| GBSD Temporary Facility Requirements: | |
| Total Foot Print: Not to exceed 24,530 square feet | |
| Supports: 204 personnel | |
| Purpose: Office space | |
| Ceiling Height: Not less than 8' floor to ceiling |
| Common Area: All exterior walls and any walls adjacent to Office Space Area #1, 2, 3, 4, Video Teleconference Room, or Computer Room must be constructed to the standards defined in ICD/ICS 705 | Supports # of Employees | Construction Specifications |
| Entry Foyer w/ Security Desk | 1 | |
| Fire Alarm Panel | ||
| Double door entry from outside (w/ vindicator access) | ||
| 6'x6' Security Desk w/ office chair (1 person) - Large enough to support single video monitor for surveillance of exterior security cameras, video switching box, and computer station | ||
| Sufficient power drops | ||
| Panel for exterior security cameras and Digital Video Recorder | ||
| Computer network drop, consisting of 2 strand single mode fiber optic cable mounted in a single port face plate with SC connectors and in a separate junction box two blue CAT6 cables and jacks mounted in a dual port face plate | ||
| Hinged floor crawl space access behind security desk | ||
| Hatch must be Bilco Type TER 30"x30" or Gov't approved alternative | ||
| Make flush with remaining floor and use same flooring type over hatch | ||
| Wall mounted cubby storage for electronic devices (i.e., cell phones) | ||
| 150 individual cubbies with individual access to each cubby (purpose is to store cell phones and electronic devices) | ||
| Single security door access to work area hallway (w/ vindicator access) | ICD/ICS 705 | |
| Hallway provides access to Office Space Areas #1, #2, #3, #4, Video Teleconference Room, Computer Lab and Communications Room, as described below | ICD/ICS 705 | |
| Break Room w/ Kitchenette - may adjoin exterior wall w/ windows | 8 | |
| Lower Cabinets appropriate for the space | ||
| Upper cabinets appropriate for the space | ||
| Laminate Counter top to cover all lower cabinets | ||
| Double basin sink w/ hot and cold running water and drain (high water faucet for filling coffee maker or large pots) | ||
| Area for 2 large refrigerators | ||
| Area for 2 large coffee makers | ||
| Area for 2 Microwaves | ||
| Cabinetry dedicated to store and sell snacks (e.g., upper display cabinet, small counter top, lower storage cabinets) - this can be suitable piece of furniture or a built in. | ||
| Appropriate room lighting | ||
| Vinyl flooring throughout | ||
| Laminate backsplash (counter top to upper cabinets) | ||
| Seating for up to 8 people | ||
| Water Fountain with Bottle Filler (Ideally located in vicinity of breakroom) | ||
| Male Bathroom (IAW: OSHA Standards 1910.141(c)(1)(i), Table J-1) Counter top w/ 3 sink basins installed and Mirror entire length of counter; 3 urinals; and 4 toilet stalls (Water closets) | UFC 1-200-01 | |
| Female Bathroom (IAW: OSHA Standards 1910.141(c)(1)(i), Table J-1) Counter top w/ 3 sink basins and mirror entire length of counter; and 4 toilet stalls (Water closets) | UFC 1-200-01 | |
| Janitor/Cleaning Supply Closet | N/A | |
| Deep basin sink (or functionally similar) w/ hot and cold running water and drain (needed to fill and empty mop buckets) | ||
| 4 shelves along one side wall for cleaning supplies | ||
| Appropriate switched lighting | ||
| Storage area for up to 30 temporary duty laptop computers and accessories, installed in single power and network rack systems (120VAC power and fiber optic network drops). |
| Office Space Area #1: Entire room constructed to ICD/ICS 705 Standards; No windows on exterior walls; access from main hallway | 100 | ICD/ICS 705 |
| Open air office space for 94 employees (carpeted w/ appropriate ceiling lighting, fire detection and suppression, and HVAC to code) | 94 | |
| Each employees cube shall be monolithic panel, 6'x6' staff cube (efficiency), w/ power to all panels | ||
| Cubicles shall be grouped into sets of 4 - to the maximum extent possible | ||
| Each set of 4 cubicles will have a single entry point (sized to code) with entry from a hall space (sized to code) | ||
| Each cubical work space shall contain: | ||
| Corner style desk space (appropriate to size of their cubical) | ||
| 2 each 3-drawer filing cabinets (attached under desk top) | ||
| Over-desk storage cabinets (appropriate to size of their cubical) | ||
| Black, swivel/tilt mesh mid-back task chair, with fixed cantilevered arms | ||
| Switched lighting under the over-desk storage cabinets | ||
| Sufficient electrical outlets to support 3 computers, 2 monitors, 1 telephone, 1 KVM Switch, and cubical lights, plus one additional double outlet | ||
