Attachment 3 to FA5205-15-R-0007-0004 Dated 21 Jul 15
KEYED NOTES
DEMOLISH TOP SLAB AND WALLS IN HATCH AREA
EXISTING CONCRETE WALLS TO REMAIN
REMOVE ALL PERIMETER GUARD RAILS
EXISTING CONCRETE BASE SLAB TO REMAIN
EXCEPT FOR AREAS NOTED ON SD140
5 REMOVE EXISTING PEELING PAINT OFF
PERIMETER WALLS. THE PAINT WAS TESTED
FOR LEAD AND FOUND TO BE BELOW LIMIT
6 DEMOLISH EXISTING SLAB, EXISTING
REINFORCING AROUND PERIMETER SHALL REMAIN
A MINIMUM OF 1200mm FOR FUTURE LAPPING
7 DEMOLISH EXISTING WATERWAY IN HATCH AREA
35450
18750 10150
8 EXISTING WALL TO REMAIN, CUT IN NOTCH
ON TOP OF WALL FOR TROUGH.
2 3 3.2 4 4.4 5 6 7.8 8 9 11 12 12.3 13 157 101 148.8
83508350
2325 750
4 11
SD341 SB541
TYP
AFTER ANY EXISTING CONCRETE IS
CUT, ALL EXPOSED REBAR ENDS
SHALL BE PAINTED WITH AN
EQUIVALENT ASTM A775 EPOXY
TOUCH UP PAINT, TYP UNO
ON THE SOUTH WALL WHERE THE EXTERIOR EXISTING WALL IS TO REMAIN, THE CONTRACTOR
SHALL PROVIDE SHORING TO RESIST A TOTAL LATERAL PRESSURE AT THE TOP OF WALL OF
2920kg/m. THE TOP SLAB AND WALLS BEING REMOVED DURING DEMOLITION MUST BE SHORED
TO SUPPORT THE SELF WEIGHT OF THE MATERIAL BEING DEMOLISHED PLUS A MINIMUM
CONSTRUCTION LIVE LOAD OF 2.5 KILOPASCALS. THE CONTRACTOR SHALL LIMIT THE LOADING
ON ANY SHORING AND SHALL NOT STORE DEBRIS IN LARGE QUANTITIES IN ANY AREAS NOT
SPECIFICALLY DESIGNED TO SUPPORT THE LOADING INDICATED ABOVE.
KEY PLAN
SD341
DE
MO
LIT
IO
N
SE
CT
IO
N
5000 2500 50000
1 DEMOLITION SECTION
SD341SD140
SD141
SD142
J J H
M J B
J J H
T/ROOF SLAB
3 4
250 250
475 475
24722126 3052
T/EXISTING SLAB
33.45
38.593
SB541AB340
TYP
AB340
AB340 SB543
SB543AB340
SB541
12 13
350 1772 350
SB542AB340
TYP/SIM
17 17
EXISTING GRADE
A.5 ABCDEF
315031504500510048004800
25500
450 450300 TYP BEAM
0 T
YP
BE
AM
TYP
27304190
875 500 550 650 550 500 875 825 500 500 500 850 1325 500 500 500500
32.20
T/ EXISTING SLAB
T/ ROOF SLAB
33.45
38.593
SB542AB340
SB543AB340
SB542AB3407
SB541AB340
SB541AB340
SB543AB340 4
SB543AB340
TYP AT BEAMS
AB340 SB541
3 5
TYP
SB542AB340
141414
3 3
3 4
250 250
475 475
15011501 1751 1000
3750 3650
SLOPE = 3mm:305mm SLOPE = 3mm:305mm
T/ROOF SLAB
38.593
T/EXISTING SLAB
33.45
SB541AB340
SB541AB340
TYP
SB541AB340
TYP
SB543AB340
TYP
SB541AB340
AB340 SB541
AB340 SB541
AB340 SB5413
SB541AB340
TYP
10 12
KEYED NOTES
CONCRETE STOOPS
PIPE BOLLARD
3 NEW STAINLESS STEEL EXTERIOR GUARDRAIL
4 NEW STAINLESS STEEL STAIR WITH STAINLESS
STEEL GUARDRAIL AND HANDRAIL
5 NEW REMOVABLE STAINLESS STEEL GUARDRAIL
6 S200x27.4 HOIST BEAMS WITH TROLLEY
7 (2) HOUSEKEEPING PADS
CONCRETE ROOF BEAMS WITH (2+4) D29
BOTTOM BARS AND (2) D13 TOP BARS AND
D13 STIRRUPS AT 200mm OC
9 CONCRETE CANOPY OVER MANDOOR
10 CONCRETE WALLS WITH D13 AT 200mm
OC EW EF
11 CONCRETE ROOF SLAB WITH D13 AT
200mm OC EW TOP AND BOTTOM
12 CONCRETE FLOOR SLAB, D13 AT 200mm
OC EW TOP AND BOTTOM
13 EXISTING CONCRETE STRUCTURE
14 NEW OPENINGS, SEE SB342 FOR MORE
INFORMATION
15 EXISTING HOLES TO BE INFILLED WITH D13 AT
200mm OC EW TOP AND BOTTOM, TYP. SEE
8/SB541
16 URETHANE SPRAYED ELASTOMERIC ROOF
SYSTEM IVER 50mm INSULATION ON CONCRETE
ROOF DECK
17 OPENING FOR MECHANICAL EQUIPMENT
AFTER ANY EXISTING CONCRETE IS
CUT, ALL EXPOSED REBAR ENDS
SHALL BE PAINTED WITH AN
EQUIVALENT ASTM A775 EPOXY
TOUCH UP PAINT, TYP UNO
CONCRETE WALL
SEALANT
SEALANT
EXTERIOR INTERIOR
MECHANICAL DUCT
AB340
SECTION SECTION
SECTION
2500 1250 25000 2500 1250 25000
2500 1250 25000
AB140 AB340
AB340
AB340
BU
ILD
IN
G
8 N
EW
A
DD
IT
IO
N
SE
CT
IO
NS
AB141
SB340
AB140
AB141
SB340
AB140
AB141
SB341
J J H
M J B
J J H
MECHANICAL OPENING DETAIL
1000 500 10000
AB340AB340
SLOPESLOPE
NEW SLAB 350mm THICK TO REPLACE EXISTING AFTER
UNDERGROUD PIPING IS INSTALLED
NEW TANK FLOOR SLAB 200mm THICK ON
TOP OF EXISTING FLOOR SLAB
NEW CONCRETE WALLS TO RESIST LATERAL EARTH
PRESSURE
67 30
1300 2100
4375 4000 2000 4200 2000 3000 800 8350
300 300 300 200
60752001500
02600
A
B
C
D
E
F
G
H
J
K
2 3 3.2 4 4.4 5 6 7.8 8 9 11 12 12.3 13 157 101 148.8
4708 3686 3556
KEYED NOTES
300200
14600
24007650 250250
8007650
4 4
18750 NEW 350mm THICK FLOOR SLAB5
6 NEW OPENINGS, SEE SB342 FOR
MORE INFORMATION
TYP
TYP
NEW CONCRETE WALLS
7 NEW CONCRETE TANK WALLS,
SEE 1/SB541 FOR SPLICING, TYP
8 NEW CONCRETE FOOTING AND
TRENCHES AROUND PROPOSED PIPING
SB341SB140 1
SB342SB140
SB342SB140
SB340SB140
SB340SB140
SB342SB140
SB542SB140
SB542SB140
TYP
SB541SB140
TYP
SB541SB140
SB542SB140
TYP
SB541SB140
TYP
SB542SB140
TYP
TYP
TY
P
SB542SB140
TYP
2001475
SB341SB140
EXISTING WALL INFILL,
SEE 5/SB542, TYP
EXISTING WALL INFILL,
SEE 5/SB542, TYP
EXISTING WALL INFILL,
SEE 5/SB542, TYPEXISTING WALL INFILL,
SEE 5/SB542, TYP
EXISTING WALL INFILL,
SEE 5/SB542, TYP
EXISTING WALL INFILL,
SEE 5/SB542, TYP
EXISTING WALL INFILL,
SEE 5/SB542, TYP
TYP
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
A L
I N
T E
G R
A T
E D
N T
E R
P R
I S
E S
P
A C
K E
R L A
R I V
E
G R
E E
N
B
A Y
W
I
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
C T
O
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L
S
A
L E
S U
B M
I T
T E
D
B
Y
F I L
E
N
A M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
B
A S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N D
A T
E A
P P
R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
F
R
C E
C I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
A
D D
E N
D U
M
M
Y
M
J B
A
D D
E N
D U
M
J U
L
M J B
5000 2500 50000
SB140
LO
W
ER
LE
VE
L P
LA
N
LOWER LEVEL PLAN1
SB140 SB140
J J H
M J B
J
CROSS WALLS
TYP
TYP
2000 8775 3000 2000 77754200
2600 1500 1500
DIA=15850
2000 3000
2600 2400
37003700
A
B
C
D
E
F
G
H
J
K
2 3 3.2 4 4.4 5 6 7.8 8 9 11 12 12.3 13 157 101 148.8
TYP
300 300
200200
NEW CONCRETE TANK WALLS,
SEE 1/SB541 FOR SPLICING, TYP
NEW CONCRETE TROUGH WALL
CONCRETE INFILLS
KEYED NOTES
NEW CONCRETE WALLS ON TOP
OF EXISTING WALL5
6 NEW CONCRETE WALL ON TOP OF
EXISTING WALL WITH NOTCH FOR
NEW TROUGH
NEW CONCRETE WALLS
7 NEW CONCRETE WALLS WITH NOTCH
FOR NEW TROUGH
8 NEW CONCRETE SLAB
50 1
5 60
0 I
NF
ILL
0 I
NF
ILL
0 I
NF
ILL
0 I
NF
ILL
1 13
1 13
TY
P
7 7
300 300
9 NEW OPENINGS, SEE SB342 FOR
MORE INFORMATION
TYP OF (8)
TYP OF (4) 9
TYP OF (4) TYP OF (8)
TYP OF (8)
TYP OF (8)
TYP OF (4)
TYP OF (4)
TYP OF (4)
9 9
17600
SB341SB141 1
SB342SB141
SB342SB141
SB340SB141
SB340SB141
SB342SB141
SB341SB141
SB541AB141
TYP
AB141 SB541
SB542
TYP
TYP
SB542AB141
TYP
SB542AB141
TYP
TYP
SB542AB141
SB542AB141
TYP
AB141
250250 250
00 50
250 1000 250
0 15
1 SB141
5000 2500 50000
W
AT
ER
W
AY
P
LA
N
WATERWAY PLAN
SB141 SB141
J J H
M J B
J
100mm METAL STUD WITH 15mm GYP ON BOTH SIDES. ANCHOR
BOTTOM TRACK TO NEW CONCRETE CURB WITH POWDER
ACTUATED FASTENER AT 600mm OC, SEE DETAIL 3/SB170.
