USSF/SPOC Uninterruptible Power Supply (UPS) Site Information Sheet
| 19 October 2022 |
| Buckley SFB, CO |
| Bldg. 1030 |
1. POINTS OF CONTACT
Primary: SSgt Ariel Sandoval Ariel.sandoval@spaceforce.mil
(720) 847-6808 DSN 847-6808
Alternate: A1C Malanie Villa Malanie.villa@spaceforce.mil
(720) 847-6151 DSN 847-6151
24-Hour Work Center 460.commandpost@us.af.mil
(720) 847-4600 DSN 847-4600
Alternate: SSgt Stephen Robles Stephen.robles@sapceforce.mil
(720) 847-9952 DSN 847-9952
Alternate: Mr. Bryan Meredith Bryan.meredith.1@spaceforce.mil
(720) 847-6971 DSN 847-6971
SPOC POC: Mr. Aller Delarosa Aller.delaorsa.1@spaceforce.mil
(719) 554-2906 DSN 692-2906
Security Management Office (SMO) Code: BU1SFP2N6
Installation/Restricted Area/Facility Access Requirements: Contact POC
3. ORGANIZATION, MISSION, & LOCATION
Organization: USSF; SPOC; SBD 2
UNCLASS Mission Supported by UPS: 460 SW Command Post & Installation Control Center and Comm Rooms
| Street Address Where UPS is Located: 510 S. Aspen St. |
| UPS/Battery Rm #: 012 |
| Installation: Buckley SFB |
| State: CO |
| Zip: 80011 |
| DoDAAC: FA2543 |
4. UPS MODULE
| Configuration: Single Module, Reverse Transfer |
| CTO/Tag #: 1932914 |
| Manufacturer: Liebert |
| Series: eXM |
| Model: 51SA050BAA00S03 |
| kVA: 50 |
| kW: 64 |
| Input/output Voltage: 480 / 480 |
| System Load: 18 kVA |
Serial Number/s: (1) M18LUS0009
| Date Manufactured: Apr 2019 |
| Date Installed: 26 Jun 19 |
| Caps Upgrade: N/A |
5. ANCILLARY EQUIPMENT (i.e. Parallel Cabinet, Maintenance Bypass Cabinet, etc.)
| Manufacturer: UNK |
| Type: Maintenance Bypass |
| Serial #: N/A |
| Remote Monitor: No |
| Emergency Power Off: No |
| Spares Kit: No |
6. BATTERIES
Configuration: (2) parallel cabinets; (36) jars in series per cabinet, (72) total jars
| Manufacturer: Deka |
| Series: |
| Model: HR1500 |
| Watts/Cell: 150 |
| Type (Flooded/Sealed): Sealed |
| # Volts per Cell/Jar: 2 / 12 |
| DC Float: 486 VDC |
| # Strings / Unit: 2 |
| # Jars / String: 36 |
| # Cells / Jar: 6 |
| # Jars / Unit: 72 |
| Total Jars / System: 72 |
| Date Code: 1118 |
| Date Installed: 24 Jun 19 |
| Installed By: AllCom |
| Warranty: 3 years |
| Battery monitoring System: No |
| Spare Batteries: No |
7. PREVENTIVE MAINTENANCE DUE
Modules, integral equipment, and sealed batteries are semi-annual (every 6 mos.); flooded batteries are quarterly (every 3 mos.)
8. ADDITIONAL DATA
Laptop Computer Permitted in UPS Room: Yes (no special requirements)
Mobile Telephone Permitted in UPS Room: Yes (no special requirements)
| Telephone in UPS Rm: No |
| Telephone in Battery Rm: No |