Final Drawings_Part8.pdf

PDF 18 MB Posted

Attached to
Y1DZ--589A4-21-700 EHRM Infrastructure Upgrades Construction Columbia, MO
Solicitation number
36C77622R0069
Issued by

About this file

This document provides details for a federal construction contract solicitation and related drawings. The solicitation number is 36C77622R0069 from the Department of Veterans Affairs Technology Acquisition Center Austin for the EHRM Infrastructure Upgrades Construction project in Columbia, MO. The contractor will be required to provide all labor, project management, materials, tools, supplies, and equipment as required by the drawings and specifications to complete the necessary infrastructure upgrade work. One of the attachments is a set of final drawings for Part 8 of the project.

View the file

Other files

File Type Posted
Answers to Technical Questions 7-15-22.pdf PDF
36C77622R0069 0007 Amendment 0007 7-15-22.pdf PDF
TERRACON ASBESTOS SURVEY Final Report-NESHAP Survey Report_updated as removed.pdf PDF
36C77622R0069 0006 Amendment 0006 7-7-2022.pdf PDF
Answers_Clarifications to Technical Questions 7-7-22.pdf PDF
Attachment A _Roof Plans_Site Layout.pdf PDF
Answers to Technical Questions 6-29-22.pdf PDF
36C77622R0069 0005 Amendment 0005 6-29-2022.pdf PDF
36C77622R0069 0004 Amendment 0004 6-27-2022.pdf PDF
36C77622R0069 0003 - Amendment 0003 - 6-22-2022.pdf PDF
36C77622R0069 0002 - Amendment 0002 - 6-16-2022.pdf PDF
Construction Wage Rates - Boone County - 5-27-22.pdf PDF
Site Visit Sign-In-Sheet 6-9-22.pdf PDF
36C77622R0069 0001 - Amendment 0001 - 6-9-22.pdf PDF
Attachment C - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Final Drawings_Part3.pdf PDF
Construction Wage Rates - Boone County - 4-22-22.pdf PDF
Attachment A - PPQ.docx DOCX document
Final Specifications-Vol 1_Rev2 - 3-28-22.pdf PDF
Attachment D - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment B - VHA Suppl. Contract Rqmnts for Combatting COVID-19 Updated 12-14-2021.pdf PDF
Final Specifications-Vol 2_Rev2 - 3-28-22.pdf PDF
Final Drawings_Part6.pdf PDF
Final Drawings_Part7.pdf PDF
Final Drawings_Part2.pdf PDF
Final Drawings_Part1.pdf PDF
36C77622R0069 Columbia EHRM Infra - 5-19-22.pdf PDF
Final Drawings_Part9.pdf PDF
Final Narrative.pdf PDF
Final Drawings_Part4.pdf PDF
Final Drawings_Part5.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F

IL

E C

A B

F

IL

E C

A B

103 104 106

100 C1A1

100A 100C

100B

107A

112 113

110105A

C B

100D

114A

109A

12"x2"

"x

12"x2" 6"x2"

"x

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:0

P

M

EG-110-22.B

FLOOR PLAN - BUILDING 22 -

OVERALL

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

1ST FLOOR_OV_NW_ELEC_BUILDING 22

GENERAL SHEET NOTES

KEYED NOTES

1. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

2. (3) EXISTING 4 INCH PVC STUB UPS BELOW TRAILER.

3. EXTEND (3) 4 INCH PVC CONDUITS TO PULL BOX BELOW

TRAILER.

4. PROVIDE (3) 4 INCH PVC CONDUITS FROM PULLBOX TO ABOVE

CEILING CABLE TRAY. VERTICAL CONDUITS SHALL BE STEEL.

5. CUT AND PATCH WALL AS NEEDED FOR NEW CONDUITS. MATCH

EXISTING WALLS.

6. PROVIDE PULLBOX. PULLBOX SHALL BE SUPPORTED SO

BOTTOM IS 6 INCHES OFF GRADE.

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

PLAN NORTH

TRUE NORTH

Revisions: Date:

EXIST.

ELEV. LOBBY

CBE5

EXIST.

TELECOM

E006

C B

E

F023A CBF3

F024

F001A

F004

F021

F018

F020 F019 F017 F016

F015A

F015

F014

F005 F010

F012

F013

F036F011

F009A

F009F008F007F006F003

F001B

F001

F002A

F002

E012

E001G

CBF1

E001

E009

E010

E008

E007

CBE1CBE2

E004

E005

F037STR #11

E001A

E001CE001D

E001B

E002NE002M

E002O

E002F

E002E

E002D E002C E002Q

E002A

E002

E002B

F029A F029 F028

F027A

F028A F025

F025A

F027 F026

F034

F034A F035A

F035

F033F032F031F030

F030A

F023 F022

E003

CBE4

C B

F

-OPEN TO BELOW-

SEE PIPE BASEMENT FLOOR PLAN

DRAWING FOR ROOM DETAILS

DN

UP

UPDN

1 2 3 4 5 5.6 6.3 7 8 9 11 11.5 12

B

C

D

E

E.11211.51110.610

F

G

H

#10

#9

#11

F

F

F

F

F

F

F

TT

B

E-401-1.B

E-401-1.B

E-401-1.B

2 2

8"x4"

"x

8"x4"

8"x4"

"x

PROVIDE NEW TRAY TO FILL

THE GAP BETWEEN EXISTING

CABLE TRAY UNDER DUCT FOR

FUTURE USE.

ROUTE

BELOW DUCT

TRANSITION HIGH

ROUTE ABOVE EXISTING TRAY. TRANSITION BELOW

DUCTS AND ADJACENT TO EXISTING TRAY TO

ROUTE AROUND DUCTS.

"x

"x

"x

8"x4"

"x

"x

12"x4"

"x

ECT

ECT

ECT

ECT

ECTECT

ECTECT

8"x4"

8"x4"

"x

"x

8"x4"

8"x4"

E-403-1.B

E-400-1.B

12"x4"

E C

T

"x

E C

T

E C

T

12"x4"

12"x4"

E C

T

ECT

E-400-1.B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:0

P

M

EP-100-1.B

FLOOR PLAN - BASEMENT - AREA

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

BASEMENT_PA_NW_ELEC_AREA 1

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. ROUTE CABLE TRAY ABOVE EXISTING TRAY.

3. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

4. PROVIDE (3) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

5. PROVIDE (3) 4 INCH CONDUITS FROM TR ROOM INTO BEAM JOIST

SPACE TO ROUTE ABOVE A WALL OF HVAC DUCTS TO CEILING

ACCESSIBLE SPACE AT ROOMS F007 AND F008. CUT OPENING IN

WALLS FOR THE INSTALLATION OF CONDUIT AND PATCH WALLS

TO MATCH EXISTING. PROVIDE 4 INCH STOP PLUGS ON EACH

END.

6. PROVIDE (2) 4 INCH CONDUITS FROM TR ROOM TO CORRIDOR

CBF1 CABLE TRAY. CUT OPENING IN WALLS FOR THE

INSTALLATION OF CONDUIT AND PATCH WALLS TO MATCH

EXISTING. PROVIDE 4 INCH STOP PLUGS ON EACH END.

7. FEEDER TO PANELBOARD PPB-D7-120VC. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

8. FEEDER TO PANELBOARD PP1-D7-120VC. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

9. FEEDER TO PANELBOARD PP2-D7-120VC. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

10. FEEDER TO PANELBOARD PP3-D2-120VC. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

11. FEEDER TO PANELBOARD PPB-D7-120VN. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

12. REMOVE WALL AS NEEDED TO ACCESS VERTICAL SHAFT FOR

CONDUIT PATHWAY. PATCH AND PAINT WALL WHEN WORK IS

COMPLETE.

13. CORE DRILL OR CUT AND PATCH WALL FOR CONDUIT. SEAL

WALL MATCHING EXISTING WALL RATING.

#GENERAL SHEET NOTES

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

2. HORIZONTAL CONDUIT RUNS IN OPEN CEILING AREAS SHALL BE

ROUTED AS HIGH AS POSSIBLE AND NO LOWER THAN 10 FEET

AFF UNLESS OTHERWISE NOTED. HORIZONTAL CONDUIT RUNS

LOWER THAN 10 FEET AFF SHALL BE APPROVED BY VA FACILITY.

PLAN NORTH

OFFICE

G051

EXIST.

TELECOM

G050

G014

CBG2

G001

C B

G

G012

G013

G048

G047

G043A

G052C

G045

G046

G043

G016 G052B

G052

G036

G032

G032A

G055

G059

G052A

G030

G029

G027A

G027

CBG6

G026

G015

G031 G024A G024B

G004

C B

G

G040A

G042

G023

G024 G018 G017

CBG4

G037

G040 G038

G019C G019A

G019B

G019

G008

G004A

G038A

G015A

STR #G1

-OPEN TO BELOW-

SEE PIPE BASEMENT

FLOOR PLAN

DRAWING FOR ROOM

DETAILS

UP

DN

DN

UU.5VWW.3W.4XYZAABBCCCC.6DD

3.6

4.1

4.5

4.7

6.1

7.1

7.6

8.3

8.9

9.8

10.2

6.3

#14

#15

#13 #12

TTB

E-402-1.B

E-402-1.B

E-402-1.B

OUTLINE OF TR G141 ABOVE

3 44

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:1

P

M

EP-101-1.B

FLOOR PLAN - BASEMENT - AREA

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

BASEMENT_PA_NW_ELEC_AREA 2

GENERAL SHEET NOTES

1. HORIZONTAL CONDUIT RUNS IN OPEN CEILING AREAS SHALL BE

ROUTED AS HIGH AS POSSIBLE AND NO LOWER THAN 10 FEET

AFF. HORIZONTAL CONDUIT RUNS LOWER THAN 10 FEET AFF

SHALL BE APPROVED BY VA FACILITY.

KEYED NOTES

1. CONTINUE FEEDERS FROM DISTRIBUTION SWITCHBOARDS DPB-

H13-120VN AND DPB-H13-120VC TO PANELBOARDS PPB-B6-120VC

AND PPB-B6-120VN. KEEP FEEDERS AS HIGH AS POSSIBLE

ABOVE CEILING.

2. CONTINUE FEEDERS FROM DISTRIBUTION SWITCHBOARDS DPB-

H13-120VN AND DPB-H13-120VC TO PANELBOARDS PPB-

DD8.3-120VC AND PPB-DD8.3-120VN. KEEP FEEDERS AS HIGH AS

POSSIBLE ABOVE CEILING.

3. CONTINUE FEEDERS FROM DISTRIBUTION SWITCHBOARDS DPB-

H13-120VN AND DPB-H13-120VC TO PANELBOARDS PP1-

Y10.2-120VC AND PP1-Y10.2-120VN. KEEP FEEDERS AS HIGH AS

POSSIBLE ABOVE CEILING.

4. CORE DRILL OR CUT AND PATCH WALL FOR CONDUIT. SEAL

WALL MATCHING EXISTING WALL RATING.

TELECOM

A056A

OFFICE

STORAGE

A060B

TELECOM

ROOM

A060

TELECOM

DEMARK ENTRANCE

A060A

A058

B013

B013A

B011B

B011A

B011C B011D B011E B011F B011G

B011

B011H

B011J B009

B007

B010

B010A

B006C

B006

B006B

B009A

B036A

S T

R

B036B

B034 B036

A056

STR #1

B025

B027A

B024 B019

B027

B031

C B

B

B030

B026 B023

B032

B014

B016

B018

B022 B021

B017

B045

B015

B012

B046A

B047 B046 B049

B050

C B

A

B051B048B042B039AB039

CBB3

A055

A054B

A004

E001EE002H E002I E002J E002K E002L

A001

A002

A003

CBA2

A007 A009

CBA3 CBA4

A005

A004A

A006 A008A A008

A012

A013

A047

CBA8

D004L

A048

A049

A006A

A051

A51A

A050

CBA9

A052

CBA10

A053

A059A

A059

A057

D004M

D004N

D002

D001B

D001A

D001

D004E

D004B

D004AD004O

CBB1

B033

B033A

B037A

B037

CBG5

A009A

B002D

B002G

B002F

B002K

B002A

B002

B001F

B002E

C009D

C009

C009A

B001E

B001B

B001D

B

1C

B001A

C001A C001C

CBD1

C B

B

A054

A016A

A016

-OPEN TO BELOW-

SEE PIPE BASEMENT

FLOOR PLAN

DRAWING FOR ROOM

C012 DETAILS

DN

UP

DN

UP

T S R Q P N M L K J H G FHbNa

7.6

1.9

2.8

3.7

4.6

5.5

5.7

6.2

6.7

7.2

5.1

4.1

3.6

1.1

S.9 Nb Mb Fa

#4

#5

#7

#8

#1#2#3

REX

NOT IN SCOPE.

KITCHEN RENO PROJECT

E-401-1.B

E-401-1.B

E-401-1.B

4 4 4 4

NEW TRAY MEETS

EXISTING.

POSSIBLE DOUBLE STACK TRAY IF NEEDED.

TRANSITION

BELOW DUCT.

TRANSITION HIGH TO GO ABOVE B026 DUCTS.

TRANSTION BACK DOWN

SHIFT TRAY FOR PIPING

18 INCH OR DUAL 12

INCH RUN 12 INCHES.

12"x4"

"x

"x

12"x4"

"x

MOVE EXISTING CONDUIT

HIGHER AND RESUPPORT

TO MAKE ROOM FOR

NEW CABLE TRAY.

12"x4" 8"x4"

"x

6"x3"

PLACE EZ-PATH PATHWAYS

ABOVE TRAY IN CORRIDOR.

12"x4" 12"x4"

12"x4"

12"x4"

12"x2" 12"x4"

12"x2"

"x

"x

12"x4"

12"x4"

18"x4"

"x

"x

"x

"x

ECTECTECTECTECT

ECT

E C

T

ECT

E C

T

12"x4"

E C

T

ECT ECT

12"x4"

ECT

E C

T

E C

T

ECT

E C

T

E C

T

E C

T

12"x2"

12"x2"

"x

ECTECT

E C T

ECT

12"x4"

E C

T

ECT ECT

ECT ECT

"x

12"x4"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:1

P

M

EP-102-1.B

FLOOR PLAN - BASEMENT - AREA

3 & 4

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

BASEMENT_PA_NW_ELEC_AREA 3 & 4

GENERAL SHEET NOTES

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. ROUTE CABLE TRAY ABOVE EXISTING TRAY.

3. INSTALL 2'X2' ACCESS PANEL IN CEILING OF ROOM.

4. MOUNT TRAY APPROXIMATELY 6 FEET FROM THE PLAN NORTH

WALL AND APPROXIMATELY 14 INCHES ABOVE CEILING TO AVOID

DUCT WORK.

5. DASHED BOUNDARY REPRESENTS ESTIMATED AREA OF A NEW

ROOM ADDED WITHIN ROOM A048. INSTALL 2'X2' ACCESS PANEL

IN HARD CEILING OF NEW ROOM.

6. CEILINGS ARE HIGHER THAN CORRIDOR. PROVIDE WATERFALLS.

7. PROVIDE (3) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

8. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

9. RELOCATE 2'X2' LIGHT FIXTURE TO ADJACENT EAST CEILING TILE.

10. CABLE TRAY INSTALLATION WILL REQUIRE REPLACEMENT OF

HARD CEILING. REMOVE, PROTECT, AND REINSTALL ELECTRICAL

CEILING DEVICES AND LIGHT FIXTURES TO ALLOW CEILING

REPLACEMENT AND CABLE TRAY INSTALLATION.

11. PROVIDE (1) 18"x2" CABLE TRAY LOW ABOVE CEILING TO CROSS

CORRIDOR AND CONNECT TO EXISTING TRAY. PROVIDE "A"

SECTION OF 24"x24" CABLE TRAY HIGH ABOVE DUCTS TO

WATERFALL TO LOWER TRAY.

12. CUT WALLS ABOVE CEILING ON BOTH SIDES OF CORRIDOR AND

PATCH TO MATCH EXISTING RATING.

13. PROVIDE SECTION OF TRAY TO CONNECT EXISTING TRAY.

14. ROUTE CABLE TRAY HIGH AS POSSIBLE IN MAIL ROOM.

WATERFALL UP OR DOWN TO EZ PATHS ON BOTH ENDS.

GENERAL SHEET NOTES

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

FG

H

JKLMNPQRST Rb Ra Na La Ja

Ha

Ga Ea

D027

CBD3

C006A

C006

STR #7

D021A

D021

STR #6

CBD7

W010

D022

D020

D023

D022CD022D

D022A

D031

D003

D003B

D004G

D004H

D028

D029

D003A

D003C

D004I

D004J

D004K

D003D

CBD5

D025D030

D024

D019C

C003A

C003B

C003C

C004D

C004BC004AC004

C005A

C005

C003

C003E

C011

C014C013C013A

C009

C009B

C001

C001D

C B

D

C002

C002B

C008

C

9J

C009C

C009E

C009F

C009G

C009I

C009K

CBC1

C009H

C009M

C010

C009N

CBC1A

C003F C003D

D019A

D019B

D019D D019

D019C

CBC2

C B

C

C002A

D026

STR#9

D018

STR #17

DN

DN

DN

UP

DN DN

UP

UP

DN

DN

DN

DN

UP

UP

8.2

9.1

10.4

11.5

12.5

13.5

10.2

8.9

8.3

Fa

MbNb

13.6

Sb

13.4

#6

NOT IN SCOPE.

MORGUE RENO. PROJECT

TRANSITION HIGH

ABOVE DUCTS.

8"x3"

TRANSITION

BOTTOM OF TRAY

TO 8'-6" A.F.F.

12"x4"

12"x4"

8"x3"

E-403-1.B

E-403-1.B

"x

E-403-1.B

OUTLINE OF ROOM C105 ABOVE.

OUTLINE OF ROOM D164 ABOVE.

12"x4"

"x

E C

T

ECT

ECT

ECT

ECT ECT

E C

T

12"x4"

ECT

7 8

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:1

P

M

EP-103-1.B

FLOOR PLAN - BASEMENT - AREA

3A & 4A

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

BASEMENT_PA_NW_ELEC_AREA 3A &4A

GENERAL SHEET NOTES

KEYED NOTES

1. LOWER EXIT LIGHT TO BELOW TRAY. REPLACE CONDUIT AND

CONDUCTORS FROM LOCAL JUNCTION BOX. PAINT CONDUIT TO

MATCH WALL.

2. FEEDERS TO PANELBOARDS PP1-M9-120VC AND PP1-M9-120VN

FROM SWITCHBOARDS DPB-H13-120VC AND DPB-H13-120VN.

FEEDERS SHALL BE ROUTED AS HIGH AS POSSIBLE IN CEILING

SPACE. PROVIDE PULLBOXES IN ACCESSIBLE LOCATIONS. PATH

SHOWN IS INTENT AND SHALL BE VERIFIED PRIOR TO

PURCHASING MATERIALS AND INSTALLATION.

3. FEEDERS FROM DPB-H13-120VC AND DPB-H13-120VN TO PP2-

F09-120VC, PP2-F09-120VN, DS2-F09-120VC, AND DS2-F09-120VN.

4. FEEDER FROM DPB-J13-277VN TO PP2-F13-480VN.

5. PROVIDE A SECTION OF CABLE TRAY ABOVE DOOR AND BELOW

DUCT.

6. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

7. PROVIDE (3) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

8. CORE DRILL OR CUT AND PATCH WALL FOR CONDUIT. SEAL

WALL MATCHING EXISTING WALL RATING.

GENERAL SHEET NOTES

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

2. IN ROOM D023, KEEP CONDUITS A MINIMUM OF 6 INCHES AWAY

FROM INSULATION ON CEILINGS AND WALL.

3. CONDUITS IN ROOMS D020, D021A, AND D023 SHALL RUN

HIGHER THAN 9'-6" AFF WHEN ROUTING HORIZONTALLY WITHIN

THE ROOMS.

7.2

6.3

5.5

4.6

4.4

3.7

2.8

1.9

A063C A063G

A063

A063A

A063H

A063D A063F

A024A

D007

D005AD005

D006

D004C

D004F

E001E E001F

CBA4

A012

A013

A010A

A010 A019 A020

A024

A024B

S T

R

A026

A027A

A027

A028

A022

A018

A025B A025

CBA5

A023 A029

A023A A031

C B

A

C B

A

A021

A045A

A015A

A015

A011

A014

A030

A032

A034

A033

A033

A035

A042A

A042A043A045A017

A033A

A033B

A038

A037

A036

A039A040A041

CBA8

A046

A047A

A047

CBA11

A009A

A020A

A016A

A016

A063EA063B

F E D C B AEa

A

Eb Ab

1.1

10.4

ABCD

EF Ea

Bb Ba

13.5

12.5

11.5

9.1

8.2

D015

D022B

D012

D010

D008

D004

D017

D016

D013

D

1A

D015A

S T

R

D011

D009

C B

D

D014

PB01C

STR #12

UP

DN

13.6

Ab

Eb

12"x3"

"x

"x

ROUTE CONDUIT HIGH

ABOVE DUCT WORK

"x

"x

12"x4"

6"x3"

E C

T

ECT

ECT

E C

T

ECT

18"x4"

8"x4"

12"x4"

BOTTOM OF TRAY 8 FEET A.F.F.

TRANSITION ABOVE

SECURITY CAMERA.

APPROX. 9 FEET A.F.F.

"x

E C

T

12"x4"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:1

P

M

EP-104-1.B

FLOOR PLAN - BASEMENT - AREA

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

BASEMENT_PA_NW_ELEC_AREA 5

1/8" = 1'-0"

BASEMENT_PA_NW_ELEC_AREA 5A

GENERAL SHEET NOTES

KEYED NOTES

1. WALL MOUNT NEW CABLE TRAY APPROXIMATELY 12 INCHES

ABOVE EXISTING TRAY. ADJUST ELEVATION OR JOG TRAY AS

NEEDED TO AVOID OTHER SYSTEMS EQUIPMENT.

2. PROVIDE (3) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

3. CUT WALLS ABOVE CEILING ON BOTH SIDES OF CORRIDOR AND

PATCH TO MATCH EXISTING RATING.

4. PROVIDE (4) 4 INCH CONDUITS TO CROSS CORRIDOR. PROVIDE 4

INCH FIRE STOP PLUG IN EACH CONDUIT ON EACH END.

5. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

GENERAL SHEET NOTES

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

TU

W010

CBG2

10.4

11.5

12.5

13.5

10.2

13.4

EXIST.

TELECOM

W05B

N1

TO HOSPITAL

PALLETS WILL

BE STACKED

TWO HIGH ON

RACKS

ENGINEERING

ENV

P R

O C

E S

S S

T O

R E

S

TSS STORAGE

E Q

U

IP

M E

N T

SPS

T S

S

12111098

TSS STORAGE

TSS STORAGE

TSS STORAGE

W03A

W03B

W03

W04A

W04

CWA3 W08

W09 W07

C W

A

CWA1

W05A

W06

W02 W01

EXIST.

ROOM

W05

75 64321

A

B

C

D

F

E

G

PS

PS

F

E-402-1.B

E-402-1.B

E-402-1.B

12"x4"

"x

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:2

P

M

EP-105-14.B

FLOOR PLAN - BASEMENT -

WAREHOUSE

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

BASEMENT_OV_NW_ELEC_WAREHOUSE

KEYED NOTES

1. CONTINUE FEEDERS FROM DISTRIBUTION SWITCHBOARDS DPB-

H13-120VN AND DPB-H13-120VC TO PANELBOARDS PPB-B6-120VC

AND PPB-B6-120VN. KEEP FEEDERS AS HIGH AS POSSIBLE ABOVE

CEILING.

2. CONTINUE FEEDERS FROM DISTRIBUTION SWITCHBOARDS DPB-

H13-120VN AND DPB-H13-120VC TO PANELBOARDS PPB-

DD8.3-120VC AND PPB-DD8.3-120VN. KEEP FEEDERS AS HIGH AS

POSSIBLE ABOVE CEILING.

3. CONTINUE FEEDERS FROM DISTRIBUTION SWITCHBOARDS DPB-

H13-120VN AND DPB-H13-120VC TO PANELBOARDS PP1-

Y10.2-120VC AND PP1-Y10.2-120VN. KEEP FEEDERS AS HIGH AS

POSSIBLE ABOVE CEILING.

4. ROUTE FEEDERS ABOVE CABLE TRAY. FEEDERS ARE SHOWN

OFFSET SO THEY CAN BE SEEN ON DRAWING.

5. BOTTOM OF CABLE TRAY 10 FEET FROM FINISH FLOOR.

6. PROVIDE (1) 4 INCH EZ PATH.

7. CORE DRILL OR CUT AND PATCH WALL FOR CONDUIT. SEAL

WALL MATCHING EXISTING WALL RATING.

GENERAL SHEET NOTESGENERAL SHEET NOTES

1. REFER TO DRAWIN EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

2. HORIZONTAL CONDUIT RUNS IN OPEN CEILING AREAS SHALL BE

ROUTED AS HIGH AS POSSIBLE AND NO LOWER THAN 10 FEET

AFF. HORIZONTAL CONDUIT RUNS LOWER THAN 10 FEET AFF

SHALL BE APPROVED BY VA FACILITY.

E109 E110E125F

E125EC1E24

E125DE125CE125BE125A

E124

E123

E126

C

E

E133

E122 E121 E120

E117

E116

E115

E114

E130

E131

E132

E112

E111

E129

E127

F100

E137

E102F E102E E102D E102C E102B E102A

F129

F135

F104

E-1204

F171

F128

F134

C1E13

F122

C1E21

F171A

F150

F101

F125

E108

C F

F123

F151B

F102

F126

E102

E106

C1F11

F124

F151A

C1F7

C1E12

E144

E140

F168

F137A

C1F7

F121

F137

F169

E146

E148

E138

C1E11

C1F1

C1F19

C

F

C1F2

C1F21

E147

C1E8 E145

F136

F118

F117

F163

C1E15

C1F20

F103

F116

C1F6

C F

F115

C1E16

E134

C1E10

F167

B137

C

F

F109

F108

C1F8

F146

F131

C1F15

F105

F113

F114A

F127 F130

F103B

F114

F132

F151

F149

C1E17

F119

F107

F106

F112 F155

F147

F152

C

F

C

F

F144

F138

F153

F138A

F145

F148

F110 F111 F142F141F140F139 F156

C1F12 C1F13

F133

F157 F158

C1F17

F142 F154

F120

E127A

F103A

LOCKERS

B143

EXIST.

TOILET

B144B

EXIST.

TELECOM

E139

UP

E X

T

EXT30EXT36

E X

T

EXT30 EXT36

M V

M V

O

O

M A

M A

E.5

F.1

F.2

F.9

G.5

Sb Nb Mb Fa

C

C.3

D

D.1

E

E.1

F

G

H

0 0.1 1 2 3 4 5 5.6 6 6.3 7 8

B

T S

R

0.1 1

Q

2 3

P Na N M La L

4 5

K

5.6 6

Jb

6.3

J Hb

H Ga G

F Ea

FE

FE

FE FE

FE

FE

TV

2 2 2

2 2 2

2 2 2 2

2 2 2 2 2 2

2 2

2 2

2 2 2

4 2 2

2 2

2 2

2 2

1 1

E-410-1.1

E-410-1.1

E-410-1.1

1 1 1

TRANSITION 12 INCH TRAY

BELOW EXISTING.

8"x4"

CONNECT TO

EXISTING TRAY.

8"x2"

8"x2" "x

"x

8"x2" 8"x2"

"x

ECT ECT

ECT

ECT

E C

T

E C

T

E C

T

E C

T

E C

T

E C

T E

C T

E C

T

E C

T

1 1 1

APPROX. 32 INCHES ABOVE CEILING.

12"x4"6"x4"

"x

12"x4"

"x

20"x4"

"x

20"x4"

6"x4"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:2

P

M

EP-110-1.1

FLOOR PLAN - FIRST FLOOR -

AREA 1

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

1ST FLOOR_PA_NW_ELEC_AREA 1

GENERAL SHEET NOTES

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. ROUTE CABLE TRAY ABOVE EXISTING TRAY.

3. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

4. CORE DRILL FLOOR FOR CONDUITS. X-RAY FLOOR TO VERIFY

LOCATION.

5. FEEDER TO PANELBOARD PP1-D7-120VC. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

6. FEEDER TO PANELBOARD PP1-D7-120VN. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

7. FEEDERS GOING UP TO PANELBOARDS PP2-D7-120VC AND PP3-

D2-120VC. PROVIDE PULLBOXES IN ACCESSIBLE LOCATIONS.

PATH SHOWN IS INTENT AND SHALL BE VERIFIED PRIOR TO

PURCHASING MATERIALS AND INSTALLATION.

8. CORE DRILL OR CUT AND PATCH WALL FOR CONDUIT. SEAL

WALL MATCHING EXISTING WALL RATING.

9. CUT AND PATCH WALL TO OBTAIN ACCESS INTO VOID SPACE TO

ROUTE CONDUIT.

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

F175

F174C

F174B

F174A

C1E33

C1E31

F181

A130

C

E

C1E35

C1E29

F176

F174

E102A

E-1100

E140

F169

C

F

E143

F179B

F177

F160

F177A

F178

F161

F164

F F

C1E32

F166

F165

F162

F179

C1F22

F170

F180

F158 F159

C1E30

E100A

E142

E141

E100

E101

DN

UP

DN

10.1 11.8

G.5

F.9

F.2

F.1

E.5

Eb Aa

9 10 10.6 11 11.5 12 13 14

H

G

F

E.1

E

D.8

D.5

D2

D

C.3

C

B.9

D.8 D.1 C.3

D

11 11.5 12

C

B.8 B.5

B

B.1 A.1 AZ AY.8 AY AX.8

B

AX.5 AX.1 AX AW.8 AW AV.9

Ea E

A

FE

FE

2 2

2 2 2

2 2

2 3

2 2

3 3

2 3

6"x4"

"x

6"x4"

ECT

E C

T E

C T

EXISTING PNLBD

PP1-D10-120VN

SECT. 1

EXISTING PNLBD

PP1-D10-120VN

SECT. 2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:2

P

M

EP-111-1.1

FLOOR PLAN - FIRST LEVEL -

AREA 1A

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

1ST FLOOR_PA_NW_ELEC_AREA 1A

GENERAL SHEET NOTES

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

2. CONTRACTOR TO ROUTE NEW CONDUIT AS HIGH AS POSSIBLE

ABOVE CEILING AND IN CRAWL SPACE.

3. FEEDERS SHOWN ARE FOR ELECTRICAL EQUIPMENT SHOWN ON

ONE-LINES. REFER TO ENLARGED PLANS FOR ADDITIONAL

ELECTRICAL REQUIREMENTS.

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. FEEDER TO PANELBOARD PP1-D7-120VN. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

3. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

4. CORE DRILL OR CUT AND PATCH WALL FOR CONDUIT. SEAL

WALL MATCHING EXISTING WALL RATING.

C133C

G

G176

G100

G101

G102

G102A

G160

G103

G

G105

G106

G

G105A

G108

G114A

G

G116

G114

G115

G113G112

G173G

G111

G110

G110A

G

G148 G147 G146 G171

G145

G143A

G144

G142A

G168

G142

G170

G169

G143

G107

G136 G139

G155

G155B

G137

G138

G163 G162

G120

G121

G123

G122

G133

G127 G128

G159

G

G

G129

G130

G131

G132

G119

G124

G

G118 G161

G164A

G164

G135 G140

G

A

G193

G149

G150

G150A

G151 G153

B176D

G152

G196E

G196H G196G G196F

G192

EXIST.

TELECOM

G141

UU.5VWW.4XYZAABBCCCC.6DD

10.4

10.2

9.8

9.1

8.9

8.3

8.2

7.6

7.2

7.1

6.7

6.3

6.2

6.1

5.5

5.4

5.1

4.7

4.6

4.1

DD CC.6 CC BB AA

3.7

3.6

3.2

5.7

9*

N7

F

F

F F

F

F

F

2 2

1 41 4

4 1 3

4 1

22 22

2 2

2 2

E-411-1.1

E-411-1.1

E-411-1.1

ROUTE IN BETWEEN

AND OVER DUCTS.

8"x4"

"x

6"x2"

TRANSITION 6 INCH TRAY

BELOW EXISITING TRAY.

6"x2"

6"x2"

"x

"x

"x

6"x2"

6"x2"

"x

12"x4"

12"x4"

8"x4"

8"x4"

8"x4"

"x

"x

8"x4"

ECT

ECT

ECT ECT

E C

T E

C T

E C

T

"x

"x

"x

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:3

P

M

EP-112-1.1

FLOOR PLAN - FIRST FLOOR -

AREA 2

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

1ST FLOOR_PA_NW_ELEC_AREA 2

GENERAL SHEET NOTES

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. ROUTE CABLE TRAY ABOVE EXISTING TRAY.

3. PROVIDE (3) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

4. FEEDERS FROM BELOW TO PANELBOARDS PP1-Y10.2-120VC AND

PP1-Y10.2-120VN. CORE DRILL FLOOR FOR CONDUITS. X-RAY

FLOOR TO VERIFY LOCATION.

5. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

G196E

G194B

G195G196DG196CG196BG196AG181

G196H G196G G196F

G182

G184B

G

A

G184G183

G185E G185

G185CG185D G185B

G185A

G188 G190

G189 G190A

G191

G194G197AG197G197B

3.6

3.2

2.8

2.7

1.9

1.6

1.09

0.9

0.5

Z X.5 W V U.2 U

B

0.5

0.9 T

F

4 3 3 4

2 2

2 2 2

2 2

3 4 4

2 2

"x

ECT ECT

ECT ECT

E C

T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:3

P

M

EP-113-1.1

FLOOR PLAN - FIRST FLOOR -

AREA 2A

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

1ST FLOOR_PA_NW_ELEC_AREA 2A

GENERAL SHEET NOTES

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

A158A160A161 A159

C168 C170 C171

C174

C175

C173

C172C167C146 C137C125C126C127C128

C136

C124

C123

C133

C134

C113

C111

C112

C114

C115

C116

C117

C118

C119

C132

C120 C121 C122

B168

B172

B176

B176C

B176B

B176A

B152

B148

B154 B167B

B160

B164

B166

B167A B167

B129

B128

B165

B136B

B136B132

B136A

B175A

B112AB108

B108A

B107A

B107

B104 B105

B109 B110 B112

B135

B133

A103

B150

C1A8

A153

A152A

A191

A149

A148A187A188

C1A9

A167

A162

A165

A166

A168

G153

B176D

C135

G196E

G194B

B106

B131A

B131B

B

B179

B126 B129

B174

C B

B119

B170

C168 B121 B120 B122

C1B4

B127

B128

B130 B131 B164

B165

C

B

B123

C176

D149

D101

A189

A147

A106A107

A194

A110

A117G

A117F

A117E

A117A

A117B A116

A115

A116A

A153C

A117C

C1A7

A156C

A156B

A156A

A157

A101

A102A108A109A111A112A113A114

A153B

B149

A186

C1A2

A193 A192

D102H D102K

D104

D102L

D

A

D

D102A

D102B

D102C

D102D

D102G D103

E102G

A163

B139

C1E14

E102J E102K

B146

E108B

E105

C1A1

E102H

E104

E107

E108

B139A

E102

E103

E108C

B145

B116

B116A

B138B134

B137

B132A

B166A

C

B

B152A

B173

B134A

A172 A171 A169

B175

B160A

EXIST.

TELECOM

A153A

BREAK

ROOM

EXIST.

TELECOM

B144A

LOCKERS

B143

EXIST.

TOILET

B144B

ELECTRIC

SHAFT

D202A

UPDN

UP

DN

UP

E X

T

E X

T

NG

NG

NG NG NG

NGNGNG

MV MV MV MV

MV

MV

MV

MV

O2 O2 O2 O2

O2

O2

O2

MA MA MA MA

MA

MA

MA MA MA MA

MAMAMAMA

MA

Sb Nb Mb FaT S R Q P Na N M La L K Jb J Hb H Ga G F

FE

T V

REFG.

REFG.

2 23

3 2 22

2 2 2 2 2 2 2 2

2 2

3 2

2 2

2 2

2 2

2 3

2 2 2

2 2

2 2 2

2 2

2 2

2 2

2 2

2 2 2 2

2 4

E-410-1.1

E-410-1.1

E-410-1.1

E-410-1.1

TRANSITION TRAY TO

MATCH HEIGHT OF

TRAY IN CORRIDOR.

"x

12"x12"

12"x4"

"x

12"x4"

RUN TRAY HIGH ABOVE

OR ADJACENT TO

EXISITING J-HOOKS.

BOTTOM OF TRAY AT LEAST 16

INCHES ABOVE CEILING.

TRANSITION OVER DUCT.

BOTTOM OF TRAY MINIMUM

24 INCHES ABOVE CEILING.

WATERFALL CABLES AND ROUTE

CABLE TRAY CLOSE TO WEST WALL.

TRANSITION

ABOVE PIPES.

"x

TRANSITION TRAY BELOW EXISITING

ROUTE TRAY HIGH.

NEW TRAY RAN BELOW EXISTING

TRAY. ENDS AT 24 INCH TRAY

TRANSITION TRAY TO MID

HEIGHT ABOVE CEILING.

ECT

ECT

ECT ECT

ECT ECT

ECT

E C

T

E C

T

E C

T

E C

T

TRANSITION TRAY HIGH.

"x

"x

CONNECT TO EXISTING TRAY

"x

6"x2"

6"x2" 12"x2"

"x

"x

"x

12"x2"

"x

12"x2"

"x

12"x2"

12"x2"

12"x2"

"x

18"x4"

"x

12"x4"

"x

12"x2"

12"x2"

12"x2"

6 6

ROUTE CLOSE TO WALL

HIGHER THAN ADJACENT

CABLE TRAY.

"x

12"x2"

CEILING OFFSETS HIGHER.

WATERFALL BELOW PIPE

INTO LOWER TRAY.

WATERFALL CABLES INTO EXISTING TRAY.

12"x2"

"x

"x

12"x2"

18"x4"

18"x4" 12"x4"

E-400-1.B

12"x2"

12"x4"

E-410-1.1

ECTECTECT

ECT

E C

T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:3

P

M

EP-114-1.1

FLOOR PLAN - FIRST FLOOR -

AREA 3 & 4

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

1ST FLOOR_PA_NW_ELEC_AREA 3 & 4

GENERAL SHEET NOTES

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. ROUTE CABLE TRAY ABOVE EXISTING TRAY.

3. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

4. PROVIDE (4) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

5. ROUTE CABLE TRAY OVER DUCT AND PROVIDE CABLE

WATERFALL.

6. ROUTE TRAY BELOW DUCT AND THEN BACK UP.

7. RELOCATE ELECTRICAL CONDUITS TO INSTALL A SECTION OF

TRAY ABOVE DUCTS WITH WATERFALLS ON BOTH ENDS.

8. FEEDERS FOR PANELBOARDS PP1-Jb4.4-120VC AND PP1-Jb4.4

120VN FROM DISTRIBUTION PANELBOARDS DPS-L7-120VN AND

DP2-L7-120VC. ROUTE CONDUITS ABOVE CEILING. VERIFY ROUTE

PRIOR TO ROUGH-IN AND PROVIDE PULLBOXES IN ACCESSIBLE

CEILING SPACE.

9. PROVIDE (4) 4 INCH CONDUIT ACROSS HARD CEILING. REMOVE,

PATCH, AND PAINT CEILING AS REQUIRED TO INSTALL CONDUITS.

10. CORE DRILL OR CUT AND PATCH WALL FOR CONDUIT. SEAL

WALL MATCHING EXISTING WALL RATING.

11. PROVIDE (3) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

12. CORE DRILL FLOOR FOR CONDUITS. X-RAY FLOOR TO VERIFY

LOCATION.

D125

D107

D124

D124A

D126

D127

D128

D129D129B

D100A

C182 C103 C102C1C2

C192

C191

C189 C184

C188

C185

C187

C186

C193

C180

C181

D194

C107

C142AC142C140AC140C139C138

C137A

C135

C134B

C136

C

A

C133B C1C10

C132

C106

C109

C179

D198

D199C

D199B

D193A

D193

D

E

D199

D183 D182 D155

D181

D180

C1C23

D

A

D

C

C

D179

D

B

D194A D189D

D185

D

C

D186

D187

D194

D199A

D195A

C152

D195

C1D23

D191 D190 D189 D170

D134

D152

D159B

D160

D161

D158

D157

C

D

D162

D156

D154 D153

D153A

D163

D175

D173 D174

D164

D165

D173A

D166D167D168

C1D21

D169

D172A

D172D171

D171A

C133

C104

C110

C1C1 D101B

D150

D151B

C143

C101

C

C

C101C

D129C

D151

D151C

C101D

C1D5

C198

C1C9

C D

D102F

D102E

C D

C1D4

C137

C144

C1C2

EXISTING

U/C WAITING

C178

EXIST.

TELECOM

C105

UP

DNUP UPDN

UP

DN

DN

FaMbNb

13.4

EaFGGaHHaJJaKLLaMNNaPQRRaRbSSbT

2 2

2 3

2 2

2 2

2 2 2 3 2 2 2

2 2

2 2 2

2 2

2 2

2 2

2 22

2 2

2 2

2 2

2 2

2 2

2 2 2

2 2 2 2

6 3

2 2 2 2

E-411-1.1

E-411-1.1

E-411-1.1

E-411-1.1

12"x2"

ROUTE CABLE TRAY

BELOW EXISTING TRAY.

12"x4"

"x

12"x2"

12"x2"

PROVIDE NEW TRAY TO FILL

IN BREAK IN EXISTING TRAY.

"x

6"x4"

6"x4"

"x

6"x4"

"x

6"x4"

"x

6"x4"

6"x4"

6"x4"

"x

PROVIDE NEW TRAY TO FILL

IN BREAK IN EXISTING TRAY.

"x

12"x4"

12"x4"

12"x4"

12"x4" 12"x2"

"x

ECT ECT

ECT

ECT

ECT

ECT ECT

ECT ECT

ECT

ECT

ECT

E C

T

E C

T

E C

T

ECT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:4

P

M

EP-115-1.1

FLOOR PLAN - FIRST FLOOR -

AREA 3A & 4A

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

1ST FLOOR_PA_NW_ELEC_AREA 3A & 4A

GENERAL SHEET NOTES

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. ROUTE CABLE TRAY ABOVE EXISTING TRAY.

3. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

4. PROVIDE (3) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

5. ROUTE CABLE TRAY OVER DUCT AND PROVIDE CABLE

WATERFALL.

6. ROUTE TRAY BELOW DUCT AND THEN BACK UP.

7. RELOCATE ELECTRICAL CONDUITS TO INSTALL A SECTION OF

TRAY ABOVE DUCTS WITH WATERFALLS ON BOTH ENDS.

8. FEEDERS FROM DPB-H13-120VC AND DPB-H13-120VN TO PP2-

F09-120VC, PP2-F09-120VN, DS2-F09-120VC, AND DS2-F09-120VN.

9. FEEDER FROM DPB-J13-277VN TO PP2-F13-480VN. REMOVE WALL

AS NEEDED FOR ACCESS TO SHAFTWAY. PATCH AND PAINT

WALL WHEN WORK IS COMPLETE.

10. CORE DRILL FLOOR FOR CONDUITS. X-RAY FLOOR TO VERIFY

LOCATION.

A128A

A128B

A144G

C

A

A136

A184

A183

A179

C

A

A144B

A177

A144C

A174 A176

D

A130

D117

D118C

D118

D105 C1A10

C

A

A145

D102L

D106

D130 D120

E102L

A

A139

A138 A146

A142

C

A

A141

A140

A141BA141A

A133

A131

C1E29

C

A

A126A124A122 A

A

A

A119A A121 A123 A125

C1A3

A118

A

A

A128

C1E30

A143

A142A

A144

A137

A144A

DN

UP

DN

DN

SLOPE

DN

Eb AaD C B

1.09

1.1

1.7

2.2

2.8

1.9

3.1

3.7

4.4

4.6

5.4

5.5

6.3

6.7

7.2

8.2

Ea E A

F

F

2 2 2 2 2

2 2

2 2

2 2

2 2

24 4

D115D118BD118A

D122

D123 D119A

D108

D119

D115A

D114

D113D112D111D110D109D107

D121

C D

UP

DN

8.2

9.1

10.4

22 222

2 2 2 2 2

24 4

2 2

12"x2"

THIS TRAY RUN MINIMUM

12 INCHES ABOVE CEILING.

ROUTE NEW TRAY

HIGHER THAN

EXISTING TRAY.

WATERFALL CABLES.

ROUTE CABLE TRAY LOW.

ECT ECT

ECT

E C

T

E C

T E

C T

12"x2"

"x

12"x2"

"x

"x

12"x2"

"x

"x

12"x2" 12"x2"

"x

"x

3 3

12"x2" 6"x2"

"x

"x

ECTECT

E C

T

ECT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:4

P

M

EP-116-1.1

FLOOR PLAN - FIRST FLOOR -

AREA 5

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

1ST FLOOR_PA_NW_ELEC_AREA 5

1/8" = 1'-0"

1ST FLOOR_PA_NW_ELEC_AREA 5A

GENERAL SHEET NOTES

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. ROUTE CABLE TRAY ABOVE EXISTING TRAY.

3. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

4. REMOVE ABANDONDED CONDUIT ABOVE CEILING IN CORRIDOR.

5. PROVIDE (3) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

C2E7

F210 F211 F212 F214 F215 F217 F235 F236

F239 F240 F267 F266 F265

F269

C2F23

F268 F264 F263

F210A

C2F3

F204

C2F1

F201

F202

F206DF206C

C2F7

F203

E202

F224

C2F8

F206AF206B

F205

F242

F237

F206

F207

C2F20

E201

C2F20

F256

F245

F241

C 2F

F231

F223

C2F14 F257

F230

F232

F219

F238

F233

C2F16

F234

F243

F246

C 2F

E207

E204A

F209

C2F4

C2F6

F216

F208

C 2F

F209A

C2E6

F247

F244

C2F17

F225

F228

E209

E205A C2E3

E222E223E225E226

F218

C2F12

F222

C 2E

E224A

E214

E213

E205

F221

C2F19

F227

F222A

E208

E217

E212E211

E

C 2E

C 2F

F250

F255

F226

E216E255

C2E1 E253

E220

F211A

F248

F249

C 2F

F220

E211A

E254

E210

F256

C 2F

F213A

F213

E221

E219

E218

C 2F

E215

F252

F257

F260F271

F261F270

F262

C 2F

F258F273

F259F272

F229

F200

F274

E209A

F275

F213B

E241

E239

E237

E236

C2E9

C2E11

E227E229

E232E233E234E235

E238 C2E16

C2E14

C 2E

E244

E240

E242 E243 E249

C2E18

E245

C 2E

E246

E247

E248 E250

E231

E228

C2E13

E251 E252

F251

F253

EXIST.

ELEV. LOBBY

C2E10

EXIST.

TELECOM

E203

#10

#9

#11

DN

UP

DN

PATIENT ED

2 3

2 3 4 5 6 7 8 9 10 11 11.6 12

H

G.5

G

F.2

F

E

D.8

D

C

B

A4 5 6 7 8 9 11 12

5.6 6.3 10.6 11.5 12.1

F.9

F.1

E.4

E.1

D.5

5.6 6.3 11.5

F

F E

FE

F

F

F

F

F

T V

2 2 2222222 4 8

22 2

2 2

2222222

2 2 2

2 2

22222 2

2 2 2

2 2 2

2 2 2

2 2 2 2

2 2

2 2 2 2 2 2

E-420-1.2

E-420-1.2

E-420-1.2

12"x2"

PROVIDE ADDITIONAL

4 INCH CONDUIT

SLEEVE.

12"x4"

"x

"x

12"x2"12"x2"

12"x2"

"x

"x

"x

12"x4"

12"x4"

"x

"x

"x

12"x2"

"x

"x

ECT

E C

T

E C

T

E C

T E

C T

E C

T

E C

T

E C

T E

C T

E C

T

E C

T

ECT ECT ECT

ECT

ECT

ECT

ECT

ECT ECT

E C

T

E C

T

E C

T

12"x2"

"x

12"x2" 12"x6"

"x

"x

"x

TRANSITION ABOVE

THEN WATERFALL

CABLE TO CONTINUE

"x

12"x2"

12"x2"

"x

12"x2"

CONNECT TO EXISITING TRAY.

"x

CONNECT TO EXISITING TRAY.

CONNECT TO EXISITING TRAY.

E C

T E

C T

12"x2"

EXISTING PNLBD PP2-D10-120VN-2

EXISTING PNLBD PP2-D10-120VN

E C

T

12"x2"

E C

T

ECT ECT

8 9

3 3

E C

T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:5

P

M

EP-120-1.2

FLOOR PLAN - SECOND FLOOR -

AREA 1

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

2ND FLOOR_PA_NW_ELEC_AREA 1

GENERAL SHEET NOTES

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. ROUTE CABLE TRAY ABOVE EXISTING TRAY.

3. PROVIDE (2) 4 INCH STI FIRE STOP EZ PATH PATHWAYS.

4. PROVIDE (4) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

5. FEEDER TO PANELBOARD PP2-D7-120VC. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

6. FEEDER TO PANELBOARD PP2-D7-120VN. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

7. FEEDER GOING UP TO PANELBOARD PP3-D2-120VC. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

8. CORE DRILL OR CUT AND PATCH WALL FOR CONDUIT. SEAL

WALL MATCHING EXISTING WALL RATING.

9. CUT AND PATCH WALL TO OBTAIN ACCESS INTO VOID SPACE TO

ROUTE CONDUIT.

10. CORE DRILL FLOOR FOR CONDUITS. X-RAY FLOOR TO VERIFY

LOCATION.

11. PROVIDE STI FIRE STOP PILLOWS FOR EXISTING CABLE TRAY

AND CABLES TO RUN THROUGH WALL.

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

C219

C220

S T

R

C218

C216

C217

C215

C214

C213

C211

C209 C209A

C210 C208 C207 C206 C205 C204 C203

C207A C2B2 C203A

B211

B212

B209

B208

B207

B212A

B227 B228 B230 B232

B206

B235

B205

B236

B204

C2B4

B237B234B233B231B229B226B223

B225

B224

B213

B215

B214

B216

B217

C 2B

C212

C 2C

UP

DN

#13 #12

DN UP

1-2

STOR

G200

G202

G201

G203

OPEN TO

ROOF

ACCESS

10.4

10.2 10.1

9.1

8.9

8.2

7.6

7.2

6.3

5.1

4.1

3.6

8.3

6.1

7.1

4.7

4.5

U.5 UVWW.4XYZ 10.5

6.7

6.3

6.2

5.7

5.5

5.4

4.6

3.7

2.8

F

4 4

2 22

22 2

2 22

22 2

2 22

22 2

2 22

22 2

2 22

22 2

2 2 2 2

22 2

22 2

22 2

2 22

1111 1

22 222

2 2 2 2

B216

B217

B218

C 2B

B221B

B219

B220

B221A

B221

B245

S T

R

B222 B222A

B221D

DN

UP

T S R

2.8

1.9

1.1

Sb Qa

22 2

22 2

22 2

"x

ECT

E C

T

"x

12"x4"

1 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:5

P

M

EP-121-1.2

FLOOR PLAN - SECOND FLOOR -

AREA 2 & 3

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

2ND FLOOR_PA_NW_ELEC_AREA 2

1/8" = 1'-0"

2ND FLOOR_PA_NW_ELEC_AREA 3

GENERAL SHEET NOTES

KEYED NOTES

1. REMOVE AND REPLACE HARD CEILING IN ROOM. MATCH

EXISTING.

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

D206A

C201C

C201B

D202

D202B

D212

D201

D206

D205A

D201A

D203

D204 D219C

D219B

D219

D220

D219H

D219G

D219F

A223

A223A

A223C

A225A222A

A220

A226A205A207

A204

C2E8

C203

B236

B204

B238

B203

B239A

B239

B241

A212

B200

B242A201

A200

B237

D219E

C201

C201D

C202

C201F

C201A

B201B A214 A215

A209

C2A05

C 2A

A202 A203 A218

D219D

A200A

A219

C2A03

A208

A216

A212

STR #1

C 2A

A222

A200

C2B4A

A201B C2A02

A200A

A206A

C2A01

A211

A223B

A223D

A221

C2A09

EXIST.

TELECOM

A217

#2#3 #1

#4

#5

UPDN

UP

OPEN TO

ROOF ACCESS

N7

N2

Na N M L K J H G FJb HbNb Ma Fa

3 2 1

6 5 4

0 #

0 #

BMS

BMS

ANT

TTB

4 3

3 3 22

2 4

E-420-1.2

E-420-1.2

E-420-1.2

4 - 4 INCH CONDUITS

TIGHT TO CEILING.

3 - 4 INCH CONDUITS

TIGHT TO CEILING.

2 - 4 INCH CONDUITS .

8"x6"

8"x6"

12"x4"

"x

12"x6"

"x

18"x4"

24"x4"

"x

"x

18"x4"

"x

12"x4"

"x

12"x4"

8"x2" TRAY BELOW 12 INCH TRAY

"x

12"x6"

"x

18"x4"

"x

18"x4"

ROUTE ABOVE DUCT

"x

"x

12"x4"

E C

T

E C

T

E C

T

E C

T

ECT

E C

T E

C T

E C

T

E C

T

E C

T

ECTECT

ECT

ECT

ECT

ECTECT

ECTECT

ECT

8"x2" TRAY BELOW 12 INCH TRAY

12"x2"

E-400-1.B

E-400-1.B

E C

T

12"x4"

"x

18"x4"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:5

P

M

EP-122-1.2

FLOOR PLAN - SECOND FLOOR -

AREA 4

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

2ND FLOOR_PA_NW_ELEC_AREA 4

GENERAL SHEET NOTES

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. ROUTE CABLE TRAY ABOVE EXISTING TRAY.

3. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

4. PROVIDE (3) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

5. RELOCATE OCCUPANCY SENSOR IN ROOM AND PROVIDE A NEW

2X2 CEILING TILE.

6. FEEDERS FOR PANELBOARDS PP2-Jb5.4-120VC AND PP2- Jb5.4-120VN FROM DISTRIBUTION PANELBOARDS DPS-L7-120VN

AND DP2-L7-120VC. ROUTE CONDUITS ABOVE CEILING VERIFY

ROUTE PRIOR TO ROUGH-IN AND PROVIDE PULLBOXES IN

ACCESSIBLE CEILING SPACE.

7. PROVIDE TWO SETS OF (4) 4 INCH STI FIRE STOP EZ-PATH

PATHWAYS.

8. CUT WALLS ABOVE CEILING ON BOTH SIDES OF CORRIDOR AND

PATCH TO MATCH EXISTING RATING.

9. PROVIDE CONDUITS TO CROSS CORRIDOR. PROVIDE 4 INCH FIRE

STOP PLUG IN EACH CONDUIT ON EACH END.

10. PROVIDE CONDUITS TO ROUTE FROM CABLE TRAY HIGH ABOVE

DUCT AND WATERFALL CABLES DOWN INTO CORRIDOR CABLE

TRAY.

11. CORE DRILL OR CUT AND PATCH WALL FOR CONDUIT. SEAL

WALL MATCHING EXISTING WALL RATING.

12. PROVIDE STI FIRE STOP PILLOWS FOR EXISTING CABLE TRAY

AND CABLE TO RUN THROUGH WALL.

13. MULTIPLE SECTIONS WILL BE NEEDED TO START HIGH ON EAST

SIDE AND THEN WATERFALL DOWN LOW TO WEST SIDE.

14. PROVIDE (3) 4 INCH CONDUITS HIGH IN CEILING ABOVE CABLE

TRAY.

15. PROVIDE (4) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

C235BC235AC234C233C232

C227

C252

C249E

C251

C257 C237A

C237

C235

C256 C236

C255 C238

C239

C241

C240C254

C253 C242 C243

C250

C249C

C249

C227B

C227A C249D

C247

C 2C

C225

C224

C223

C222

C246

C2C3

C249B

C249A

C221

C 2D

D212A D212D

D212B D212E

D212C D212F D205C

D205B

D200A

D205

D206A

D207C D207B

D209A

D219E

D213A

C2D3

D210

D214 D215

C 2D

D213C

D213E

D218

D218C D218B D218A

D217

D213G

D218

C2C1

C 2C

C 2C

C226

D213J

D213K

D213H

D213F

D213B

D213L

D207

D216D

C230

C231

C226A

C226B

C227C

C229

D208

EXIST.

DATA CENTER

D216

#6

UPDNDNUP

UP

DN

EaFGHJKLMN GaHaJaLa EbFaMa

F

3 3

3 3

3 3

3 3

1 2

2 4

3 4

E-421-1.2

E-421-1.2

"x

7 - 4 INCH CONDUITS

RAN HIGH.

CONNECT TO EXISITING TRAY.

12"x2"12"x2"

12"x2"

"x

12"x2"

"x

ECT

CONNECT TO EXISITING TRAY.

ECT

ECT ECT

ECT

ECT

ECT

ECT

ECT

E C

T

E C

T E

C T

E C

T

E C

T

E C

T

"x

EXISTING MCC-M10-480VQ

12"x4"

999999

11 11

18"x4" 18"x4"

"x

"x

4"x2"

E C

T

18"x4"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:0

P

M

EP-123-1.2

FLOOR PLAN - SECOND LEVEL -

AREA 4A

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

2ND FLOOR_PA_NW_ELEC_AREA 4A

GENERAL SHEET NOTES

KEYED NOTES

1. PROVIDE TEMPORARY CABLE SUPPORTS ABOVE EXISTING TRAY

FOR NEW CABLES.

2. PROVIDE (2) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

3. FEEDERS FROM DPB-H13-120VC AND DPB-H13-120VN TO PP2-

F09-120VC AND PP2-F09-120VN.

4. FEEDERS FROM DPB-H13-120VC AND DPB-H13-120VN TO DS2-

F09-120VC AND DS2-F09-120VN.

5. FEEDER FROM DPB-J13-277VN TO PP2-F13-480VN.

6. FEEDERS FROM EXISTING MCC2-M10-480VQ TO PP2-F13-480VN.

7. CUT WALLS ABOVE CEILINGS ON BOTH SIDES OF CORRIDOR AND

PATCH TO MATCH EXISTING RATING.

8. PROVIDE CONDUITS TO CROSS CORRIDOR. PROVIDE 4 INCH FIRE

STOP PLUG IN EACH CONDUIT ON EACH END.

9. CUT AND PATCH WALL FOR CONDUIT. SEAL WALL MACTCHING

EXISTING WALL.

10. CORE DRILL FLOOR FOR CONDUITS. X-RAY FLOOR TO VERIFY

LOCATION.

11. PROVIDE (4) 4 INCH STI FIRE STOP EZ-PATH PATHWAYS.

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

C2A6

D221

D222

A258 A257

A228 A230

A256 A255

A232 A234

A254

D226

A253

A236

A235 A233A229A227A225

D221A

A246

A244A

A244

C 2A

A241

A252A

A252

A251

A251A

D229

D227A D227

D228

D229A

D231A

D231

C 2D

D232

D230

D233 D235 D235A

D237

D239

D241

D238

S T

R

D240

D234

C2A4

D236

DN

UP

W

D

5.5

6.3

7.2

8.2

9.1

10.4

2.8

3.7

4.4

4.6

5.4

6.2

6.7

10.1

10.5

F

2 2

2 2

2 2

2 2 2

2 2

2 2

2 2 2

2 2

A249A

A249

A246

A244A

A250

S T

R

DN

UP

PATIENT ED

W

D

B AC

1.9

2.8

3.7

1.1

Aa

F

2 2

12"x2"

"x

12"x4"

12"x2"

12"x2"

"x

"x

12"x2"

"x

ECT

ECT

E C

T E

C T

E C

T

E C

T

12"x2"

E C

T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:0

P

M

EP-124-1.2

FLOOR PLAN - SECOND LEVEL -

AREA 5

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

2ND FLOOR_PA_NW_ELEC_AREA 5

GENERAL SHEET NOTES

KEYED NOTES

1. MATCH EXISTING CABLE TRAY HEIGHT AND PROVIDE NEW TRAY

TO THE END OF THE CORRIDOR.

2. REPLACE (2) 2X4 FLOURESCENT LIGHT FIXTURES IN ROOM WITH

(2) 2X2 LED FIXTURES. PROVIDE (2) 2X2 ACCESS PANELS IN

CEILING.

1. REFER TO DRAWING EP-510 FOR CABLE TRAY DETAILS AND

CABLE TRAY GENERAL NOTES.

C3F3

E312

E306

E308

E310

E311

E329 E332 E333 E334 E338

E339

E340

E341

E337E336

E331

E328

E327

E324

E323 E322

E321

E319

C3E2

E320

E318 E317

C3F1

E316

E315 E314

E313

E300 E301

E301A

E307

E304

C3F5

E305

E309

F396

F395

F397

F370

F367

F300

F303

F302

F322

F304

F307

F 8 F305

F309F310

F312.1

F312

S T

R

F .2 F311

E325

C E

C3E4

C E

E330

E335

F348 F346 F345 F343 F340 F339 F338 F337

C3F9

F349

F350

F321

F320

F317

F316

C F

F347 F344

F342 F341

F336

F324 F325 F326

F334

F333

F335

F332

F331

F330 F329

F328F327

F323

F318

F314

F315

C3F7

C F

F352 F353 F354 F355 F356 F357

F393

F392

F391

F389

F388 F385

F382

F381 F380

F364

C3F17

F361

F360 F358

F365

F362

F366

F369

F373

F376 F378

F387

F375

F363

C F

F390

F383

F371

F377

C3F11

C3F15

F372

C F

F359

F368

F386

F379

F319

CSF13

EXIST.

TELECOM

E326

#11

#10

#9

DN

UP

DN

DN

UP

OPEN TO

ROOF ACCESS

ISTL

TTB

2 2

2 2

2 2

2 2 2

2 2

2 2 2

2 2

2NOT IN SCOPE.

PROJECT XXXX-XX-XXX

2 2

2 2 2 2 2 2 2 1

2 2

2 2

2 2 2

2 2

2 2

2 2

2 2

E-431-1.3

E-431-1.3

E-431-1.3

EXISTING PNLB

PP3-D2-120VN

SECT. 2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENT

FULLY SPRINKLERED

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

PROJECT MANAGEMENTCONSULTANT

321 4 5 6 7 8 9 10

6 S. OLD ORCHARD AVE.

WEBSTER GROVES, MO 63119

PHONE #: 314-918-8383

Consultant POC

KEY PLAN

8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com

Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com

D U s e rs

\c b a c h e s ta

\D o c u m e n ts

\0

-M E

P F

P -H

O S

-R c b a c h e s ta

T

T

P .r v t

/2

/2

:2

:0

P

M

EP-130-1.3

FLOOR PLAN - THIRD FLOOR -

AREA 1

EHRM INFRASTRUCTURE

UPGRADES - COLUMBIA, MO

800 HOSPITAL DR.

COLUMBIA, MO 65201

589A4-21-700

1/25/2022 GNF CRB

1/8" = 1'-0"

3RD FLOOR_PA_NW_ELEC_AREA 1

KEYED NOTES

1. FEEDER TO PANELBOARD PP3-D2-120VC. FEEDER SHALL BE

ROUTED AS HIGH AS POSSIBLE IN CEILING SPACE. PROVIDE

PULLBOXES IN ACCESSIBLE LOCATIONS. PATH SHOWN IS INTENT

AND SHALL BE VERIFIED PRIOR TO PURCHASING MATERIALS AND

INSTALLATION.

2. FEEDER TO PANELBOARD PP3-D2-120VN.