Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
1 General About warranty. Does warranty covers each individual parts and equipment? Or it should cover the entire plant system?
Any equipment warranty requirements, beyond those required for the project as a whole, are included in the individual equipment specification sections.
2 General
What is the base of calculation? Need to know the Max water amount per day, Max water amount per hour, average water amount per day.
The design flows and loadings are included in the DA, in Section II, Paragraph C. The process treatment tankage and equipment are already sized for the design flows and loadings. We will provide a separate document with the wastewater loading and sizing information that government can provide to bidders in Bid Addendum 02.
Current Avarage flow Main Base 0.681 MSD North Base 0.165 MSD Current Maximum Month Flows Main Base 0.737 MGD North Base 0.229 MGD Current WWTP Design Flows Main Bsae 1.3MGD North Base 0.43 MGD Design Peak Hour Flow 3.9 MGD
3 General
Upgrading the system,. Does this mean upgrading the quality of water? If so, we need to know the current quality and condition of the system regarding water treatment.
The system is designed to meet JEGS permit requirements. Should the Offeror want to see the permit, the base would need to make that available. The process treatment tankage and equipment are already sized for the design flows and loadings. Also, the additional information Addendum 02 should address this.
4 General
Production of Existing System. Understand that we need to replace 4 units. How many unit can we shut down at a time do to the work. That changes our work procedure. In order for us to work without interruption, we need to know capacity and ability of each current unit. Especially the flow load.
Section 01 11 00 Summary of Work, suggests a viable construction sequence, and which treament units may be taken off line and shut down at any given time. Shut down will be one unit by one unit. Needs to be clarified by Waste Water Treatment Plant Manager ( Officially)
5 General
Japanese Waste Water Treatment Plant Law. Japanese Waste Water Treatment System Law. We believe that this will not match the Japanese law once we upgrade the system as described. Should we not to follow the Japanese Law? ①There is no Primary Conditioning Tank ②There is no Third Chemical Sedimentation Process * We need the third process if we need to do the nitrogen removal.
The proposed treatment system will meet JEGS permit requirements.
Microscreens are designed to replace the primary clarifier. Nitrogen removal is accomplished with the use of a pre‐denitrification single sludge nitrification/denitrification system, incorporating Anoxic Zones and an internal recyle system, reducing the reliance on chemicals and eliminating the need for separate nitrification/denitrification stages.
6 Specifications 01 11 00, para. 1.1.1 About the Bid Option. Should we include this option plan into the cost? Is this up to us to determine which option we select.
Addendum 01 removes Bid Options
7 Specifications 22 00 00 Rating for Plumbling. Please tell us the standard for flange. Can we use JIS standard for flanges and nut and bolt?
Yes, JIS standards for flanges, nuts and bolts are acceptable. Need to be selected by CE Operation
RFP No. FA5205‐15‐R‐0007, Repair Main Wastewater Treatment Plant, B1190, Misawa AB, Japan Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
Attachment 2 to FA5205-15-R-0007-0002 dated 5 Jun 15
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
RFP No. FA5205‐15‐R‐0007, Repair Main Wastewater Treatment Plant, B1190, Misawa AB, Japan Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
8 Specifications 43 11 33.10
46 76 33 00
Designation of Vender and Specification. Under the “ACCEPTABLE MANUFACTUREER/MODEL” , if it doesn’t say “OR EQUAL”, are we not allowed to use other manufacturer? For example, it says; Rotary Lobe Blowers: Aerzen/Model GM25S under 43 11 33.10
Section 43 11 33.10 states :"The product brand is for informational purposes only and shall not be construed as the only product available." Therefore, any "OR EQUAL" product is acceptable, as long as it meets the requirements of the specifications.
9 Specifications 43 11 33.10
46 76 33 00
Designation of Vender and Specification. If it says “OR EQUAL”, we need to know detail specification of each equipment. Considering maintenance in the future, we intend to use Japan made manufacturer as much possible. We need detail description of each item, so that we can research for the item to match the current description.
Japanese manufacturers are not excluded, provided the equipment is equal to the specified equipment. A detailed description is provided in the individual specification section.
10 Specifications 43 22 56.20 Designation of Vender and Specification. What is the flow speed of the bottom (cm/Sec)when using the HYPERBOLIC MIXERS?
The Hyperbolic mixers are a slow speed mixer, operating at 18 rpm, to completely mix the tank contents while not damaging MLSS floc.
11 Drawings D‐613
Descrepancy of description. At the site visit, we were told that sludge dehydrator will be replaced with new screw press type, but on the drawing, it says replace with new centrifugal extractor. Which is correct?
A centrifuge is included in the design.
12 Drawings D‐621 Descrepancy of description. At the site visit, we were told to remove the methanol tank, but on drawing, it says to reuse the existing one.
The existing methanol tank and pumps will remain.
13 Drawings D‐604 and Others Material for Piping. About CLDI (Mortar lining duck tile), can we use polyethylene lining duck tile instead?
