C-130Atomizer899981TestInstruction.pdf.pdf

PDF 282 KB Posted

Attached to
Universal Fuel Control Test Stand Federal contract opportunity
Solicitation number
FA8224-15-R-0013
Issued by
Department of the Air Force Materiel Command Lifecycle Management Center Hill Air Force Base

About this file

Attachment AW -- C-130Atomizer899981TestInstruction.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Universal Fuel Control Test Stand, newest first.
File Type Posted
pd24E87.doc DOC document
Section_M_Fuels_28_January_2016.pdf PDF
Section_L_Fuels_28_January_2016.pdf PDF
Dec3PS.pdf PDF
Amendment_0007.doc DOC document
F-15FuelControl_TestInstruction.pdf.pdf PDF
Questions_and_Answers__10_Aug_2015.pdf PDF
FA8224-15-R-0013_0002.pdf PDF
Universal_Test_Stand.doc DOC document
B252_fp2008.pdf PDF
Bldg252_TestingAreaDrawing.PDF PDF
Questions_and_Answers_24_July_2015.pdf PDF
Bldg252Pictures.pdf PDF
C-130_FuelControl-1__TestInstruction.pdf.pdf PDF
C-17FuelAccessories_TestInstruction.pdf.pdf PDF
C-17FuelControl_TestInstruction.pdf.pdf PDF
A011_DI_ADMN_81249A 1 .pdf PDF
Robins_TM-86-01N 1 .pdf PDF
F-22TestInstruction_pdf.pdf PDF
A001_DI_MISC_8145B 1 .pdf PDF
FED-STD-313D 1 .pdf PDF
A014_DIMGMT-81842 1 .pdf PDF
A002_DI_IPSC_81488 1 .pdf PDF
C-5FuelControl_TestInstruction.pdf PDF
A005_DI_QCIC_80278B 1 .pdf PDF
C-5FlowDivider_TestInstruction.pdf.pdf PDF
METCAL_TM_86_01N 1 .pdf PDF
A003_CDRL_TMCR 1 .pdf PDF
A008_DI_ATTS_80283B 1 .pdf PDF
F-16FuelPump_TestInstruction.pdf.pdf PDF
A004_DI-SESS-8100DT 1 .pdf PDF
FA8224-15-R-0013.pdf PDF
C-5AtomizerTestInstruction.pdf.pdf PDF
C-17IGV_TestInstruction.pdf.pdf PDF
F-15AtomizerTestInstruction.pdf.pdf PDF
A-10_FuelControl__TestInstruction.pdf.pdf PDF
A010_FED_STD_313D 1 .pdf PDF
A013_DIMGMT-81580 1 .pdf PDF
KC-135TestInstruction.pdf.pdf PDF
C-130Atomizer3601193TestInstruction.pdf.pdf PDF
A009_AFMETACL_TM-86-01 1 .pdf PDF
KC-135AtomizerTestInstruction.pdf.pdf PDF
C-17FlowDivider_TestInstruction.pdf.pdf PDF
Purchase_Specification.pdf PDF
A-10AtomizerTestInstruction.pdf.pdf PDF
A007_DI_ATTS_80282B 1 .pdf PDF
F-16AtomizerTestInstruction.pdf.pdf PDF
C-130Atomizer75076TestInstruction.pdf.pdf PDF
F-15FuelFilter_TestInstruction.pdf.pdf PDF
C-130FuelControl-8__TestInstruction.pdf.pdf PDF
Show all 50

Universal Fuel Control Test Stand has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OO-MAN-2014-02871

TO 2G-GTCP85-43-9

WP 004 00

9. TESTING.

a. Preparation for Test.

WARNING

Calibration fuel is flammable; do not use near open flames, liquid contact with eyes or skin can cause severe irritation and blurred vision. Inhalation of vapor can cause irritation, headache, nausea, and dizziness. Wear approved PPE when exposed to vapors.

NOTE

Refer to TO 33D2-3-106-1 for operation and maintenance of 164101-100 test stand assembly.

Prior to start of all tests, all valves shall be open and regulators adjusted to zero.

(1) Provide test setup as shown in Figure 3 or connect X8750322-01 tester assembly to 164101-100 test stand assembly.

(2) Provide a test record sheet, see Table 3, to record results of test procedures.

(3) Install fuel atomizer assembly on X8750322-01 tester assembly.

(4) Provide filtered calibration fuel (43-21) at an inlet temperature of 80 (±5)°F (26 (±3)°C).

b. Leak Check

(1) Provide 3 (±1) psig inlet fuel pressure to bleed air from system.

(2) Apply 350 (±10) psig inlet fuel pressure.

(3) Check fuel atomizer assembly for leakage. No leakage permitted from flow divider valve (Figure 2,9) or housing

(11).

Required Actual Required Actual Required Actual Required Actual

9.b 350 psig Leak Check 350 (±10) Pass / Fail N/A N/A N/A N/A N/A N/A N/A

9.c 10 psig Spray Pattern 10 (±1) N/A Pass / Fail N/A N/A N/A N/A N/A N/A

9.d 25 psig Spray Pattern 25 (±1) N/A Pass / Fail 30 (±1) 80 to 95 N/A N/A

Begin at 70

End at 85

9.f 200 psig Spray Pattern 200 (±2) N/A Pass / Fail 220 (±12) 70 to 100 N/A N/A

9.g 350 psig Spray Pattern 350 (±2) N/A Pass / Fail 333 (±17) 70 to 100 N/A N/A

Table 3. Fuel Atomizer Assembly Pressure/Flow Rate Limits and Test Record Sheet

Flow Divider Opening

Pressure (psig)

Date:Part No: 899981-2

Serial No:

Fuel Type:

Fuel Temp (°F): Recorded By:

Spray Angle (degrees)

Spray Pattern

Fuel Atomizer Assembly Test Record Sheet

Leakage

T.O.

