.pdf PDF
36C77622R0069 0005 Amendment 0005 6-29-2022.pdf PDF
36C77622R0069 0004 Amendment 0004 6-27-2022.pdf PDF
36C77622R0069 0003 - Amendment 0003 - 6-22-2022.pdf PDF
36C77622R0069 0002 - Amendment 0002 - 6-16-2022.pdf PDF
Construction Wage Rates - Boone County - 5-27-22.pdf PDF
Site Visit Sign-In-Sheet 6-9-22.pdf PDF
36C77622R0069 0001 - Amendment 0001 - 6-9-22.pdf PDF
Attachment C - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Final Drawings_Part3.pdf PDF
Construction Wage Rates - Boone County - 4-22-22.pdf PDF
Attachment A - PPQ.docx DOCX document
Final Specifications-Vol 1_Rev2 - 3-28-22.pdf PDF
Attachment D - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment B - VHA Suppl. Contract Rqmnts for Combatting COVID-19 Updated 12-14-2021.pdf PDF
Final Specifications-Vol 2_Rev2 - 3-28-22.pdf PDF
Final Drawings_Part6.pdf PDF
Final Drawings_Part7.pdf PDF
Final Drawings_Part1.pdf PDF
36C77622R0069 Columbia EHRM Infra - 5-19-22.pdf PDF
Final Drawings_Part9.pdf PDF
Final Drawings_Part8.pdf PDF
Final Narrative.pdf PDF
Final Drawings_Part4.pdf PDF
Final Drawings_Part5.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SOUND ATTENUATION

BATT INSULATION

5/8" 3 5/8" 5/8"

CONTINUOUS FIRE-RATED

SEALANT EACH SIDE

6"

2"

SOUND ATTENUATION

BATT INSULATION

5/8" 3 5/8" 5/8"

6" TYP. (UNO)

2"

5/8" FIRE-RATED GYPSUM BOARD

ON 3 5/8" METAL STUDS

4", 6" OR 8" CMU LINTEL HEADER

CMU W. + 1"

2"

EX. CMU

3/ 8"

4", 6" OR 8" CMU JAMB WITH

MINIMUM 3 MASONRY TYPE

ANCHORS

CMU W. + 1"

2"

EX. CMU

3/ 8"

1 DOOR HEAD

SCALE: 3" = 1'-0" 6 DOOR HEAD

SCALE: 3" = 1'-0"

7 DOOR JAMB

SCALE: 3" = 1'-0"2 DOOR JAMB

SCALE: 3" = 1'-0"

DOOR/FRAME ASSEMBLY

AS SCHEDULED

CONTINUOUS FIRE-RATED

SEALANT EACH SIDE

5/8" FIRE-RATED GYPSUM BOARD

ON 3 5/8" METAL STUDS

GROUT FILL SOLID

CONTINUOUS FIRE-RATED

SEALANT EACH SIDE

CONTINUOUS FIRE-RATED

SEALANT EACH SIDE

DOOR/FRAME ASSEMBLY

AS SCHEDULED

DOOR/FRAME ASSEMBLY

AS SCHEDULED

DOOR/FRAME ASSEMBLY

AS SCHEDULED

GROUT FILL SOLID

3 DOOR SILL

SCALE: FULL SIZE

4 DOOR SILL

SCALE: FULL SIZE

1 3/4"

1 3/4"

DOOR AS

SCHEDULED

DOOR AS

SCHEDULED

EXISTING

FLOORING

FLOOR AS

SCHEDULED

ROPPE #159

'BLACK' (B.O.D.)

DETAIL 'A'

DETAIL 'B'

FLOOR AS

SCHEDULED

ROPPE #59

'BLACK' (B.O.D.)

EXISTING

FLOORING

DOOR AS

SCHEDULED

FLOOR AS

SCHEDULED

FLOOR AS

SCHEDULED

MARBLE

THRESHOLD

4" MAX.

5 DOOR SILL

SCALE: FULL SIZE

DOOR AS

SCHEDULED

SET UNIT IN

FULL BED OF

MASTIC

ALUMINUM

THRESHOLD

PER HARDWARE

SCHEDULE

5"

3 JAMB ANCHORS MIN.

11 1/2" 11 1/2"

5/

8"

2"

6' -4

/8

H x

4' -1

0"

W

M

AS

O N

R Y

O

PN

G

6' -0

" H . x

'-7

" W

W

IN

D O

W O

PN

G

12 EXISTING WINDOW OPENING ENCLOSURE

SCALE: 3" = 1'-0"

1 1/2" 10"10"

15/16"

13 ELECTRIC SHAFT GRATE

SCALE: 3" = 1'-0"

SEE PLAN (FIELD VERIFY)

15/16"

3/4"

1'-0" W. x 3'-0" L.

11 1/4"

8 FLOOR STEP @ A060

SCALE: 3" = 1'-0"

5"

1 1/2"

4' -6

3"

1' -0

3'

-6

1' -4

10 RAISED FLOOR GUARDRAIL

SCALE: 3" = 1'-0"

26 WALL PROTECTION AT CBE5

27 WALL PROTECTION AT C1E9 & C2E10

28 WALL PROTECTION AT G191

29 WALL PROTECTION AT G191

30 WALL PROTECTION AT C176 & C178

PLASTIC

LAMINATE AT

TREAD AND

RISER

1" ALUMINUM

ANGLE AT

PERIMETER

2X WOOD

BLOCKING

3/4" 'AC' FACE

PLYWOOD

1 1/2" ROUND MILL

FINISH ALUMINUM

HORIZONTAL RAIL

1 1/2" SQUARE MILL

FINISH ALUMINUM

VERTICAL POST

(MIN. 3 EQUALLY

SPACED)

ALUMINUM BREAK

METAL TRIM

2"

4"

ALUMINUM BREAK

METAL TRIM

EXISTING RAISED

FLOOR SYSTEM AS

INDICATED BY

HATCH

2 X 4 WOOD NAILERS

BETWEEN FLOOR

SUPPORTS

ALUMINUM ANCHOR

PLATE AT EACH

VERTICAL POSTS

EXISTING MODULAR BRICK

VENEER WITH CMU

BACK-UP

EXISTING STEEL ANGLE

LINTELS

DEMOLITION RENOVATION

REMOVE EXISTING

CEILING ASSEMBLY AND

WOOD BLOCKING (AS

INDICATED BY HATCH)

REMOVE EXISTING

WINDOW ASSEMBLY

COMPLETE

REMOVE EXISTING SILL

PLASTER AND WOOD

BLOCKING (AS INDICATED

BY HATCH)

REMOVE EXISTING

HEATER UNIT

EXISTING PLASTER ON

FURRING CHANNELS

BACKER ROD AND

SEALANT AS INDICATED

MODULAR BRICK

TO MATCH EXISTING

(TOOTH-IN)

RIGID INSULATION

BOARD (MIN. 12.5

R-VALUE)

W/FULLY SEALED

JOINTS

4" CMU INFILL -

FULLY DAMPROOFED

MIN. 3/4" PLASTER

OVER METAL LATH

ON 7/8" FURRING

CHANNELS

ADJUSTABLE

MASONRY ANCHOR

EXISTING PLASTER AT

JAMBS TO REMAIN

MIN. STL. L4x3x1/4"

W/ANCHOR BOLTS

@ 18" O.C. MAX.

