Text version
E2E2
ELECTRICAL POWER PLAN
SCALE: 1/4"= 1'-0"
ELECTRICAL POWER AND LIGHTING PLAN E2 24 OF 27
AS NOTED
TJM 06/12/07
AJH 09/05/07
ELECTRICAL CODED NOTES:
EXISTING 480/277 VOLT, 3-PHASE, 4-WIRE DISTRIBUTION PANEL DP1. REMOVE
EXISTING 20 AMP, 3-POLE CIRCUIT BREAKER FOR THE AIR COMPRESSOR AND SET
ASIDE TO LATER INSTALL INTO NEW PANEL DP3 (SEE CODED NOTE #9). FURNISH
AND INSTALL ONE (1) NEW 100 AMP, 3-POLE CIRCUIT BREAKER. MATCH EXISTING
BREAKER SIZE AND TYPE.
FOR NEW FIXTURES IN ADDITION USE 2 #12, #12 EG-3/4" PVC TO FEED
FIXTURES FROM EXISTING PANEL LCP. ELECTRICAL CONTRACTING SHALL FURNISH
AND INSTALL MOUNTING BRACKETS TO MOUNT TYPE "A" FIXTURES TO JOISTS.
PLACE BRACKETS AS CLOSE TO PANEL POINTS AS POSSIBLE.
REFER TO: ELECTRICAL LEGEND AND FIXTURE SCHEDULE, DWG. E1;
ONE LINE DIAGRAM, DWG. E1; AND ELECTRICAL PANEL SCHEDULES FOR
INSTALLATION DETAILS FEEDER AND CONDUIT SIZES, ETC., DWG. E1.
SEE MECHANICAL DRAWINGS FOR T-STAT LOCATIONS.
GENERAL ELECTRICAL NOTES:
1.
3.
NEW SURFACE MOUNTED 480:120/208 VOLT MINI POWER CENTER WITH PANEL DP3.
FURNISH AS SHOWN ON ONE LINE DIAGRAM, DWG. E1.
NEW GARAGE DOOR OPENER/CONTROLLER FURNISHED BY CONTRACTOR. ELECTRICAL
CONTRACTOR SHALL INSTALL LOCAL PUSHBUTTON STATION, DOOR EDGE, PHOTO EYES
AND MOTOR CONTROLLER ALONG WITH ALL ASSOCIATED CONDUIT AND WIRE REQUIRED
FOR PROPER DOOR OPERATION. REFER TO MANUFACTURERS SUPPLIED DOOR
OPERATOR WIRING DIAGRAM FOR EXACT REQUIREMENTS.
NEW 250 VOLT, 30 AMP, NON-FUSED, NEMA-4X, SURFACE MOUNTED DISCONNECT
SWITCH. FURNISH AND INSTALL AS SHOWN ON ONE LINE DIAGRAM, DWG. E1.
EQUIPMENT SERVED AS INDICATED.
NEW 120 VOLT, 20 AMP FRACTIONAL HORSEPOWER STARTER (ST) MOUNTED ON
EXHAUST FANS AND LOUVER AS SHOWN. FURNISH AND INSTALL 2 #12, #12
EG-3/4" PVC FROM CIRCUIT AS INDICATED ON PANEL SCHEDULES TO EXHAUST FAN
VIA THERMOSTAT CONTROL IF PROVIDED WITH EXHAUST FAN OR LOUVER. SEE
MECHANICAL DRAWINGS FOR LOCATIONS. TYPICAL FOR ALL (ST).
E2E2
ELECTRICAL LIGHTING PLAN
SCALE: 1/4"= 1'-0"
ALL CIRCUITS SHALL BE RUN WITH INDIVIDUAL #12 NEUTRAL WIRE.
CIRCUITS SHALL NOT SHARE NEUTRAL WIRES.
4.
NIGHT LIGHTS, EMERGENCY LIGHTS, AND EXIT LIGHTS TO BE CONNECTED TO
ROOM CIRCUIT AHEAD OF ANY SWITCHING.
5.
