USSF/SPOC Uninterruptible Power Supply (UPS) Site Information Sheet
| 1 April 2022 |
| Buckley SFB, CO |
| Bldg. 442 |
1. POINTS OF CONTACT
| Primary: Mr. Kevin Purdue |
| Alternate: Mr. Mitchell Cuthbert |
| Additional: Mr. Patrick Holder |
| Utilities Plant Supervisor |
| Utilities Plant Lead |
| Facilities Superintendent |
| Kevin.perdue.2@spaceforce.mil |
| Mitchell.cuthbert@spaceforce.mil |
| Patrick.holder.1@spaceforce.mil |
| (720) 847-5794/5; (720) 847-9893 |
| (720) 847-6153 (720) 847-5794/5 |
| (720) 847-9916 |
| DSN 847-9916 |
24-Hour Work Center: Power Plant Control Room, (720) 847-5794/5, DSN 847-5794/5
USSF POC: Mr. Aller Delarosa; aller.delarosa.1@spaceforce.mil; (719) 554-2906; DSN 692-2906
Security Management Office (SMO) Code: BU1SFB4L6
Installation/Restricted Area/Facility Access Requirements: Contact Mr. Patrick Holder
2. ORGANIZATION, MISSION, & LOCATION
Organization: USSF; SPOC; Delta 4
| UNCLASS Mission Supported by UPS: SBIRS (Technical Bus) |
| UPS Room #: 140 |
| Street Address Where UPS is Located: 18079 E. Buttermilk Ave. |
| Battery Rm #: 150 |
| Installation: Buckley SFB |
| State: CO |
| Zip: 80011 |
| DoDAAC: F03000 |
3. UPS MODULE
| Configuration: Parallel Redundant w/manual Hot Tie |
| Configuration/CTO #: CC50136160100R6 |
| Manufacturer: Eaton |
| Series: 9395 |
| Model: 9395-550 |
| Date Manufactured: September 2015 |
| Date Installed: Jan 16 |
| Caps Date Code: |
| kVA: 550 |
| kW: 495 |
| Input/output Voltage: 480 / 480 |
| System Load: ____ kVA |
Module S/N: 1 (1A): EJ384BAA07 2 (1B): EJ384BAA04 3 (2A): EJ384BAA02 4 (2B): EJ384BAA03
4. ANCILLARY EQUIPMENT (i.e. Parallel Cabinet, Maintenance Bypass Cabinet, etc.)
| Manufacturer: |
| Type: |
| Serial #: |
| Eaton |
| Parallel Cabinet (A) |
| No S/N |
| Eaton |
| Parallel Cabinet (B) |
| No S/N |
| Square D |
| Manual Hot Tie |
| No S/N |
| Remote Monitor: Yes, Power Plant Ctrl. Rm. |
| Emergency Power Off: No |
| Spares Kit: Yes, B-level |
5. BATTERIES
Configuration: (2) parallel cabinets per module, (8) total cabinets; (30) jars in series per cabinet, (240) total jars
| Manufacturer: Enersys |
| Series: DataSafe HX |
| Model: 16HX925FR |
| Watts/Cell: 925 |
| Type (Flooded/Sealed): Sealed |
| # Volts per Cell/Jar: 2 / 16 |
| DC Float: 540 VDC |
| # Strings / Unit: 2 |
| # Jars / String: 30 |
| # Cells / Jar: 8 |
| # Jars / Unit: 60 |
| Total Jars / System: 240 |
| Date Code: 0120 |
| Date Installed: 3 Mar 20 |
| Installed By: Eaton |
| Warranty: 3 years |
| Battery Monitoring: No |
| Spare Batteries: No |
6. PREVENTIVE MAINTENANCE DUE
Modules, integral equipment, and sealed batteries are semi-annual (every 6 mos.); flooded batteries are quarterly (every 3 mos.)
7. ADDITIONAL DATA
Laptop Computer Permitted in UPS Room: Yes (Submit attached Laptop Authorization Letter, Wi-Fi deactivated)
Mobile Telephones Permitted in UPS Room: No (Not permitted in Restricted Area)