(EA. SIDE AS

SHOWN)

EXISTING CMU

WALL EXISTING DOOR

SILL CAN REMAIN

GALVANIZED STEEL

GRATE (McNICHOLS

GW-200 B.O.D.)

EQ

U

AL

EQ

U

AL

6"

NOTE: FIELD CUT GRATE CONDUIT

OPENINGS.

22 EXISTING WALL PANEL @ C1E9 & C2E10

23 EXISTING WALL PANEL @ C1E9 & C2E10

AS-710

DOOR & MISCELLANEOUS DETAILS

IAR

IAR, JFB

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

ETS

T

TA

GE

S

R I

E T E X

FO

T

CE

TI

H

AS

DER CRA

F. BIAN

C

OJ

O

SE

P

H

7 6 22 1

1/25/2022 8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

3 5/8" STUD (NON-RATED)

4 7/8"+

3 5/8" STUD (1-HR FIRE-RATED, UL NO 465)

CONTINUOUS METAL

TRACK

CONTINUOUS FIRE RATED

SEALANT (ACOUSTICAL

SEALANT AT 1A)

3 5/8" 22 GAGE METAL

STUD FRAMING AT 16" O.C.

SOUND ATTENUATION

BATT INSULATION

LINE OF STRUCTURE

DECK UNDERSIDE

CONTINUOUS FIRE RATED

SEALANT BOTH SIDES (ACOUSTICAL

SEALANT AT 1A)

3 5/8" STUD (NON-RATED)

4 7/8"+

CONTINUOUS METAL

DEFLECTION TRACK

CEILING AS SCHEDULED

BASE AS

SCHEDULED

5/8" FIRE RATED GYPSUM BOARD

BOTH SIDES TO STRUCTURE

DECK UNDERSIDE (PROVIDE

REGULAR GYPSUM BOARD

AT 1A)

WAINSCOT (AS SCHEDULED)

EXISTING METAL STUD

FRAMED WALL W/ FIRE RATED

GYPSUM BOARD TO FULL

HEIGHT EACH SIDE (ACOUSTICAL

SEALANT AT 3A)

3 5/8" STUD (EXISTING PRESUMED 1 HR.)

4 7/8"±

FINISH W/5/8" FIRE RATED GYPSUM

BOARD BOTH SIDES TO STRUCTURE

DECK UNDERSIDE (WHERE REQUIRED)

1 PARTITION TYPES

SCALE: NTS

1A

2 3

CONTINUOUS METAL

TRACK

SOUND ATTENUATION

BATT INSULATION

LINE OF STRUCTURE

DECK UNDERSIDE

CONTINUOUS METAL

DEFLECTION TRACK

BASE AS

SCHEDULED

CONTINUOUS ACOUSTICAL

SEALANT

3 5/8" 22 GAGE METAL

STUD FRAMING AT 16" O.C.

5/8" GYPSUM BOARD

BOTH SIDES TO STRUCTURE

DECK UNDERSIDE

CEILING AS SCHEDULED

CONTINUOUS ACOUSTICAL

SEALANT BOTH SIDES

LINE OF STRUCTURE

DECK UNDERSIDE

CONTINUOUS FIRE RATED

SEALANT BOTH SIDES (TOP AND

BOTTOM OF WALL) ACOUSTICAL

SEALANT AT 3A

BASE AS

SCHEDULED

3 5/8" STUD (EXISTING NON-RATED)3A

4" CMU (EXISTING PRESUMED 1 HR.)

3 5/8"

LINE OF STRUCTURE

DECK UNDERSIDE

CONTINUOUS FIRE RATED

SEALANT BOTH SIDES (TOP AND

BOTTOM OF WALL)

BASE AS

SCHEDULED

EXISTING CMU WALL EXISTING METAL STUD

FRAMED WALL W/ FIRE RATED

GYPSUM BOARD (2 LAYERS)

3 5/8" STUD (EXISTING PRESUMED 2 HR.)

6 1/8"±

LINE OF STRUCTURE

DECK UNDERSIDE

CONTINUOUS FIRE RATED

SEALANT BOTH SIDES (TOP AND

BOTTOM OF WALL)

BASE AS

SCHEDULED

EXISTING METAL STUD

FRAMED WALL W/ FIRE RATED

GYPSUM BOARD (2 LAYERS)

3 5/8" STUD (EXISTING NON-RATED)

4 1/4"±

LINE OF STRUCTURE

DECK UNDERSIDE

CONTINUOUS SEALANT BOTH

SIDES (TOP AND BOTTOM OF

WALL)

BASE AS

SCHEDULED

AS-720

PARTITION TYPES

IAR

IAR, JFB

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

ETS

T

TA

GE

S

R I

E T E X

FO

T

CE

TI

H

AS

DER CRA

F. BIAN

C

OJ

O

SE

P

H

7 6 22 1

1/25/2022 8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

AC ABOVE COUNTER

A.F.F. ABOVE FINISHED FLOOR

A.F.G. ABOVE FINISHED GRADE

AER AERIAL

A.W.G. AMERICAN WIRE GAUGE

CC CONTRACTOR FURNISHED AND INSTALLED

CER CABLE ENTRANCE ROOM (ER NOT USED IN HEALTHCARE)

CLG ABOVE CEILING

CMP COMMUNICATIONS MULTIPURPOSE CABLE, PLENUM

CMR COMMUNICATIONS MULTIPURPOSE CABLE, RISER

C.O.R. CONTRACT OFFICER REPRESENTATIVE

DEMARC DEMARCATION POINT

DEMO DEMOLITION

DIAG DIAGRAM

DISTR DISTRIBUTION

(E) EXISTING

EMT ELECTRIC METAL TUBING

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATION

EMER EMERGENCY

F.O.C. FIBER OPTIC CABLE

GFE GOVERNMENT FURNISHED EQUIPMENT

GFCI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED (VC)

GFGI GOVERNMENT FURNISHED AND INSTALLED (VV)

GIP GALVANIZED IRON PIPE

GTB GROUND TERMINAL BOX

HE HEAD-END (PA, INTERCOM)

HDPE HIGH DENSITY POLYETHYLENE

IMC INTERMEDIATE METAL CONDUIT

ISP INSIDE CABLE PLANT

IDF INTERMEDIATE DISTRIBUTION FRAME (NOT USED)

-BOX JUNCTION BOX

MDF MAIN DISTRIBUTION FRAME (NOT USED)

MH MAINTENANCE HOLE (FORMERLY MANHOLE)