PROVIDE SLIP TRACK AT TOP OF WALL. FASTEN SIM TO
BOTTOM TRACK TO SLAB ABOVE.
NEW 125mm x 800mm CONCRETE CURB AROUND TANK REINFORCED WITH (1) D13 CONTINUOUS AT 200mm HORIZONTAL AND D13 VERTICAL BARS AT 200mm OC DRILLED AND EPOXY SET INTO
EXISTING SLAB. NEW CURB WALLS, EXISTING CONCRETE WALLS,
AND SLAB TO BE PAINTED WITH CHEMICAL RESISTIVE FINISH.
C
1 3 42 6 7 9 11
A
B
KEYED NOTES
DOOR AND FRAME SCHEDULE
OP
EN
IN
G
NO
TY
PE
MA
TE
RI
AL
WIDTH HEIG'T
DOOR
TY
PE
MA
TE
RI
AL
FRAME
FI
RE
R
AT
IN
G
(M
IN
S)
HA
RD
W
AR
E
SE
T
REMARKS
OP
EN
IN
G
NO
1021.2xF HM 1900 2375 DF1 HM 90102
DOOR TYPE FRAME TYPE
SEE
SCHED
SE
E
SC
HE
DU
LE
2 FLUSH DOORS
(PAINTED)
2xF
SEE SCHED
SE
E
SC
HE
DU
LE
2"x5 3/4"" DOUBLE RABBET
FRAME (PAINTED)
DF2
3575150
SEE
SCHED
SE
E
SC
HE
DU
LE
FLUSH (PAINTED)
F
1011.F HM 950 2075 DF1 HM 90101
TYP OF (6)
3 PATCH EXISTING FLOOR WHERE EXISTING HOUSEKEEPING
PADS WERE DEMOLISHED. INFILL ALL EXISTING PIPE
PENETRATIONS. COAT ALL PATCH AREAS WITH A HEAVY
DUTY FINISH
4 NEW 50mm CONCRETE PAD REINFORCED WITH 152x152MW13.3/13.3 WWM
D13 CONT
D13 x 152mm AT 200mm OC EPOXIED
INTO EXISTING SLAB
CONC CURB
ROOM FINISH SCHEDULE
RO
OM
N O
F1 W1101
FL
OO
R
BA
SE
RO
OM
N O
WALLS
NORTH EAST SOUTH WEST
CEILING
MATERIAL HEIGHT REMARKS
FLOOR: BASE:
F1. CONCRETE - HEAVY DUTY FINISH B1. NONE
F2. CONCRETE - CHEMICAL RESISTIVE FINISH
F3. CARPET
WALLS: CEILING:
W1. GYPSUM WALL BOARD, BOTH SIDES - PAINTED C1. CONCRETE - PAINTED
B1 W1 - - C1 C1 101
F2102 B1 - - 101
F3201 B1 - - 101
TYP OF (4)
5 530mm x 2050mm x 100mm CONCRETE BASE WITH D10 AT 200mm EACH WAY
6 (4) 304mm x 304mm x 612mm TALL CONCRETE PIERS REINFORCED WITH (8) #16 VERTICAL BARS AND #10 TIES AT 76mm OC. THE
VERTICAL BARS SHALL BE DRILLED AND EPOXY SET INTO THE
EXISTING SLAB A MINIMUM OF 102mm. THE CORNER BARS SHALL
BE HOOKED AT THE TOP OF THE PIER
7 SEE DP171, AND DP570 FOR POLYMER SYSTEM. ALL CONCRETE
SHALL BE REINFORCED WITH D13 AT 200mm OC, EACH WAY, TYP
SB170
5000 2500 50000
5000 2500 50000
1 UPPER LEVEL PLAN
SB170 SB170
2 LOWER LEVEL PLAN
SB170 SB170
BU
ILD
IN
G
P
LA
NS
J J H
M J B
J J H
250 125 2500
3 WALL CURB DETAIL
SB170 SB170
5 4
548 7
1 1 1
2 3 3.2 4 4.4 5 6 7.8 8 9 11 12 12.3 13 157 101 148.8
AB440SB341
7950 8150 2675 5180
TYP
TYP
TYP
TY
P
15240 1360 15240 805
6850 2150 14450 2150 6850 11650
TY
P
TY
P
TY
P
TY
P
SB341 SB542
TYP
SB341 SB543
TYP
SB341 SB542
SB341 SB542
TYP
SB341 SB541
TYP 7
SB341 SB542
TYP
TY
P
SB341 SB542
-2
00 3 3
KEYED NOTES
1100mm HIGH STAINLESS STEEL GUARDRAIL WITH
CENTER RAIL AROUND TANK WALLS
CONCRETE ROOF SLAB, D13 AT 200mm OC EW
TOP AND BOTTOM
5 CONCRETE TANK FLOOR SLAB, D16 AT 200mm OC EW
TOP AND BOTTOM
4 CONCRETE TANK WALLS, D16 AT 180mm OC EF HORIZONTAL RING STEEL, D16 AT 180mm OC EF
VERTICAL
TYP CONCRETE TROUGH WALL, D13 AT 200mm OC
EF VERTICAL AND HORIZONTAL (EACH WAY IN
200mm SLAB IN TROUGH TOP AND BOTTOM)
CONCRETE WALLS, D13 AT 200mm OC EF VERTICAL
AND HORIZONTAL6
REPLACE EXISTING CONCRETE SLAB, D16 AT 200mm
OC NORTH AND SOUTH TOP AND BOTTOM AND D13
AT 200mm OC EAST/WEST TOP AND BOTTOM
EXISTING OPENINGS TO BE FILLED IN8
NEW OPENINGS, SEE SB342 FOR OPENING
ELEVATIONS
KEY PLAN
ABCDEFGHJK
19200 25500
AB340SB341
500600 600
AFTER ANY EXISTING CONCRETE IS
CUT, ALL EXPOSED REBAR ENDS
SHALL BE PAINTED WITH AN
EQUIVALENT ASTM A775 EPOXY
TOUCH UP PAINT, TYP UNO
SB341
SE
CT
IO
NS
5000 2500 50000
5000 2500 50000
2 SECTION
SB341
1 SECTION
SB140 SB341
SB141
SB142
SB140
SB141
SB142
J J H
M J B
J
GRID 1
M
M
P
V C
M
M
P
V C
B F
V
X
M
M
P
V C
100MM
BUTTERFLY
VALVE
100MM
BUTTERFLY
VALVE
D-607 E
TO AERATION
STAGE B
TANK B1
PRESSURE
MONITORING
BOX
PMB-32X30
BV-32X16
PRESSURE
MONITORING
BOX
PMB-32X10
10MM O.D. TUBING
HEADER PRESSURE
15MM O.D. TUBING
STATIC PRESSURE
AE
32X50
D.O.