FURNISH AND INSTALL THE FOLLOWING TO UPGRADE THE WASTEWATER PRETREATMENT
FACILITY COMPUTER MONITORING SYSTEM: REPLACE THE EXISTING ALLEN-BRADLEY
PROGRAMMABLE LOGIC CONTROLLER SLC-5/03 WITH A SLC-5/05, UPGRADE THE
EXISTING DOS SOFTWARE TO THE MOST CURRENT MICROSOFT OPERATING SYSTEM,
RSLOGIX 500 SOFTWARE, 1747-SDN DEVICENET SCANNER MODULE, RSNETWORX
SOFTWARE, A NEW 13-SLOT RACK, NEW MODULES, INTEGRATION SOFTWARE TO CREATE
NEW USER INTERFACE SCREENS, AND NEW COMPUTER (2.40 GHZ PROCESSOR) AND
PRINTER. CONTRACTOR SHALL SUPPLY ALL PROGRAMMING SETUP INCLUDING HARDWARE
AND SOFTWARE FOR A MINIMUM OF 7 SCREENS (DUPLICATING CURRENT SCREENS).
CONTRACTOR SHALL PROVIDE TRAINING FOR BASE PERSONNEL TO ADEQUATELY
OPERATE/MAINTAIN COMPUTER SYSTEM.
W-500 ULTRASONIC OCCUPANCY SENSOR-SEE DETAIL #3, THIS DRAWING.7
EXISTING 480/277 VOLT, 3-PHASE, 4-WIRE LIGHTING CONTROL PANEL LCP. FURNISH
AND INSTALL EXISTING 20 AMP, 3-POLE CIRCUIT BREAKER FOR THE AIR COMPRESSOR
AND ONE (1) NEW 20 AMP 1-POLE CIRCUIT BREAKER FOR THE NEW LIGHTING. MATCH
EXISTING BREAKER SIZE AND TYPE.
R E D
B L K
B L U
WHT
BLK
POWER
PACK
CONTROL OUTPUT
COMMON
+24VDC
D
A
L
O
OCCUPANCY SENSOR CEILING
MOUNTED ULTRASONIC DETAIL
SCALE: NONE
E2E2
W-500
OCCUPANCY SENSOR WALL
MOUNTED DUAL TECH. DETAIL
SCALE: NONE
E2E2
LIGHT LEVEL OUTPUT
NORMALLY CLOSED
R e d
B lk
B lu
WHT
BLK
POWER
PACK
COMMON
ISOLATED RELAY
+24VDC
COMMON
NORMALLY OPEN
CONTROL OUTPUT
7-Vio
8-Gry
6-Grn
5-Yel
4-Blu
3-Brn
2-Orn
1-Red
D
A
L
O
DT-200
MOMENTARY SWITCH
#12 NEUTRAL
#12 HOT #12 RED
#12 RED
#12 NEUTRAL
#12 HOT #12 RED
#12 RED
IN ADDITION TO CODED NOTE #6, PROVIDE 2 ADDITIONAL I/O MODULES AND
ADDITIONAL INTEGRATION SOFTWARE. THIS WILL ENABLE THE PERSONNEL IN BUILDING
309 TO VIEW THE DATA FROM THE NEW EFFLUENT FLOW METER, PH MONITOR, AND
OPERATE THREE NEW DEICING VALVES.
PROVIDE A NEW FIBER OPTIC RUN FROM BUILDING 309 TO BUILDING 308. THIS RUN
WILL BE PARALLEL TO THE EXISTING SECURED BASE NETWORK, NOT INTERFACING WITH
IT. ALSO PROVIDE A NEW COMPUTER FOR BUILDING 503 IDENTICAL TO SETUP AS
DESCRIBED IN CODED NOTE #6. THIS WILL ENABLE PERSONNEL FROM BUILDING 503 TO
INTERFACE WITH THE CONTROL SYSTEM IN BUILDING 309.
NORTH
NORTH
FOR NEW RECEPTACLES USE 2 #12, #12 EG-1/2" PVC TO FEED
RECEPTACLES FROM PANEL DP3.
2.