MM MULTI MODE

N/A NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

N NEUTRAL

N.I.C. NOT IN CONTRACT

N.T.S. NOT TO SCALE

OFCP OPTICAL FIBER CONDUCTIVE, PLENUM

OFCR OPTICAL FIBER CONDUCTIVE, RISER

OFNP OPTICAL FIBER NONCONDUCTIVE, PLENUM

OFNR OPTICAL FIBER NONCONDUCTIVE, RISER

OSP OUTSIDE CABLE PLANT

PB PULL BOX

PR PAIR

PVC POLYVINYL CHLORIDE

RSC RIGID STEEL CONDUIT

SM SINGLE MODE

SP SERVICE PROVIDER

STD STANDARD

STP SHIELDED TWISTED PAIR

TB TERMINAL BLOCK

TR TELECOMMUNICATIONS ROOM

TYP TYPICAL

TZ TELECOMMUNICATIONS ZONE

UG UNDERGROUND

UGC UNDERGROUND COMMUNICATIONS CABLE

UON UNLESS OTHERWISE NOTED

UTP UNSHIELDED TWISTED PAIR

VC GOVERNMENT FURNISHED, CONTRACTOR INSTALLED (GFCI)

VV GOVERNMENT FURNISHED AND INSTALLED (GFGI)

WP WEATHERPROOF

1. GENERAL CONSTRUCTION

1.1. DEMOLITION

1.1.1. THE CONTRACTOR SHALL COORDINATE WITH THE C.O.R. TO MAKE SAFE ALL

THAT WILL NOT BE REMOVED DURING DEMOLITION.

1.1.2. EXISTING CABLES, MODULAR JACKS, FACEPLATES, AND PATCH CABLES MAY

NOT BE REMOVED UNTIL AFTER CUT-OVER TO THE NEW CABLE SYSTEM IS

COMPLETE. CUT-OVER MAY BE BY ZONE, FLOOR, BUILDING, ETC. AND SHALL BE

COORDINATED WITH THE C.O.R. PRIOR TO WORK BEING PERFORMED.

1.1.3. EXISTING PATCH PANELS, PATCH CABLES, EQUIPMENT RACKS, ETC., MAY BE

"FLOATED" DURING CONSTRUCTION AND REMOVED AFTER CUT-OVER IS

COMPLETE.

1.2. CONSTRUCTION

1.1.1. CONTRACTOR SHALL INSTALL AND "BUILD-OUT" TR EQUIPMENT RACKS, CABLE

TRAYS, AND FITTINGS TO THE EXTENT POSSIBLE. FINAL INSTALLATION MAY NOT

BE COMPLETE UNTIL AFTER FINAL CUT-OVER OF THE CONSTRUCTION AREA IS

COMPLETE.

1.1.2. INSTALL FIBER OPTIC BACKBONE RISER CABLES TO THE TR(S) IN

CONSTRUCTION AREA.

1.1.3. INSTALL HORIZONTAL CATEGORY 6A CABLES FROM WORK AREAS TO THE TR(S)

IN THE CONSTRUCTION AREA.

1.1.4. CONTRACTOR SHALL TEST AND CERTIFY 100% OF INSTALLED HORIZONTAL

CABLES.

2. DATA CENTER CONSTRUCTION

2.1. DEMOLITION

2.1.1. REMOVAL OF EXISTING CABINETS AND ABANDONED CABLING WILL FOLLOW

CUT-OVER TO NEW CABLE SYSTEMS AND RELOCATION OF EQUIPMENTS TO NEW

CABINETS.

2.1.2. CONTRACTOR WILL REMOVE "OLD CABINETS" AS THEY ARE EMPTIED.

2.1.3. "OLD" CABINETS WILL BE MOVED TO A STAGING AREA FOR DISPOSAL. THE

CONTRACTOR SHALL COORDINATE WITH THE C.O.R. PRIOR TO BEGINNING

WORK.

2.2. CONSTRUCTION

2.2.1. CONTRACTOR SHALL INSTALL CABINETS, EQUIPMENT RACKS, CABLE TRAYS

AND FITTINGS.

2.2.2. CONTRACTOR SHALL INSTALL BACKBONE CABLES FROM THE TR(S).

2.2.3. CONTRACTOR SHALL TEST AND CERTIFY 100% OF BACKBONE CABLE.

2.2.4. CONTRACTOR SHALL PROVIDE FIBER OPTIC PATCH CABLES PRIOR TO MOVING

EQUIPMENT TO NEW CABINETS.

3. CLOSEOUT (COMMISSIONING)

3.0.1. CONTRACTOR SHALL PERFORM TESTING AND CERTIFICATION IN ACCORDANCE

WITH SPECIFICATION 27 08 00.

3.0.2. CONTRACTOR SHALL PROVIDE TEST DOCUMENTATION AND AS-BUILT DRAWINGS

AS SPECIFIED.

1. THE CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS INCLUDING THE DRAWINGS AND SPECIFICATIONS.

2. THE CONTRACTOR SHALL COMPLETE ALL WORK INCLUDED IN THE CONTRACT DOCUMENTS.

3. THE CONTRACTOR SHALL PHYSICALLY SURVEY AND VERIFY EXISTING CONDITIONS PRIOR TO STARTING CONSTRUCTION TO MINIMIZE UNFORESEEN CONDITIONS.

4. THE SCALE OF DRAWINGS IS PROVIDED AS A REFERENCE. THE CONTRACTOR IS RESPONSIBLE FOR CABLE LENGTHS, PATHWAY SIZING, DIMENSIONS, MEASUREMENTS, QUANTITIES, ETC.

5. THE CONTRACTOR SHALL COORDINATE AND VERIFY ALL ITEMS OF CASEWORK, CEILINGS, AND MILLWORK.

6. CONDUIT, CABLE TRAY, J-HOOKS, AND OTHER CABLE SUPPORTS ARE SHOWN IN APPROXIMATE LOCATIONS. CONTRACTOR SHALL COORDINATE WITH OTHER TRADES PRIOR TO INSTALLATION.

7. DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS AND SPECIFICATIONS SHALL BE CALLED TO THE ATTENTION OF THE DESIGN TEAM. DISCREPANCIES OR CONFLICTS BETWEEN THE DRAWINGS AND SPECIFICATIONS NOT CALLED TO THE ATTENTION OF THE DESIGN TEAM SHALL BE DEEMED TO HAVE BEEN RESOLVED WITHIN THE BID OR PROPOSAL AND THE CONTRACTOR SHALL PERFORM THE WORK IN THE IN THE MANNER, GREATER QUANTITY, BETTER QUALITY, IN ACCORDANCE WITH THE DESIGN TEAM'S INTERPRETATION.

GENERAL NOTES

TELECOMMUNICATION - GENERAL INFORMATION

ABBREVATIONS PHASING PLAN

LEGEND

T-001

TELECOMMUNICATIONS

GENERAL INFORMATION

RMJr

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

DATA OUTLET; LETTER INDICATES AS FOLLOWS:

N = JACK QUANTITY

COMBINED VOICE&DATA OUTLET; LETTER INDICATES AS FOLLOWS:

N = JACK QUANTITY

FLOOR BOX - OVER-COUNTER; LETTER INDICATES AS FOLLOWS:

N = JACK QUANTITY

DATA OUTLET - CEILING MOUNTED; LETTER INDICATES AS FOLLOWS:

N = JACK QUANTITY

WIRELESS ACCESS POINT

EZ PATH FIRESTOP PENETRATION

ELECTRICAL PANEL BOARD.

