USSF/SPOC Uninterruptible Power Supply (UPS) Site Information Sheet
| 29 April 2022 |
| Buckley SFB, CO |
| Bldg. 442 |
1. POINTS OF CONTACT
| Primary: Mr. Kevin Purdue |
| Alternate: Mr. Mitchell Cuthbert |
| Additional: Mr. Patrick Holder |
| Utilities Plant Supervisor |
| Utilities Plant Lead |
| Facilities Superintendent |
| Kevin.perdue.2@spaceforce.mil |
| Mitchell.cuthbert@spaceforce.mil |
| Patrick.holder.1@spaceforce.mil |
| (720) 847-5794/5; (720) 847-9893 |
| (720) 847-6153 (720) 847-5794/5 |
| (720) 847-9916 |
| DSN 847-9916 |
24-Hour Work Center: Power Plant Control Room, (720) 847-5794/5, DSN 847-5794/5
SPOC POC: Mr. Aller Delarosa; aller.delarosa.1@spaceforce.mil; (719) 554-2906; DSN 692-2906
Security Management Office (SMO) Code:
Installation/Restricted Area/Facility Access Requirements: Contact Mr. Patrick Holder
2. ORGANIZATION, MISSION, & LOCATION
Organization: USSF; SPOC; Delta 4
| UNCLASS Mission Supported by UPS: SBIRS (Utility Bus) |
| UPS Room #: 191 |
| Street Address Where UPS is Located: 18079 E. Buttermilk Ave. |
| Battery Rm #: 193 |
| Installation: Buckley SFB |
| State: CO |
| Zip: 80011 |
| DoDAAC: F03000 |
3. UPS MODULE
| Configuration: Two parallel redundant systems |
| Configuration/CTO #: 9PL13C0009C00R2 |
| Manufacturer: Eaton |
| Series: 93PM |
| Model: 110-150 |
| kVA: 130 |
| kW: 130 |
| Input/output Voltage: 480 / 480 |
| System Load: ____ kVA |
Module Serial #: 1. EK481UXX03 (3A) 2. EK481UXX02 (3B) 3. EK481UXX01 (4A) 4. EK474UXX01 (4B)
| Date Manufactured: Nov 2016 |
| Date Installed: 26 Jan 17 |
| Caps Date Code: |
4. ANCILLARY EQUIPMENT (i.e. Parallel Cabinet, Maintenance Bypass Cabinet, etc.)
| Manufacturer: |
| Type: |
| Serial #: |
| Type: |
| Serial # |
| Eaton |
| Parallel Cabinet (3AB) |
| No Serial Number |
| Maintenance Bypass 3 |
| No Serial Number |
| Eaton |
| Parallel Cabinet (4AB) |
| No Serial Number |
| Maintenance Bypass 4 |
| No Serial Number |
| Square D |
| Manual Hot Tie (3,4) |
| No Serial Number |
| Remote Monitor: Yes, Ctrl. Rm; Sense a Phone |
| Emergency Power Off: No |
| Spares Kit: Yes |
5. BATTERIES
Configuration: (2) strings per S/N, (8) strings total; (40) jars in series per string; (320) total jars
| Manufacturer: Enersys |
| Series: DataSafe |
| Model: 12HX300FR |
| Watts/Cell: 284 |
| Type (Flooded/Sealed): Sealed |
| # Volts per Cell/Jar: 2 / 12 |
| DC Float: 540 VDC |
| # Strings / Unit: 2 |
| # Jars / String: 40 |
| # Cells / Jar: 6 |
| # Jars / Unit: 80 |
| Total Jars / System: 320 |
| Date Code: 0222 |
| Date Installed: 27 Apr 22 |
| Installed By: Pergravis |
| Warranty: 3 years |
| Battery Monitor: No |
| Spare Batteries: No |
6. PREVENTIVE MAINTENANCE DUE
Modules, integral equipment, and sealed batteries are semi-annual (every 6 mos.); flooded batteries are quarterly (every 3 mos.)
7. ADDITIONAL DATA
Laptop Computer Permitted in UPS Room: Yes (Submit attached Laptop Authorization Letter, Wi-Fi deactivated)
Mobile Telephones Permitted in UPS Room: No (Not permitted in Restricted Area)