| 6 strand single mode fiber optic cable installed in a single 3 port face plate with SC connectors per location and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate per location | ||
| Centrally located workspace for three (3) Network Printers, w/ 1 power and fiber optic network drop per printer | ||
| Centrally located workspace for one (1) 5-drawer safe (18"x28" - weighs 1,000 lbs. loaded) and 1 paper shredder (20"x27") | ||
| 6 individual offices (carpeted w/ appropriate ceiling lighting and HVAC to code) | 6 | |
| Supervisor’s office shall be a stackable panel, 8'x10' manager cube, with power on all panels, and with office height panels (76"-81") with door. | ||
| Each supervisor’s office shall be furnished with freestanding "U" shaped desk, with 24" wide storage tower with shelves | ||
| Chairs shall be black, swivel/tilt mesh mid-back task chair, with fixed cantilevered arms | ||
| Sufficient electrical | ||
| 6 strand single mode fiber optic cable installed in a single 3 port face plate with SC connectors per location and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate per location | ||
| Intrusion Detection System (IDS) Panel (throughout area #1) - tied back to communication room (CER) | ||
| IDS consists of door intrusion and motion sensors tied to IDS panel within room | ||
| Vindicator Access Control on area #1 entry door - tied back to Communication Room (CER) | ||
| Centrally located workspace for two (2) Network Printers, w/ 1 power and fiber optic network drop, and 1 power and fiber optic network drop | ||
| Conference Room #1: | 18 | ICD/ICS 705 |
| 1 Conference Room Table for 8 (office chairs) with seating around perimeter wall for 10 additional persons | ||
| 2 strand single mode fiber optic cable installed in a single port face plate with SC connectors and a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate, at conference room table | ||
| Computer work stations and desk with one (1) 60" wall mounted monitor, Power outlet, and 1 fiber optic video line from computer work station to monitor | ||
| Teleconference phone (located on conference table) w/ 1 fiber optic network drop in close proximity of conference table to allow connectivity. | ||
| Fire detection and suppression system (to code) | ||
| Multi-zoned lighting throughout with dimming capability | ||
| HVAC to Code | ||
| Conference Room #2: | 18 | ICD/ICS 705 |
| 1 Conference Room Table for 8 (Office chairs) with seating around perimeter wall for 10 additional persons | ||
| 2 strand single mode fiber optic cable installed in a single port face plate with SC connectors and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate, at conference room table | ||
| Computer work stations and desk with one (1) 60" wall mounted monitor, Power outlet, and 1 fiber optic video line from computer work station to monitor | ||
| Teleconference phone (located on conference table) w/ 1 fiber optic network drop in close proximity of conference table to allow connectivity. | ||
| Fire detection and suppression system (to code) | ||
| Multi-zoned lighting throughout with dimming capability | ||
| HVAC to Code |
| Office Space Area #2: Entire room constructed to ICD/ICS 705 Standards; No windows on exterior walls; access from main hallway | 50 | ICD/ICS 705 |
| Open air office space for 48 employees (carpeted w/ appropriate ceiling lighting, fire detection and suppression, and HVAC to code) | 48 | |
| Each employees cube shall be monolithic panel, 6'x6' staff cube (efficiency), w/ power to all panels | ||
| Cubicles shall be grouped into sets of 4 - to the maximum extent possible | ||
| Each set of 4 cubicles will have a single entry point (sized to code) with entry from a hall space (sized to code) | ||
| Each cubical work space shall contain: | ||
| Corner style desk space (appropriate to size of their cubical) | ||
| 2 each 3-drawer filing cabinets (attached under desk top) | ||
| Over-desk storage cabinets (appropriate to size of their cubical) | ||
| Black, swivel/tilt mesh mid-back task chair, with fixed cantilevered arms | ||
| Switched lighting under the over-desk storage cabinets | ||
| Sufficient electrical outlets to support 3 computers, 2 monitors, 1 telephone, 1 KVM Switch, and cubical lights, plus one additional double outlet | ||
| 6 strand single mode fiber optic cable installed in a single 3 port face plate with SC connectors per location and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate per location | ||
| Centrally located workspace for three (3) Network Printers, w/ 1 power and fiber optic network drop per printer | ||