TMGB - TELECOM MAIN GROUND BUS BAR

BASKET CABLE TRAY

NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER TOP

NURSE CALL TERMINAL CABINET

NURSE CALL STATION.

2= DUPLICATE FACILITIES FOR TWO BEDS.

D= DUTY STATION.

E= MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF FOR TUB LOCATION,

MTD 3'-0" AFF FOR TOILET LOCATION.

P= PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH.

S= AUDIO VISUAL MALL STATION MTD 5'-0" AFF UNLESS OTHERWISE NOTED.

U= UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE NOTED.

NURSE CALL STATION.

2= NURSE'S CALL DOME LIGHT. MTD 6" ABOVE DOOR.

D= CORRIDOR DOME LIGHT.

I= AUXILIARY INTERSECTIONAL DOME LIGHT.

TELEPHONE TERMINAL CABINET

TELEPHONE BACKBOARD (WALL MOUNTED)

N

N

N

N

25-JAN-22

RESPONSIBILITY MATRIX CF/CI -

DIV 27/28

CF/CI -

DIV 26 GFE/CI GF/GI GO/GRI GC

CATV N/A

Intercom System N/A Neutral Host - Distributed Antenna System Antennas (DAS) N/A Nurse Call System N/A Neon Coding N/A Patient Wandering System Devices N/A Public Address/Overhead Paging Speakers N/A Physical Security - Acess Controls (EXISTING) X Physical Security - Acess Controls (NEW) X RTLS (CenTraK) N/A Telecommunications Infrastructure Plant (TIP) X Telecom Room Equipment Fittings X Telecom Room Electrical & Lighting X Telecommunications Equipment Backboard - fire retardant plywood, fire retardant paint X

Telecommunications Pathway - cable tray, conduits, bushings, back-boxes, fittings X

Telecommunications Room Equipment Bonding X Telecommunications Grounding & Bonding - bus bars, ground conductor, backbone conductor X

TV Monitors N/A Video Surveillance Cameras N/A Wireless Network - VA Internal WLAN (WAPs) X Wireless Network - Patient Network WLAN (WAPs) X

* GC = General Contractor Furnished/General Contractor Installed

* CF/CI = Contractor Furnished/Contractor Installed

* GFE/CI = Government Furnished Equipment/Contractor Installed

* GF/GI = Government Furnished/Government Installed

* GO/GRI = Government Owned (Existing)/Government Removed and Installed

* X = Responsible

* NIC = Not In Contract

* N/A = Not Applicable to this scope of work or no systems currently installed.

PREFERRED PRODUCTS MATRIX

LINE DESCRIPTION MANUFACTURE PART NUMBER LINE DESCRIPTION MANUFACTURE PART NUMBER

01 Copper Connectivity 47 Cable support, steel, J-hook, 2"x3", integrated retainer clip, galvanzied MonoSystems H-233-S 02 Cable, UTP, CMP, Category 6, 4-pair, white Panduit PUP6504WH-UY 48 Center hanger bracket, steel, galvanized MonoSystems H-433-H 03 Cable, UTP, CMP, Category 6A, 4-pair, green Panduit PUP6AS04GR-G 49 Cable tray, "J-Tray", solid aluminum, 2-7/8"x 1-7/8"x10' MonoSystems H-433-AB 04 Cable, UTP, CMP, Category 6A, 4-pair, orange Panduit PUP6AS04OR-G 50 Cover, "J-Tray", solid aluminum MonoSystems H-433-AC 05 Cable, UTP, CMP, Category 6A, 4-pair, blue Panduit PUP6AS04BU-G 51 Threaded rod, 3/8"x6' Chatsworth 11440-001 06 Cable, UTP, CMP, Category 6A, 4-pair, pink CommScope UN874040614/10 52 Grounding & Bonding 07 Patch cable, UTP, CMP, Category 6, 4-pair, white, 6 ft. Panduit UTPSP6Y 53 Ground bus bar, TMGB, 2"x20" Chatsworth 40153-020 08 Patch cable, UTP, CMP, Category 6A, 4-pair, green, 6 ft. Panduit UTP6ASD6GR 54 Ground bus bar, TGB, 2"x12" Chatsworth 13622-212 09 Patch cable, UTP, CMP, Category 6A, 4-pair, orange, 6 ft. Panduit UTP6ASD6OR 55 Ground terminal block, 1-mounting hole Chatsworth 08009-001 10 Patch cable, UTP, CMP, Category 6A, 4-pair, blue, 6 ft. Panduit UTP6ASD6BU 56 Ground lug connector, compression type, #6 gauge Burndy YGA6C2TC38E2G1

11 Patch cable, UTP, CMP, Category 6, 4-pair, white, 10 ft. Panduit UTPSP10Y 57 Copper-to-Copper Antioxidant Joint Compound Chatsworth 40168-801 12 Patch cable, UTP, CMP, Category 6A, 4-pair, green, 10 ft. Panduit UTP6A10GR 58 Ground lug connector, compression type, #6 gauge Burndy YGA6C2TC38E2G1

13 Patch cable, UTP, CMP, Category 6A, 4-pair, orange, 10 ft. Panduit UTP6ASD10OR 59 Copper-to-Copper Antioxidant Joint Compound Chatsworth 40168-801 14 Patch cable, UTP, CMP, Category 6A, 4-pair, blue, 10 ft. Panduit UTP6ASD10BU 60 Telecom Room Fittings 15 Modular jack, Category 6, Mini-Com, 8P/8C, white Panduit CJ688TGWH 61 Equipment rack, Mighty Mo 20® Channel Racks, black Legrand OR-MM20730-B 16 Modular jack, Category 6A, Mini-Com, 8P/8C, green Panduit CJ6X88TGGR 62 Rack installation kit, concrete, 1/2" Chatsworth 40604-003 17 Modular jack, Category 6A, Mini-Com, 8P/8C, orange Panduit CJ6X88TGOR 63 Mounting plate, rack to runway, with bracket, 15-18", black Chatsworth 12730-718 18 Modular jack, Category 6A, Mini-Com, 8P/8C, blue Panduit CJ6X88TGBU 64 Cable runway, UL Classified, 18", 1-1/2"x3/8" stringers, black Chatsworth 11275-718 19 Modular jack, Category 6A, Mini-Com, 8P/8C, black Panduit CJ6X88TGBL 65 Cable runway, E-Bend, 18", 1-1/2"x3/8" stringers, black Chatsworth 10822-718 20 Modular jack, Category 6A, Mini-Com, 8P/8C, red Panduit CJ6X88TGRD 66 Radius drop, cross member Chatsworth 14304-718 21 Faceplate, wall phone, Category 6, stainless steel, 1-P, 1-gang Panduit KWP6PYY 67 Cross member, movable, 18", black Chatsworth 12115-718 22 Faceplate, Mini-Com, white, 1-P, 1-gang Panduit CFPL1WHY 68 Butt splice, UL Classified, 1-1/2"x3/8" stringer, black Chatsworth 16301-701 23 Faceplate, Mini-Com, white, 4-P, 1-gang Panduit CFPL4WHY 69 Junction splice, UL Classified, 1-1/2"x3/8" stringer, black Chatsworth 16302-701 24 Faceplate, Mini-Com, stainless steel, 8-P, 2-gang Panduit CFPL6S-2GY 70 Butt swivel splice, UL Classified, 1-1/2"x3/8" stringer, black Chatsworth 16487-701 25 Surface mount box, Mini-Com, white, 2-P Panduit CBX2WH-AY 71 Junction swivel splice, UL Classified, 1-1/2"x3/8" stringer, black Chatsworth 16488-701 26 Patch panel, angled, modular jack, with strian relief bar, 24-P, 1U Panduit CPPLA24WBLY 72 Vertical swivel splice, UL Classified, 1-1/2"x3/8" stringer, black Chatsworth 16489-701 27 Patch panel, angled, high density, modular jack, 48-P, 1U Panduit CPPA48HDWBLY 73 Triangular support bracket, aluminum Chatsworth 11312-718 28 Fiber Optic Connectivity 74 Threaded ceiling kit, 3/8" rod Chatsworth 11310-001 29 Cable, fiber optic, interlocking armor, OFCP, 9/125, SM OS2, 12-strand, yellow, pre-term 12F MPO * Leviton FT-AK012KK999F36C36CY-NNAS 75 Network cabinet, Gen 3 cabinet, 45U x 40" x 43.3", perf. 2-door front/rear, sq. punch rails, glacier white Chatsworth NF8N-113N-C42-1

