USSF/SPOC Uninterruptible Power Supply (UPS) Site Information Sheet
| 6 October 2022 |
| Buckley SFB, CO |
| Bldg. 433 |
1. POINTS OF CONTACT
| Primary: Mr. Kevin Perdue |
| Alternate: Mr. Mitchell Cuthbert |
| Additional: Mr. Patrick Holder |
| Utilities Plant Supervisor |
| Utilities Plant Lead |
| Facilities Superintendent |
| Kevin.perdue.2@spaceforce.mil |
| Mitchell.cuthbert@spaceforce.mil |
| Patrick.holder.1@spaceforce.mil |
| (720) 847-5794/5; (720) 847-9893 |
| (720) 847-6153 (720) 847-5794/5 |
| (720) 847-9916 |
| DSN 847-9916 |
24-Hour Work Center: Power Plant Control Room, (720) 847-5794/5, DSN 847-5794/5
SPOC POC: Mr. Aller Delarosa; aller.delarosa.1@spaceforce.mil; (719) 554-2906; DSN 692-2906
Security Management Office (SMO) Code:
Installation/Restricted Area/Facility Access Requirements: Contact Mr. Patrick Holder
2. ORGANIZATION, MISSION, & LOCATION
Organization: USSF; SPOC; Delta 4
| UNCLASS Mission Supported by UPS: SBIRS Mission Control Station |
| UPS Room #: 2nd Flr, Power Plant |
| Street Address Where UPS is Located: 18220 E. Crested Butte Ave. |
| Battery Rm #: 1st Flr, Power Plant |
| Installation: Buckley SFB |
| State: CO |
| Zip: 80011 |
| DoDAAC: F03000 |
3. UPS MODULE
Configuration: N+1 Parallel Redundant with isolated A & B Bus
| Manufacturer: Liebert |
| Series: NXL 40 |
| Model: 40S400A0AAA32A |
| kVA: 400 |
| kW: 360 |
| Input/Output Voltage: 480 / 480 |
| System Load: 70/138 kVA |
Serial Number/s:
Tag Number:
1 (1A) D11C240014 1 (1A) 1552953 2 (1B) D11C240015 2 (1B) 1552954 3 (2A) D11D240002 3 (2A) 1552955 4 (2B) D11D240003 4 (2B) 1552956
| Date Manufactured: Apr 2011 |
| Date Installed: 6 Jun 2011 |
| Caps Upgrade: 26 Sep 18 (AllCom) |
4. ANCILLARY EQUIPMENT (i.e. Parallel Cabinet, Maintenance Bypass Cabinet, etc.)
| Manufacturer: |
| Type: |
| Serial #: |
| Tag #: |
| Liebert |
| Static Transfer Switch # 2 |
| D11D5J0014 |
| 1552957 |
| Liebert |
| Static Transfer Switch # 1 |
| D11D5J0012 |
| 1552958 |
| Square D |
| Battery Disconnect Switch (x 12) |
| No S/N |
| No Tag # |
| Remote Monitor Panel: Yes, Power Plant Control Rm. |
| Emergency Power Off: No |
| Spares Kit: Yes |
5. BATTERIES
Configuration: Racks, (4) tiers per rack; (3) parallel racks per module; (40) jars in series per rack, (480) total jars
| Manufacturer: Fiamm |
| Series: |
| Model: 12FLX540 |
| Watts/Cell: 570 |
| Type (Flooded/Sealed): Sealed |
| # Volts per Cell/Jar: 2 / 12 |
| DC Float: 540 VDC |
| # Strings / Unit: 3 |
| # Jars / String: 40 |
| # Cells / Jar: 6 |
| # Jars / Unit: 120 |
| Total Jars / System: 480 |
| Date Code: 0822 |
| Date Installed: 26-30 Sep 22 |
| Installed By: Pergravis |
| Warranty: 3 yrs. |
| Battery Monitoring System: No |
| Spare Batteries: No |
6. PREVENTIVE MAINTENANCE
Modules, integral equipment, and sealed batteries are semi-annual (every 6 mos.); flooded batteries are quarterly (every 3 mos.)
7. ADDITIONAL DATA
Laptop Computer Permitted in UPS Room: Yes (Submit attached Laptop Authorization Letter, Wi-Fi deactivated)
Mobile Telephones Permitted in UPS Room: No (Not permitted in Restricted Area)
Telephone in UPS/Battery Rooms: No/No