| Centrally located workspace for one (1) 5-drawer safe (18"x28" - weighs 1,000 lbs. loaded) and 1 paper shredder (20"x27") | ||
| 2 individual offices (carpeted w/ appropriate ceiling lighting and HVAC to code) | 2 | |
| Supervisor’s office shall be a stackable panel, 8'x10' manager cube, with power on all panels, and with office height panels (76"-81") with door. | ||
| Each supervisor’s office shall be furnished with freestanding "U" shaped desk, with 24" wide storage tower with shelves | ||
| Chairs shall be black, swivel/tilt mesh mid-back task chair, with fixed cantilevered arms | ||
| Sufficient electrical | ||
| 6 strand single mode fiber optic cable installed in a single 3 port face plate with SC connectors per location and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate per location | ||
| Intrusion Detection System (IDS) Panel (throughout area #2 - tied back to communication room (CER) | ||
| IDS consists of door intrusion and motion sensors tied to IDS panel within room | ||
| Vindicator Access Control on area #2 main entry door - tied back to Communication Room (CER) | ||
| Centrally located workspace for two (2) Network Printers, w/ 1 power and fiber optic network drop, and 1 power and fiber optic network drop |
| Office Space Area #3: Entire room constructed to ICD/ICS 705 Standards; No windows on exterior walls; access from main hallway - must be adjacent to Workspace #4 | 35 | ICD/ICS 705 |
| Open air office space for 33 employees (carpeted w/ appropriate ceiling lighting fire detection and suppression, and HVAC to code) | 33 | |
| Each employees cube shall be monolithic panel, 6'x6' staff cube (efficiency), w/ power to all panels | ||
| Cubicles shall be grouped into sets of 4 - to the maximum extent possible | ||
| Each set of 4 cubicles will have a single entry point (sized to code) with entry from a hall space (sized to code) | ||
| Each cubical work space shall contain: | ||
| Corner style desk space (appropriate to size of their cubical) | ||
| 2 each 3-drawer filing cabinets (attached under desk top) | ||
| Over-desk storage cabinets (appropriate to size of their cubicle) | ||
| Black, swivel/tilt mesh mid-back task chair, with fixed cantilevered arms | ||
| Switched lighting under the over-desk storage cabinets | ||
| Sufficient electrical outlets to support 2 computers, 4 monitors, 1 telephone, 1 KVM Switch, and cubical lights) plus one additional double outlet | ||
| 6 strand single mode fiber optic cable installed in a single 3 port face plate with SC connectors per location and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate per location | ||
| Centrally located workspace for three (3) Network Printers, w/ 1 power and fiber optic network drop per printer | ||
| Centrally located workspace for one (1) 5-drawer safe (18"x28" - weighs 1,000 lbs. loaded) and 1 paper shredder | ||
| 2 individual offices (carpeted w/ appropriate ceiling lighting and HVAC to code) | 2 | |
| Supervisor’s office shall be a stackable panel, 8'x10' manager cube, with power on all panels, and with office height panels (76"-81") with door. | ||
| Each supervisor’s office shall be furnished with freestanding "U" shaped desk, with 24" wide storage tower with shelves | ||
| Chairs shall be black, swivel/tilt mesh mid-back task chair, with fixed cantilevered arms | ||
| Sufficient electrical | ||
| 6 strand single mode fiber optic cable installed in a single 3 port face plate with SC connectors per location and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate per location | ||
| Intrusion Detection System (IDS) Panel (throughout area #3) - tied back to communication room (CER) | ||
| IDS consists of door intrusion and motion sensors tied to IDS panel within room | ||
| Vindicator Access Control on area #3 entry door - tied back to Communication Room Switch | ||
| Centrally located workspace for two (2) Network Printers, w/ 1 power and fiber optic network drop per printer |
| Office Space Area #4: Entire room constructed to ICD/ICS 705 Standards; No windows on exterior walls; access from main hallway - must be adjacent to Workspace #3 | 15 | ICD/ICS 705 |
| Open air office space for 14 employees (carpeted w/ appropriate ceiling lighting fire detection and suppression, and HVAC to code) | 14 | |
| Each employees cube shall be monolithic panel, 6'x6' staff cube (efficiency), w/ power to all panels | ||
| Cubicles shall be grouped into sets of 4 - to the maximum extent possible | ||
| Each set of 4 cubicles will have a single entry point (sized to code) with entry from a hall space (sized to code) | ||
