ELECTRICAL SITE PLAN - BUILDING 309 E4 26 OF 27
AS NOTED
TJM 06/12/07
AJH 09/05/07
E4E4
BUILDING 309 SITE PLAN
SCALE: 1/32"= 1'-0"
ELECTRICAL CODED NOTES:
1 REDUNDANT PUSH BUTTON CONTROLS FOR MOTOR-OPERATED BUTTERFLY VALVES IN
DEICING FLUID DIVERSION MANHOLES #1, #2 AND #3.
E4E4
DUCT BANK SECTION
SCALE: NONE
E4E4
DUCT BANK SECTION
SCALE: NONE
E4E4
DUCT BANK SECTION
SCALE: NONE
E4E4
DUCT BANK SECTION
SCALE: NONE
GREEN/RED BUTTERFLY VALVE SIGNAL LED FIXTURE AS MANUFACTURED BY SIGNAL TECH,
MODEL #TCILV-RG. SURFACE MOUNT FIXTURE ON BUILDING 308 SO PERSON(S) ON SITE
AT EACH MANHOLE CAN SEE FIXTURE CLEARLY. CONNECT TO LIMIT SWITCH AT DEICING
FLUID DIVERSION MANHOLE. LIMIT SWITCH SHALL BE POSITIONED AS TO ACTIVATE GREEN
WHEN BUTTERFLY VALVE IS FULLY OPENED, OTHERWISE LIGHT SHOULD BE RED. SEE
CONTROL WIRING DIAGRAM, DETAIL #6, THIS DRAWING.
OPTION #2: 1 - 2" PVC SCHEDULE 40 DIRECT BURIED
3 - 1-1/2" PVC SCHEDULE 40 DIRECT BURIED 3 - 1-1/2" PVC SCHEDULE 40 DIRECT BURIED 2 - 1-1/2" PVC SCHEDULE 40 DIRECT BURIED 1 - 1-1/2" PVC SCHEDULE 40 DIRECT BURIED
INSTALL CONDUITS ALONG CEILING. INSTALL SO THAT CONDUITS DO NOT INTERFERE
WITH OR OBSTRUCT INTERIOR LIGHTING FIXTURES, COLUMNS, AIR SYSTEM EQUIPMENT,
FIRE LINES, ETC.
REFER TO: ELECTRICAL LEGEND AND FIXTURE SCHEDULE, DWG. E1;
ONE LINE DIAGRAM, DWG. E1; AND ELECTRICAL PANEL SCHEDULES FOR
INSTALLATION DETAILS FEEDER AND CONDUIT SIZES, ETC., DWG. E1.
SEE MECHANICAL DRAWINGS FOR T-STAT LOCATIONS.
GENERAL ELECTRICAL NOTES:
1.
ROUTE CONDUIT PER SPACE RATING AS PER THE 2005 EDITION OF THE NATIONAL
ELECTRIC CODE, CHAPTER 5.
E4E4
CONTROL WIRING DIAGRAM
TYPICAL FOR 3 SCALE: NONE
FURNISH AND INSTALL A 480:120 VOLT, 1-PHASE TRANSFORMER, FUSES AND GFCI
RECEPTACLE IN NEMA-4X RATED BOX. SEE CONTROL WIRING DIAGRAM, DETAIL #6,
THIS DRAWING.
SUMP PUMP
FURN. BY
OTHERS
OSBORN
DESCRIPTION OF ISSUE DATE BY
APPROVED DATE
DRAWN DATE
CHECKED DATE
DRAWING NO SCALE
PRINTED ISSUE NO
MARK DESCRIPTION OF REVISIONMARK DATE BY
ARCHITECTS
CLEVELAND OHIO
ENGINEERS
AKRON OHIO
OEC PROJECT 12910-280
AIR FORCE RESERVE COMMAND HEADQUARTERS
910 AIRLIFT WING
INDUSTRIAL WASTEWATER - BLDG. 309
SHEET NO
TH
OSBORN ARCHITECTS ENGINEERS0 ISSUED FOR BIDS 1/23/08 OEC
PROJECT ZQEL 06-0003
1 REVISED ELECTRICAL CODED NOTE #4 03/20/08 EAM
75 KVA
3∅
P V C
P V C
P V C
P
VC
P V C
V C P
V C P
R C P
R C P
R C P
P
R C P
B309 x x x x x x x x
J
DEICING FLUID
DIVERSION MANHOLE #2
DEICING FLUID
DIVERSION MANHOLE #3
E4 E4
FIN GRADE
CAUTION WARNING TAPE
1-1/2" PVC SCHEDULE 40
CONDUIT (TYPICAL FOR 3)
6" MIN COMPACTED
CLEAN FILL
2'-6"
1'-0"
EXCEEDING SIX INCHES LOOSE DEPTH AS SHOW.
FILL MATERIAL IN CONTINUOUS LAYERS NOT
COMPACT TO A MINIMUM OF 95 PERCENT.
THREE INCHES. PLACE AND COMPACT COMMON
THAN SIX INCHES AND ROCKS LARGER THAN
MATERIAL, GRADED FREE OF LUMPS LARGER
BACKFILL HOLE AROUND CONDUIT WITH EXCAVATED
12" MIN SAND
RESEED IN GRASS AREAS.
FINISHED GRADE SURFACE
AS PER DRAWINGS.