Provide cement lined ductile iron pipe, NOT polyethelyene which can delaminate, and may not be suitable at higher temperatures.
14 General
Items not identified on Documentation. At the current third treatment process, we will remove the filler equipment. What is the model, size, load amount? ①Current condition of this equipment. ②What is inside and how much of sludge left?
Regarding sludge in tanks, refer to Section 01 11 00, Paragraph 1.1.1.1.C.1.h : "Contractor shall be responsible for all bypass pumping required, tank draining, cleaning, and disposal of all settled solids and grit from treatment tankage."
15 General
Due date for submitting. We will need at least 2 months to gather all the information and calculate once we receive the answers. Information provided to us was not enough to cover the knowledge for us to do the cost estimation.
Solicitation submission due date was changed from "12 Jun 15" to "31 Jul 15" with Amendment No. 0001 issued on 4 Jun 15, and it is posted on the FedBizOpps.
Drawings and Specifications
The Bid Option is indicated both on contract drawings and specifications.
However, only Base Bid is provided at Section B of the Solicitation. Please clarify.
Addendum 01 removes Bid Options
17 Drawings F‐001
The item No. 6 of notes for NEW WORK indicates that “Obtain approval from structural engineer before making any penetration through structural members, walls and slabs.” Please advise the procedure for obtaining approval from structural engineer.
As this is an existing building, the design intent is to not penetrate any structural members unless physically impossible to install the fire sprinkler piping. Should a penetration be required, the contractor is responsible for submitting an RFI to the government who will forward it on to the structural designer of record .
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
Drawings and Specifications
F‐001 21 13 17.00 10
From the drawings and specification for Fire Protection works, such as dry pipe sprinkler system installation and Mass Notification System, we assume that these works shall be designed by the Contractor and these drawings shall be endorsed and approved by the registered Fire Protection Engineer under NFPA. Please confirm.
Contractor is responsible for final fire sprinkler shop drawings in accordance with NFPA 13 and shall be approved by the Fire Protection Specialist.
19 Specifications 21 13 17.00 10 Para. 1.4.1 and 1.4.2
Para. 1.4.1, Section 21 13 17.00 10 of the contract specification indicates that the Fire Protection Specialist (FPS) should be appointed and he should be a registered professional engineer and Full Member of the Society of Fire Protection Engineer or Level III Technician under NICET. Please advise whether this requirement is mandatory or not.
In papa. 1.4.2 of the same section, we assume that the Sprinkler System Installer should be approved by the Government. Please advise whether experienced Japanese Sprinkler System Installer is acceptable or not.
It is manditory that the FPS meet the requirements of the specifications. A Japanese contractor meeting the requirements of paragraph 1.4.2 is acceptable.
Specifications and Drawings General
There are lot of material, equipment, machineries and devices are indicated and specified in the contract drawings and specification. Can we prepare the bid price based on the Japanese material, equipment, machineries and devices, if the quality of these are equal or exceed the specified material, equipment, machineries and devices?
Yes. Japanese manufactured equipment and materials that meet the specifications are acceptable.
21 Specifications 01 33 29
IAW para. 1.3, Section 01 33 29, USGBC LEED‐NC rating system will be utilized and LEED Sustainability coordinator is required to be employed.
However, LEED is not so familiar and common in Japanese construction market and almost of Japanese engineer has no experience in LEED certified or registered project. Please advise whether LEED requirement under this section is mandatory or some sort of relaxation will be considered by the Government.
LEED certification is preferred but not mandatory.
22 Specifications 01 11 00 01 35 29
We understand the SSHO will be acceptable if he has a certificate issued by JCSHA. However, Master Entry Plan (MEP) should be approved prior to commencement of the work under confined space and this Plan should be prepared to comply with US safety regulation such as Air Force Occupational Safety and Health Standard (AFOSH) and MEP prepared based only on Japanese Safety Regulation will not be acceptable.
Please advise.
MEP must comply with AFOSH standards.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
23 Drawings
We understand that a lot of structural modifications to the existing waste water treatment plant structure, such as cutting opening to the existing concrete wall and slab, new additional structure on to the existing structure and change of the structural wall and slab layout, have been indicated. To make sure KTR’s scope of work, please clarify the followings:‐
1) We assume that the structural stability taking into consideration of this structural modification has been examined/verified by the structural engineer and no additional retrofit work (reinforcement work) to the existing structure other than the work indicated on the contract drawings will be necessary.
2) Please provide the treatment detail of the cut end of the structural wall.
3) Please provide the treatment detail for the cold joint between existing concrete and newly cast concrete at wall and slab.
1) No additional retrofit work to the existing structure, other than the work indicated on the contract drawings, will be necessary.
2) The treatment detail for the cut end of the structural walls is provided in Addendum 1. Use an equivalent ASTM A775 Epoxy paint to protect exposed rebar at new cuts in existing concrete. 3) Details for the cold joint between new and existing concrete at wall and slab are provided in details 3, 6, 7, 8, &11/SB541 and in details 1, 2, 4, 5, 8, 9, 10, 11, & 14/SB542. Use an equivalent ASTM A775 Epoxy paint to protect exposed rebar at new cuts in existing concrete.