| Each cubical work space shall contain: | ||
| Corner style desk space (appropriate to size of their cubical) | ||
| 2 each 3-drawer filing cabinets (attached under desk top) | ||
| Over-desk storage cabinets (appropriate to size of their cubical) | ||
| Black, swivel/tilt mesh mid-back task chair, with fixed cantilevered arms | ||
| Switched lighting under the over-desk storage cabinets | ||
| Sufficient electrical outlets to support 3 computers, 2 monitors, 1 KVM Switch, and cubical lights) plus one additional double outlet | ||
| 6 strand single mode fiber optic cable installed in a single 3 port face plate with SC connectors per location and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate per location | ||
| Centrally located workspace for three (3) Network Printers, w/ 1 power and fiber optic network drop per printer | ||
| Centrally located workspace for one (1) 5-drawer safe (18"x28" - weighs 1,000 lbs. loaded) and 1 paper shredder (20"x27") | ||
| 1 individual office (carpeted w/ appropriate ceiling lighting and HVAC to code) | 1 | |
| Supervisor’s office shall be a stackable panel, 8'x10' manager cube, with power on all panels, and with office height panels (76"-81") with door. | ||
| Each supervisor’s office shall be furnished with freestanding "U" shaped desk, with 24" wide storage tower with shelves | ||
| Chairs shall be black, swivel/tilt mesh mid-back task chair, with fixed cantilevered arms | ||
| Sufficient electrical | ||
| 6 strand single mode fiber optic cable installed in a single 3 port face plate with SC connectors per location and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate per location | ||
| Intrusion Detection System (IDS) Panel (throughout area #3) - tied back to communication room (CER) | ||
| IDS consists of door intrusion and motion sensors tied to IDS panel within room | ||
| Vindicator Access Control on area #3 entry door - tied back to Communication Room Switch |
| Video Teleconference Room: Entire room constructed to ICD/ICS 705 Standards; access from main hallway; must be adjacent to Computer Lab | 24 | ICD/ICS 705 |
| 1 Conference Room Table for 8, with seating around the walls for 16 additional persons | ||
| Computer workstation w/ 9 fiber optic computer network cable drops | ||
| Teleconference phone (located on conference table) w/ 1 fiber optic network drop in close proximity of conference table to allow connectivity. | ||
| Intrusion Detection System (IDS) Panel (inside room); can be tied with computer lab - all tied back to the Comm Rm (CER) | ||
| IDS consists of door intrusion and motion sensors tied to IDS panel within room | ||
| Vindicator Access Control on entry door - tied back to Communication Room Switch | ||
| Video Teleconference Equipment with two (2) 60" wall mounted monitors and one overhead projector. | ||
| Multi-zoned lighting throughout room with dimming capability | ||
| Fire detection and suppression system (to code) |
| Computer Lab: Entire Room constructed to ICD/ICS 705 Standards; access from main hallway; must be adjacent to Video Teleconference Room. | 3 employees and 20 additional workstations | ICD/ICS 705 |
| Open air office space for 3 employees (carpeted w/ appropriate ceiling lighting fire detection and suppression, and HVAC to code) | 3 | |
| Each employees cube shall be monolithic panel, 6'x6' staff cube (efficiency), w/ power to all panels | ||
| Each cubical work space shall contain: | ||
| Corner style desk space (appropriate to size of their cubical) | ||
| 2 each 3-drawer filing cabinets (attached under desk top) | ||
| Over-desk storage cabinets (appropriate to size of their cubical) | ||
| Black, swivel/tilt mesh mid-back task chair, with fixed cantilevered arms | ||
| Switched lighting under the over-desk storage cabinets | ||
| Sufficient electrical outlets to support 3 computers, 2 monitors, 1 KVM Switch, and cubical lights, plus one additional double outlet | ||
| 6 strand single mode fiber optic cable installed in a single 3 port face plate with SC connectors per location and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate per location | ||
| 20 additional independent work spaces (these do not have to contain cubicle furniture - 6 foot long work desks will suffice) - Each work space shall contain: | 20 | |
| 5 desktop computers, 2 monitors, 1 keyboard, 1 mouse, 1 KVM switch | ||
| Dividers between each work station | ||
| Black, swivel/tilt mesh mid-back task chair, with fixed cantilevered arms (1 chair per work station) | ||