DT-200 DUAL TECHNOLOGY OCCUPANCY SENSOR-SEE DETAIL #4, THIS DRAWING.8
RELOCATED SIDEWALL EXHAUST FAN, SEE MECHANICAL DRAWING M1. EXTEND CONDUIT
AND WIRE TO NEW LOCATION. MATCH EXISTING CONDUIT AND WIRE SIZE AND TYPE.
CONNECT NEW GROUND LOOP TO EXISTING BUILDING GROUND LOOP OR EXISTING
BUILDING COLUMNS.
OFF
277V LOCAL
SWITCH
OFF
277V LOCAL
SWITCH
OSBORN
DESCRIPTION OF ISSUE DATE BY
APPROVED DATE
DRAWN DATE
CHECKED DATE
DRAWING NO SCALE
PRINTED ISSUE NO
MARK DESCRIPTION OF REVISIONMARK DATE BY
ARCHITECTS
CLEVELAND OHIO
ENGINEERS
AKRON OHIO
OEC PROJECT 12910-280
AIR FORCE RESERVE COMMAND HEADQUARTERS
910 AIRLIFT WING
INDUSTRIAL WASTEWATER - BLDG. 309
SHEET NO
TH
OSBORN ARCHITECTS ENGINEERS0 ISSUED FOR BIDS 1/23/08 OEC
PROJECT ZQEL 06-0003
1 ELECTRICAL CODED NOTES 12 & 13 REVISED 03/20/08 EAM
VERBAGE "OPTION 2" REMOVED 06/17/08 EAM2
EXISTING
37.5 kVA
TRANSFORMER
EXISTING
PANEL SMP
EXISTING
PANEL LCP
EXISTING
PANEL DP2EXISTING
PANEL DP1
EXISTING
PANEL SMP
EXISTING
PANEL LCP
EXISTING
PANEL DP2EXISTING
PANEL DP1
X
EM
EMEM
GFCI
+44"
GFCI
GFCI
GFCI
GFCI
GFCI
+44"
GFCI
WP
GFCI
WP
S
TO
PANEL DP3
CKT-7
T
T
EF-1
120/1/60
RH-1
120/1/60
ST
T
T
RH-1
T-STAT
24 VOLT
#4/0 COPPER
GROUND WIRE IN
1" PVC PER N.E.C.
TO EXISTING
DISTRIBUTION
PANEL
DWH-1
120/1/60
ST
ST
L-1
120/1/60
F A C P
FEEDS THREE POST INDICATOR
VALVE CONTROLS LOCATED
UNDERGROUND ON THE DEICING
PAD'S COLLECTION PIPELINE AND
REDUNDANT CONTROLS AND
MONITORING LIGHTS ON BLDG.
308. FOR CONTINUATION, SEE
DWG. E4.
C O N T R O L
P A N E L
(M C P
S3
EXISTING PANEL
MCP-AA
EXISTING
37.5 kVA
TRANSFORMER
EXISTING PANEL
MCP-AA
EFFLUENT
J
(N)
12 #10, #8 EG-1-1/2"PVC
TYPICAL FOR 3
MINI POWER
CENTER AND
PANEL DP3
120/208 VOLT
TO
PANEL DP3
CKT-18
J
T
T
(E)(E)
(E) (E)
(E)
B
B
A
A
A
A
A
A
A
A
A
A
A
A
(E)
J
(E)
A
D
GFCI
+44"
G G G
G
G
G
G
G
G G G
6/6 SINGLE/MULTI
FIBER OPTIC
GFCI
GFCI
GFCI
GFCI
GFCI
+44"
NL
NL
(N)
COUNTERTOP
HOOD
GFCI
+44"
S
2 4/0, #16 SHIELDED CABLE-1" PVC. ROUTE 1
TO EACH DEVICE.
J
BASE BID:
2" PVC
TO
PANEL DP3
CKT-1
ST
EF-2
120/1/60
EF-3
120/1/60
WH-1
277/1/60
TOILET ROOM
WAREHOUSE
SHOWER
EXIST
WAREHOUSE
EXIST
CONTROL ROOM
TOILET ROOM
WAREHOUSE
SHOWER
EXIST
WAREHOUSE
EXIST
CONTROL ROOM
EF-1
120 VOLT
T-STAT
GFCI
GFCI
Paper