30 Cable, fiber optic, interlocking armor, OFCP, 50/125, MM OM4, 24-strand, aqua, pre-term 12F MPO * Leviton FT-FK024KK999F36C36CY-NNAS

76 Server cabinet, Gen 3 cabinet, 45U x 23.6" x 43.3", perf. dbl-door front/rear, sq. punch rails, glacier white Chatsworth FF1N-113C-E42-B

31 Patch cable, fiber optic, OFNP, 9/125, SM OS-2, duplex LC, type A/A, yellow * Leviton PCF-S2PD1RR-0100MAA 77 Threaded rod cover Chatsworth 11085-001 32 Patch cable, fiber optic, OFNP, 9/125, SM OS-2, duplex LC, type A/B, yellow * Leviton PCF-S2PD1RR-0100MAB 78 Threaded rod, 3/8"x6' Chatsworth 11440-001 33 Patch cable, fiber optic, OFNP, 50/125, MM OM-4, duplex LC, type A/A, aqua * Leviton PCF-M4PD1RR-0100MAA 79 Hardware, hex nut, 3/8"-16 Chatsworth 20142-091

34 Patch cable, fiber optic, OFNP, 50/125, MM OM-4, duplex LC, type A/B, aqua * Leviton PCF-M4PD1RR-0100MAB 80 Hardware, split lock washer, 3/8" Chatsworth 20141-090 35 Cassette, 12-fiber, 9/125, single mode OS2, 1x12F MTP, shuttered duplex LC, universal polarity, blue Leviton FM-A012CSAC0U 81 Hardware,flat washer, wide, 3/8" Chatsworth 04002-002

36 Cassette, 24-fiber, 50/125, multi mode OM4, 2x12F MTP, shuttered duplex LC, universal polarity, aqua Leviton FM-F024CSAC0U

82 Hardware,flat washer, narrow, 3/8" Chatsworth 20283-113

37 Enclosure, fiber optic, (12) SDX MTP cassettes, 19"x4U Leviton 5R4UH-W12 38 Enclosure, fiber optic, (3) SDX MTP cassettes, 19"x1U Leviton 5R1UH-W03 39 Pathways 40 Cable tray, wire mesh, 12"x4" MonoSystems MM4-12-118 41 Adaptor, conduit to tray MonoSystems MM-CTA-X 42 Ground lug, split bolt MonoSystems MM-GL-IK2 43 Splice bolt assembly MonoSystems TM-CPL-JN3 * CONTRACTOR SHALL DETERMINE PART NUMBER BASED ON LENGTH REQUIRED FOR EACH ITEM PRIOR TO

ORDERING

44 Support strut, 12" tray, pre-galvanized MonoSystems MM-P-TRP-12 45 Retaining clip MonoSystems MM-CPL-KBT 46 Cable support, steel, J-hook, 4"x3", integrated retainer clip, galvanzied MonoSystems H-433-S

1 RESPONSIBILITY MATRIX

SCALE: N.T.S. 2 PREFERRED PRODUCTS MATRIX

SCALE: N.T.S.

SHEET NOTES:

1. MATERIALS SHOWN IN THE "PREFERRED PRODUCTS MATRIX ARE THE BASIS OF DESIGN AND ARE COMPATIBLE WITH EXISTING CONDITIONS. EQUIVALENT

PRODUCTS MAY BE SUBMITTED FOR APPROVAL.

2. CONTRACTOR IS RESPONSIBLE FOR DETERMINING QUANTITIES, LENGTH, DISTANCES, COLOR, AND OTHER DETAILS.

3 CABLE SCHEDULE

SCALE: N.T.S.

CABLE SCHEDULE

DESCRIPTION CABLE TYPE UL LISTING PERFORMANCE CABLE COLOR STRANDS/PAIRS CABLE CONFIG. OUTLET COLOR

VOICE (EXISTING) UTP CMP EXISTING WHITE 4-PAIR WHITE

DATA UTP CMP CATEGORY 6A BLUE 4-PAIR BLUE/ORANGE

WIRELESS LAN UTP CMP CATEGORY 6A GREEN 4-PAIR ORANGE

SECURITY (EXISTING) UTP CMP EXISTING PURPLE (VIOLET) 4-PAIR ORANGE

GET WELL (EXISTING) UTP CMP EXISTING BROWN 4-PAIR ORANGE

GUEST WIFI (EXISTING) UTP CMP EXISTING PINK 4-PAIR ORANGE

MM - DATA RISER 50/125 OFCP* MULTI MODE AQUA 24-STRAND TIGHT BUFFER AQUA-DUPLEX LC

SM - DATA RISER 9/125 OFCP* SINGLE MODE YELLOW 24-STRAND TIGHT BUFFER BLACK-DUPLEX LC

SM - DATA RISER - OSP 9/125 OFNR** SINGLE MODE BLACK 24-STRAND LOOSE TUBE BLACK-DUPLEX LC

* INTERLOCKING ARMORED CABLE, UL LISTED OFCP FOR USE IN PLENUM SPACES.

** ALL DIELECTRIC, NON-CONDUCTING, INDOOR/OUTDOOR CABLE, UL LISTED OFNR FOR USE IN NON-PLENUM, RISER SPACES.

SCHEDULE NOTES:

1. CABLE CONNECTORS, FACEPLATES, MODULAR JACKS, PATCH CABLES, AND PATCH PANELS SHALL BE A SINGLE MANUFACTURER, SUCH AS HUBBELL OR PANDUIT.