| 6 strand single mode fiber optic cable installed in a single 3 port face plate with SC connectors per location and in a separate junction box two blue CAT 6 cables and jacks mounted in a two port face plate per locations | ||
| Appropriate power outlets for all equipment | ||
| Intrusion Detection System (IDS) Panel (inside room); can be tied with video teleconference room - all tied back to the Comm Rm (CER) | ||
| IDS consists of door intrusion and motion sensors tied to IDS panel within room | ||
| Vindicator Access Control on entry door - tied back to Communication Room Switch | ||
| Centrally located workspace for six (6) Network Printers, w/ 1 power and fiber optic network drop per printer | ||
| Centrally located workspace for one (1) 5-drawer safe (18"x28" - weighs 1,000 lbs. loaded) and 1 paper w/optical shredder (20"x27") |
| Main Communications Room (CER): ICD/ICS 705; centrally located to provide direct network access to each workspace (no pass-throughs) Reference Tab K - 75 ABW/SC, Telecommunications Installation Criteria for Facility Design and Renovation | N/A | ICD/ICS 705 |
| Room shall be sized to accommodate 3 equipment racks installed side by side and shall be placed to provide front and rear access with a minimum of 36" clearance front and back | ||
| Racks shall be 19" X 7' two post racks, racks shall have 6" vertical cable managers located on the left and right sides, front and back, and seismically braced | ||
| Racks shall be grounded; shall have one (1) quad-plex 120 VAC, 60Hz, 1 phase electrical outlets and two (2) 208 VAC, 60Hz, 1 phase electrical outlets per rack and installed on the back side bottom of each rack | ||
| Provide, install, terminate, test and label 12 strand single mode fiber optic cable in a rack mounted fiber patch panel with SC connectors from the CER to a rack mounted fiber patch panel in each TR | ||
| Provide, install, terminate, test and label a 25 pair house cable on a 24 port rack mounted CAT 6 patch panel from the CER to a 24 port rack mounted CAT 6 patch panel in each TR | ||
| 5 SwitchesThe Government shall provide and install required switches | DELETED | |
| 5 TACLANEs The Government shall provide and install required TACLANES | DELETED | |
| Intrusion Detection System (IDS) Panel (inside room) - tied back to communication room (CER) | ||
| IDS consists of door intrusion and motion sensors tied to IDS panel within room | ||
| Vindicator Access Control on entry door - tied back to Communication Room Switch | ||
| Fire detection and suppression system (to code) |
| Mechanical/Electrical: Secure exterior entry - entire room constructed to ICD/ICS 705 standards; mechanical lock on exterior door. | N/A | ICD/ICS 705 |
| Design to support all required mechanical systems | ||
| Design to support all required electrical systems | ||
| Design to support all required HVAC systems with capabilities to emergency shut down for Shelter-In-Place requirements | ||
| Fire detection and suppression (to code) |
| Exterior Camera System: Day, night, and all weather security cameras; 360 degrees around outside of facility; mounted to the building; linked to security desk in foyer |
| Clear line of sight to all entrances, emergency exits, and door ways. |
| Exterior Communications Cabling | N/A | N/A |
| Provide, install, terminate, test and label 24 strand single mode fiber optic cable in a rack mounted fiber patch panel with SC connectors from MH 19011-30 to CER | ||
| Provide, install, terminate, test and label 50 pair cable in a backboard mounted BET from MH 19011-30 to CER. From BET provide, install, terminate, test and label a 50 pair house cable in a CAT 6 rack mounted patch panel | ||
| Provide and install 2, 4" conduit from MH 19011-30 to CER. Within one of the 4" conduits install 4, 1" inner-ducts | ||
| Provide, install, terminate, test and label a 300 pair cable in Bldg 1214 | ||
| Provide, Install, terminate, test and label 288 strand single mode fiber from MH 19011-30 through MH19011-29, MH19011-28 to Bldg 1214. Unspliced cable shall be tested using OTDR | ||
| Splice 24 strand single mode fiber in MH 19011-30 to 288 strand fiber | ||
| Splice 50 pair cable in MH 19011-30 to 300 pair cable |
| Amendment 0004 changes incorporated: |
| Lines: 14, 56, 64, 71, 79, 98, 106, 124, 132, 150, 158, 184, and 189 - Amended to clarify computer drop requirements. |
| Lines: 65, 67, 133, 159, 167, 191, and 205 - Amended to clarify reference to "CER." |
| Lines: 73 and 87 - Deleted fiber requirement for teleconference phones |
| Lines: 198-204 - Amended to provide clarification of requirements |
| Lines: 220-227 - Added to define exterior comm cabling requirements |