OPTION #2: CONDUIT PULL AND
INSTALL 6/6 SINGLE/MULTI FIBER
OPTIC CABLE IN 2" PVC FROM
B309 TO B308
DEICING FLUID
DIVERSION MANHOLE #1
FIN GRADE
CAUTION WARNING TAPE
1-1/2" PVC SCHEDULE 40
CONDUIT (TYPICAL FOR 3)
6" MIN COMPACTED
CLEAN FILL
2'-6"
1'-0"
EXCEEDING SIX INCHES LOOSE DEPTH AS SHOW.
FILL MATERIAL IN CONTINUOUS LAYERS NOT
COMPACT TO A MINIMUM OF 95 PERCENT.
THREE INCHES. PLACE AND COMPACT COMMON
THAN SIX INCHES AND ROCKS LARGER THAN
MATERIAL, GRADED FREE OF LUMPS LARGER
BACKFILL HOLE AROUND CONDUIT WITH EXCAVATED
12" MIN SAND
RESEED IN GRASS AREAS.
FINISHED GRADE SURFACE
AS PER DRAWINGS.
1'-0"
FIN GRADE
CAUTION WARNING TAPE
1-1/2" PVC SCHEDULE 40
CONDUIT
6" MIN COMPACTED
CLEAN FILL
2'-6"
1'-0"
EXCEEDING SIX INCHES LOOSE DEPTH AS SHOW.
FILL MATERIAL IN CONTINUOUS LAYERS NOT
COMPACT TO A MINIMUM OF 95 PERCENT.
THREE INCHES. PLACE AND COMPACT COMMON
THAN SIX INCHES AND ROCKS LARGER THAN
MATERIAL, GRADED FREE OF LUMPS LARGER
BACKFILL HOLE AROUND CONDUIT WITH EXCAVATED
12" MIN SAND
RESEED IN GRASS AREAS.
FINISHED GRADE SURFACE
AS PER DRAWINGS.
1'-0"
FIN GRADE
CAUTION WARNING TAPE
1-1/2" PVC
SCHEDULE 40 CONDUIT
6" MIN COMPACTED
CLEAN FILL
2'-6"
1'-0"
EXCEEDING SIX INCHES LOOSE DEPTH AS SHOW.
FILL MATERIAL IN CONTINUOUS LAYERS NOT
COMPACT TO A MINIMUM OF 95 PERCENT.
THREE INCHES. PLACE AND COMPACT COMMON
THAN SIX INCHES AND ROCKS LARGER THAN
MATERIAL, GRADED FREE OF LUMPS LARGER
BACKFILL HOLE AROUND CONDUIT WITH EXCAVATED
12" MIN SAND
RESEED IN GRASS AREAS.
FINISHED GRADE SURFACE
AS PER DRAWINGS.
1'-0"
CONDUIT PULL AND INSTALL 12 #10, #8
EG-1-1/2" PVC FROM B309 TO B308
(TYPICAL FOR 3)
CONDUIT PULL AND INSTALL 6 #10, #8
EG-1-1/2" PVC FROM B308 TO DEICING F
DIVERSION MANHOLE #1 (TYPICAL FOR 3)
CONDUIT PULL AND INSTALL 6 #10, #8
EG-1-1/2" PVC FROM B308 TO DEICING
FLUID DIVERSION MANHOLE #2
(TYPICAL FOR 2)
CONDUIT PULL AND INSTALL 6 #10, #8
EG-1-1/2" PVC FROM B308 TO DEICING
FLUID DIVERSION MANHOLE #3
E4 E4
E4 E4
E4 E4
OPENCLOSE
C.B.
L3
L2
L1
HEATER
TO MOTOR
L1
GRD
C.B.
R1
R
LS #2
R
C
R2
R
TS #2
R
R2
LS #1
CLOSE
R1
120 VOLT
OPEN
TS #1 OLS
C
OLS
MOTOR
SOLID STATE REVERSING
STARTER 480V, 3, SIZE1
OPEN
CONTROL
TRANSFORMER
480 VOLT
CLOSE
SHORTED SCR
CONTACT
L2
VALVE
OLS
BUILDING 308
OPEN
G
OPEN
G
CLOSED
R
CLOSED
R
OPENCLOSE
BUILDING 309
ENTER/EXITING BUILDING
WITH LB CONDULET 24"
ABOVE GRADE (TYPICAL)
SLL CONDUIT SHALL BE
RGS IN BUILDING 308
VALVE CONTROL PANEL FURNISHED AND INSTALLED
BY VALVE SUPPLIER. ELECTRICAL CONTRACTOR
SHALL PLACE CONNECTIONS AS SHOWN.
3 #10, #8 EG-1 1/2" PVC
3 #10, #10 EG-3/4" SEALTITE
NEW NEMA-4X J-BOX
IN COVER
BUILDING 308
BUILDING 309
PLC OPTION #2
TORQUE SWITCH
LIMIT SWITCH
ON VALVE
IN COVER
BUILDING 308
BUILDING 309
PLC OPTION #2
PLC
120 VOLT
480 VOLT
5A 5A
20A
2kVA
TRANSFORMER
NEMA-4X
ELECTRICAL BOX
GFCI
, #12 EG-3/4" SEALTITE
, #12 EG-3/4" SEALTITE
WP
(W
AT
ER
L
IN
E)
(WATER LINE)