2. CATEOGORY 6A TELECOMMUNICATIONS OUTLETS AND PATCH PANELS OUTLETS TO BE TERMINATED T568B

3. PREFERRED CABLE AND CONNECTIVITY MANUFACTURER IS PANDUIT

4. EXISTING CABLES SHALL NOT BE REMOVED DURING DEMOLITION. RE-TERMINATE ON NEW PATCH PANEL. COORIDINATE WITH COR FOR PLACEMENT.

4 TR ZONE SCHEDULE

SCALE: N.T.S.

TR ZONE TR ROOM NO. BLDG. FLOOR/LEVEL

1 A060A 1 BASEMENT

2 E006 1 BASEMENT

3 G050 1 BASEMENT

4 W05B 14 BASEMENT

5 A153A 1 1st

6 E139 1 1st

7 B144A 1 1st

8 G141 1 1st

9 C105 1 1st

10 A213 1 2nd

11 E203 1 2nd

12 A306A 1 3rd

13 C308 1 3rd

14 E326 1 3rd

15 445 1 4th

16 551 1 5th

17 650 1 6th

18 C358C 1 3rd

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

T-002

RESPONSIBILITY AND

PREFERRED PRODUCTS MATRIX

RMJr

#10

#9

#11

DN

UP

UPDN

F

F

F

F

F

F

F

CB

E3

F023A CBF3

F024

F001A F004

F021

F018

F020 F019 F017 F016

F015A

F015

F014

CB

F4

F005 F010

F012F013

F036F011

F009A

F009F008F007F006F003

CBF5

F001B F001

F002A

F002

E012 E001G

CBF1

E001

E009

E010

E008

E007

CBE1CBE2

E004

E005

F037STR #11

B051B048B042B039AB039

E001AE001CE001D

E001B

E002NE002M

E002O

E002F

E002E

E002D E002C E002Q

E001E

E002A

E002

E002B

E002H E002I E002J E002K E002L E001F

A001

A003 A007 A009

A010A

A010 A019 A020

37A

F029A F029 F028

F027A

F028A F025

F025A

F027 F026

F034

F034A F035A

F035

F033F032F031F030 F030A

F023 F022

E003

CBE4

A009A

CB

F2

A020A

MATCH LINE 'A'MATCH LINE 'A'

EXIST.

ELEV. LOBBY

CBE5

EXIST.

TELECOM

E006

1 DEMO FLOOR PLAN - BASEMENT - AREA 1

SCALE: 1/8 = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TD-100-1.B

BASEMENT TECHNOLOGY

DEMO PLAN - AREA 1

VV

KEY PLAN

N

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNT EQUIPMENT,

ELECTRICAL CABLES AND EQUIPMENT, OR ANY

CABLING OR DEVICE THAT IS NOT DATA

RELATED. COORDINATE WITH COR PRIOR TO

REMOVING CABLING FROM WALL FIELDS OR

FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6A OR UNLESS OTHERWISE

NOTED. CONTRACTOR SHALL COORDINATE

WITH THE COR PRIOR TO REMOVING CABLES,

OUTLETS, FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CABLE SUPPORTS, SUCH AS CABLE TRAYS, OR

J-HOOKS, THAT ARE NOT TO BE REUSED SHALL

BE PRESERVED FOR REUSE. COORDINATE WITH

THE COR PRIOR TO REMOVING CABLE

SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.PRIOR TO RELOCATING WALL MOUNTED TV,

CONTRACTOR SHALL COORDINATE WITH THE

COR FOR THE NEW LOCATION AND PROVIDE

NEW CATEGORY 6A DATA AND ELECTRICAL

OUTLETS.

UP

#14

#15

#13 #12

DN

DN

DN

G014

B025

B027A

B027 CB

B3

CBG2

G001

CB

G1

G012

G013

G048

G047

G043A

G052C

G045

G046

G043

G016 G052B

G052

G036

G032

G032A

G055 G059

G052A

G030

G029

G027A

G027

CBG6

G026

G015

G031 G024A G024B

CBG5

G004

CB

G3

G040A

G042 G023

G024 G018 G017

CBG4

G037

G040 G038 G019C G019A

G019B

G019

G008

G004A

G038A

G015A

STR #G1

M

AT

C H

L

IN

E 'B

EXIST.

OFFICE

G051

EXIST.

TELECOM

G050

1 DEMO FLOOR PLAN - BASEMENT - AREA 2

SCALE: 1/8" = 1'-0"

KEYED NOTES

1. CATEGORY 6 CABLES TO REMAIN. PRESERVE

CABLES, MODULAR JACKS, AND PATCH PANELS

FOR REUSE.

2. CONTRACTOR SHALL RELOCATE NURSE CALL

CABINET OR TELEPHONE BACKBOARD

COORDINATING THE NEW LOCATION WITH THE

COR.

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TD-101-1.B

BASEMENT TECHNOLOGY

DEMO PLAN - AREA 2

VV

KEY PLAN

N

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNT EQUIPMENT,

ELECTRICAL CABLES AND EQUIPMENT, OR ANY

CABLING OR DEVICE THAT IS NOT DATA

RELATED. COORDINATE WITH COR PRIOR TO

REMOVING CABLING FROM WALL FIELDS OR

FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6A OR UNLESS OTHERWISE

NOTED. CONTRACTOR SHALL COORDINATE

WITH THE COR PRIOR TO REMOVING CABLES,

OUTLETS, FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CABLE SUPPORTS, SUCH AS CABLE TRAYS, OR

J-HOOKS, THAT ARE NOT TO BE REUSED SHALL

BE PRESERVED FOR REUSE. COORDINATE WITH

THE COR PRIOR TO REMOVING CABLE

SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.PRIOR TO RELOCATING WALL MOUNTED TV,

CONTRACTOR SHALL COORDINATE WITH THE

COR FOR THE NEW LOCATION AND PROVIDE

NEW CATEGORY 6A DATA AND ELECTRICAL

UP

#4

#5

#7

#8

REX

#1#2#3

DN

UP

DN

A058

B013

B013A

B011B

B011A

B011C B011D B011E B011F B011G

B011

B011H

B011J B009

B007

B010

B010A

B006C

B006

B006B

B006A

B009A

B036A

ST

R

B036B

B034 B036

A056

STR #1

B025

B027A

B024 B019

B027

B031

CB

B3

B030

B026 B023

B032

B014

B016

B018

B022 B021

B017

B045

B015

B012

B046A

B047 B046 B049

B050

CB

A1

B051B048B042B039AB039

CBB3

A055

A054B

A004

E001E

E002B

E002H E002I E002J E002K E002L

A001

A002 A003

CBA2

A007 A009

CBA3 CBA4

A005

A004A

A006 A008A A008

A012

A013

A047

CBA8

A060

D004L

A048

A049

A006A

A051

A51A

A050

CBA9

A052

CBA10

A053

A059A

A059

A057

D004M

D004N

D002

D001B

D001A

D001

D004E

D004BD004AD004O

D031

D003

D003B D004G

D004H

D028 D003A D004I

CBB1

B033

B033A

B037A

B037 A009A

B002D

B002G

B002F

B002K

B002A

B002

B001F

B002E

C009D

C009

C009B

C001

C009A

B001E

B001B

B001D

B0

C

B001A

C001A C001C

C001D

CB

D4

C009C

CBD1

CB

B4

A054

A016A

A016

MATCH LINE 'A'

MATCH LINE 'C'

EXIST.

