RESPONSES TO CONTRACTOR QUESTIONS AS OF 4 AUG 08
SOLICITATION NBR FA6656-08-R-0004
Modify/Upgrade Industrial Wastewater Pretreatment Facility, Bldg 309
1. Could you please tell me if this project bids to General Contractor or to the station directly? Response: Only one award will be made-to the General Contractor; therefore, you need to submit your bid to them. A list of interested primes and subcontractors will be posted to the FBO site after the site visit.
2. Also, is the telecommunication separate from the electrical? I am looking for those particular prints and wondering if they are included with the electrical drawings. Response: Telecommunications requirements are included, in part, with the electrical requirements as well as in Specification Section 27 13 13 COMMUNICATIONS CABLING, and on the electrical drawings.
3. On the back page of form 1442 block 17 says (SEE SCHEDULE OF PRICES). Does that refer to Page 5 of 45, Section B-Supplies or Services and Prices? Is that the only place we need to fill in the bid price? Response: Yes.
4. Page 38 of 45 (2)(b) 1. It says to provide the reproducible Performance Rating Questionnaire (Atch 5.) Is it suppposed to be Attachment 4? Response: Yes, Corrected by Amendment 0001 to read Attachment 4.
5. Also we have to send these Performance Rating Questionnaires to ALL COMPANIES ON REFERENCE LIST. Does REFERENCE LIST refer to ALL people listed on our “no more than 10 relevant contracts” as shown on page 38 of 45, (2)(a)? Response: Yes.