24 Drawings
There is no particular indication for ACM in the contract drawings.
However, contract specs includes the section for ACM abatement works at Section 02 82 14.00 10. Do we need to perform bulk sampling prior to start the demolition work or can we start the work without taking any action for
ACM?
Addendum 01 addressess ACM specifically on drawings and specs.
25 Specifications 01 11 00 1.1.1
Project Description: There are BID OPTIONS, Number 1 and Number 2 indicated in this clause. How shall the Offeror show the option prices?
Addendum 01 removes Bid Options
26 Related to Above
01 11 00 1.1.1.2, D. (Page. 6) also indicates,
a. Base Bid, and
b. Alternate Bid Above relates to following chapters, E and F.
26 28 01.00 10, 1.2, 1200A Spare Breaker (for optional portable generator service).
Addendum 01 removes Bid Options
27 Drawings D‐631 The "MAIN BASE NEW PROCESS FLOW SHCEMATIC" shows only "Sodium Hypochlorite" for Chlorine Contact Tank. There is no indiction for the "Option Item" Ultra Violet System.
Addendum 01 removes UV Bid Option
28 General
There is no indiction of influent sewer volume Suspended Solids (SS), Biological Oxygen Demand (BOD), and discharge volume. Please clarify the characteristics of sewer water and treated water to handle both in the old system and the new system.
The design flows and loadings are included in the DA, in Section II, Paragraph C. The process treatment tankage and equipment are already sized for the design flows and loadings. This information will be provided in Addendum 02.
29 General What is the required quality of discharge water in terms of S.S and BOD? Water quality dischardged is required to meet JEGS permit requirements.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
30 General
What is the quality of sludge discharge in terms of cubic meter or ton, on the operation record?
Sludge production is calculated to be 1004 Kg/day (2213 pounds /day) of solids. At 1% solids concentration, this is equivalent to 100 cubic meters/day (26,534 gallons/day). This is the vloume fed to the centrifuge.
31 Specifications 33 52 10, 2.2.1 (P3) And others
This clause indicates ASTM A53/53M for pipe material, especially it indicates SCH 80 for 65mm or smaller and SCH 40 for 65mm and larger pipes. It is not a standard practice in Japan. Please allow not only JIS standard, but regular Japanese practices in selelction of pipe materials.
Equivalent JIS standards for piping and Japanese methods are acceptable. See Specification 01 42 00.00 33 JIS ACCEPTABLE ALTERNATIVES Page 2.
32 Specifications 35 20 16.26, 2.7, A This requires SUS IAM ASTM. Please allow JIS standard and also Japanese manufacturers independent standards for equivalent SUS material.
Equivalent JIS standards for piping and Japanese methods are acceptable.
33 Specifications 35 20 16.26, 2.7, C.1 This requires ACME threads. Please allow JIS threads, too. Equivalent JIS standards for stem threads are acceptable.
34 Specifications 35 20 16 .27 Part 2 Same request as #9 and #10. (Question No. 32 and 33) Equivalent JIS standards are acceptable.
35 Specifications 40 05 13.96, 1.1 Please include JWS standards in addition to AWS standards.
Nondestructive Examination shall include standards made by Japanese Society for Non‐Destructive Inspection.
JWA would be acceptable.
36 Specifications 40 05 13.96, 1.5 For qualificcation of welder, please include JWA qualification. JWA would be acceptable.
37 Specifications 40 15 13, Part 1 Please include JWWA standards in addition to AWWA standards. JWA would be acceptable.
38 General Requests #8 thru #14 (Question No. 32 thru 38) are redundant. Please add reasonable list of acceptble Japanese Standards to 01 42 00.00 33, below 33 30 00.
JWA would be acceptable. There is no Section 33 30 00.
39 Specifications 40 91 13.10, 2.2
Although it allows "or equal" in 2.1, B, the listed specifications like 7.a, "dimensions" may practically eliminate usage of alternate manufacturer's product. Please revisit all of "equipment" related specifications, and let the AE firm segregate the "BASIC" requirments and those specific characteristics copied from the manufacturer's catalog sheets. The characteristics copied from manufacturer's catalog sheet shall be indicated as "reference" information.
The dimensions for a specific equipment item are not the sole determining factor when deciding if a piece of equipment is equal. If the proposed equipment fits in the space available, it is not an issue.
40 Drawings EP142, EP143
There is no indication of sizes and types, for conduits and wirings related to sensors, switches, and transmitters listed as "plan tags". Please provide that inforamtion.
Wiring for the tagged devices is indicated on the Electrical Field Wiring Diagrams, the "EF" series of drawings. For example, the instrument that is tagged as Plan Tag "A1," FE/FIT‐30000," has the wiring indicated on Drawing EF611. For conduit type, refer to specifications. Where conduit size is not indicated, provide in accordance with NFPA 70 conduit fill requirements.