TELECOM

A056A

NOT IN SCOPE.

KITCHEN RENO PROJECT

1 DEMO FLOOR PLAN - BASEMENT - AREA 3 & 4

SCALE: 1/8" = 1'-0"

KEYED NOTES

1. EXISTING TELECOM SERVICE PROVIDER RACKS

TO REMAIN. NOT IN SCOPE OF WORK FOR THIS

PROJECT.

2. EXISTING TELECOM ROOM TO BE RELOCATED

TO NEW TELECOM ROOM TR A060.

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TD-102-1.B

BASEMENT TECHNOLOGY

DEMO PLAN AREA 3 & 4

VV

KEY PLAN

N

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNT EQUIPMENT,

ELECTRICAL CABLES AND EQUIPMENT, OR ANY

CABLING OR DEVICE THAT IS NOT DATA

RELATED. COORDINATE WITH COR PRIOR TO

REMOVING CABLING FROM WALL FIELDS OR

FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6A OR UNLESS OTHERWISE

NOTED. CONTRACTOR SHALL COORDINATE

WITH THE COR PRIOR TO REMOVING CABLES,

OUTLETS, FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CABLE SUPPORTS, SUCH AS CABLE TRAYS, OR

J-HOOKS, THAT ARE NOT TO BE REUSED SHALL

BE PRESERVED FOR REUSE. COORDINATE WITH

THE COR PRIOR TO REMOVING CABLE

SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.PRIOR TO RELOCATING WALL MOUNTED TV,

CONTRACTOR SHALL COORDINATE WITH THE

COR FOR THE NEW LOCATION AND PROVIDE

NEW CATEGORY 6A DATA AND ELECTRICAL

#5

#6

REX

DN

DN

DN

UP

DN DN

UP

UP

DN

DN

DN

DN

UP

UP

.4

.5

.5

.5

D027

CBD3

C006A

C006

STR #7

D021A

D021

STR #6

CBD7

D022

D020

D023

D022CD022D

D022A

D002D001

D004BD004AD004O

D031

D003

D003B D004G

D004H

D028

D029

D003A

D003C

D004I

D004J

D004KD003D

CBD5

D025D030

D024

D019C

C003A

C003B

C003C

C004D

C004BC004AC004

C005A

C005

C003

C003E

C011

C014C013C013A

B002E

C009D

C009

C009B

C001

C009A C001A C001C

C001D

CB

D4

C002

C002B C008

C0

J

C009C

C009E

C009F C009G

C009I

C009K

CBC1

C009H

C009M

C010

C009N

CBC1A

C003F C003D

D019A

D019B

D019D D019

D019C

CBC2

CB

C3

CBD1

C002A

D026

STR#9

D018

STR #17

MATCH LINE 'C'

NOT IN SCOPE.

MORGUE RENO. PROJECT

1 DEMO FLOOR PLAN - BASEMENT - AREA 3A & 4A

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TD-103-1.B

BASEMENT TECHNOLOGY

DEMO PLAN - AREA 3A & 4A

VV

KEY PLAN

N

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNT EQUIPMENT,

ELECTRICAL CABLES AND EQUIPMENT, OR ANY

CABLING OR DEVICE THAT IS NOT DATA

RELATED. COORDINATE WITH COR PRIOR TO

REMOVING CABLING FROM WALL FIELDS OR

FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6A OR UNLESS OTHERWISE

NOTED. CONTRACTOR SHALL COORDINATE

WITH THE COR PRIOR TO REMOVING CABLES,

OUTLETS, FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CABLE SUPPORTS, SUCH AS CABLE TRAYS, OR

J-HOOKS, THAT ARE NOT TO BE REUSED SHALL

BE PRESERVED FOR REUSE. COORDINATE WITH

THE COR PRIOR TO REMOVING CABLE

SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.PRIOR TO RELOCATING WALL MOUNTED TV,

CONTRACTOR SHALL COORDINATE WITH THE

COR FOR THE NEW LOCATION AND PROVIDE

NEW CATEGORY 6A DATA AND ELECTRICAL

A063C A063G

A063

A063A

A063H

A063D A063F

A024A

D008 D004

D009

CB

D2

D007

D005AD005

D006

D004C

D004F

E001E2L E001F

CBA4

A012

A013

A010A

A010 A019 A020

A024

A024B

ST

R

A026

A027A

A027

A028

A022

A018

A025BA025CBA5

A023 A029

A023A A031

CB

A7

CB

A6

A021

A045A

A015A A015

A011

A014 A030

A032

A034 A033

A033

A035

A042A

A042A043A045A017

A033A

A033B

A038

A037

A036

A039A040A041

CBA8

A046

A047A

A047

CBA11

CBA8

004G

004H

004I

A009A

A020A

A016A

A016

A063EA063B

MATCH LINE 'A'

MATCH LINE 'C'

M

AT

C H

L

IN

E 'D

M

RANCE

1 DEMO FLOOR PLAN - BASEMENT - AREA 5

SCALE: 1/8" = 1'-0"

N

UP

DN

D021

STR #6

D015

D022B

D012

D010

D008 D004

D017

D016

D013

D0

A

D015A

ST

R

D011

D009

CB

D2

D007

D014

004G

004H

004I

004J

004K

PB01C

STR #12 #17

MATCH LINE 'C'

M

AT

C H

L

IN

E 'D

2 DEMO FLOOR PLAN - BASEMENT - AREA 5

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TD-104-1.B

BASEMENT TECHNOLOGY

DEMO PLAN - AREA 5

VV

KEY PLAN

NN

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNT EQUIPMENT,

ELECTRICAL CABLES AND EQUIPMENT, OR ANY

CABLING OR DEVICE THAT IS NOT DATA

RELATED. COORDINATE WITH COR PRIOR TO

REMOVING CABLING FROM WALL FIELDS OR

FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6A OR UNLESS OTHERWISE

NOTED. CONTRACTOR SHALL COORDINATE

WITH THE COR PRIOR TO REMOVING CABLES,

OUTLETS, FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CABLE SUPPORTS, SUCH AS CABLE TRAYS, OR

J-HOOKS, THAT ARE NOT TO BE REUSED SHALL

BE PRESERVED FOR REUSE. COORDINATE WITH

THE COR PRIOR TO REMOVING CABLE

SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.PRIOR TO RELOCATING WALL MOUNTED TV,