D-611V
AIR FROM
BLOWERS
GRID 2 GRID 3
B F
V
X
B F
V
X
100MM
BUTTERFLY
VALVE
AERATION STAGE A
LOOP 32000
(TYP. 4 TANKS)
BV-32X26
PRESSURE
MONITORING
BOX
PMB-32X20
BV-32X36
25MM
HOSE
8MM O.D. TUBING
HOLDER PRESSURE
8MM O.D. TUBING
HOLDER PRESSURE
10MM O.D. TUBING
HEADER PRESSURE
15MM O.D. TUBING
STATIC PRESSURE
8MM O.D. TUBING
HOLDER PRESSURE
10MM O.D. TUBING
HEADER PRESSURE
15MM O.D. TUBING
STATIC PRESSURE
M
M
S
L
T
A E
R A
T I O
N
D R
P
G
25MM
HOSE
25MM
HOSE
TANK A1: TNK-32100
TANK A2: TNK-32200
TANK A3: TNK-32300
TANK A4: TNK-32400
'X' = TANK NUMBER (1, 2, 3, 4)
TANK A1
TANK A2
TANK A3
TANK A4
TANK A2
TANK A3
TANK A4
(SIMILAR TO A1)
(SIMILAR TO A1)
(SIMILAR TO A1)
D-607 F
TO AERATION
STAGE B
TANK B2
D-607 G
TO AERATION
STAGE B
TANK B3
D-607 H
TO AERATION
STAGE B
TANK B4
D-605A
FROM ANOXIC
STAGE
TNK-31100
TO TANK A1
D-605B
FROM ANOXIC
STAGE
TNK-31200
TO TANK A2
D-605C
FROM ANOXIC
STAGE
TNK-31300
TO TANK A3
D-605D
FROM ANOXIC
STAGE
TNK-31400
TO TANK A4
D-609 EE
TO FINAL
CLARIFIER
SPLITTER BOX
AE
32X45 pH
AIT
32X45 pH
S G
S G
S G
S G
S G
S G
S G
S G
SG-32095
350MM SCH 10
304L SST
AIR MAIN
200MM SCH 10
304L SST
AIR MAIN
150MM SCH 10
304L SST
AIR MAIN
TO TANK A2
GRID 1
TO TANK A2
GRID 2
TO TANK A2
GRID 3
AIT
32X50
D.O.
AI
pH
AI
D.O.
Y
ALUM
D-619
DUCKBILL CHECK
VALVE
SG-32012
SG-32023
SG-32034
LD-607
MD-607
PORTABLE
SUMP PUMP
M
M
C
L
C
L D
I
M
P
V C
P U
R G
E
M
M
S
T
A E
R A
T I O
N
D R
G
P
V C
P U
R G
E
M
M
S
T
A E
R A
T I O
N
D R
G
P
V C
P U
R G
E
Q K
K A
D d w g
A E
R A
T I O
N
S
T A
G
A
G R
A M
D-606
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L
A
L E
S U
B M
I T
T E
D
B
Y
F I L
E
N
A M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
KEY PLAN
D
E N
D U
M
K
D
E N
D U
M
K
3 3 3
W :\P
R O
JE
C
TS
\O
\9
7\
\D
R
AW
IN
G
S\
D es ig n
In fo rm at io n\
C
AD
\0
M cM ah on
\Q
KK
A-
-1
4- D
-6
.d w g, L ay ou t1 , 7
/2 1/
0:
:2
AM
, p ko la rik
, 1 :1
GRID 1
M
M
P
V C
100MM
BUTTERFLY
VALVE
D-608 CC
TO AERATION
STAGE C
BV-33X16
PRESSURE
MONITORING
BOX
PMB-33X10
10MM O.D. TUBING
HEADER PRESSURE
15MM O.D. TUBING
STATIC PRESSURE
AIT
33X50
D.O.
AE
33X50
D.O.
D-611Z
AIR FROM
BLOWERS
B F
V
X
AERATION STAGE B
LOOP 33000
(TYP. 4 TANKS)
25MM
HOSE
8MM O.D. TUBING
HOLDER PRESSURE
M
M
S
T
A E
R A
T I O
N
D R
G
100MM SCH 10
304L SST
AIRMAIN
TANK B1: TNK-33100
TANK B2: TNK-33200
TANK B3: TNK-33300
TANK B4: TNK-33400
'X' = TANK NUMBER (1, 2, 3, 4)
TANK B1
TANK B2
TANK B3
TANK B4
(SIMILAR TO B1)
(SIMILAR TO B1)
(SIMILAR TO B1)
TANK B2
TANK B3
TANK B4
D-606E
FROM AERATION
STAGE A
TNK-32100
TO TANK B1
D-606F
FROM AERATION
STAGE A
TNK-32200
TO TANK B2
D-606G
FROM AERATION
STAGE A
TNK-32300
TO TANK B3
D-606H
FROM AERATION
STAGE A
TNK-32400
TO TANK B4
D-609 FF
TO FINAL
CLARIFIER
SPLITTER BOX
AE
33X45 pH
S G
S G
S G
S G
SG-34001
AIT
33X45 pH
AI
pH
AI
D.O.
D-620VV
CAUSTIC SODA
D-620UU
CAUSTIC SODA
D-620TT
CAUSTIC SODA
D-620SS
CAUSTIC SODA
15MM SCH 80 PVC
K D-606
L D-606
M D-606
PORTABLE
SUMP PUMP
SG-33095
DUCKBILL CHECK
VALVE
M
M
C
L
C
L D
I
P
V C
15MM SCH 80 PVC
15MM SCH 80 PVC
15MM SCH 80 PVC
D-619Y
ALUM
15MM SCH 80 PVC
Q K
K A
D d w g
A E
R A
T I O
N
S
T A
A
G R
A M
D-607
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L
A
L E
S U
B M
I T
T E
D
B
Y
F I L
E
N
A M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
KEY PLAN
D
E N
D U
M
D
E N
D U
M
K
W :\P
R O
JE
C
TS
\O
\9
7\
\D
R
AW
IN
G
S\
D es ig n
In fo rm at io n\
C
AD
\0
M cM ah on
\Q
KK
A-
-1
4- D
-6
.d w g, L ay ou t1 , 7
/2 1/
0:
:4
AM
, p ko la rik
M
M
P
V C
100MM
BUTTERFLY
VALVE
D-609 GG
TO FINAL
CLARIFIER
SPLITTER BOX
BV-34X16
PRESSURE
MONITORING
BOX
PMB-34X10
10MM O.D. TUBING
HEADER PRESSURE
15MM O.D. TUBING
STATIC PRESSURE
D-611AA
AIR FROM
BLOWERS
B F
V
X
AERATION STAGE C
LOOP 34000
(TYP. 4 TANKS)
25MM
HOSE
8MM O.D. TUBING
HOLDER PRESSURE
M
M
S
T
A E
R A
T I O
N
D R
G
100MM SCH 10
304L SST
AIR MAIN
TANK C1: TNK-34100
TANK C2: TNK-34200
TANK C3: TNK-34300
TANK C4: TNK-34400
'X' = TANK NUMBER (1, 2, 3, 4)
TANK C1
TANK C2
TANK C3
TANK C4
(SIMILAR TO C1)
(SIMILAR TO C1)
(SIMILAR TO C1)
TANK C2
TANK C3
TANK C4
D-607CC
FROM
AERATION
STAGE B
S G
S G
S G
S G
S G
S G
S G
S G
AE
34X50
D.O.
AE
34X45 pH
AIT
34X45 pH
AIT
34X50
D.O.
AI
pH
AI
D.O.
MLSS CHANNEL
TO C4
TO C3
TO C2
P
V C
P U
R G
E
PORTABLE
SUMP PUMP
DUCKBILL CHECK
VALVE
M
M
C
L
C
L D
I
Q K
K A
D d w g
A E
R A
T I O
N
S
T A
A
G R
A M
D-608
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L
A
L E
S U
B M
I T
T E
D
B
Y
F I L
E
N
A M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
KEY PLAN
D
E N
D U
M
D
E N
D U
M
K
W :\P
R O
JE
C
TS
\O
\9
7\
\D
R
AW
IN
G
S\
D es ig n
In fo rm at io n\
C
AD
\0
M cM ah on
\Q
KK
A-
-1
4- D
-6
.d w g, L ay ou t1 , 7
/2 1/
0:
:0
AM
, p ko la rik
AIR INLET
BLOWER 1
B-36110
PI
M
M-36110
36110
VFD
BLOWER 2
B-36120
PI
M
M-36120
36120
VFD
BLOWER 3
B-36130
PI
M
M-36130
36130
VFD
BLOWER 4
B-36140
PI
M
M-36140
BLOWER 5
B-36150
PI
M
M-36150
D-608 AA
TO C1, C2
C3, C4
350MM SCH 10
304L SST
AIR INLET
AIR INLET
AIR INLET
AIR INLET
TO EXHAUST
SILENCER
SILENCER
PI
SILENCER
PI
SILENCER
PI
SILENCER
P.O.C.
AIR TO
EXHAUST
D-607 Z
TO B4
SIM
D-606 V
TO A3 & A4
SIM
D-607 Z
TO B3
SIM
D-607 Z
TO B2
SIM
D-606 V
TO A1 & A2
D-607 Z
TO B1
D-615 J
TO GRAVITY
THICKENER
AIR LIFTS
M
M
C
L
U N
L I N
I
350MM SCH 10
304L SST
FE/FIT
30000
FE/FIT
32012
FE/FIT
34000
FE/FIT
32024
A1
M A
R
F L
T
E
A1
A
O
W
A1
A
O
W
A1
S T
A G
E
C
A
O
W
P.O.C.
BLIND FLANGE
P.O.C.
BLIND FLANGE
HS
36110
O/O/R
HS
36120
O/O/R
HS
36130
O/O/R
Q K
K A
D d w g
A E
R A
T I O
N
B
L O
W E
A
G R
A M
D-611
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L
A
L E
S U
B M
I T
T E
D
B
Y
F I L
E
N
A M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
KEY PLAN
D
E N
D U
M
D
E N
D U
M
K
W :\P
R O
JE
C
TS
\O
\9
7\
\D
R
AW
IN
G
S\
D es ig n
In fo rm at io n\
C
AD
\0
M cM ah on
\Q
KK
A-
-1
4- D
-6
.d w g, L ay ou t1 , 7
/2 1/
0:
:2
AM
, p ko la rik
UP
50 MM BALL VALVE (TYP. 3)
350 MM SST BLIND FLANGE
350 MM SCH. 40 SST
DISCHARGE HEADER
CONNECT TO EXISTING
350 MM FLANGE P.O.C.
200 MM SST KNIFE GATE
VALVE (TYP. 4)
100 MM SCH. 40 SST DRAIN LINE -
CONNECT TO EXISTING 100 MM
DRAIN LINE P.O.C
50 MM CHECK VALVE (TYP. 2)
INSTALL SALVAGED QUICK
DISCONNECT COUPLINGS
(TYP. 2)
CONNECT 50 MM SCH. 40 SST TO
EXISTING 50 MM PVC (TYP. 2) P.O.C
INFLUENT FLOW METER
TRANSDUCER W/ SST
MOUNTING BRACKET
INFLUENT FLOW METER
TRANSDUCER LOCATION
P.O.C.
COARSE SCREEN IN EXISTING
CHANNEL (TYP. 2)
INFLUENT SAMPLER
GROUT FILL STILLING WELL
SST STOP GATE (TYP. 2)
SAWCUT CHANNEL WALLS AND
INVERT AND GROUT IN NEW STOP
GATE FRAMES (TYP. 2)
SST STOP GATE (TYP. 2)
SAWCUT CHANNEL TOP, WALLS,
AND INVERT AND GROUT IN NEW
STOP GATE FRAMES (TYP. 2)
NOTE:
CORE DRILL AND LINK SEAL PIPE
PENETRATIONS THROUGH EXISTING
CONCRETE WALLS AND SLABS UNLESS NOTED
OTHERWISE. SLEEVE PIPE PENETRATIONS
THROUGH NEW CONCRETE WALLS AND SLAB.
INSPECTION PORT IN EXISTING
CONCRETE FLOOR SLAB
ABOVE STILLING WELL - SEE
DETAIL ON SHEET DP548
DP111 DP311
Q K
K A
D
P d w g
P I P
I N
G
P
L A
N
H E
A D
W O
R K
S
B
U I L D
I N
G
B
DP111
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L
A
L E
S U
B M
I T
T E
D
B
Y
F I L
E
N
A M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
LOWER LEVEL PLAN
2500 0 mm 1250 2500
1:50
When inserting this block (in paperspace) into a drawing you need to manually edit the cell to the left of this one (cell
"C2"). The cell needs to reference the following field:
OBJECT ----> VIEWPORT
----> "CUSTOM SCALE" ---->
"USE SCALE NAME"
DP111 DP311
DP111 DP111
DP111 DP312
DP111 DP310
DP111 DP310
B1191 PIPING SCHEDULE
100 MM SCH. 40 SST DRAIN: 1.5 M (5 FT)
350 MM SCH. 40 SST DISCHARGE HEADER: 4.1 M (13 FT)
50 MM SCH. 40 SST GRIT PUMP DISCHARGE: 1.8 M (6 FT)
B1191 EQUIPMENT SCHEDULE
46 21 26.00 MECHANICALLY CLEANED BAR SCREENC
D
E N
D U
M
D
E N
D U
M
K
W :\P
R O
JE
C
TS
\O
\9
7\
\D
R
AW
IN
G
S\
D es ig n
In fo rm at io n\
C
AD
\0
M cM ah on
\Q
KK
A-
-1
4- D
P-
1.
dw g, L ay ou t1 , 7
/2 1/
0:
:4
AM
, p ko la rik
CENTRIFUGE ROOM
CENTRIFUGE ON CONCRETE PIERS
ON TOP OF EXISTING CONCRETE
SUPPORTS. SEE STRUCTURAL
DRAWINGS FOR MODIFICATIONS
TO EXISTING CONCRETE
SAND BLAST AND REPAINT
EXISTING WATER SUPPLY TANK
SAND BLAST AND REPAINT
EXISTING SLUDGE SERVICE TANK
ULTRASONIC LEVEL SENSOR.
MOUNT ON TOP OF EXISTING
TANK, PROVIDE NEW
MOUNTING FLANGE.
SLUDGE DAY TANK MIXER. MOUNT
ON TOP OF EXISTING TANK, USING
EXISTING MIXER BRIDGE
100 MM BLIND FLANGE
P.O.C.
50 MM BALL VALVE
50 MM IN-LINE WATER
BOOSTER PUMP. CONNECT TO
EXISTING 50 MM WATER LINE
NOTE:
WATER SUPPLY AND SLUDGE
FEED PIPING TO EXISTING TANKS
SHALL REMAIN IN PLACE.
125 MM x 150 MM FLEXIBLE CONNECTOR
CENTRIFUGE FEED PUMP ON 100 MM
THICK CONCRETE BASE
150 MM ISO-RING WITH PRESSURE SWITCH
150 MM x 150MM
FLEXIBLE CONNECTOR
150 MM PLUG VALVE
150 MM SCH. 10 304L
SST PUMP SUCTION
150 MM SCH. 10 304L
SST PUMP DISCHARGE
P.O.C.
150 MM SCH. 10 304L
SST PUMP SUCTION
80 MM FLEXIBLE CONNECTOR
EXISTING MONORAIL BEAM ABOVE
PI
TO EXISTING WATER SUPPLY
EXISTING 100 MM DRAIN
100 MM x 150 MM
FLEXIBLE CONNECTOR
EXISTING 100 MM DRAIN
EXISTING 100 MM STEEL DRAIN
EXISTING 100 MM
STEEL DRAIN
150 MM x 80 MM CONCENTRIC REDUCER
50 MM SCH. 40 304L SST
FLUSHING WATER
EXISTING 100 MM STEEL DRAIN
50 MM SCH. 80 PVC
POLYMER SOLUTION
25 MM SCH. 80 PVC
50 MM x 25 MM REDUCER
25 MM SCH. 40 304L SST
WATER SUPPLY TO
DIVERTER SYSTEM
50 MM SCH. 40 304L
SST WATER SUPPLY
EXISTING 50 MM STEEL
POLYMER SYSTEM DRAIN
POLYMER SYSTEM ON
CONCRETE EQUIPMENT PAD
WITH CONTAINMENT CURB
(SEE SHEET DP570 FOR DETAILS)
ACCESS STAIR AND
PLATFORM (SEE SHEET
DP570 FOR DETAILS)
40 MM FLEXIBLE CONNECTOR (TYP. 2)
50 MM SCH. 80 PVC
SOLUTION TRANSFER
25 MM I.D. FLEXIBLE HOSE
P.O.C.
40 MM SCH. 40 304L SST
MAKEUP WATER SUPPLY
40 MM SCH. 40 304L SST
MAKEUP WATER SUPPLY
40 MM SCH. 40 304L SST
DILUTION WATER SUPPLY
50 MM SCH. 40 304L SST
MAKEUP WATER SUPPLY
50 MM SCH. 80 PVC
POLYMER SOLUTION
DISCHARGE
NOTE:
CENTRIFUGE SOUND
ENCLOSURE OMITTED
FROM VIEW FOR CLARITY
50 MM SCH. 40 304L SST
WATER SUPPLY
50 MM WATER SUPPLY
FLOW METER
150 MM ISO-RING
150 MM SLUDGE FLOW METER
50 MM 18-8 SST BALL VALVE
50 MM POLYMER SOLUTION FLOW METER
25 MM 18-8 SST BALL VALVE
50 MM SCH. 80 PVC DRAIN
50 MM PVC BALL VALVES
EXISTING 100 MM SLUDGE FEED
P.O.C.
PI
40 MM 18-8 SST BALL VALVE
40 MM WATER SUPPLY
FLOW METER
50 MM 18-8 SST BALL VALVE
50 MM SST CHECK VALVE
40 MM 18-8 SST BALL VALVE
100 MM PLUG VALVE
IN-LINE PRESSURE SENSOR FOR
SLUDGE SERVICE TANK LEVEL CONTROL
IN-LINE PRESSURE SENSOR
FOR BOOSTER PUMP CONTROL
Q K
K A
D
P d w g
C E
N T
R I F
U G
E
P
L A
N
C O
N T
R O
L
B
U I L D
I N
G
B
DP171
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L
A
L E
S U
B M
I T
T E
D
B
Y
F I L
E
N
A M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
CENTRIFUGE PIPING PLAN
1250 0 mm 625 1250
1:25
When inserting this block (in paperspace) into a drawing you need to manually edit (use
"edit-in-place") the cell to the left of this one (cell "C2"). The cell needs to reference the following field:
OBJECT ----> VIEWPORT
----> "CUSTOM SCALE" ---->
"USE SCALE NAME"
DP171 DP371
DP171 DP371
DP170 DP171
DP171 DP372
B1190 EQUIPMENT SCHEDULE
22 11 23.13 WATER BOOSTER PUMP
43 21 36.30 PROGRESSIVE CAVITY PUMP
40 91 23.33 MAGNETIC FLOW METER
46 33 33.00 POLYMER BLENDING & FEED EQUIPMENT
46 76 33.00 CENTRIFUGE DEWATERING EQUIPMENT
43 41 45.00 FRP TANKS
A
B
C
D
E
F
A
B
C
E
D
B1190 PIPING SCHEDULE
50 MM WATER SUPPLY: 25.2 M (83 FT)
40 MM WATER SUPPLY: 3.4 M (11 FT)
150 MM PUMP SUCTION: 6.7 M (22 FT)
150 MM PUMP DISCHARGE: 6.1 M (20 FT)
250 MM CENTRATE: 2.3 M (8 FT)
150 DIVERTER DRAIN: 1.6 M (5 FT)
50 MM POLYMER SOLUTION: 12.5 M (41 FT)
50 MM DRAIN: 6.4 M (21 FT)
D
E N
D U
M
D
E N
D U
M
K
W :\P
R O
JE
C
TS
\O
\9
7\
\D
R
AW
IN
G
S\
D es ig n
In fo rm at io n\
C
AD
\0
M cM ah on
\Q
KK
A-
-1
4- D
P-
1.
dw g, L ay ou t1 , 7
/2 1/
0:
:0
AM
, p ko la rik
51 203
(4) TREADS AT 279.5 MM
R
I S
E R
S
M
M
ALUMINUM
L80X80X8
GRATING
ALUMINUM 50 MM
DIA. SCH. 40 PIPE
SPACED AT 1200
MM MAXIMUM
15X80X225 ALUMINUM PLATE
W/ (2) 15 MM DIA. SST
ANCHORS, POWERS WEDGE
BOLT, EMBED 50 MM
300 MM ALUMINUM
CHANNEL
15X100X250 PLATE W/ (2)
15 MM DIA. SST BOLTS
ALUMINUM 80 MM DIA.
SCH. 40 PIPE
15X100X250 ALUMINUM PLATE
W/ (2) 15 MM DIA. SST
ANCHORS, POWERS WEDGE
BOLT, EMBED 100 MM
Q K
K A
D
P d w g
P O
L Y
M E
R
S
Y S
T E
M
D
E T
A I L S
C O
N T
R O
L
B
U I L D
I N
G
B
DP570
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L
A
L E
S U
B M
I T
T E
D
B
Y
F I L
E
N
A M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
1000 0 mm 500 1000
1:20
When inserting this block (in paperspace) into a drawing you need to manually edit (use
"edit-in-place") the cell to the left of this one (cell "C2"). The cell needs to reference the following field:
OBJECT ----> VIEWPORT
----> "CUSTOM SCALE" ---->
"USE SCALE NAME"
NOT USED NOT USED DETAIL DETAIL DETAIL
DP170 DP570
DP170 DP570
DP170 DP570
DP170 DP570
DP170 DP570
D
E N
D U
M
D
E N
D U
M
K
3 3
W :\P
R O
JE
C
TS
\O
\9
7\
\D
R
AW
IN
G
S\
D es ig n
In fo rm at io n\
C
AD
\0
M cM ah on
\Q
KK
A-
-1
4- D
P-
0.
dw g, L ay ou t1 , 7
/2 1/
0:
:2
AM
, p ko la rik
LS-1
NEW PULLBOX (250x150), AND
CONDUIT (ABOVE AND BELOW)
NEW JUNCTION BOXES (300x200), AND CONDUIT (ABOVE AND BELOW)
NEW PULLBOX (250x150)
PULLBOX (150x100)
PULLBOX (150x100)
NEW INFLUENT PUMPS BELOW
(TYP. 4, SEE SHEET EP110)
COARSE SCREEN NO. 2
SCRN-11200
COARSE SCREEN NO. 1
SCRN-11100
LE-13201
FIT-13201
KEYED NOTES:
REFURBISHED MOUNTING PEDESTAL.
PROVIDE RECEPTACLE IN NEMA 7 ENCLOSURE FOR
SAMPLER. MATCH SAMPLER VOLTAGE AND PLUG
CONFIGURATION.
WALL-MOUNT, AT 600MM ABOVE FLOOR.
SIMILAR TO DETAIL 2/EP111.
CONTRACTOR SHALL PROVIDE MATERIALS AND
METHODS TO ENSURE COMPLIANCE WITH NFPA 70
REQUIREMENTS FOR INDICATED AREA
CLASSIFICATION.
GRIT PUMP, BELOW
NFPA 70 CLASS I, DIVISION 2
CLASSIFIED HAZARDOUS LOCATION
LEVEL SENSOR PE/LT 14200
SAMPLER
SAM-13100
LDIT-11100
LCS-11100
LDIT-11200
LCS-11200
M-11100
M-11200
LEA-11100
LEA-11200
LCS-11100
LDIT-11100
LDIT-11200
LCS-11200
GE-15201, H₂S SENSOR
LEB-11200
GRIT PUMP, BELOW
LEB-11100
ELECTRICAL ROOM ABOVE
(SEE SHEET EP112)
GENERAL NOTES:
1. CONDUIT THIS AREA: USE RIGID ALUMINUM
CONDUIT.
2. PROVIDE CONDUIT SEAL FITTINGS AT POINTS OF
PENETRATION INTO DIVISION 2 SPACE.
Q K
K A
E
P d w g
L O
W E
R
L
E V
W
A
N
H E
A D
W O
R K
S
B
U I L
D I N
G
B
EP111
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
LOWER LEVEL POWER PLAN
2500 0 mm 1250 2500
1:50
When inserting this block (in paperspace) into a drawing you need to manually edit (use
"edit-in-place") the cell to the left of this one (cell "C2"). The cell needs to reference the following field:
OBJECT ----> VIEWPORT
----> "CUSTOM SCALE" ---->
"USE SCALE NAME"
(N) CABLE TRAY ABOVE
2" PVC RISER CONDUIT
NEW PULL BOX
- 250MM x 150MM
- NEMA 4X FIBERGLASS
TRANSITION BOX (NOTE 1)
PVC BRANCH CONDUITS
EXISTING CONCRETE BASE
1. PROVIDE TRANSITION PULL BOX AS A
MEANS TO FACILITATE TERMINATION OF
NEW CONDUITS FROM ABOVE, AND ALSO
AS A MEANS TO COVER EXISTING
CONDUIT OPENINGS IN BASE BELOW.
EP111 EP111
PULL BOX
EP111 EP111
EP111 EP111
D
E N
D U
M
D
E N
D U
M
M
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4-
EP
-1
.dw g, La yo ut1 , 7
/21 /20
1:
:34
P M, JR
eib old
SCADA PC 1
SCADA PC 2
SCADA PC 3
HH-6
M92 - VENTILATOR FAN
RELOCATED LS-12
RELOCATED SODIUM HYPOCHLORITE FEED PUMP NO.2
(FORMERLY M63)
RELOCATED SODIUM HYPOCHLORITE FEED PUMP NO.1
(FORMERLY M62)
NEW CHEMICAL FEED
LOCAL PANEL LP-35
CABLE TRAY (E)
M50 - VENTILATOR (E)
PANEL LP-13 (E)
M103 (E)
NEW MCC 1190A
CABLE TRAY
CONDUIT
STUB-UP (TYP.)
AERATION BLOWERS (E)
(FORMERLY M79, M80, M81, M82, M83)
PANEL L-1
PANEL HP-1
P.BOX
M-65006 (N)
CABLE
TRAY
NEW CENTRIFUGE LOCAL
CONTROL PANEL LP-53
M75 - SHUTTER (E)
M72 - COMPRESSOR (E)
M73 - BELT CONVEYOR NO.1 (E)
M91 - VENTILATOR (E)
M74 - BELT CONVEYOR NO.2 (E)
HOT WATER
CIRCULATION PUMPS
M M M M M
M
M
M
M
M
M
M
M
M
M
M M M M M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
MM
M
M
M
M
M
NEW CONTROL LOCAL
PANEL LP-34
208V TRANSFORMER -
TX-1190D
208V DISTRIBUTION PANEL -
PP-1190D
SPLICE BOX (N)
KEYED NOTES:
MOUNT TOP OF PANEL LP-53A AT 1372MM A.F.F.
DISCONNECT EXISTING ALUM FEED PUMPS TO
FACILITATE INSTALLATION OF NEW CHEMICAL
STORAGE TANK. RE-WIRE COMPLETE TO NEW
MCC AFTER TANK INSTALLATION.
STRUT-MOUNT TO CONTAINMENT WALLS, AT
EYE-LEVEL.
STRUT-MOUNT ABOVE FEED PUMPS. ROUTE
SENSOR CABLE VIA TRAY ABOVE.
NEW CABLE TRAY TO BE RUN AT SAME
ELEVATION AS EXISTING. NEW CABLE TRAY
INSTALLED IN AREA OF PIPES AFTER
DEMOLITION OF PIPES. NEW CABLES CAN BE
TIED UP UNTIL NEW CABLE TRAY IS INSTALLED.
NEW CEILING-MOUNTED TERMINAL BOXES FOR
TERMINATION OF EXISTING 208V, 150KVA
TRANSFORMER, SECONDARY LEADS.
SCADA SYSTEM: REFER TO SHEET EF600-A AND
SPECIFICATIONS, SECTION 40 95 00. PROVIDE
ANALOG TELEPHONE WIRING FROM TELEPHONE
SERVICE ENTRANCE TO BOTH PC1 & PC2 TO BE
USED FOR SOFTWARE ALARM DIALER.
AUXILIARY WIRING PANEL
CENTRIFUGE MAIN DRIVE
M-65210
CENTRIFUGE SCROLL DRIVE
M-65220
LOCAL CENTRIFUGE
OPERATOR PANEL
LP-53A
NEW 208V MCC 1190B
DIGESTER BLOWER NO. 1
M-64110
DIGESTER BLOWER NO. 2
M-64120
NO.1NO.2NO.3NO.4NO.5
M-36110M-36120M-36130M-36140M-36150
SLUDGE FEED PUMP P-65110
& DS-65110
EXISTING NETWORK
EQUIPMENT
DS-65005
LE-71200
LIT-71200
EXISTING ALUM FEED PUMPS 2
LIT-71100 3
LE-71100
POLYMER SYSTEM
CONTROL PANEL
SOLUTION FEED PUMP
P-62651
MIXER, MX-65630
POLYMER DISPERSION
UNIT, M-65625
WATER BOOSTER PUMP
P-65701 (N)
LIT-65700
LE-65700
LE-65000
LIT-65000
NOTES:
1. NEW AND EXISTING CABLE TRAY TO HAVE BARE
COPPER WIRE 120MM² RUN ON SIDE RAIL. WIRE
ELECTRICALLY BONDED TO SIDE RAIL EVERY 20
METERS.
2. ALL GROUND WIRES RUN WITH SINGLE
CONDUCTOR (PHASE WIRES) IN THE CABLE
TRAY TO BE TERMINATED TO CABLE TRAY
GROUNDING WIRE AT ENTRANCE TO CABLE
TRAY.
3. CABLE TRAY ELEVATIONS AND LOCATIONS ARE
APPROXIMATE. CONTRACTOR TO REVISE AS
REQUIRED, INCLUDING ADDITIONAL FITTINGS.
MINIMUM RUNG SPACING IS 225MM.
NEW SWITCHGEAR
SWGR-1190A
FRONT
TOP OF STRUT
ELEV.= 150MM BELOW
MAIN TRAY
TOP OF STRUT
ELEV.= BELOW UPPER
LEVEL HORIZ. BEAM
CABLE TRAY PARTS
600MM300MM90HT600MMR
450MM45HT300MMR
600MM90HB600MMR
300MM90HB300MMR
600MM45HT600MMR
60MM45HB600MMR
300MM90HB600MMR
NEW CABLE TRAY
NEW GENERATOR
LEGEND
R - RADIUS
HT - HORIZONTAL TEE
HB - HORIZONTAL BEND
TRAILERABLE GENERATOR
TERMINAL BOX (N)
Q K
K A
E
P d w g
P O
W E
R
P
L A
N S
C O
N T
R O
L
B
U I L
D I N
G
EP170
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
GRADE LEVEL POWER PLAN
UPPER LEVEL POWER PLAN
5000 0 mm 2500 5000
1:100
When inserting this block (in paperspace) into a drawing you need to manually edit (use
"edit-in-place") the cell to the left of this one (cell "C2"). The cell needs to reference the following field:
OBJECT ----> VIEWPORT
----> "CUSTOM SCALE" ---->
"USE SCALE NAME"
EP170 EP170
EP170 EP170
D
E N
D U
M
M
D
E N
D U
M
M
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4-
EP
-1
.dw g, La yo ut1 , 7
/21 /20
1:
:27
P M, JR
eib old
NOTES:
1. UNLESS OTHERWISE NOTED ALL EQUIPMENT IS
EXISTING.
2. UNLESS OTHERWISE NOTED ALL EQUIPMENT IN
BUILDING 1190 IS ON FIRST FLOOR.
NEW POWER PANEL PP-83108
420V, 600A, 3P3W
600AF
___AT
420V, 600A, 3P3W
NEW MCC 1191A
1200AF
600AS
___AT
1200AF
1200AS
____AT
NEW 1200A SWITCHGEAR
SWGR-1190A
2ND FLOOR
NEW 420V MCC 1190A
420V, 600A, 3P3W
TRAILERABLE
GENERATOR
TERMINAL BOX
LSIG LSIG
1200AF
600AS
___AT
LSIG
1200AF
600AS
___AT
LSIG
420V, 1200A, 3P3W
CONSTRUCTION NOTES:
1. DURING TEAR OUT OF THE EXISTING
GENERATOR, FEEDING NEW AND REUSED
PLANT LOADS AND INSTALLATION/STARTUP OF
THE NEW GENERATOR, A PORTABLE
GENERATOR SHALL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR. SEE DRAWING E-601
FOR DETAILS.
NOT USED
TWO ELECTRICALLY OPERATED MAIN
BREARERS ARE CONTROLLED AS AN
AUTOMATIC TRANSFER SWITCH. CONTROL
LOCATED IN SWITCHGEAR.
KEY SWITCH LOGIC: BOTH KEYS ARE REQURED
TO CLOSE TRAILERABLE GENERATOR FEEDER
BREAKER IN CONNECTED POSITION.
1200AF
1200AS
____AT
ATS
LSIG
CONSTRUCTION NOTES:
INTERCHANGEABLE WITH EITHER MAIN
BREAKER.
ONE NEW FEEDER TO NEW MCC 1191A TO BE
INSTALLED DURING CONSTRUCTION. AFTER
TRANSFER OF ALL LOAD TO SWGR-1190A, A
SECOND REPURPOSED MOSTLY EXISTING
CABLE IS TO PARALLED THE NEW FEEDER AS
SHOWN.
1200AF
1200AS
____AT
1200AF
1200AS
____AT
1200AF
1200AS
____AT
1200AF
1200AS
____AT
NEW TX-1190 750KVA
6.6KV
420V
PAD-MOUNT
Z=5.75%
NEW
CVQ150MM²
EXISTING DUCT
NEW
CVQ150MM²
EXISTING DUCT
NEW
CVQ150MM²
NEW
DUCT/CONDUIT
TWO PIPES
NEW DUCT
TWO PIPES
NEW
2-CVQ150MM²
2-EXISTING DUCT
6KVEPRT38MM²
K2
TERMINAL BOX
W/POWER TERMINALS
SOURCE 1, 6.6KV
SWITCH STATION
(POLE F20-1)
3PLDS 200A
T40A
TX 300KVA
6.6KV
420V
3P600AF
3P600AT
3PLDS 200A
T30A
3P400AF
3P400AT
TX 150KVA
6.6KV
208/120V
3P600AF
3P500AT
6.6KV
G
LP-14 (BLOWER
PANEL)
6.6KV
425KVA
CONTROL BUILDING 1190
TX 200KVA
6.6KV
208Y/120V
TREATMENT WORKS 83108,
MICROSCREEN BLDG.
6.6KV
HH-8
HH-7
HH-10
HH-15
HH-14
HEADWORKS 1191
3PLDS 200A
3PLDS 200A 3PLDS 200A
7.2KVMgDT
3P200A
HH-186KVCETMM38²
6KVCET38MM²
3P800AF
3P700AT
3P250AF
3P250AT
2-CVQ 200MM²
3P400AF
3P300AT
PANEL PP-1
(NO 2)
2ND FLOOR
PANEL PP-1
(NO 1)
2ND FLOOR
CVQ150MM²
HH-11
G
250KW
208/120V
3P4W
600V
3P900A
CLOSED
3P225AF
3P225AT
420V, 600A
MCC LP16
HH-17
HH-11A
3P1000AF
3P900AT
208V, 1000A
LP16A
3P225AF
3P225AT
3P1000AF
3P900AT
NEW UNDERGROUND
4-CVQ300MM²
3-4/C200MM²
3-4/C200MM²
6KVCET38MM²-3C
6KV38MM²-3C
2-CVT150MM²
CVQ150MM²
TAPED IN BOX
CONDUIT FOR
CVQ150MM²
CONDUIT
FOR
CVQ150MM²
HH-17
SPLICED
CONDUIT FOR
CVQ150MM²
HH-1
HH-3
CVQ150MM²
OPEN
NEW
CONDUIT
FOR
CVQ150MM²
NEW SPLICE
PERMANENT
SPLICE (NEW)
CVQ150MM²
NEW
2-CVQ150MM²
HH-6
NEW
CVQ150MM²
EXISTING DUCT
CVQ150MM²
TRAY & BURIED
CONDUIT TO HH-7
NEW
SPLICE
BOX
NEW
CVQ150MM²
CABLE TRAY
SEPARATELY
DERIVED GND AT
1ST DISCONNECT
TERMINAL BOX
W/POWER
TERMINALS
3-CVQ200MM²
REROUTED
CVQ150MM²
NEW
4-CVQ300MM²
CABLE TRAY
NEW
3-CVQ185MM²-4/C
CABLE TRAY
NEW
3-CVQ185MM²-4/C
CABLE TRAY
NEW
2-CVQ150MM²
CABLE TRAY
NEW UNDERGROUND
4-CVQ300MM²
NEW UNDERGROUND
6KVEPRT38MM²
SPARE
ATS
G
NEW GENERATOR
360KW, 450KVA, .8PF
420V, 3P4W
SEPARATELY
DERIVED GND AT
SOURCE TERMINAL
K1 K2
ATS
K1
1200AF
1200AS
___AT
LSIG
K1
1200AF
PREPARED
SPACE
K2
EO
1200AF
600AS
___AT
LSIG
SPARE
CONNECTION FOR LOAD BANK
DURING GENERATOR/SWGR-1190A
TESTING
1200AF
1200AT
LSIG
VCB
7.2KV, 600A
12.5KA
50/51
Q K
K A
E d w g
O N
E L
I N
E
D
I A
G R
R A
N S
I T
I O
N
E-602
ONE-LINE DIAGRAM - OVERVIEW W/ TRANSITION
E-602 E-602
D
E N
D U
M
M
D
E N
D U
M
M
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4- E-
2.d wg , L ay ou t1, 7/
/20
1:
:21
P M, JR
eib old
420V, 3-PHASE, 600A
150A
3P
420V
FROM
SWGR-1190A
600A
LUGS
TX-1190D 75KVA
420V
208Y/120V
TO 208V
POWER PANEL
PP-1190D
(SHEET E-611)
A
225A
3P
TO CENTRIFUGE
CONTROL PANEL
LP-53
(SHEET E-612)
B
3%
ILR
VFD
dv/dt
M-36110
AERATION
BLOWER 1
(FORMERLY M83)
3%
ILR
VFD
dv/dt
M-36120
AERATION
BLOWER 2
(FORMERLY M82)
3%
ILR
VFD
dv/dt
M-36230
AERATION
BLOWER 3
(FORMERLY M81)
3%
ILR
VFD
M-64110
DIGESTER
BLOWER 1
3%
ILR
VFD
M-64120
DIGESTER
BLOWER 2
3%
ILR
VFD
M-65110
SLUDGE FEED
PUMP
MCC 1190A
MAIN LUGS
SLUDGE FEED
PUMP
VFD
635 635 635
SLUDGE DAY
TANK MIXER
VFD
FEEDER TO
TX-1190D
AERATION
BLOWER 1
VFD
AERATION
BLOWER 2
VFD
AERATION
BLOWER 3
VFD
SF-2
55KW
420V
55KW
420V
55KW
420V
50HP
420V
50HP
420V
11KW
420V
3F0A 4F0000A 3V75 3V75 3V75 3V50 3V50 3V15
150A
MCP
150A
MCP
150A
MCP
100A
MCP
100A
MCP
20A
MCP
3%
ILR
VFD
M-65005
SLUDGE DAY
TANK MIXER
1.5KW
420V
3V2
7A
MCP
3%
ILR
VFD
P-65701
WATER BOOSTER
PUMP
3.7KW
420V
3V5
15A
MCP
SF-2
SUPPLY FAN
2HP
420V
3M2
__A
MCP
NEMA
SIZE 1
4F0000A
140A
55KW, H.D.
140A
55KW, H.D.
140A
55KW, H.D.
85A
37KW, H.D.
85A
37KW, H.D.
5A 15.4A 8.7A
KEYED NOTES:
H.D. INDICATES HEAVY DUTY VFD RATING FOR
POSITIVE DISPLACEMENT LOAD.
1 1 1 1 1
DIGESTER
BLOWER 1
VFD
DIGESTER
BLOWER 2
VFD
FEEDER TO
LP-53
WATER
BOOSTER
PUMP
VFD
SEE WIRE/CONDUIT TABLES,
SHEET E-646 (TYP.)
Q K
K A
E d w g
O N
E L
I N
E
D
I A
G R
A
E-610
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
MCC 1190A
FRONT ELEVATION
E-610 E-610
INCOMING
MCC 1190A
ONE-LINE DIAGRAM
E-610 E-610
E-610 E-512
TYPICAL
E-610 E-703
E-610 E-703
E-610 E-703
E-610 E-705
E-610 E-705
E-610 E-707
E-610 E-703
E-610 E-702
D
E N
D U
M
D
E N
D U
M
M
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4- E-
0.d wg , L ay ou t1, 7/
/20
1:
:47
P M, JR
eib old
208/120V, 3-PHASE, 4W, 300A
75A
3P
208V
FROM
208V XFMR
(SHEET E-610)
A
50A
3P
TO NEW MCC 1190B
(SHEET E-613)
50A
3P
30A
3P
150A
3P
100A
3P
EXISTING
PANEL 1190-L1
2ND FLOOR
100A
3P
NEW
PANEL 1190-L2
ELECTRICAL ROOM
208V POWER PANEL PP-1190D
EXISTING LP-13
GENERATOR RM.
VENTILATOR
CONTROL PANEL
M90 M103
EXISTING
C
TO NEW MCC 1190C
(SHEET E-614)
D
EXISTING
GENERATOR
AUTO START
PANEL
(GENERATOR RM.)
EXISTING HP-1
HOT WATER
CIRC. PUMP
CONTROL PANEL
3F4A 3F10A 3F0A3F8A 3F8A 4F1A 4F1A
300A
3P
50A
3P
3F8A
15A
3P
3F12A
EXISTING
M72
COMPRESSOR
EXISTING
M75
SHUTTER
30A
3P
3F10A
DRY POLYMER
SYSTEM
40A
2P
3F8A
ACCU-2
OUTDOOR
AIR-COOLED
CONDENSING UNIT
30A
5.5KW 0.75KW
M-65625
DISPENSER
MOTOR
1HP
208V
M-65630
MIXER
MOTOR
2HP
208V
3M23M1
POLYMER
SYSTEM
PANEL
LP-54
SEE PANEL SCHEDULES,
SHEET E-612
SEE
WIRE/CONDUIT
TABLES, SHEET
E-646 (TYP.)
40A
2P
3F8A
GENERATOR
PANELBOARD
Q K
K A
E d w g
O N
E L
I N
E
D
I A
G R
P
D
E-611
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
208V POWER PANEL PP-1190D
ONE-LINE DIAGRAM
E-611 E-611
D
E N
D U
M
M
A
D D
E N
D U
M
M
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4- E-
1.d wg , L ay ou t1, 7/
/20
1:
:58
P M, JR
eib old
420V
FROM
MCC 1190A
(SHEET E-610)
B
225A
3P
(3)
__A
VFD
SCROLL
MOTOR
(3)
__A
VFD
DRIVE
MOTOR
GREASE
PUMP
___A
3P
___A
2P
PLC
24VDC
P.S.
C.P.T.
CENTRIFUGE CONTROL PANEL LP-53
(VENDOR -FURNISHED)
420V, 3-PHASE, 3W
0.25HP 75HP 20HP
3M1 3XH75 3XH20
SEE WIRE/CONDUIT TABLES,
SHEET E-646 (TYP.)
Q K
K A
E d w g
O N
E L
I N
E
D
I A
G R
P
A
H
E U
D L
E-612
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
CENTRIFUGE CONTROL PANEL LP-53
ONE-LINE DIAGRAM
E-612 E-612
D
E N
D U
M
D
E N
D U
M
M
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4- E-
2.d wg , L ay ou t1, 7/
/20
1:
:09
P M, JR
eib old
NEW MCC 1191A
50A
MCP
3%
ILR
VFD
30A dv/dt
J
P-14110
INFLUENT PUMP
NO. 1
OUTPUT
FILTER
50A
MCP
3%
ILR
VFD
30A dv/dt
J
P-14120
INFLUENT PUMP
NO. 2
OUTPUT
FILTER
50A
MCP
3%
ILR
VFD
30A dv/dt
J
P-14130
INFLUENT PUMP
NO. 3
OUTPUT
FILTER
30A
MCP
3%
ILR
VFD
30A dv/dt
J
P-14140
INFLUENT PUMP
NO. 4
OUTPUT
FILTER
7A
MCP
3%
ILR
VFD
4A dv/dt
J
P-12100
GRIT PUMP 1
OUTPUT
FILTER
7A
MCP
3%
ILR
VFD
4A dv/dt
J
P-12100
GRIT PUMP 1
OUTPUT
FILTER
PUMP
CABLE
PUMP
CABLE
PUMP
CABLE
PUMP
CABLE
PUMP
CABLE
PUMP
CABLE
300A
3P
420V
FROM
SWGR-1190A
15A
3P
VFD
M-11100
COARSE SCREEN
NO.1
1HP
420V
SCREEN
CONTROL
PANEL
LP-50A
15A
3P
VFD
M-11200
COARSE SCREEN
NO.2
1HP
420V
SCREEN
CONTROL
PANEL
LP-50B
1.5KW 1.5KW
3F12A 3F12A 3V5 3V5
150A
3P
3F0A
TX-1191D 75KVA
420V
208Y/120V
15KW 15KW 15KW 15KW
3V20 3V20 3V20 3V20
420V, 3-PHASE, 3W
A
TO 208V
POWER PANEL
PP-1191D
(SHEET E-621)
4F0000A
3XH1 3XH1
KEYED NOTES:
SCREEN CONTROL PANELS FURNISHED WITH
SCREEN EQUIPMENT, INSTALLED AND WIRED BY
CONTRACTOR.
1 1
LIMITS OF CLASS I, DIVISION 2
CLASSIFIED HAZARDOUS LOCATION
LIMITS OF CLASS I, DIVISION 1
CLASSIFIED HAZARDOUS LOCATION
LISTED CONDUIT SEAL
FITTING (TYP.)
SPACE
SPACE
INFLUENT
PUMP NO. 4
VFD
dv/dt
SPACE
SPACE
INFLUENT
PUMP NO. 3
VFD
dv/dt
SPACE
SPACE
INFLUENT
PUMP NO. 2
VFD
dv/dt
150A
BREAKER
SPACE
I.L.R.
INFLUENT
PUMP NO. 1
VFD
dv/dt
I.L.R. I.L.R. I.L.R.
15A
BREAKER
15A
BREAKER
I.L.R.
dv/dtdv/dt
I.L.R.
300A
MAIN
BREAKER
GRIT PUMP
NO. 1
VFD
GRIT PUMP
NO. 2
VFD
SEE MOTOR FEEDER SCHEDULE
SHEET E-646 (TYP.)
Q K
K A
E d w g
N E
W
M
E
L
I N
E
D
I A
G R
A M
E-620
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
E-620 E-703
E-620 E-703
E-620 E-703
E-620 E-703
E-620 E-703
E-620 E-703
MCC 1191A
ONE-LINE DIAGRAM
E-620 E-620
E-620 E-512
TYPICAL
MCC 1191A
FRONT ELEVATION
E-620 E-620
D
E N
D U
M
M
D
E N
D U
M
M
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4- E-
0.d wg , L ay ou t1, 7/
/20
1:
:20
P M, JR
eib old
420V, 3-PHASE, 600A
300A
3P
420V
FROM
SWGR-1190A
TO
MCC 83108A
(SHEET E-631)
A
300A
3P
B
POWER PANEL PP-83108
3F350K 3F350K
600A
3P
TO
MCC 83108B
(SHEET E-632)
300A
3P
C
3F350K
TO
MICROSCREEN
POWER/VFD PANEL
LP-51A
(SHEET E-633)
PANEL 83108-L1
60A
3P
3F6A
125A
3P
TX-83108-L1 30KVA
420V
208Y/120V
50A
3P
3F8A
25KW
EUH-1
ELECTRIC UNIT
HEATER
50A
3P
3F8A
25KW
EUH-2
ELECTRIC UNIT
HEATER
SEE SHEET E-646 FOR WIRE
TAG DESCRIPTIONS (TYP.)
4F1A
Q K
K A
E d w g
P O
W E
R
P
A N
E
L
I N
E
D
I A
G R
A M
E-630
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
POWER PANEL PP-83108
ONE-LINE DIAGRAM
E-630 E-630
D
E N
D U
M
D
E N
D U
M
M
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4- E-
0.d wg , L ay ou t1, 7/
/20
1:
:31
P M, JR
eib old
NEMA
SIZE 1
M-31251
ANOXIC TANK
AN2
MIXER 1
NEMA
SIZE 1
M-31252
ANOXIC TANK
AN2
MIXER 2
NEMA
SIZE 1
M-31451
ANOXIC TANK
AN4
MIXER 1
NEMA
SIZE 1
M-31452
ANOXIC TANK
AN4
MIXER 2
30A
3P
MCP
15A
3P
MCP
15A
3P
MCP
3%
ILR
VFD
15KW
M-45120
RECIRCULATION
PUMP NO. 2
NEMA
SIZE 1
M-41200
FINAL CLARIFIER
NO. 2
M-42210
SCUM PUMP
NO. 2
3%
ILR
VFD
11.5A
M-43120
RAS PUMP
NO. 1B
3%
ILR
VFD
11.5A
M-43220
RAS PUMP
NO. 2B
NEMA
SIZE 1
M-61200
SLUDGE
THICKENER 2
3%
ILR
VFD
11.5A
M-63102
SLUDGE TRANSFER
PUMP NO. 2
15A
3P
MCP
NEMA
SIZE 1
M77
SPRAY PUMP
NO. 2
420V, 3-PHASE, 3W, 600A
NEW MCC 83108B
LOCATION: TREATMENT WORKS 83108
B
FROM
NEW POWER PANEL
PP-83108
(SHEET E-630)
NEMA
SIZE 1
SPARE
1/2-SIZE
FVNR
1.5HP
420V
3M2
3-PH
50Hz
1.5HP
420V
1.5HP
420V
1.5HP
420V
15KW
420V
1/2HP
420V
1/2HP
420V
0.75KW
420V
5.5KW
420V
5.5KW
420V
5.5KW
420V
5.5HP
420V
3-PH
50Hz
NEMA
SIZE 1
dv/dt dv/dt dv/dt dv/dt
SPRAY PUMP
NO. 2
SPACE
SPACE
SPACE
FINAL
CLARIFIER
NO.2
SLUDGE
THICKENER
I.L.R.
SPARE
SPACE
300A
MAIN LUGS
SCUM PUMP
NO. 2
I.L.R.
RECIRC. PUMP
NO. 2
VFD
dv/dt
AN2
MIXER 1
AN2
MIXER 2
I.L.R.
RAS PUMP
NO. 1B
VFD
dv/dt
AN4
MIXER 1
AN4
MIXER 2
I.L.R.
RAS PUMP
NO. 2B
VFD
dv/dt
SLUDGE
TRANSFER
PUMP NO.2
VFD
dv/dt
3-PH
50Hz
3-PH
50Hz
3-PH
50Hz
3-PH
50Hz
3-PH
50Hz
3-PH
50Hz
3-PH
50Hz
3-PH
50Hz
3-PH
50Hz
3-PH
50Hz
3M2 3M2 3V25 3M1 3M1 3M1 3V10 3V10 3M1 3V10 3M10
SEE FEEDER & CIRCUIT SCHEDULES,
SHEET E-646 (TYP.)
Q K
K A
E d w g
M C
C
B
O
N E
L
I N
E
D
I A
G R
A M
E-632
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
MCC 83108B
ONE-LINE DIAGRAM
E-632 E-632
MCC 83108B
FRONT ELEVATION
E-632 E-632
E-632 E-702
E-632 E-702
E-632 E-702
E-632 E-702
E-632 E-701
E-632 E-701
E-632 E-702
E-632 E-704
E-632 E-704
E-632 E-701
E-632 E-701
E-632 E-706
E-632 E-707
D
E N
D U
M
M
D
E N
D U
M
M
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4- E-
2.d wg , L ay ou t1, 7/
/20
1:
:44
P M, JR
eib old
Q
K A
E d w g
N E
W
M
O T
E
C I A
L
O
U T
L E
T
S
C H
E D
U L
E
E-641
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
D
E N
D U
M
D
E N
D U
M
M
3 3 3
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4- E-
1.d wg , L ay ou t1, 7/
/20
1:
:55
P M, JR
eib old
EF612-AB
SLUDGE FEED
CENTRIFUGE
CENT-65200
S
S
M
DIVERTER
GATE
M
TE/TT
65203
BEARING
TEMP
TE/TT
65202
BEARING
TEMP
ST
65211
BOWL
SPEED
ST
65221
SCROLL
SPEED
EF614 C
CAKE TO
CONVEYORS
CENTRATE
TO PLANT
DRAIN
SAMPLE
TAP
M
M-65210
BOWL
M-65220
SCROLL
VE/VT
65201
VIBR
GREASE
RESERVOIR
GREASE
PUMP
M
1/4 HP
LSL
65231
LOW LEVEL
SIMP
OIL
LSLL
65215
LOW LOW
LEVEL
LSL
65215
LOW LEVEL
FS
65232
CV
65250
DRAIN
P.O.C.
P.O.C.
EF612D
POLYMER
SYSTEM DRAIN
DRAIN
P.O.C.
ALTERNATE
POLYMER TAP
SAMPLE
TAP
CENTRIFUGE VCP
LP-53
P
420V
C2
SV-65761 OPEN
CENTRIFUGE
OPERATOR
PANEL
LP-53A
E C7
X51 X52
L3
L4
C8L
L4
L3
P P
C2L
P
C2L
DEVICES PRE-WIRED TO X51 & X52
BY MANUFACTURER
EF612E
FLUSH WATER
SUPPLY FROM
BOOSTER PUMP
MC VFD VFD
S
S V
D-612 Z
TO POLYMER
SYSTEM
EF612A
POLYMER
FEED
M-65230
Q K
K A
E
F d w g
C E
N T
R I F
U G
E
F
I E
R
I N
G
D
I A
G R
A M
EF613
SHEET OF
SHEET
IDENTIFICATION
O N
E I D
A
T
O T
T E
G R
A T
T
E R
P R
I S
E S
C
K E
R L
A N
D
D
R I V
E
G R
E E
N
B
A Y
X X
X
X X
X
I S
O
A
D E
S I G
N E
D
B
Y
D W
N
B
Y
C K
D
B
Y
S O
L I C
I T
A T
I O
N
N
O
D A
T E
C O
N T
R A
D R
A W
I N
G
C
O D
E
I S
S U
E
D
A T
E
P L O
T
S
C A
L E
S U
B M
I T
T E
D
B
Y
F I
M
E
S I Z
E
P R
O J E
Q
K K
A
M I S
A W
A
A
S
E
A
B
C
D
1 2 3 4 5
M A
R K
D E
S C
R I P
T I O
N
D A
T E
A P
P R
SIGNED
THIS WORK WAS
PREPARED BY ME OR
UNDER MY SUPERVISION
OF
U S
A
R
C E
C I V
G
I N
E E
R
S
Q U
A D
R O
N
X X
X
Oneida Total Integrated Enterprises
D
E N
D U
M
D
E N
D U
M
M
W :\P
RO
JE
CT
S\
O0
4\9
7\0
0\D
RA
W
IN
GS
\08
D es ign In for ma tio n\C
AD
\02
M cM ah on
\Q
KK
A-
-1
4-
EF
-6
.dw g, La yo ut1 , 7
/21 /20
1:
:17
P M, JR
eib old
| SD140 |
| SD341 |
| SD342 |
| AB340 |
| SB140 |
| SB141 |
| SB170 |
| SB340 |
| SB341 |
| D-606 |
| D-607 |
| D-608 |
| D-611 |
| DP111 |
| DP171 |
| DP570 |
| EP111 |
| EP170 |
| E-602 |
| E-610 |
| E-611 |
| E-612 |
| E-620 |
| E-630 |
| E-632 |
| E-641 |
| EF613 |