41 Drawings E602 Construction Notes#2: May we understand that we can reuse the modified ATS when we use the existing generator?
Addendum 01 Removes Construction Note #2, and the bid options.
42 Drawings E602 Construction Note#2: What is the required capacity of temporary generator in terms of kVA?
Addendum 01 Removes Construction Note #2. The temporary generator is still required, and is described in Specifications, Section 01 11 00, Paragraph 1.1.1.2.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
43 Drawings EP142, EP143
W1 thru W6, and X3 thru X7 listed on EP143 are not found in EP142.
Please clarify.
Items W1 through W4 are shown on Drawing EP141. Items X3 through X6 are shown on Drawing EP141. Items W5 and W6 are located in the same area as W1 through W4. See also Drawing DP347 for reference.
44 Drawings EP142, DIM (3, B)
At the North side of #2 final clarifier, the motor connected to BRKs DS‐ 45110 and DS‐45120 looks like existing motors. However, in DRWNGS E‐ 631 and E‐632, new motors are indicated. Which is correct?
Motors for Pumps P‐45110 and P‐45120 are new. They are shown dashed not to indicate existing, but to indicate that they are located below the concrete deck. The same motors appear on Drawing EP141 (Waterway Power Plan), where they are indicated as new.
45 Drawings E614
A PLC I/O Panel is associated with MCC 1190C. Please indicate details of this PLC panel.
The PLC I/O Panel shown on E614 is LP‐37. It is to contain a PLC processor, I/O, and ancillary devices for control of the Caustic and Methanol pumps. The I/O list for LP‐37 is in Table 40 95
00.00. LP‐37 is one of the control panels to be designed by the Control System Integrator (CSI).
46 Drawings E703, dimension (2, D)
There is a 3%Z Line Reactor indicted. What is the purpose of this line reactor?
The 3% line reactor adds a minimum amount of impedance in front of the VFD to prevent excess current that can damage the VFD under certain line types of line disturbances and ground faults. (Note that the line reactors are also indicated for VFD's on the one‐line diagrams.)
47 Drawings Ditto (2, C)
What is a "SEAL FAIL" with R of PTT? The "SEAL FAIL" with R of PTT is a Red Push‐to‐Test (PTT) pilot light mounted on the door of the MCC‐mounted VFD. It lights when a failure of the pump's seal is detected. It also lights when the pilot light itself is pushed, as a test procedure. A pump's seal failure is detected by probes in the motor housing that sense moisture, as indicated by dashed line "To Motor S.F. Probes".
48 Drawings Ditto (3, B) Regarding HIM, Human Interace Module, please provide cut sheet reference for estimation purpose.
The HIM is the Panel‐Mounted Operator Station, specified in Specifications Section 26 29 23, 2.3, B.
49 Drawings Ditto (3, C)
#29, D12P SEAL FAIL is to be "read by PLC only." Additionally to question #23 (Question No. 47) regarding Seal Fail itself, please clarify what kind of data shall the PLC read?
#29, D12P SEAL FAIL is to be "read by PLC only." The "29" is the terminal number on the VFD. The "P" is a typographical error.
"Seal Fail" is a description of the signal, i.e., this input will become true when the Seal Fail Relay changes state, indicating a seal failure in the pump (see answer to Query 47). The "Read by PLC Only" indicates that the PLC reads this VFD input via Ethernet/IP as if it were an input to a PLC I/O module, but does not use it in any control; it just generates a "Seal Fail Alarm" for the pump.
The data for the Seal Fail itself is binary, either it is true or it is false.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
50 Drawings E610 thru E633
Dimentions for electrical panels are given precisely. The offeror anticipates a conflict in the specified dimensions of the SWGR versus actual area required. Will Government issue change order in such event?
Contractors will provide panels sized to meet the power requirement and fit the space given. No change orders will be issued.
51 Drawings E621 The location of New panel 1191‐L1 is no indicated. Please show the location.
The location of New Panel 1191‐L1 is indicated, on Drawing EP112.
52 Drawings E610 On the second row and second from top, there is SF‐2 indicated. What is this load for?
This is a supply fan.
53 Drawings E601, dimension (3, A)
Please indicated the one line diagram of "RELOCATED ATS FROM B1191
REVISE FOR 420V SERVICE"
"B1191" should read "Q1191." "Q1191" refers to the existing service that serves Building 1191, with the 200 kVA transformer. The existing Automatic Transfer Switch (ATS) referred to in the note can be seen on Drawing E600, between the existing 250 kW generator and existing Panel LP16A. The existing ATS is outdoor (see also sheet ES100), and the Contractor shall modify the ATS for 420V temporary service.
54 Drawings E611, dimension (4, C)
Where is the location for NEW PANEL 1190‐L2? Control Building 1190, Grade Level Electrical Room, south wall (adjacent to Panel PP‐1190D).
