USSF Uninterruptible Power Supply (UPS) Site Information Sheet
| 4 April 2022 |
| Buckley SFB, CO |
| Bldg. 730 |
1. POINTS OF CONTACT
| Primary: David Zubiate |
| Alternate: SSgt Eric Martineau |
| Alternate: Arthur Engelbrecht |
| david.zubiate.2@spaceforce.mil |
| eric.martineau@spaceforce.mil |
| arthur.engelbrecht@spaceforce.mil |
| (720) 847-5700 |
| DSN 847-5700 |
| (720) 847-5706 |
| DSN 847-5706 |
| (720) 847-2034 |
| DSN 847-2034 |
SPOC POC: Mr. Aller Delarosa; Comm: (719) 554-2906, DSN 692-2906; Email: aller.delarosa.1@spaceforce.mil
Security Management Office POC: TSgt Emmett Ladd; emmett.ladd@us.af.mil; (720) 847-5850; DSN 847-5850
Installation/Restricted Area/Facility Access Requirements: Contact POC
2. ORGANIZATION, MISSION, & LOCATION
Organization: USSF; SPOC; SBD 2; 460 SCS
UNCLASS Mission Supported by UPS: Network Control Center, AFSPC SharePoint, MHSI, JWICS PoP
| Street Address Where UPS is Located: 84 N. Aspen St. |
| UPS/Battery Rm #: L008 |
| Installation: Buckley SFB |
| State: CO |
| Zip: 80011 |
| DoDAAC: 503000 |
3. UPS MODULE
| Configuration: Parallel Redundant |
| Configuration/CTO #: TC1022201130010 |
| Manufacturer: Powerware |
| Series: 9390-120 |
| Model: 120 |
| kVA: 120 |
| kW: 96 |
| Input/output Voltage: 480 / 480 |
| System Load: 58 kVA |
Serial Number/s: (1) EA463CAA12 (2) EA465CAA07
| Date Manufactured: Nov 2007 |
| Date Installed: 17 Dec 2007 |
| Caps Upgrade: 9 Nov 16 |
4. ANCILLARY EQUIPMENT (i.e. Parallel Cabinet, Maintenance Bypass Cabinet, etc.)
| Manufacturer: |
| Type: |
| Serial #: |
| Powerware |
| Integrated Distribution Cabinet (MIS, MBP) |
| EA442EAA04 |
| Powerware |
| Parallel Tie Cabinet |
| No Serial # |
| Remote Monitor: No |
| Emergency Power Off: Yes, Rm. L008 |
| Spares Kit: No |
5. BATTERIES
Configuration: (2) parallel cabinets per module, (4) total cabinets; (40) jars in series per cabinet, (160) total jars
| Manufacturer: CSB |
| Series: |
| Model: HRL12280WFR |
| Watts/Cell: 283 |
| Type (Flooded/Sealed): Sealed |
| # Volts per Cell/Jar: 2 / 12 |
| DC Float: 540 VDC |
| # Strings / Unit: 2 |
| # Jars / String: 40 |
| # Cells / Jar: 6 |
| # Jars / Unit: 80 |
| Total Jars / System: 160 |
| Date Code: 0619 |
| Date Installed: 1 Nov 19 |
| Installed By: CSI |
| Warranty: 3 years |
| Battery Monitoring System: No |
| Spare Batteries: No |
6. PREVENTIVE MAINTENANCE
Modules, integral equipment, and sealed batteries are semi-annual (every 6 mos.); flooded batteries are quarterly (every 3 mos.)
7. ADDITIONAL DATA
Telephone in UPS/Battery Room: No
Mobile Telephone Permitted in UPS Room: No
Laptop Computer Permitted in UPS Room: Yes (Submit laptop authorization letter, contact POC)