Paragraph

Number

Test Sequence

Inlet Fuel Pressure (psig) Fuel Flow (lb/hr)

9.e Flow Divider Valve

Opening Check N/A N/A N/A N/A N/A N/A 75 (±2)

Figure 4: Fuel Atomizer Assembly Spray Pattern

c. Perform 10 psig Spray Pattern Check.

(1) Apply 10 (±1) psig inlet pressure.

(2) There shall be no fizzing or bubbling (Figure 4, Pattern D), solid jets of fuel (pattern F), or discontinuities (pattern

E) in the spray pattern.

(3) Replace matched plate set (Figure 2, 3) or distributor head (4) if spray pattern is unacceptable and retest.

d. Perform 25 psig Spray Pattern Check.

(1) Apply 25 (±1) psig inlet fuel pressure.

(2) There shall be no fizzing or bubbling (Figure 4, Pattern D), solid jets of fuel (pattern F), or discontinuities (pattern

E) in the spray pattern.

(3) Flow spray angle and weight flow rate shall be within limits of Table 3.

(4) Check and calculate spray angle concentricity.

(a) Using protractor (Figure 3, 11) establish centerline of 90 degrees.

(b) At 1 inch from nozzle tip (Figure 5, RAD Q), measure ANGLE R and ANGLE T.

(c) Each angle measured from centerline shall compare within 3 degrees.

(d) Fuel atomizer assembly is unacceptable if flow spray angle or weight flow rate is not within limits of

Table 3.

(5) Replace plate set (Figure 2, 8) or distributor head (Figure 2, 9) if flow spray angle is not within limits of Table 3 or spray pattern is unacceptable and retest.

e. Flow Divider Valve Opening Check.

NOTE

Flow divider valve opening is distinguished by a general thickening of spray pattern.

(1) Adjust fuel inlet pressure to 5 psig (±1) below flow divider pressure shown in Table 3, as indicated on inlet fuel pressure gage (8). Gradually increase pressure to 10 (±2) psig above opening pressure. Check for opening of flow divider valve. Valve opening shall occur within limits of Table 3.

(2) Decrease fuel inlet pressure to 25 psig (±1) Recheck flow rate specified in Table 3 to ensure that flow divider valve has closed.

(3) Replace flow divider valve (Figure 2, 9) if opening pressure is not within limits of Table 3.

Figure 5: Fuel Atomizer Assembly Spray Angles

f. Perform 200 Psig Spray Pattern Check.

(1) Apply 200 (±2) psig fuel inlet pressure. There shall be no fizzing or bubbling (Figure 4, Pattern D), solid jets of fuel

(pattern F), or discontinuities (pattern E) in the spray pattern. An acceptable pattern is pattern C.

(2) Weight flow rate and flow spray angle shall be within the limits of Table 3.

(3) Check and calculate spray angle concentricity.

(a) Using 180 degree protractor (Figure 3, 11) establish centerline of 90 degrees.

(b) At 1 inch from nozzle tip (Figure 5, RAD Q), measure ANGLE R and ANGLE T.

(c) Each angle measured from centerline shall compare within 3 degrees.

(d) Fuel atomizer assembly is unacceptable if flow spray angle or weight flow rate is not within limits of

Table 3.

(4) Replace matched plate set (Figure 2, 3) or distributor head (4) if flow spray angle or weight flow rate is not within limits of Table 3 or if spray pattern is unacceptable. Retest if any replacements are made.

g. Perform 350 Psig Spray Pattern Check.

(1) Apply 350 (±2) psig fuel inlet pressure. There shall be no fizzing or bubbling (Figure 4, Pattern D), solid jets of fuel

(pattern F), or discontinuities (pattern E) in the spray pattern. An acceptable pattern is pattern C.

(2) Weight flow rate and flow spray angle shall be within the limits of Table 3.

(3) Check and calculate spray angle concentricity.

(a) Using 180 degree protractor (Figure 3, 11) establish centerline of 90 degrees.

(b) At 1 inch from nozzle tip (Figure 5, RAD Q), measure ANGLE R and ANGLE T.

(c) Each angle measured from centerline shall compare within 3 degrees.

(d) Fuel atomizer assembly is unacceptable if flow spray angle or weight flow rate is not within limits of

Table 3.

(4) Replace matched plate set (Figure 2, 3) or distributor head (4) if flow spray angle or weight flow rate is not within limits of Table 3 or if spray pattern is unacceptable. Retest if any replacements are made.

(5) Remove inlet pressure and disconnect X8750322-01 tester assembly. Remove fuel atomizer assembly from tester assembly.

(6) Drain duel atomizer assembly completely.

(7) Inspect atomizer housing (Figure 2, 11) for proper atomizer assembly part number. If part number is correct, proceed to next step. If part number is incorrect, vibro-etch a single line through the incorrect part number no more than 0.010 inch deep. Vibro-etch the correct assembly part number on a non-functional surface of the housing (figure 2, 11) using 1/8 inch high characters no deeper than 0.010 inch. Use Alodine (43-15) to touch up etched areas.

(8) Plug or cap all openings.

h. Preservation

Preserve and package fuel atomizer assembly in accordance with Specification MIL-STD-2073, Method 10.