55 Drawings E602, dimension (2, A)
There is NEW 3‐CVQ185MM2‐4/C. May we understand this means 3 lines of 185 square millimeter CVQ wires?
"New 3‐CVQ 185MM2 ‐4/C" means three (3) parallel runs of 4‐ conductor 185MM2 CVQ cable. The fourth conductor shall be re‐ identified as a ground conductor.
56 General The electrical drawings are very extensive, and it takes time to study through it. Please extend the deadline of questioning by 14 calendar days.
Bidders/Offerors' submission of questionnaires was closed on 27 May 15.
57 Drawings E630 Please indicate locations for EUH‐1 and EUH‐2. EUH‐1 and EUH‐2 are located in Microscreen Building, 83108, Screen
Room. Refer to Mechanical Drawing M140.
58 Drawings E630
LP‐53B "MICROSCREEN" is not indicated in EP142. There are NEW LP‐51A and LP‐51B in EP142. Please clarify what to do with LP‐53B.
On Sheet E630, the Microscreen Power/VFD Panel should be identified as "LP‐51A" (not LP‐53B). On Sheet EP142, Panel LP‐51A should be identified as LP‐51; Panel LP‐51B should be identified as VFD Panel LP‐ 51A.
59 Drawings E631 Exhaust Fan is not indicated in EP142. Please indicate the location. Exhaust Fan EF‐3 is located in Microscreen Building, 83108, Screen
Room. Refer to Mechanical Drawing M140.
60 Drawings EP142
Please indicte the details for PANELS, LP‐1, LP‐2, S‐1, S‐2, and S‐3. Panel LP‐1 is existing, and is to be demolished (refer to Drawing ED142). Panel LP‐2 is existing Local Panel for the Spray Pumps, and is to remain (abandon in place). Panels S‐1, S‐2, and S‐3 are existing power wiring junction boxes, to remain. (Refer also to ED143 and ED144, for existing wire runs to/from these panels, and their associated scope of work.)
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
61 Drawings EF600A
Please indicate the details for PANELS LP‐35, LP‐36, LP‐37, and LP‐41. In accordance with Section 40 95 00.00, these control panels are to be designed by the Control System Integrator (CSI), under the responsbility of the Contractor. The functionality of each panel shall be as described in Appendix 40 95 00.00. The inputs and outputs (I/O) for each panel is listed in Table 40 95 00.00. The devices that are to be used in the design of each panel are also listed in Section 40 95 00.00.
62 General
Where is the NEW PANEL SCHEDULE? Please indicate in the drawings. It is presumed that the offeror is refereing to one or more of the "New Panel Schedules" that are indicated on the drawings, with the one‐line diagrams. There are several "New Panels" included in the project.
Each "New Panel" has a Panel ID, as indicated in the schedule for that panel. The schedule also indicates a "Location," which indicates the Facility number where the panel is located. For each new panel, the Panel ID shows up on the floor plan of the indicated facility.
63 Drawings F101, F102
The drawing indicates all of Sprinkler System, Fire Alarm Receivers, and Radios to be installed on the first floor "Stock Room". Is there enough space in the room in accordance with NFPA standard?
Design drawings are schematic in nature, contractor to provide shop drawings and coordinate clearance requirements
64 Drawings F102, F103
The sprinkler system covers the entire building including 2nd floor. May we understand that the flow sensor can monitor the entire system as activation at the first floor only? Or shall we install flow sensors separately on each of the floors?
The entire building may monitored as a single zone (i.e. one flow switch).
65 Drawings F102 There is no manual fire alarm near the door on the second floor corridor to the stair case. Don't we need this?
Manual fire alarm Should be added in this location
66 Drawings FA102 There is a manual fire alarm in first floor Carry out Room. Is this location in accordance with NFPA standard?
Manual fire alarm Should be deleted in this area
67 Drawings FA001, FA501 Mass Notification System (MNS) is in scope. Please indicate the radio signal type of MNS currently operative in Misawa Base.
Federal Signal Radio system
68 Drawings FA501 The MNS requires communication between Base Fire Station. Please indicate the existing MNS system specifications.
Federal Signal Big Voice
69 Drawings ED113, dimension (C, 6)
Wires related the hoist is to be removed. Can we abandon the existing hoist in place?
For the existing Hoist (M13), the existing wiring for the hoist is to be removed. The hoist itself is to remain in operation. The Contractor shall re‐wire the existing hoist to new source of power in new Headworks 1191 Electrical Room.
70 General Could you give us the capacity calculation sheet for the existing plant system?
The process treatment tankage and equipment are already sized for the design flows and loadings. See addendum 02.
71 General Could you give us the capacity calculation sheet for new plant system? The process treatment tankage and equipment are already sized for the design flows and loadings. See Addendum 02.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
72 General Please show us influent quality of water in BOD,SS,T‐N date) The process treatment tankage and equipment are already sized for the design flows and loadings. See Addendum 02.
73 General Please show us final effluents upper limit of water quality BOD, SS, T‐N. At during construction period.
Treatment shall comply with JEGS permit requirements during construcion.