CONTRACTOR SHALL COORDINATE WITH THE

COR FOR THE NEW LOCATION AND PROVIDE

NEW CATEGORY 6A DATA AND ELECTRICAL

M V

M

AO2

M V

M

AO2

EX

T3

EXT30EXT36

EX

T3

EXT30 EXT36

FE

FE

FE

FE

FE

FE

FE

UP

UP

#10

#9

#11

E109 E110E125F

E125EC1E24

E125DE125CE125BE125A

E124

E123

E126

C

E2

E133

E122 E121 E120

E117 E116

E115

E114

E130

E131

E132

E112

E111

E129

E127

B109 B110 B112

F100

B131A

C

E6

E137

E102LE102G

E102F E102E E102D E102C E102B E102A

F129

F135

C1E14

E102J E102K

F104

E-1204

F171

F128

F134

C1E13

E108B

F122

C1E21

F171A F150

F101

F125

E102H

E107

E108

C 1F

F123

F151B

F102

F126

E102

E106

E108C

C1F11

F124

F151A

C1F7

C1E12

E144

E140

F168

F137A

C1F7

F121

F137

F169

E146

E148

E138

C1E11

C1F1

C1F19

C

F1

C1F2

C1F21

E147

C1E8 E145

E143

F136

F118

F117

B138

F163

C1E15

C1F20

F103

F160

F161

B134

F116

C1F6

C 1F

F115

C1E16

F164

E134

C1E10

F166

F167

F165

F162

B137

C

F9

F109

F108

C1F8

F146 F131

C1F15

F105

F113

F114A

F127 F130

F103B

F114

F132

F151

F149

C1E17

F119

F107

F106

F112 F155

F147

F152

C

F1

C

F1 4 F144

F138

F153

F138A

F145

F148

F110 F111 F142F141F140F139 F156

C1F12 C1F13

F133

F157 F158 F159

C1F17

F142 F154

F120

E127A

F103A

B134A

MATCH LINE 'A'

M

AT

C H

L

IN

E 'D

BREAK

ROOM

EXIST.

TELECOM

B144A

LOCKERS

B143

EXIST.

TOILET

B144B

EXIST.

ELEV. LOBBY

C1E9

EXIST.

TELECOM

E139

2 2 2

2 2 2

2 2 2 2

2 2 2 2 2 2

2 2

2 2

2 2 2

2 2

2 2

4 2 2

2 2

2 2

2 2

1 1

2 23

3 2

1 DEMO FLOOR PLAN - FIRST FLOOR - AREA 1

SCALE: 1/8 = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TD-105-1.1

FIRST FLOOR TECHNOLOGY

DEMO PLAN- AREA 1

VV

KEY PLAN

N

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNT EQUIPMENT,

ELECTRICAL CABLES AND EQUIPMENT, OR ANY

CABLING OR DEVICE THAT IS NOT DATA

RELATED. COORDINATE WITH COR PRIOR TO

REMOVING CABLING FROM WALL FIELDS OR

FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6A OR UNLESS OTHERWISE

NOTED. CONTRACTOR SHALL COORDINATE

WITH THE COR PRIOR TO REMOVING CABLES,

OUTLETS, FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CABLE SUPPORTS, SUCH AS CABLE TRAYS, OR

J-HOOKS, THAT ARE NOT TO BE REUSED SHALL

BE PRESERVED FOR REUSE. COORDINATE WITH

THE COR PRIOR TO REMOVING CABLE

SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.PRIOR TO RELOCATING WALL MOUNTED TV,

CONTRACTOR SHALL COORDINATE WITH THE

COR FOR THE NEW LOCATION AND PROVIDE

NEW CATEGORY 6A DATA AND ELECTRICAL

FE

FE

FE

DN

UP

UP

DN

F175

F174C

F174B

F174A

C1E33

C1E31

F181

A130

C

E6

E102L

C1E35

C1E29

F176

F174

E102C E102B E102A

E-1100

E102J E102K

F171

F171A F150

E102H

F151B

E102

F151A

E144

E140

F168 F169

E146

C1F19

C

F1

C1E8 E145

E143

F163

F179B

F177

F160 F177A

F178

F161

F164

F1 F2

C1E32

F166

F167

F165

F162

F179

C1F22

F170

F151

F180

156 F157 F158 F159

C1F17

A119A A121 A123 A125

C1E30

E100A

E142

E141

E100

E101

MATCH LINE 'A'

M

AT

C H

L

IN

E 'D

2 2 2

2 2 2 2

2 2 2

2 2

2 3

2 2

3 3

2 3

2 2 2 22

1 DEMO FLOOR PLAN - FIRST FLOOR - AREA 1A

SCALE: 1/8 = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TD-106-1.1

FIRST FLOOR TECHNOLOGY

DEMO PLAN- AREA 1A

VV

KEY PLAN

N

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNT EQUIPMENT,

ELECTRICAL CABLES AND EQUIPMENT, OR ANY

CABLING OR DEVICE THAT IS NOT DATA

RELATED. COORDINATE WITH COR PRIOR TO

REMOVING CABLING FROM WALL FIELDS OR

FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6A OR UNLESS OTHERWISE

NOTED. CONTRACTOR SHALL COORDINATE

WITH THE COR PRIOR TO REMOVING CABLES,

OUTLETS, FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CABLE SUPPORTS, SUCH AS CABLE TRAYS, OR

J-HOOKS, THAT ARE NOT TO BE REUSED SHALL

BE PRESERVED FOR REUSE. COORDINATE WITH

THE COR PRIOR TO REMOVING CABLE

SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.PRIOR TO RELOCATING WALL MOUNTED TV,

CONTRACTOR SHALL COORDINATE WITH THE

COR FOR THE NEW LOCATION AND PROVIDE

NEW CATEGORY 6A DATA AND ELECTRICAL

9*

N7

F

F

F

F F

F

F

F

#14

#13 #12

#15

C133C

C133B

C111

C112

C1

B176C

B176B

B176

C

G

G176

G100

G101

G102

G102A

G160

G103

G

G105

G106

G

G105A

G108

G114A

G

G116

G114

G115

G113G112

G156

G173G

G111

G110

G110A

G

G148 G147 G146 G171

G145 G143A

G144

G142A G168

G142

G170

G169 G143

G107

G191

G136 G139

G155

G155B

G137

G138

G163 G162

G120

G121

G123

G122

G133

G127 G128

G159

G

G

G129

G130

G131

G132

G119

G124 G

5 G118 G161

G164A C104

G164

C110

G135 G140

G

A

G193

G149

G150

G150A

G151 G153

B176D

G152

G196E

G196H G196G G196F

G192

M

AT

C H

L

IN

E 'B

MATCH LINE 'F'

EXIST.

TELECOM

G141

2 2

1 41 4

4 1 3

4 1

2 21

22 22

2 2

2 2

2 2

1 DEMO FLOOR PLAN - FIRST FLOOR - AREA 2

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

589A4-21-700

1/25/2022

100% CONSTRUCTION

DOCUMENT

EHRM Infrastructure Upgrades - Columbia, MO

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TD-107-1.1

FIRST FLOOR TECHNOLOGY

DEMO PLAN- AREA 2

VV

KEY PLAN

N

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNT EQUIPMENT,

ELECTRICAL CABLES AND EQUIPMENT, OR ANY

CABLING OR DEVICE THAT IS NOT DATA

RELATED. COORDINATE WITH COR PRIOR TO

REMOVING CABLING FROM WALL FIELDS OR

FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6A OR UNLESS OTHERWISE

NOTED. CONTRACTOR SHALL COORDINATE

WITH THE COR PRIOR TO REMOVING CABLES,

OUTLETS, FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .