This document provides details on a federal solicitation and related construction project. The solicitation number is 36C77622R0069 from the Department of Veterans Affairs Technology Acquisition Center Austin for the Y1DZ--589A4-21-700 EHRM Infrastructure Upgrades Construction project in Columbia, MO. The contractor will be required to provide all labor, project management, materials, tools, supplies, and equipment as drawn in the specifications for the EHRM Infrastructure Upgrades Construction project. The final drawings for part 9 of the project are referenced but not included.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXIST.
TELECOM
A056A
OFFICE
STORAGE
A060B
TELECOM
ROOM
A060
TELECOM
DEMARK ENTRANCE
A060A
A058
B013
B013A
B011B
B011A
B011C B011D B011E B011F B011G
B011
B011H
B011J B009
B007
B010
B010A
B006C
B006
B006B
B006A
B009A
B034 B036
A056
STR #1
B024 B019
B026 B023
B014
B016
B018
B022 B021
B017
B045
B015
B012
B046A
B047 B046 B049
B050
C B
A
B051B048B042B039AB039
CBB3
A055
A054B
A004
A001
A002
A003
CBA2
A007 A009
CBA3 CBA4
A005
A004A
A006 A008A A008
A012
A013
A047
CBA8
D004L
A048
A049
A006A
A051
A51A
A050
CBA9
A052
CBA10
A053
A059A
A059
A057
D004M
D004N
D002
D001B
D001A
D001
D004E
D004B
D004AD004O
D003
D003B
D004G
CBB1
B037
A009A
B002D
B002G
B002F
B002K
B002A
B002
B001F
B002E
C009D
C009
C009B
C001
C009A
B001E
B001B
B001D
B
1C
B001A
C001A C001C
C001D
CBD1
C B
B
A054
A016A
A016
DN
UP
DN
UP
#4
#5
#7
#8
#1#2#3
REX
FX-401-C-1.B
FX-401-C-1.B
1 1 1 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:1
P
M
FX-105-C-1.B
FIRE PROTECTION BASEMENT
FLOOR PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - BASEMENT FIRE PROTECTION - AREA 3 & 4
04 8 16268
SCALE: 1/8"=1'-0"
KEYED NOTES
1. EXISTING CEILING TO BE REMOVED AND REPLACED. CONTRACTOR TO
VERIFY EXISTING SPRINKLER HEADS AND REWORK AS REQUIRED.
PLAN NORTH
Revisions: Date:
A158
F175
F174C
F174B
F174A
A160A161 A159
A128A
A128B
C1E33
C1E31
E109 E110E125F
E125EC1E24
E125DE125CE125BE125A
E124
E123
E126
C E
E133
E122 E121 E120
E117
E116
E115
E114
E130
E131
E132
E112
E111
E129
E127
A144G
C A
A136
A184
A183
A179
C A
A144B
A177
A144C
A174 A176
D
D115D118BD118A
D122
D123
D125
D119A
D108
D119
D115A
D114
D113D112D111D110D109D107
D124
D124A
D126
D127
D128
D129D129B
D100A
C168 C170 C171
C174
C175
C173
C172C167C146
C182 C103 C102C1C2
C137C125C126C127C128
C192
C191
C189 C184
C188
C185
C187
C186
C193
C180
C181
D194
C107
C136
C124
C123
C133
C134
C142AC142C140AC140C139C138
C137A
C135
C134B
C136
C A
C133C
C133B C1C10
C132
C106
C109
C113
C111
C112
C114
C115
C116
C117
C118
C119
C132
C120 C121 C122
B168
B172
B176
B176C
B176B
B176A
B152
B148
B154 B167B
B160
B164
B166
B167A B167
B129
B128
B165
B136B
B136 B132
B136A
B175A
B112AB108
B108A
B107A
B107
B104 B105
B109 B110 B112
B135
B133
C1D3
A103
C179
F181
F100
D198
D199C
D199B
D193A
D193
D E
D199
D183 D182 D155
D181
D180
C1C23
D A
D
C C
D179
D B
C C
D194A D189D
D185
D C
D186
D187
D194
D199A
D195A
C152
D195
C1D23
D191 D190 D189 D170
D134
D152
D159A
D159B
D159
D160
D161
D158
D157
C D
D162
D156
D154 D153
D153A
D163 D175A
D175
D173 D174
D164
D165
D173A
D166D167D168
C1D21
D169
D172A
D172D171
D171A
D121
C133
A130
B150
D117
D118C
D118
D105 C1A10C1A8
A153
A152A
A191
A149
A148A187A188
C1A9
A167
C A
A162
A165
A166
A168
A
G
G176
G100
G101
G102
G102A
G160
G103
G
G105
G106
G
G105A
G108
G114A
G
G116
G114
G115
G113G112
G156
G173G
G111
G110
G110A
G
G148 G147 G146 G171
G145
G143A
G144
G142A
G168
G142
G170
G169
G143
G107
G136 G139
G155
G155B
G137
G138
G163 G162
G120
G121
G123
G122
G133
G127 G128
G159
G
G
G129
G130
G131
G132
G119
G124
G
G118 G161
G164A C104
G164
C110
G135 G140
G A
G193
G149
G150
G150A
G151 G153
B176D
G152
C135
G196E
G194B
G195G196DG196CG196BG196AG181
G196H G196G G196F
G182
G184B
G A
G184G183
G185E G185
G185CG185D G185B
G185A
G188 G190
G189 G190A
G191
G194G197AG197G197B
B106
B131A
B131B
B
B179
B126 B129
B174
C B
B119
B170
C169
C168 B121 B120 B122
C1B4
B127
B128
B130 B131 B164
B165
C B
B123
C176
D149
D101
C1C1 D101B
D150
D151B
C143
C101
C C
C101C
D129C
D151
D151C
C101D
C1D5
C198
C1C9
A189
A147
A106A107
A194
A110
A117G
A117F
A117E
A117A
A117B A116
A115
C B
A116A
A153C
A117C
C1A7 A117D
A156C
A156B
A156A
A157
A101
A102A108A109A111A112A113A114
C E
A145
A153B
B149
A186
C1A2
E137
A193 A192
G192
D102H D102K
D104
D102L
D106
D130
D A
C D
D
D102A
D102B
D102C
D102D D120
D102F
D102E
C D
C1D4
D102G D103
C137
C144
E102LE102G
C1E35
A
A139
A138 A146
A142
C A
A141
A140
A141BA141A
A133
A131
C1E29
F176
F174
E102F E102E E102D E102C E102B E102A
A163
F129
F135
B139
E-1100
C1E14
E102J E102K
F104
E-1204
F171
F128
F134
B146
C1E13
E108B
E105
C1A1
F122
C1E21
F171A
F150
F101
F125
E102H
E104
E107
E108
B139A
C F
F123
F151B
F102
F126
E102
E103
E106
E108C
B145
C1F11
F124
F151A
C1F7
C1E12
E144
E140
F168
B116
F137A
C1F7
F121
F137
B116A
F169
E146
E148
E138
C1E11
C1F1
C1F19
C F
C1F2
C1F21
E147
C1E8 E145
E143
F136
F118
F117
B138
F163
C1E15
F179B
F177
C1F20
F103
F160
F177A
F178
F161
B134
F116
C1F6
C F
F115
C1E16
F164
F F
E134
C1E32
C1E10
F166
F167
F165
F162
B137
C F
F109
F108
C1F8
F146
F179
F131
C1F15
F105
F113
F114A
C1F22
F170
F127 F130
F103B
F114
F132
F151
F180
F149
C1E17
F119
F107
F106
F112 F155
F147
F152
C F
C F
F144
F138
F153
F138A
F145
F148
F110 F111 F142F141F140F139 F156
C1F12 C1F13
F133
F157 F158 F159
C1F17
F142 F154
F120
E127A
B132A
B166A
C A
C1C2
C B
B152A
B173
F103A
A126A124A122
A A
A
A119A A121 A123 A125
C1A3 A129A129B
A118
A
A
A129A
A128
B134A
C1E30
A172 A171 A169
A143
A142A
B175
A144
A137
A144A
B160A
E100A
E142
E141
E100
E101
EXIST.
TELECOM
G141
EXIST.
CORRIDOR
G191
EXISTING
U/C WAITING
C178
EXIST.
TELECOM
C105
EXIST.
TELECOM
A153A
BREAK
ROOM
B144
EXIST.
TELECOM
B144A
LOCKERS
B143
EXIST.
TOILET
B144B
EXIST.
ELEV. LOBBY
C1E9
EXIST.
TELECOM
E139
ELECTRIC
SHAFT
D202A
# SF
# SF
# SF
# SF
# SF
# SF# SF
# SF
# SF
# SF
# SF
# SF # SF
# SF
# SF
# SF# SF
# SF
16 SF
A174A
A145A
A144C
A174B
A144A
A144B
A183
A184
A145B
108A1
#4
#5
#6
#10
#9
#11
#1#2#3
#14
#13 #12
#15
UP
UP
DNUP UPDN
UPDN
UP
DN
DN
UP
DN
UPUP
DN
UP
DN
DN
DN
SLOPE
DN
DN
E X
T
E
X T
E X
T
EXT30EXT36
E X
T
EXT30 EXT36
NG
NG NG
NG NG NG
NGNGNG
MV MV MV MV
MV
MV
MV
MV
M V
M V
O2 O2 O2 O2
O2
O2
O2
O
O
MA MA MA MA
MA
MA
MA MA MA MA
MAMAMAMA
MA
M A
M A
E.5
F.1
F.2
F.9
G.5
10.1 11.8
G.5
F.9
F.2
F.1
E.5
13.6
AaEbFaMbNb
13.4
13.6
13.4
Sb Nb Mb Fa Eb Aa
C
C.3
D
D.1
E
E.1
F
G
H
0 0.1 1 2 3 4 5 5.6 6 6.3 7 8 9 10 10.6 11 11.5 12 13 14
H
G
F
E.1
E
D.8
D.5
D2
D
C.3
C
B.9
D.8 D.1 C.3
D
11 11.5 12
C
B.8 B.5
B
B.1 A.1 AZ AY.8 AY AX.8
B
AX.5 AX.1 AX AW.8 AW AV.9
1.09
1.1
1.7
2.2
2.8
1.9
3.1
3.7
4.4
4.6
5.4
5.5
6.3
6.7
7.2
8.2
9.1
10.4
11.5
12.5
13.5
ABBaBbCDEEaFGGaHHaJJaKLLaMNNaPQRRaRbSSbT
13.5
12.5
11.5
UU.5VWW.4XYZAABBCCCC.6DD
10.4
10.2
9.8
9.1
8.9
8.3
8.2
7.6
7.2
7.1
6.7
6.3
6.2
6.1
5.5
5.4
5.1
4.7
4.6
4.1
DD CC.6 CC BB AA
3.7
3.6
3.2
2.8
2.7
1.9
1.6
1.09
0.9
0.5
Z X.5 W V U.2 U
B
0.5
0.9 T S
R
0.1 1
Q
2 3
P Na N M La L
4 5
K
5.6 6
Jb
6.3
J Hb
H Ga G
F Ea E
A
5.7
Bd
9*
N7
F
FE
FE
FE
FE
FE
FE
FE
F
F
F F
F
F
F
F
F
FE
FE
REFG.
REFG.
AREA 1 AREA 1A
AREA 2
AREA 2A
AREA 3
AREA 3A
AREA 5
AREA 5A
NO WORK THIS AREA
NO WORK THIS AREA
NO WORK THIS AREA
NO WORK THIS AREA
AREA 4
AREA 4A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:3
P
M
FX-106-C-1.1
FIRE PROTECTION FIRST FLOOR
OVERALL
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1" = 20'-0"
FLOOR PLAN - FIRST FLOOR FIRE PROTECTION OVERALL
E109 E110E125F
E125EC1E24
E125DE125CE125BE125A
E124
E123
E126
C
E
E133
E122 E121 E120
E117
E116
E115
E114
E130
E131
E132
E112
E111
E129
E127
F100
E137
E102F E102E E102D E102C
F129
F135
F104
E-1204
F171
F128
F134
C1E13
F122
C1E21
F150
F101
F125
C F
F123
F102
F126
E106
C1F11
F124
C1F7
C1E12
F168
F137A
C1F7
F121
F137
E148
E138
C1E11
C1F1
C1F19
C1F2
C1F21
E147
C1E8
F136
F118
F117
C1E15
C1F20
F103
F116
C1F6
C F
F115
E134
C1E10
C
F
F109
F108
C1F8
F146
F131
C1F15
F105
F113
F114A
F127 F130
F103B
F114
F132
F151
F149
F119
F107
F106
F112 F155
F147
F152
C
F
C
F
F144
F138
F153
F138A
F145
F148
F110 F111 F142F141F140F139 F156
C1F12 C1F13
F133
C1F17
F142 F154
F120
E127A
F103A
#10
#9
#11
UP
E X
T
EXT30EXT36
E X
T
EXT30 EXT36
M V
M V
O
O
M A
M A
E.5
F.1
F.2
F.9
G.5
C
C.3
D
D.1
E
E.1
F
G
H
0 0.1 1 2 3 4 5 5.6 6 6.3 7 8
B
FE
FE FE
FE
FE
FX-402-C-1.1
FX-402-C-1.1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:3
P
M
FX-107-C-1.1
FIRE PROTECTION FIRST FLOOR
PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - FIRST FLOOR FIRE PROTECTION - AREA 1
04 8 16268
SCALE: 1/8"=1'-0"
C133C
G
G176
G100
G101
G102
G102A
G160
G103
G
G105
G106
G
G105A
G108
G114A
G
G116
G114
G115
G113G112
G156
G173G
G111
G110
G110A
G
G148 G147 G146 G171
G145
G143A
G144
G142A
G168
G142
G170
G169
G143
G107
G136 G139
G155
G155B
G137
G138
G163 G162
G120
G121
G123
G122
G133
G127 G128
G159
G
G
G129
G130
G131
G132
G119
G124
G
G118 G161
G164A
G164
G135 G140
G
A
G193
G149
G150 G151 G153
B176D
G152
G192
G191
EXIST.
TELECOM
G141
#14
#13 #12
#15
UU.5VWW.4XYZAABBCCCC.6DD
10.4
10.2
9.8
9.1
8.9
8.3
8.2
7.6
7.2
7.1
6.7
6.3
6.2
6.1
5.5
5.4
5.1
4.7
4.6
4.1
5.7
N7
F
F
F F
F
F
F
FX-402-C-1.1
FX-402-C-1.1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:3
P
M
FX-108-C-1.1
FIRE PROTECTION FIRST FLOOR
PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - FIRST FLOOR FIRE PROTECTION - AREA 2
04 8 16268
SCALE: 1/8"=1'-0"
A161
C168 C170 C171
C174
C175
C173
C172C167C146
C182 C103 C102C1C2
C137C125C126C127C128
C189 C184
C136
C124
C123
C133
C134
C113
C111
C112
C114
C115
C116
C117
C118
C119
C132
C120 C121 C122
B168
B172
B176
B176C
B176B
B176A
B152
B148
B154 B167B
B160
B164
B166
B167A B167
B129
B128
B165
B136B
B136B132
B136A
B175A
B112AB108
B108A
B107A
B107
B104 B105
B109 B110 B112
B135
B133 B150
A153
A152A
A191
A162
A165
A166
C104
B176D
C135
G196E
G194B
B106
B131A
B131B
B
B179
B126 B129
B174
C B
B119
B170
C169
C168 B121 B120 B122
C1B4
B127
B128
B130 B131 B164
B165
C
B
B123
C176
D149
D101
C1C1 D101B
C143
A106A107
A194
A110
A117G
A117F
A117E
A117A
A117B A116
A115
C
B
A116A
A153C
A117C
C1A7 A117D
A156C
A156B
A156A
A157
A108A109A111A112A113A114
A153B
B149
C1A2
A193
D
A
C D
D
D102A
D102G
E102G
A163
B139
C1E14
B146
E108B
E105
C1A1
E104
E107
E108
B139A
E103
E108C
B145
B116
B116A
B138B134
B137
C1E17
B132A
B166A
C1C2
C
B
B152A
B173
B134A
B175
B160A
B144
B143
B144B
EXIST.
TELECOM
A153A
EXIST.
TELECOM
EXIST.
TELECOM
B144A
#4
#5
#1#2#3
UPDN
UP
DN
E X
T
E X
T
Sb Nb MbT S R Q P Na N M La L
4 5
K
5.6 6
Jb
6.3
J Hb
H
T V
REFG.
REFG.
FX-402-C-1.1
FX-402-C-1.1
FX-402-C-1.1
FX-402-C-1.1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:4
P
M
FX-109-C-1.1
FIRE PROTECTION FIRST FLOOR
PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - FIRST FLOOR FIRE PROTECTION - AREA 3 & 4
04 8 16268
SCALE: 1/8"=1'-0"
D100A
C182 C103 C102C1C2
C192
C191
C189 C184
C188
C185
C187
C186
C193
C180
C181
D194
C107
C142AC142C140AC140C139C138
C137A
C135
C134B
C136
C
A
C133C
C133B C1C10
C132
C106
C109
C179
D198
D199C
D199B
D193A
D193
D
E
D199
D183 D182 D155
D181
D180
C1C23
D
A
D
C
C
D179
D
B
C
C
D194A
D189D
D185
D
C
D186
D187
D194
D199A
D195A
C152
D195
C1D23
D191 D190 D189 D170
D154
D169
D171
D171A
C133
G155B
G164A C104
G164
C110
G135 G140
G
A
G193
C1C1 D101B
D150
D151B
C143
C101
C
C
C101C
D129C
D151
D151C
C101D
C1D5
C198
C1C9C137
C144
C1C2
EXIST.
TELECOM
C105
EXISTING
U/C WAITING
C178
#6
UP
DNUP
MbNb
13.4
13.6
13.4
HaJJaKLLaMNNaPQRRaRbSSbT
13.5
12.5
11.5
U
N7
FX-402-C-1.1
FX-402-C-1.1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:4
P
M
FX-110-C-1.1
FIRE PROTECTION FIRST FLOOR
PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - FIRST FLOOR FIRE PROTECTION - AREA 3A &4A
04 8 16268
SCALE: 1/8"=1'-0"
C2A6
C235BC235AC234C233C232
C227
C252
C249E
C251
C257 C237A
C237
C235
C256 C236
C255 C238
C239
C241
C240C254
C253 C242 C243
C250
C249C
C249
C227B
C227A C249D
C247
C 2C
C225
C224
C223
C222
C246
C2C3
C248
C249B
C249A
C221
C 2D
D212A D212D
D212B D212E
D212C D212F D205C
D205B
D200A
D205
D206A
D207C D207B
C201C
C201B
D202
D202B
D212
D201
D206
D205A
D201A
C 2D
D203
D204 D219C
D219B
D219
D220
D219H
D219G
D219F
D221
D222
D223
A223
A223A
A223C
A258 A257
A228 A230
A256
D224 D225
A255
A232 A234
A254
D226
A253
A236
A235 A233A229A227A225A222A
A220
A226A205A207
A204
C2E8
C219
C220
S T R
C218
C216
C217
C215
C214
C213
C211
C209 C209A
C210 C208 C207 C206 C205 C204 C203
C207A C2B2 C203A
B211
B212
B209
B208
B207
B210
B212A
B227 B228 B230 B232
B206
B235
B205
B236
B204
B238
B203
B239A
B239
B241
A212
B200
C2B4
B242A201
A200
B237B234B233B231B229B226B223
B225
B224
B213
B215
B214
B216
B217
B218
C 2B
B221B
B219
B220
B221A
B221
B245
S T R
B222 B222A
B221D
D209A
D219E
D221A
D213A
C2D3
D210
D214 D215
C 2D
D213C
D213E
D218
D218C D218B D218A
D217
D213G
D218
C2C1
C 2C
C 2C
C226
D213D
D213J
D213K
D213H
D213F
D213B
D213L
C201
C201D
C202
C201F C201E
C201A
B201B A214 A215
A209
C2A05
C 2A
A202 A203 A218
C212
C 2C
D219D
A200A
C2E7
C2E12
F210 F211 F212 F214 F215 F217 F235 F236
F239 F240 F267 F266 F265
F269
C2F23
F268 F264 F263
F210A
C2F3
F204
C2F1
F201
F202
F206DF206C
C2F7
F203
E202
F224
C2F8
F206AF206B
F205
F242
F237
F206
F207
C2F20
E201
C2F20
F256
F245
F241
C 2F
F231
F223
C2F14 F257
F230
F232
F219
F238
F233
C2F16
F234
F243
F246
C 2F
E207
E204A
F209
C2F4
C2F6
F216
F208
C 2F
F209A
E204
C2E6
F247
F244
C2F17
F225
F228
E209
E205A C2E3
E222E223E225E226
F218
C2F12
F222
C 2E
E212A
E224A
E214
E213
E205
F221
C2F19
F227
F222A
E208
E217
E212E211
E
C 2E
C 2F
F250
F255
C 2F
F226
E216E255
C2E1 E253
E220
F211A
F248
F249
C 2F
F220
E211A
E254
E210
F256
C 2F
F213A
F213
E221
E219
E218
C 2F
E215
F252
F257
F260F271
F261F270
F262
C 2F
F258F273
F259F272
F229
F200
F274
A219
E209A
F275
F213B
E241
E239
E237
E236
C2E9
C2E11
E227E229
E230E232E233E234E235
E238 C2E16
C2E14
C 2E
E244
E240
E242 E243 E249
C2E18
E245
C 2E
E246
E247
E248 E250
E231
E228
C2E13
E251 E252
A249A
A249
A246
A244A
A244
C 2A
A241
A252A
A252
A251
A251A
D229
D227A D227
D228
D229A
D231A
D231
C 2D
D232
D230
D233 D235 D235A
D237
D239
D241
D238
S T R
D240
D234
C2A4
C2A03
A208
A216
A212
STR #1
C 2A
A222
A200
C2B4A
D207
D216D
C230
C228
C231
C226A
C226B
C227C
C229
F251
F253
A250
S T R
D236
D208
A201B C2A02
A200A
A206A
C2A01
A211
A213
A210
A223B
A223D
A221
C2A09
EXIST.
ELEV. LOBBY
C2E10
EXIST.
TELECOM
E203
EXIST.
TELECOM
A217
EXIST.
DATA CENTER
D216
#10
#9
#11
#2#3 #1
#4
#5
#6
DN
UP
UPDNDNUP
UP
DN
DN
UP
DN
UP
DN
UPDN
UP
DN
DN
UP
#13 #12
DN UP
1-2
MECH
EQPM RM
STOR
G200
G202
G201
G203
OPEN TO
ROOF ACCESS
OPEN TO
ROOF
ACCESS
OPEN TO
ROOF ACCESS
OPEN TO
ROOF ACCESS
OPEN TO
ROOF ACCESS
DP-CRITICAL-1
N7
N2
N2
PATIENT ED
W
D
A
B
2 3
C
D
F
G
H
1 2 3 4 5 6 7 8 9 10 11 11.6 12
H
G.5
G
F.2
F
E
D.8
D
C
B
A4 5 6 7 8 9 11 121
5.6 6.3 10.6 11.5 12.1
F.9
F.1
E.4
E.1
D.5
E.1
D.1
5.6 6.3 11.5
UVWW.4XYZ U.5W.3
10.4
10.2 10.1
9.1
8.9
8.2
7.6
7.2
6.3
5.1
4.1
3.6
8.3
6.1
7.1
4.7
4.5
U.5
PQRST
UVWW.4XYZ
EaFGHJKLMNNa ABCDE
5.5
6.3
7.2
8.2
9.1
10.4
T S R Q P B ANa N M L K J H G F Ea E D C
1.9
2.8
3.7
4.4
4.6
5.4
6.2
6.7
10.1
10.5
11.5
12.5
13.5
BaGaHaJaLaQaRaRb
13.5
12.5
10.5
6.7
6.3
6.2
5.7
5.5
5.4
4.6
3.7
2.8
1.9
Jb Hb
1.1
13.9
AaEbFaMaNbR.1Sb
13.9
1.1
Sb Qa Nb Ma Fa Eb Aa
3 2 1
6 5 4
0 #
3 2 1
6 5 4
0 #
BMS
BMS
F
F
F E
FE
F
F
F
F
F
F F
F
T V
T V
TV
AREA 1
AREA 2
AREA 3
AREA 4
AREA 4A
AREA 5
NO WORK THIS AREA
NO WORK THIS AREA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:5
P
M
FX-111-C-1.2
FIRE PROTECTION SECOND
FLOOR OVERALL
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1" = 20'-0"
FLOOR PLAN - SECOND FLOOR FIRE PROTECTION OVERALL
E203
EXIST.
ELEV. LOBBY
C2E10
C2E7
C2E12
F210 F211 F212 F214 F215 F217 F235 F236
F239 F240 F267 F266 F265
F269
C2F23
F268 F264 F263
F210A
C2F3
F204
C2F1
F201
F202
F206DF206C
C2F7
F203
E202
F224
C2F8
F206AF206B
F205
F242
F237
F206
F207
C2F20
E201
C2F20
F256
F245
F241
C 2F
F231
F223
C2F14 F257
F230
F232
F219
F238
F233
C2F16
F234
F243
F246
C 2F
E207
E204A
F209
C2F4
C2F6
F216
F208
C 2F
F209A
E204
C2E6
F247
F244
C2F17
F225
F228
E209
E205A C2E3
E222E223E225E226
F218
C2F12
F222
C 2E
E212A
E224A
E214
E213
E205
F221
C2F19
F227
F222A
E208
E217
E212E211
E
C 2E
C 2F
F250
F255
C 2F
F226
E216E255
C2E1 E253
E220
F211A
F248
F249
C 2F
F220
E211A
E254
E210
F256
C 2F
F213A
F213
E221
E219
E218
C 2F
E215
F252
F257
F260F271
F261F270
F262
C 2F
F258F273
F259F272
F229
F200
F274
E209A
F275
F213B
E241
E239
E237
E236
C2E9
C2E11
E227E229
E230E232E233E234E235
E238 C2E16
C2E14
C 2E
E244
E240
E242 E243 E249
C2E18
E245
C 2E
E246
E247
E248 E250
E231
E228
C2E13
E251 E252
F251
F253
#10
#9
#11
2 3
2 3 4 5 6 7 8 9 10 11 11.6 12
H
G.5
G
F.2
F
E
D.8
D
C
B
A4 5 6 7 8 9 11 12
5.6 6.3 10.6 11.5 12.1
F.9
F.1
E.4
E.1
D.5
5.6 6.3 11.5
F
F E
FE
F
F
F
F
F
FX-403-C-1.2
FX-403-C-1.2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:5
P
M
FX-112-C-1.2
FIRE PROTECTION SECOND
FLOOR PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - SECOND FLOOR FIRE PROTECTION - AREA 1
04 8 16268
SCALE: 1/8"=1'-0"
D209
TELECOM
A217
EXIST.
DATA CENTER
D216
C227
C252
C249E
C251
C257 C237A
C237
C235
C256 C236
C255 C238
C239
C241
C240C254
C253 C242 C243
C250
C249C
C249
C227B
C227A C249D
C247
C 2C
C225
C224
C223
C222
C246
C2C3
C248
C249B
C249A
C221
C 2D
D212A D212D
D212B D212E
D212C D212F D205C
D205B
D200A
D205
D206A
D207C D207B
C201C
C201B
D202
D202B
D212
D201
D206
D205A
D201A
C 2D
D203
D204 D219C
D219B
D219
D220
D219H
D219G
D219F
D221
A223
A223A
A223C
A258
C203
B236
B204
B238
B203
B239A
B239
B241
A212
B200
D209A
D219E
D221A
D213A
C2D3
D210
D214 D215
C 2D
D213C
D213E
D217
D213G
D218
C2C1
C 2C
C 2C
C226
D213D
D213J
D213K
D213H
D213F
D213B
D213L
C201
C201D
C202
C201F C201E
C201A
B201B A214 A215
A209
C2A05
C 2A
D219D
A200A
A208
A216 STR #1
C 2A
A222
A200
C2B4A
D207
D216DC228
C226A
C226B
C227C
C229
D208
A211
A213
A210
A223B
A223D
A221
C2A09
#2#3 #1
#4
#5
#6
DP-CRITICAL-1
N7
N2
3 2 1
6 5 4
0 #
3 2 1
6 5 4
0 #
BMS
BMS
F
TV
FX-403-C-1.2
FX-403-C-1.2
FX-404-C-1.2
FX-404-C-1.2
FX-405-C-1.2
FX-405-C-1.2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:5
P
M
FX-113-C-1.2
FIRE PROTECTION SECOND
FLOOR PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - SECOND FLOOR FIRE PROTECTION - AREA 3A & 4A
A306A
EXIST.
OFFICE
B345
# SF
# SF
# SF
# SF
# SF
#2#3 #1
#13 #12
#11
#10
#9
#6
#7
#8 #4
#5
DN
UP
DN
UP
DN
DN
DN
DN
UPDN
DNDN
UP
DN
DN
DN
DN
UP
UP
DN
OPEN TO
ROOF ACCESS
ISTL
4 7
9 *
AREA 1
AREA 2
AREA 3
AREA 4
AREA 4A
AREA 5
NO WORK THIS AREA
NO WORK THIS AREA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:0
P
M
FX-114-C-1.3
FIRE PROTECTION THIRD FLOOR
OVERALL
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1" = 20'-0"
FLOOR PLAN - THIRD FLOOR FIRE PROTECTION OVERALL
C3F3
E312
E306
E308
E310
E311
E329 E332 E333 E334 E338
E339
E340
E341
E337E336
E331
E328
E327
E324
E323 E322
E321
E319
C3E2
E320
E318 E317
C3F1
E316
E315 E314
E313
E300 E301
E301A
E307
E304
C3F5
E305
E309
F396
F395
F397
F370
F367
F300
F303
F302
F322
F304
F307
F 8 F305
F309F310
F312.1
F312
S T
R
F .2 F311
E325
C E
C3E4
C E
E330
E335
F348 F346 F345 F343 F340 F339 F338 F337
C3F9
F349
F350
F321
F320
F317
F316
C F
F347 F344
F342 F341
F336
F324 F325 F326
F334
F333
F335
F332
F331
F330 F329
F328F327
F323
F318
F314
F315
C3F7
C F
F352 F353 F354 F355 F356 F357
F393
F392
F391
F389
F388 F385
F382
F381 F380
F364
C3F17
F361
F360 F358
F365
F362
F366
F369
F373
F376 F378
F387
F375
F363
C F
F390
F383
F371
F377
C3F11
C3F15
F372
C F
F359
F368
F386
F379
F319
CSF13
EXIST.
TELECOM
E326
#11
#10
#9
FX-406-C-1.3
FX-406-C-1.3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:0
P
M
FX-115-C-1.3
FIRE PROTECTION THIRD FLOOR
PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - THIRD FLOOR FIRE PROTECTION - AREA 1
04 8 16268
SCALE: 1/8"=1'-0"
C348A
C337A
C3B8
C302
C
C308
C
C C
C305
C319
C318
C320
C307
C306
G320
S T
R
G322G323
G315
G321
G313A
G313
G317
G324G325G327
G373
G311A
G311
G325A
G327AG330A
G347
G346
1-3
STR #G1
G355
G
G344
G300
G344A
G301
G340
C B
G302
G336
G371
G342
G330
G342A
G
G362
G375
G360
G309
G340A
G363
G307A
G305
G338
G332A
G336A
G361A
G361
G334A
G309A
G338A
G364
G334
B337
B311A
G
G359
G307
G332
G304
G301A
G303
B311
C B
B312
B312A
B330
B329
B336 B310
B310A
B326
B327
B328
B309
B309A
B307
B307A
B305
B305A
B308A B306A
B325
B324 C3B1
B308 B306 B304
B304A
B303A
B303
G329
G357
G356
EXIST.
TELECOM
C316
#13 #12
4 7
9 *
FX-406-C-1.3
FX-406-C-1.3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:0
P
M
FX-116-C-1.3
FIRE PROTECTION THIRD FLOOR
PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - THIRD FLOOR FIRE PROTECTION - AREA 2
04 8 16268
SCALE: 1/8"=1'-0"
C360A
C363
C361AC362A
C349
C347
C348
C337
C335
C336
C345
C344
C343
C328
C329
C327
C321
C322
C325
C3C9
D308C
D302
D301
D301A
C323
C C
D320
STR #6
D319
C358A
D321
D322
D323
D324
D326
D327
D328
D329
C D
C
D
D330
D331
S T
R
D331B
D331C
C D
D352
D316C
D316
D316A
C358
C330
STR #7
C360C361C362C364C365
C363AC364AC365A
C3C4
C355
C353
C357
C359
C356
C346
C354C352
C356A
C357A
C351
C351A
C350
C350A
C349A
C3C6
C348A
C337A C332
C334
C341
C333
C338
C C
C339
C340
D333 D333A D333B D334
D334A
D335
A323A322
A318
A320
A321A
A354
A319
A356 A357
A317
A358
A316
A318A
A318
A312
STR #1
C3A2
A313
A314
C A
D301B
D332
D332C
D325
C C
B302
B302A
B301A
B301 B300
B323 B322
B321
B320
C3B4
B342
B
B338
B340 C3B5
B315A
B315B
B315
B316A
B316
B316B
B341
B317A
B317
B348
B347
B344
B318A
B318
A300
D332B D332A D332D
D353
D353A
C368
C369
C328A
C324
EXIST.
TELECOM
C358C
EXIST.
TELECOM
A306A
EXIST.
OFFICE
B345
#2#3 #1
#6
#7
#8 #4
#5
FE
FX-406-C-1.3
FX-406-C-1.3
FX-406-C-1.3
FX-406-C-1.3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:0
P
M
FX-117-C-1.3
FIRE PROTECTION THIRD FLOOR
PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
3/32" = 1'-0"
FLOOR PLAN - THIRD FLOOR FIRE PROTECTION - AREA 4 & 4A
ROOM
TELECOM
FaMb
#7
#8
#2#3 #1
#4
#5
ZONE 26
553 555 558
503A
501 501A
508B
501C 501B
508C
S T
R
508A
516 513
514A 512B512C
510A
C
557556
554A
550545544
545A
C57 C58
C
C53
C56
C51
520A
C54 512B
558A
6.7
Jb
4.4
5.4
6.2
6.7
FGGaHHbJJaKLLaMN
F
F
F
F
F
F
FX-407-C1.5,6
FX-407-C1.5,6
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLANKEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:1
P
M
FX-118-C-1.5
FIRE PROTECTION FIFTH FLOOR
PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - FIFTH FLOOR FIRE PROTECTION
04 8 16268
SCALE: 1/8"=1'-0"
TELECOM
EXIST.
TELECOM
Ma Fa
2.9
10.1
#2#3 #1
#4
#5
625B
623 625F
625C 625D
619 615A
C67
625E 612A
615 614
612B 612C
613C 613B
612D
612G
612F
612E
STR #1
632A
645 646 647 648 656 657 663 664 666 668 670
607608
S T
R
605604603683
C
667665660
662656B
C65
660A 676 675
C003
682685
C004686
656A
670A 659 658
624654
650A
C
601A
601B
C
C63
617618621622
C
625A632
C
626A
C
C69
652A653
C71
C61
601C
GHHbJbKLM J
Ja
GaLaN F
4.4
5.4
6.2
6.7
F
F
F
F
FX-407-C1.5,6
FX-407-C1.5,6
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
KEY PLAN
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:1
P
M
FX-119-C-1.6
FIRE PROTECTION SIXTH FLOOR
PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - SIXTH FLOOR FIRE PROTECTION
04 8 16268
SCALE: 1/8"=1'-0"
C1K18
K
P-18A
K
K A
K
K001
K
K
K005
K
C0K01
CORRIDOR
P-18
ELEV
K053
STAIR
K001
MECHANICAL
K005
LOADING
C0K03
CORRIDOR
K004
MED.
GAS
EQUIPMENT
ROOMK003
ELEC.
ROOM
K002
STORAGE
K006
STORAGE
K007
TELECOM
DEMARK
ENT. RM.
N.5
G.5
H
G
13121110
P
N
K
1.7
H.2
E.5
M
J
F
E
UP 24R
TELECOM DEMARK
ENTRANCE ROOM
K007
FX-120-C-2.B
1 1/2"
SPR
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING &
PROVIDE NEW SPRINKLER
HEAD/S AS REQUIRED FOR NEW
IT/ DATA WORK. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE
COMPLIANT WET AUTOMATIC
SPRINKLER SYSTEM.
CABLE TRAY
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS
AND RACKS, PROVIDE ADDITIONAL
SPRINKLER HEADS IF REQUIRED
DUE TO OBSTRUCTIONS
EX 1 1/2"
S P
R
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:1
P
M
FX-120-C-2.B
FIRE PROTECTION BASEMENT
FLOOR PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - BASEMENT FIRE PROTECTION - COMMUNITY LIVING CENTER
1/4" = 1'-0"
BASMENT FIRE PROTECTION NEW WORK - K007
04 8 16268
SCALE: 1/8"=1'-0"
TU
W010
CBG2
10.4
11.5
12.5
13.5
10.2
13.4
EXIST.
TELECOM
W05B
N1
PALLETS WILL
BE STACKED
TWO HIGH ON
RACKS
ENGINEERING
ENV
P R
O C
E S
S S
T O
R E
S
TSS STORAGE
E Q
U
IP
M E
N T
SPS
T S
S
12111098
TSS STORAGE
TSS STORAGE
TSS STORAGE
W03A
W03B
W03
W04A
W04
CWA3 W08
W09 W07
C W
A
CWA1
W05A
W06
W02 W01
EXIST.
ROOM
W05
75 64321
A
B
C
D
F
E
G
PS
PS
F
FX-408-C-14.B
FX-408-C-14.B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:2
P
M
FX-121-C-14.B
FIRE PROTECTION BASEMENT
FLOOR PLAN
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/8" = 1'-0"
FLOOR PLAN - BASEMENT FIRE PROTECTION - WAREHOUSE
04 8 16268
SCALE: 1/8"=1'-0"
A060 A063C
E007
EXIST.
ELEV. LOBBY
CBE5 EXIST.
TELECOM
E006
G046
EXIST.
OFFICE
G051
EXIST.
TELECOM
G050
CBF1
E007
EXIST.
ELEV. LOBBY
CBE5 EXIST.
TELECOM
E006
OFFICE
STORAGE
A060B
TELECOM
ROOM
A060
TELECOM
DEMARK ENTRANCE
A060A
G046
EXIST.
OFFICE
G051
EXIST.
TELECOM
G050
UP
REMOVE/ REWORK/ EXTEND EXISTING
SPRINKLER PIPING AND SPRINKLER HEADS
AS REQUIRED FOR NEW IT/ DATA WORK.
FIRE PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE COMPLIANT
AUTOMATIC WET PIPE SPRINKLER SYSTEM.
SEE NEW WORK PLANS.
2 1/2" 2 1/2"
1 1/4"
1 1/2"
1 1/2"
1 1/4"
1"
1"
1"
SPR
SPR
S P
R
S P
R
EXISTING 1" SPR. TO
BE RECONNECTED.
EXISTING 1-1/2" SPR.
TO BE RE-EXTENDED
TO NEW SYSTEM.
REMOVE/ REWORK/ EXTEND
SPRINKLER PIPING AND
SPRINKLER HEADS AS
REQUIRED FOR NEW IT/ DATA
WORK. FIRE PROTECTION
CONTRACTOR TO PROVIDE A
COMPLETE CODE COMPLIANT
AUTOMATIC WET PIPE
SPRINKLER SYSTEM. SEE NEW
WORK PLANS.
1" SPR
1 1/4" SPR
S P
R
1"
1"
E006 TO EXPAND INTO THIS AREA,
SPRINKLER PIPING AND HEADS MAY
NEED TO BE REWORKED. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A FULLY CODE COMPLIANT
WET SPRINKLER SYSTEM INSIDE AND
OUTSIDE OF E006
PROPOSED EXPANDED AREA
1 1/4"
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING AND
SPRINKLER HEADS AS REQUIRED
FOR NEW IT/ DATA WORK. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE
COMPLIANT AUTOMATIC WET
PIPE SPRINKLER SYSTEM. SEE
NEW WORK PLANS. SPRINKLER HEADS
AND PIPING OUTSIDE
PROPOSED TELECOM
ROOM MAY NEED TO
BE REWORKED TO
PROVIDE A CODE
COMPLIANT SYSTEM.
S P
R
1 1/2"
1" 1"
1 1/2" 1 1/2"
3"
3"
2"
1"
2"1"
1" 1"
SPR
SPR
S P
R
PROPOSED EXPANDED AREA
REMOVE SPRINKLER PIPE.
SEE NEW WORK PLAN FOR
ADDED PIPING.
REMOVE SPRINKLER
PIPING AND HEADS
EXISTING 3" TO REMAIN
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING &
SPRINKLER HEAD/S AS
REQUIRED FOR NEW IT/ DATA
WORK. FIRE PROTECTION
CONTRACTOR TO PROVIDE A
COMPLETE CODE COMPLIANT
WET AUTOMATIC SPRINKLER
SYSTEM.
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS,
LIGHTS AND RACKS, PROVIDE
ADDITIONAL SPRINKLER HEADS IF
REQUIRED DUE TO
OBSTRUCTIONS.
CABLE TRAY
DUE TO NEW ROOM
CONFIGURATION THIS AREA WILL
REQUIRE AN ADDITIONAL
SPRINKLER HEAD. REWORK
EXISTING SYSTEM AS NEEDED.
EXISTING SPRINKLER
HEADS TO REMAIN.
EX 1" SPR
EX 1"
EX 1"
EX 1 1/4"
EX 1 1/4"
S P
R
REMOVE/ REWORK/ EXTEND
SPRINKLER PIPING & SPRINKLER
HEAD/S AS REQUIRED FOR NEW
IT/ DATA WORK. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE
COMPLIANT WET AUTOMATIC
SPRINKLER SYSTEM.
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS
AND RACKS, PROVIDE ADDITIONAL
SPRINKLER HEADS IF REQUIRED
DUE TO OBSTRUCTIONS.
CABLE TRAY
RECONNECT EXISTING
SPRINKLER HEAD BRANCH
TO NEW TELECOM OFFICE
SPRINKLER SYSTEM
EXISTING 1 1/2" EXTEND AS NEEDED.
SPR SPR
EX 2 1/2" EX 2 1/2"
EX 1" SPR
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING &
SPRINKLER HEAD/S AS
REQUIRED FOR NEW IT/ DATA
WORK. FIRE PROTECTION
CONTRACTOR TO PROVIDE A
COMPLETE CODE COMPLIANT
WET AUTOMATIC SPRINKLER
SYSTEM.
SPRINKLER HEADS
AND PIPING OUTSIDE
OF EXPANDED AREA
MAY NEED TO BE
REWORKED TO
PROVIDE A CODE
COMPLIANT SYSTEM.
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS
AND RACKS, PROVIDE ADDITIONAL
SPRINKLER HEADS IF REQUIRED
DUE TO OBSTRUCTIONS.
EX 3"
EX 1 1/2"
EX 1 1/2"EX 1 1/2"
EX 3"
EX 2"
CABLE TRAY
SPR
SPR
S P
R
CABLE TRAY
CONNECT NEW
TO EXISTING
EX 3"
CONNECT NEW TO EXISTING
SPR
S P
R
3"
CONNECT NEW
TO EXISTING
NEW SPRINKLER
BRANCH TO FEED NEW
TELECOM ROOM
HAZARD GROUP AND DENSITY REQUIREMENTS
A. TELECOM ROOMS AND DATA ROOMS TO BE PROVIDED WITH A DENSITY OF 0.1
GPM/SQ.FT. OVER THE HYDRAULIC REMOTE 1500 SQ.FT. (LIGHT HAZARD) WITH A
HOSE STREAM ALLOWANCE OF 100 GPM.
B. STORAGE ROOMS TO BE PROVIDED WITH A DENSITY OF 0.20 GPM/SQ.FT. OVER
THE HYDRAULIC REMOTE 1,500 SQ. FT. (ORDINARY HAZARD GROUP 2) WITH A
HOSE STREAM ALLOWANCE OF 250 GPM.
C. CORRIDORS/ BREAKROOMS/ OFFICES/ AND OTHER ROOMS ALIKE SHALL BE
PROVIDED WITH A DENSITY OF 0.10 GPM/ SQ.FT. (LIGHT HAZARD) OVER THE
HYDRAULIC REMOTE 1500 SQ.FT. WITH A HOSE STREAM ALLOWANCE OF 100 GPM
EXISTING SPRINKLERS TO REMAIN
1"
1"1"
SPR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:2
P
M
FX-401-C-1.B
FIRE PROTECTION ENLARGED
PLANS
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/4" = 1'-0"
FIRE PROTECTION DEMOLITION - A060
1/4" = 1'-0"
FIRE PROTECTION DEMOLITION - E006
1/4" = 1'-0"
FIRE PROTECTION DEMOLITION - G050
KEYED NOTES
1. EXISTING UPRIGHT SPRINKLER HEAD.
2. RECESSED SPRINKLER HEAD.
1/4" = 1'-0"
FIRE PROTECTION NEW WORK - E006
1/4" = 1'-0"
FIRE PROTECTION NEW WORK - A060
1/4" = 1'-0"
FIRE PROTECTION NEW WORK - G050
02 4 8134
SCALE: 1/4"=1'-0"
1/4" = 1'-0"
PIPE BASEMENT FIRE PROTECTION NEW WORK - HOISTWAY
GENERAL SHEET NOTES
PLAN NORTH
A. REFER TO OVERALL PLANS FOR RATED ASSEMBLIES, ANY THROUGH
PENETRATIONS ARE TO BE SEALED ACCORDINGLY.
B. CEILING PLANS NOT SHOWN FOR CLEARITY, REFER TO ARCHITECTURAL
PLANS FOR CEILING PLANS.
REFG.
B144
B143
B144B
EXIST.
TELECOM
B144A
E138
EXIST.
ELEV. LOBBY
C1E9
EXIST.
TELECOM
E139
G191
EXIST.
TELECOM
G141
A153
A156C
A153B
EXIST.
TELECOM
A153A
EXIST.
TELECOM
C105
REFG.
REFG.
BREAK
ROOM
B144
B144A
LOCKERS
B143
EXIST.
TOILET
B144B
E138
EXIST.
ELEV. LOBBY
C1E9
EXIST.
TELECOM
E139
EXIST.
TELECOM
G141
EXIST.
CORRIDOR
G191
A153
A156C
A153B
EXIST.
TELECOM
A153A
EXIST.
TELECOM
C105
UPRIGHT SPRINKLER HEAD
TELECOM ROOM TO
EXPAND INTO THIS AREA.
EXISTING WET AUTOMATIC
SPRINKLER SYSTEM MAY
NEED TO BE REWORKED
FOR NEW LAYOUT. SEE
NEW WORK PLAN.
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING
AND PROVIDE NEW
SPRINKLER HEADS AS
REQUIRED FOR NEW IT/ DATA
WORK. FIRE PROTECTION
CONTRACTOR TO PROVIDE A
COMPLETE CODE COMPLIANT
AUTOMATIC WET PIPE
SPRINKLER SYSTEM. SEE
NEW WORK PLANS.
EXISTING
SPRINKLER HEAD
TO REMAIN
EXISTING TO REMAIN
S P
R
1 1/4"
S P
R
SPR SPR
1 1/4" 1 1/4"
EXISTING TO REMAIN
PROPOSED
EXPANDED AREA
REMOVE SPRINKLER
PIPING TO REROUTE
AROUND NEW
ELECTRICAL PANEL
EXISTING 1 1/4"
TO REMAIN
UPRIGHT SPRINKLER HEAD
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING AND
PROVIDE NEW SPRINKLER HEADS
AS REQUIRED FOR NEW IT/ DATA
WORK. FIRE PROTECTION
CONTRACTOR TO PROVIDE A
COMPLETE CODE COMPLIANT
AUTOMATIC WET PIPE SPRINKLER
SYSTEM. SEE NEW WORK PLANS.
TELECOM ROOM TO
EXPAND INTO THIS
AREA. EXISTING WET
AUTOMATIC SPRINKLER
SYSTEM MAY NEED TO
BE REWORKED FOR
NEW LAYOUT. SEE NEW
WORK PLAN.
RECESSED SPRINKLER HEAD
RECESSED SPRINKLER HEAD
SPR
SPR
1"
1 1/4"
EXISTING 1" SPR TO REMAIN
EXISTING 1 1/4" SPR
TO REMAIN
1 1/4"
EXISTING 1 1/4" SPR
TO REMAIN
EXISTING TO REMAIN
PROPOSED EXPANDED AREA
RECESSED SPRINKLER HEAD
TELECOM ROOM TO
EXPAND INTO THIS AREA.
EXISTING WET AUTOMATIC
SPRINKLER SYSTEM MAY
NEED TO BE REWORKED
FOR NEW LAYOUT. SEE
NEW WORK PLAN.
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING AND
PROVIDE NEW SPRINKLER HEADS
AS REQUIRED FOR NEW IT/ DATA
WORK. FIRE PROTECTION
CONTRACTOR TO PROVIDE A
COMPLETE CODE COMPLIANT
AUTOMATIC WET PIPE SPRINKLER
SYSTEM. SEE NEW WORK PLANS.
RECESSED SPRINKLER HEADS
RECESSED SPRINKLER HEADS
RECESSED SPRINKLER HEADS
1"
S P
R
PROPOSED EXPANDED AREA
EXISTING 2" TO REMAIN
EXISTING 2" TO REMAIN
REMOVE SPRINKLER
PIPING AND HEADS
SPR
REMOVE/ REWORK/
EXTEND EXISTING
SPRINKLER PIPING AND
PROVIDE NEW
SPRINKLER HEADS AS
REQUIRED FOR NEW IT/
DATA WORK. FIRE
PROTECTION
CONTRACTOR TO
PROVIDE A COMPLETE
CODE COMPLIANT
AUTOMATIC WET PIPE
SPRINKLER SYSTEM. SEE
NEW WORK PLANS.
UPRIGHT SPRINKLER HEAD
1" SPR
2 1/2"
1"
UPRIGHT SPRINKLER HEAD
EXISTING TO REMAIN
S P
R
TELECOM ROOM TO
EXPAND INTO THIS
AREA. EXISTING WET
AUTOMATIC SPRINKLER
SYSTEM MAY NEED TO
BE REWORKED FOR
NEW LAYOUT. SEE
NEW WORK PLAN.
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING AND
PROVIDE NEW SPRINKLER HEADS
AS REQUIRED FOR NEW IT/ DATA
WORK. FIRE PROTECTION
CONTRACTOR TO PROVIDE A
COMPLETE CODE COMPLIANT
AUTOMATIC WET PIPE SPRINKLER
SYSTEM. SEE NEW WORK PLANS.
1 1/2"
RECESSED SPRINKLER HEAD
SPR
PROPOSED EXPANDED AREA
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING &
SPRINKLER HEAD/S AS
REQUIRED FOR NEW IT/ DATA
WORK. FIRE PROTECTION
CONTRACTOR TO PROVIDE A
COMPLETE CODE COMPLIANT
WET AUTOMATIC SPRINKLER
SYSTEM.
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS
AND RACKS, PROVIDE ADDITIONAL
SPRINKLER HEADS IF REQUIRED
DUE TO OBSTRUCTIONS.
EX 1 1/4"
EX 1 1/4"
EX SPR
SPR
CABLE TRAY
CABLE TRAY
EXPANDED ROOM, REWORK EXISTING
SPRINKLER SYSTEM AS NEEDED.
NEWLY CREATED ROOM
WILL REQUIRE SPRINKLER
PROTECTION. EXTEND
SPRINKLER PIPING FROM
EXISTING TO NEW
SPRINKLER HEAD.
SPR
S P
R
1 1/4"
S P
R
CONNECT NEW TO EXISTING
REWORK SPRINKLER
PIPING AROUND NEW
ELECTRICAL PANEL.
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING &
PROVIDE NEW SPRINKLER
HEAD/S AS REQUIRED FOR NEW
IT/ DATA WORK. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE
COMPLIANT WET AUTOMATIC
SPRINKLER SYSTEM.
EXISTING SPRINKLER HEAD
MAY NEED TO MOVE DUE TO
NEW WALL AND/OR CABLE
ENTRY. VERIFY SPRINKLER
HEAD IS IN COMPLIANCE WITH
NFPA 13. IF NOT IN
COMPLIANCE WITH NFPA 13,
RELOCATE SPRINKLER HEAD.
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS
AND RACKS, PROVIDE ADDITIONAL
SPRINKLER HEADS IF REQUIRED
DUE TO OBSTRUCTIONS.
S P
R
SPR
S P
R
S P
R
1"
1 1/4"
1 1/4"
1 1/4"
1"
CABLE TRAY
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING &
PROVIDE NEW SPRINKLER
HEAD/S AS REQUIRED FOR NEW
IT/ DATA WORK. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE
COMPLIANT WET AUTOMATIC
SPRINKLER SYSTEM.
AUTOMATIC SPRINKLERS
OUTSIDE OF EXPANDED ROOM
MAY NEED TO BE REWORKED
TO PROVIDE A CODE
COMPLIANT SYSTEM.
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS
AND RACKS, PROVIDE ADDITIONAL
SPRINKLER HEADS IF REQUIRED
DUE TO OBSTRUCTIONS.
CABLE TRAY
EX 2"
CONNECT NEW TO EXISTING
EX 2"
CONNECT NEW TO EXISTING
S P
R
NEW SPRINKLER BRANCH TO
FEED NEW TELECOM ROOM
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING &
PROVIDE NEW SPRINKLER
HEAD/S AS REQUIRED FOR NEW
IT/ DATA WORK. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE
COMPLIANT WET AUTOMATIC
SPRINKLER SYSTEM.
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS
AND RACKS, PROVIDE ADDITIONAL
SPRINKLER HEADS IF REQUIRED
DUE TO OBSTRUCTIONS.
EXISTING 1" SPR
EXISTING 1" SPR
EXISTING 2 1/2" SPR
CABLE TRAY
S P
R
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING &
PROVIDE NEW SPRINKLER
HEAD/S AS REQUIRED FOR NEW
IT/ DATA WORK. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE
COMPLIANT WET AUTOMATIC
SPRINKLER SYSTEM.
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS
AND RACKS, PROVIDE ADDITIONAL
SPRINKLER HEADS IF REQUIRED
DUE TO OBSTRUCTIONS.
EXISTING 1 1/2" SPR TO REMAIN
CABLE TRAY
SPR
HAZARD GROUP AND DENSITY REQUIREMENTS
A. TELECOM ROOMS AND DATA ROOMS TO BE PROVIDED WITH A DENSITY OF 0.1
GPM/SQ.FT. OVER THE HYDRAULIC REMOTE 1500 SQ.FT. (LIGHT HAZARD) WITH A
HOSE STREAM ALLOWANCE OF 100 GPM.
B. STORAGE ROOMS TO BE PROVIDED WITH A DENSITY OF 0.20 GPM/SQ.FT. OVER
THE HYDRAULIC REMOTE 1,500 SQ. FT. (ORDINARY HAZARD GROUP 2) WITH A
HOSE STREAM ALLOWANCE OF 250 GPM.
C. CORRIDORS/ BREAKROOMS/ OFFICES/ AND OTHER ROOMS ALIKE SHALL BE
PROVIDED WITH A DENSITY OF 0.10 GPM/ SQ.FT. (LIGHT HAZARD) OVER THE
HYDRAULIC REMOTE 1500 SQ.FT. WITH A HOSE STREAM ALLOWANCE OF 100 GPM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:4
P
M
FX-402-C-1.1
FIRE PROTECTION ENLARGED
PLANS
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/4" = 1'-0"
1ST FLOOR FIRE PROTECTION DEMOLITION - B143/B144
1/4" = 1'-0"
1ST FLOOR FIRE PROTECTION DEMOLITION - E139
1/4" = 1'-0"
1ST FLOOR FIRE PROTECTION DEMOLITION - G141
1/4" = 1'-0"
1ST FLOOR FIRE PROTECTION DEMOLITION - A153A
1/4" = 1'-0"
1ST FLOOR FIRE PROTECTION DEMOLITION - C105
1/4" = 1'-0"
1ST FLOOR FIRE PROTECTION NEW WORK - B143/B144
1/4" = 1'-0"
1ST FLOOR FIRE PROTECTION NEW WORK - E139
1/4" = 1'-0"
1ST FLOOR FIRE PROTECTION NEW WORK - G141
1/4" = 1'-0"
1ST FLOOR FIRE PROTECTION NEW WORK - A153A
1/4" = 1'-0"
1ST FLOOR FIRE PROTECTION NEW WORK - C105
02 4 8134
SCALE: 1/4"=1'-0"
GENERAL SHEET NOTES
PLAN NORTH
A. REFER TO OVERALL PLANS FOR RATED ASSEMBLIES, ANY THROUGH
PENETRATIONS ARE TO BE SEALED ACCORDINGLY.
B. CEILING PLANS NOT SHOWN FOR CLEARITY, REFER TO ARCHITECTURAL
A216 STR #1
A210
DN
EXIST.
GREEN CLINIC
A202
EXIST.
CORRIDOR
C2A1
EXIST.
TELECOM
A213
E202
EXIST.
TELECOM
E203
A216
DN
EXIST.
GREEN CLINIC
A202
EXIST.
TELECOM
A217
E202
EXIST.
TELECOM
E203
ELEV. LOBBY
UPRIGHT SPRINKLER HEADS
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING AND
PROVIDE NEW SPRINKLER HEADS
AS REQUIRED FOR NEW IT/ DATA
WORK. FIRE PROTECTION
CONTRACTOR TO PROVIDE A
COMPLETE CODE COMPLIANT
AUTOMATIC WET PIPE SPRINKLER
SYSTEM. SEE NEW WORK PLANS.
TELECOM ROOM TO
EXPAND INTO THIS
AREA. EXISTING WET
AUTOMATIC SPRINKLER
SYSTEM MAY NEED TO
BE REWORKED FOR
NEW LAYOUT. SEE NEW
WORK PLAN.
RECESSED SPRINKLER HEADS
RECESSED SPRINKLER HEADS
S P
R
S P
R
2"
S P
R
1"
1"
1"
1"
PROPOSED EXPANDED AREA
REMOVE SPRINKLER
PIPING AND HEADS
EX 2" TO REMAIN
EX 2" TO REMAIN
REMOVE/ REWORK/ EXTEND
SPRINKLER PIPING AND
SPRINKLER HEADS AS REQUIRED
FOR NEW IT/ DATA WORK. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE
COMPLIANT AUTOMATIC WET PIPE
SPRINKLER SYSTEM. SEE NEW
WORK PLANS.
TELECOM ROOM TO
EXPAND INTO THIS
AREA. EXISTING WET
AUTOMATIC SPRINKLER
SYSTEM MAY NEED TO
BE REWORKED FOR
NEW LAYOUT. SEE NEW
WORK PLAN.
UPRIGHT SPRINKLER HEAD
1"
1 1/4"
1 1/2" 2"
1 1/4"
1"
RECESSED SPRINKLER HEADS
RECESSED SPRINKLER HEADS
1"
S P
R
S P
R
PROPOSED EXPANDED AREA
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING &
PROVIDE NEW SPRINKLER
HEAD/S AS REQUIRED FOR NEW
IT/ DATA WORK. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE
COMPLIANT WET AUTOMATIC
SPRINKLER SYSTEM.
AUTOMATIC SPRINKLERS
OUTSIDE OF EXPANDED ROOM
MAY NEED TO BE REWORKED
TO PROVIDE A CODE
COMPLIANT SYSTEM.
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS
AND RACKS, PROVIDE ADDITIONAL
SPRINKLER HEADS IF REQUIRED
DUE TO OBSTRUCTIONS.
EXISTING 1" SPR
EX 2"
EX 2"
S P
R EX 1"
CABLE TRAY
AUTOMATIC SPRINKLERS
OUTSIDE OF EXPANDED ROOM
MAY NEED TO BE REWORKED
TO PROVIDE A CODE
COMPLIANT SYSTEM.
S P
R
CONNECT NEW TO EXISTING
CONNECT NEW TO EXISTING
NEW SPRINLER BRANCH TO
FEED NEW TELECOM ROOM
REMOVE/ REWORK/ EXTEND
EXISTING SPRINKLER PIPING &
PROVIDE NEW SPRINKLER
HEAD/S AS REQUIRED FOR NEW
IT/ DATA WORK. FIRE
PROTECTION CONTRACTOR TO
PROVIDE A COMPLETE CODE
COMPLIANT WET AUTOMATIC
SPRINKLER SYSTEM.
AUTOMATIC SPRINKLERS
OUTSIDE OF EXPANDED ROOM
MAY NEED TO BE REWORKED
TO PROVIDE A CODE
COMPLIANT SYSTEM.
FIRE PROTECTION CONTRACTOR
TO COORDINATE SPRINKLER HEAD
LOCATIONS WITH CABLE TRAYS
AND RACKS, PROVIDE ADDITIONAL
SPRINKLER HEADS IF REQUIRED
DUE TO OBSTRUCTIONS.
CABLE TRAY
EX 1 1/2"EX 1 1/4" EX 2"
HAZARD GROUP AND DENSITY REQUIREMENTS
A. TELECOM ROOMS AND DATA ROOMS TO BE PROVIDED WITH A DENSITY OF 0.1
GPM/SQ.FT. OVER THE HYDRAULIC REMOTE 1500 SQ.FT. (LIGHT HAZARD) WITH A
HOSE STREAM ALLOWANCE OF 100 GPM.
B. STORAGE ROOMS TO BE PROVIDED WITH A DENSITY OF 0.20 GPM/SQ.FT. OVER
THE HYDRAULIC REMOTE 1,500 SQ. FT. (ORDINARY HAZARD GROUP 2) WITH A
HOSE STREAM ALLOWANCE OF 250 GPM.
C. CORRIDORS/ BREAKROOMS/ OFFICES/ AND OTHER ROOMS ALIKE SHALL BE
PROVIDED WITH A DENSITY OF 0.10 GPM/ SQ.FT. (LIGHT HAZARD) OVER THE
HYDRAULIC REMOTE 1500 SQ.FT. WITH A HOSE STREAM ALLOWANCE OF 100 GPM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENT
FULLY SPRINKLERED
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PROJECT MANAGEMENTCONSULTANT
321 4 5 6 7 8 9 10
6 S. OLD ORCHARD AVE.
WEBSTER GROVES, MO 63119
PHONE #: 314-918-8383
Consultant POC
8718 Botts Lane San Antonio, Texas 78217 www.hfscompany.com
Phone: (210) 816-4784 Fax: (210) 881-6808 jbianco@hfscompany.com
D U s e rs
\j a c o b .n o le n \D o c u m e n ts
\0 -M
E P
F P
-H O
S -R ja c o b .n o le n .r v t
/2
/2
:4
:5
P
M
FX-403-C-1.2
FIRE PROTECTION ENLARGED
PLANS
EHRM INFRASTRUCTURE
UPGRADES - COLUMBIA, MO
800 HOSPITAL DR.
COLUMBIA, MO 65201
589A4-21-700
1/25/2022 JDB JCN
1/4" = 1'-0"
2ND FLOOR FIRE PROTECTION DEMOLITION - A213
1/4" = 1'-0"
2ND FLOOR FIRE PROTECTION DEMOLITION - E203
1/4" = 1'-0"
2ND FLOOR FIRE PROTECTION NEW WORK - A213
1/4" = 1'-0"
2ND FLOOR FIRE PROTECTION NEW WORK - E203
02 4 8134
SCALE: 1/4"=1'-0"
GENERAL SHEET NOTES
PLAN NORTH
A. REFER TO OVERALL PLANS FOR RATED ASSEMBLIES, ANY THROUGH
PENETRATIONS ARE TO BE SEALED ACCORDINGLY.
B. CEILING PLANS NOT SHOWN FOR CLEARITY, REFER TO ARCHITECTURAL
D217
DP-CRITICAL-1
TV
D209
EXIST.
DATA CENTER
D216
D217
DP-CRITICAL-1
D209
EXIST.
DATA CENTER
D216
D217
D209
EXIST.
DATA CENTER
D216
D217
EXIST.
DATA CENTER
D216
EXISTING AREA IS PROVIDED
WITH WET TYPE AUTOMATIC
SPRINKLER SYSTEM. SEE
NEW WORK PLAN FOR NEW
WORK IN THIS AREA.
1 1/2"
1"
1"
1"
1"
1"
1"
1"
1"
1"
1"
1"
1"
1 1/2"
DRAIN
S P
R S
P R
2"
1 1/4"
1 1/4"
1"
1 1/4"
1"
SPR
S P
R
SPR
S P
R S
P R
1" 2"
ABANDONED FLOW SWITCH
SPR
SPR
RECESSED
SPRINKLER HEAD
(TYP.)
SHUT OFF VALVE
TO BE REMOVED
REMOVE AND CAP
SPRINKLER TO A
POINT PAST THE
TEMPORARY WALL
REMOVE EXISTING SPRINKLER HEAD AND CAP OR PLUG PIPE AT BRANCH.
EXISTING AREA IS PROVIDED
WITH WET TYPE AUTOMATIC
SPRINKLER SYSTEM. SEE
NEW WORK PLAN FOR NEW
WORK IN THIS AREA.
1 1/2"
1"
1"
1"
1"
1"
1"
1"
1"
1"
1"
DRAIN
S P
R S
P R
2"
1 1/4"
1 1/4"
S P
R
SPR
S P
R S
P R
RECESSED
SPRINKLER HEAD
(TYP.)
NEW INDICATING SHUT
OFF VALVE WITH
TAMPER SWITCH
CONNECT NEW TO EXISTING
CAP
PHASE ONE
2" VALVED SPRINKLER
BRANCH TO BE EXTENDED TO
PHASE 1 AND PHASE 2 WET
TYPE SPRINKLER SYSTEM.
THE EXISTING SPRINKLER
SYSTEM FEEDING THE
PHASE 2 EXISTING AREA TO
BE TEMPORARILY BACK FED
FROM EXISTING 2"
SPRINKLER BRANCH.
FIRE PROTECTION CONTRACTOR TO
COORDINATE SPRINKLER HEADS AND
PIPING WITH EXACT LOCATION OF DIVIDER
CURTAIN, SEE ARCHITECTURAL SET.
EXISTING AREA IS PROVIDED
WITH NEW WET TYPE
AUTOMATIC SPRINKLER
SYSTEM. SEE NEW WORK
PLAN FOR NEW WORK IN THIS
AREA.
1 1/2"
1"
1"
1"
1"
1"
1"
1"
1"
1"
1"
DRAIN
S P
R S
P R
2"
1 1/4"
1 1/4"
S P
R
SPR
S P
R S
P R
RECESSED
SPRINKLER HEAD
(TYP.)
EXISTING WET TYPE
SPRINKLER SYSTEM
INCLUDING TEMPORARY
CONNECTION TO BE
REMOVED.
FIRE PROTECTION
CONTRACTOR TO PROVIDE A
NEW COMPLETE CODE
COMPLIANT WET AUTOMATIC
SPRINKLER SYSTEM.
EX 2"
S P
R
S P
R
EX 1 1/4"
EX 1 1/4"
CABLE TRAY
NOTE: ROOM D216 SHALL BE
PROVIDED WITH BOTH A
CLEAN AGENT SYSTEM AND
A WET PIPE SYSTEM.
CABLE TRAY
PHASE 2
FIRE PROTECTION CONTRACTOR TO
COORDINATE SPRINKLER HEADS AND
PIPING WITH EXACT…