74 General After completion of the plant, please show us final effluents upper limit of release water quality.
Treatment shall comply with JEGS permit requirements upon completion of construcion.
75 General
Please show existing equipment of weight, specifications, electrical power consumption.
Electrical requirements for equipment are specified. The weight of each item is not specified. Equivalent equipment should have similar weight compared to the specified equipment.
76 General Could you give us the existing as‐built of waste water plant? See Attachment
77 General Do you have a summary sheet for renewal equipment list? The new equipment is listed by specification section, as noted in the table of contents.
78 Drawings Structural General The drawing instructs to make opening and demolish on existing wall and floor. Is it safe to follow design term designed the existing structural calculation.
Shoring will be required under the two new additions to help support the concrete pour of the new slabs.
79 General Is the structural calculation is Japanese or US standard base? The structural calculations are based on the US Department of Defense
Unified Facilities Criteria 3‐301‐01
80 Drawings SD140、SD342 When demolished existing slab and wall; do we need piling on the slab? Piling is not needed on the slab when demolishing existing slab.
81 Drawings Structural General Please show us protecting coating (anti‐corrosive paint) specification and range on current structure.
The protective coating (anit‐corrosive paint) should be an equivalent ASTM A775 Epoxy paint.
82 Drawings
G002、DP146、DP1
The drawing shows DP146 on the G002. We cannot see DP146 or instead of DP147?
DP146 is correct. Sheet DP147 was renamed DP146 in Addendum #1.
83 Drawings
PROCESS PIPING
GENERAL
Please show location lagging and thermal insulation new piping. Process piping is not designed to have lagging nor thermal insulation.
84 Drawings D601~D613
What mean in dot leader line for Limit of vender‐supplied package? Do we need to make separate order beside plant construction? Do we need to follow this specification when we order?
The limits indicate items that are included in a specific equipment specification section.
85 Drawings DD110~DD371 Please show us size and material for piping need to be removed. Piping Demolition Schedules are shown on Drawings DD110, DD111, DD143, DD170, and DS100 and the material is steel.
86 Drawings DP145、DP348 Please show us distance gap between the existing piping height and new piping height at crossing point.
The new piping will occupy the same space as the existing piping.
Retrofit thickeners one at a time, per Section 01 11 00, Paragraph 1.1.1.1.C.1.g
87 Drawings
DP141、DP144、
DP147
Please show us new piping material as follows:
*・83108 LOWER LEVEL PIPING SCHEDULE
④φ100Sluge treatment pump discharge piping material?
*・83108 WATERWAY PIPING SCHEDULE
④φ150 RAS piping material?
⑦φ100Sump pump discharge piping material?
With reference to the two sludge pumps "F" located in zone 3 of the aerobic digester, the new piping is 100mm cement lined ductile iron.
Each pump discharge includes 1 plug valve and 1check valve. Delete the check valve shown on teh common discharge line. The 150mm RAS piping is Class 52 cement lined ductile iron. The 100mm sump pump discharge piping is Class 52 cement lined ductile iron.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
88 Drawings DP171
Can we sand blast inside location for existing water supply tank and sludge services tank? Can we work to sand blast in this location?
Specification section 43 41 13.00 allows sandblasting, and requires tenting to confine dust and prevent any dust from entering the room.
At the Contractor's option, removing the tanks from the building to blast and paint would be allowable.
89 Specifications
Section 01 11 00
1.1.1 Project
Description
Please show us the bid option number 2 ultra‐violet light specification. Addendum 01 removes UV Bid Option
90 Specifications
Section 01 11 00
1.1.1.1 Suggested
Construction Sequence B B1190 Control C 83108 Treatment Work
Do you have a temporally piping schedule plan for temporary aluminum surface storage tank, temporary connect to influent piping, temporary aeration piping?
Any temporary piping is considered "Means and Methods" and is at the Contractor's sole discretion. A Suggested Construction Sequence is provided in Section 01 11 00, Summary of Work.
91 Specifications
Section 01 11 00
1.1.1.1 Suggested
Construction Sequence B B1190 Control
Please show us existing centrifugal dehydrator of operation time, daily running schedule, and sludge output value?
The performance requirements for the new centrifuge are specified in Section 46 76 33.00
92 General Existing centrifugal dehydrator. Please show us possible outage days for existing centrifugal dehydrator.
Please refer to section 01 11 00, Paragraph 1.1.1.1 B. 4. The number of days available will be contingent upon the current operating status of the plant at the time the request is made.
93 Drawings DP311 What type of material for piping 200MM ISO‐ring (TYP.4)? 316 Stainless Steel, per Section 40 91 19.29.
94 Drawings E610、E613、E614 、E620、E631、E63
Can we use different size for current MCP? It could be bigger than existing one.
Question is unclear. If asking to replace with equipment of equal quality and performance, this is acceptable.
95 Drawings
ED142、EP142、E61
The word” contractors discretion”, is it required to have a meeting with government? Or do we submit our plan?
Where "Contractor's Discretion" is indicated, a meeting with government is not required. Submit the Contractor's intention.
96 Specifications
Section 01 11 00
1.1.1.3 Qualification
for Project Engineer
Any other requirement and certification for site manger other than first grade construction engineer?
No
97 Specifications Section 01 33 29
1.1 Reference
Do we need LEED manager in permanently stationed at job site? No
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
98 Specifications Section 01 33 29
1.1 Reference
LEED manager must be prime contractor employment? No
99 Specifications Section 01 33 29
1.1 Reference
Is LEED manager acceptable of subcontractor employee? Yes
100 Specifications Section 01 33 29
1.4 LEED Coordinator
Can the LEED certification substitution for CASBEE? Yes
101 General
Depending on the day we receive the answers to these questions, we may need more time to gather information for this bid. We would like to request extension of 5 weeks of dead line for bidding.
Solicitation submission due date was changed from "12 Jun 15" to "31 Jul 15" with Amendment No. 0001 issued on 4 Jun 15, and it is posted on the FedBizOpps.
102 General Could you accept our question after 27-May? Bidders/Offerors' submission of questionnaires was closed on 27 May 15.
103 Drawings G‐002 page 99 Dwg.G‐002Prcess Piping page 99 DP146 show on the table of contents.
Where the dog. number DP147?
DP146 is correct. Sheet DP147 was renamed DP146 in Addendum #1.
104 Drawings C-101 Please show dairy or weekly truck schedule. We would like to make asphalt working schedule for escape the truck passage in the Bldg1190 outside.
The asphalt repair shown in the drawing will be performed in this contract after the necessary piping and utility work is completed.
105 Drawings C‐101
Please clarify the [new 360mm tall transformer/with D13 at 304 mm OC each way]
The concrete pad for the transformer is to have D13 reiforcing at 304 mm on center horizontally. Reinforcing is to be centered in the slab vertically. See electrical sheet for specific transformer information.
Horizontal dimensions of the concrete transformer pad are based on the dimensions of the transformer supplied.
106 Drawings SD140 symbol ④TYP OF 4. Please show the Symbol 4 typ of 4 this drawing or picture.
What is 4 type of 4?
This is note 4 that is typical for the 4 similar conditions on the same grid line. TYP is an abbreviation for the word typical.
107 Drawings SD141 ④Type OF (4). What is type of (4)? Is there a difference between 4 and (4)?
TYP is an abbreviation for the word typical. Typical for the (4) similar conditions. There is no difference between 4 and (4).
108 Drawings SD141 ④ SEE DWG.SB342. the drawing SD141 shown ④ we see drawing SB342 but SD 342 do not show drawing number SD141.
Note 4 on sheet SB141 should read "CUT IN NEW OPENINGS, SEE SD342 FOR MORE INFORMATION". SD342 currently lists SD141.
109 Drawings SD142
Note All remove cover plate to be kept for possible reuse. After removal of covers for reuse, where is the storage location? What is the line of judgement for possible reuse and not reuse?
The cover plates should be stored in a safe and easily accessible on‐site location which the contractor and owner agree to. If the cover plates have no damage, then they can be reused. If the cover plates are damaged, do not reuse.
110 Drawings SD142 ⑤see SB540. We see SB540 but SD540 do not show SD142. SB540 should list SD142. Sheet SD540 does not exist.
111 Drawings SD340 ⑥ see SB342. We see SD340.SD 340 show SB342, but SB342 do not show SD340.
SB342 should list SD340.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
112 Drawings AB111 ①TYP of (3). AB111 show 1 typ of (3). what is typ(3) and we see SB541,SB541 do not show the typ.
This is note 1 that is typical for the 3 similar walls. TYP is an abbreviation for the word typical.
113 Drawings AB140 OH1. Clarify DH1 is OH1? The OH1 is the roll‐up door.
114 Drawings AB140 ⑥New S200X27.4 Hoist beam with trolley. Please see the trolley load size? Is 2.8t acceptable?
The hoist beam was sized for a 2 ton point load.
115 Drawings SB141 ⑨TYP OF (4), (8). What indicates the typ of (4) (8)? This is note 9 that is typical for 4 and 8 other similar conditions. TYP is an abbreviation for the word typical.
116 Drawings DD140 note, See sheet DD143 treatment work (83108). DD143 do not show treatment work. ① are three(3). which ① is correct.
Although shown in 3 different types of tankage, the dropleg designation "1" is correct for all 3 locations.
117 Drawings DD140 Typ① TYP2.Tank, And piping TYP.4. Where are typ1, 2, and 4 on the drawing?
The description of each item, is typical for each item in the basin where it is referenced.
118 Drawings DD141
Typ .2 tank,Typ.3Tanks,TYP.4 Trains. Where the location is indicates typ2.3.4?
The description of each item is given once, and is typical for the number items referenced. For example, the demolition Work associated with the thickeners is described once and is noted "Typical 2", and the intent is that the same Work is required for the 2nd thickener as well.
119 Drawings DD141
Note see sheet DD143. DD143 do not show Piping demolition schedule There are three(3) shown ①is where?
The schedules on DD143 are identified as "Lower Level Piping", "Waterway Piping", and "Top Level Piping", which correspond to "DD140 Lower Level Demolition Plan", "DD141 Waterway Demolition Plan", "DD142 Top Level Demolition Plan".
120 Drawings DD142
Thickener driver Typ.2.Typ3 tanks, Typ 4 trains. Please clearly typ2, 3.4 Where is the location?
The description of each item is given once, and is typical for the number items referenced. For example, the demolition Work associated with the thickeners is described once and is noted "Typical 2", and the intent is that the same Work is required for the 2nd thickener as well.
121 Drawing DD142
Note See sheet Dd143. There are three ①,please clearly . The 274 airmain drop legs identified as "1" in the Lower level Piping Demolition Schedule are shown on DD140 Lower Level Demolition Plan.The 138.9m Airmain Distribution Header identified as "1" in the Waterway Piping Demolition Schedule are shown on DD141 Waterway Demolition Plan.The 152 m Airmain identified as "1" in the Top Level Demolition Schedule are shown on DD142 Top Level Demolition Plan.
122 Drawings DD170 see Photo A. There are three Photos A, on DD910, DD940, and DD970, please clearly on which is which.
DD170 is Titled as the Control Building B1190, and as such, the corresponding "photo A" is on DD970 which is TitledControl Building B1190. The other Drawings reference Work in the Headworks B1191 or Treatment Works 83108.
123 Drawings DD370 TYP.5 Blowers. Where is the location of typ 5? On Drawing DD370. The description of the item is given once, and is typical for the 5 blowers on that Drawing.
124 Drawings DP110 Grid pump (TYP.2) Slide rail system(TYP.4). Please clearly show typ.2 and typ 4.
Similar anwer to above question.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
125 Drawings DP111 TYP.2,TYP.3 TYP.4. Please clearly show typ2, 3, and 4 and its location and number.
Similar answer to above question.
126 Drawings DP140 See sheet DP146 . There is no DP146 listed. Please show us where we can find.
This item is addressed in Addendum #1.
127 Drawings DP142 see sheet DP146. There is no DP146. Please show us where to find. This item is addressed in Addendum #1.
128 Drawings DP144 E,350mm flow meter (TYP.2). Where is TYP2 located? In the plan view,there is one 350mm pipe directly above another.
Refer to section 2 on DP 347 which clearly shows both flowmeters.
129 Drawings DP171 (B‐1) 40mm polymer solution flow meter. The polymer solution flow meter, there is no equipment list from A to F.
The polymer flowmeter should be referenced as "C" in the schedule.
130 Drawings DP172 F, FRP Alum/ferric tank. Where do we find equipment list F? A note on DP172 directs the Contractor to the Equipment Schedule on
DP171.
131 Drawings DP310 TYP.2. Please clearly typ 2 mean. "Typ 2" means there are 2 of the items being referenced.
132 Drawings DP311 TYP.4. There are many typ.4 what mean typ4, please show drawing typ4. "Typ 4" means there are 4 of the items being referenced.
133 Drawings DP312 TYP.2). What is the meaning of typ 2. Similar to previous answer.
134 Drawings DP370 TYP.2. Where is typ 2 located? Similar to previous answer.
135 Drawings DP371 Concrete support Typical 4. Please show typical 4 . Similar to previous answer.
136 Drawings DP372 See sheet DP570 . There is no DP372 at DP570. Both DP171 and DP372 reference the details on DP570. The details on
DP 570 are correctly referenced.
137 Drawings DP541 TYP 8. What is the meaning of typ8? Typ 8 means there are 8 gates.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
138 Specifications
23 05 15 page 6, 23 09 33.00 40 Page 4, 23 09 53 00 20 page 12, 23 82 00.00 20 page 3, 26 05 71.00 40 page 6,10,11,12, 26 05 71.00 40 page4,5, 26 05 19.00 10 page 9,10, 26 05
71.00 page 12, 26 20 00 page 10,23, 26 24
19.00 40 page 7,9,10,11,12, 26 29 23 page 10, 26 56 00 page10, 28 31 76 page 15,17,24,25, 40 91 13,32 page 6,7, 40 91 19.29 page2, 40 95 00 page 7,8,10,11,16, 46 21
26.00 page9, 43 21
36.30 page3, 46 21
99.10 page6, 46 50
02.00 page2, 46 76 33.00page13
The specification says voltage 120 VAC. If we make the 120VAC power equipment in Japan.
It is very high cost and long delivery time. It is in‐convenient for maintenance work.
Could you change to 100VAC?
Equipment in this voltage range (line‐to‐neutral) that is supplied for this project shall be compatible with the available voltage, which is 120VAC, 50Hz.
139 Drawings E‐602
New generator 座標C‐3. Please show generator specification. The generator specification is included in Addendum 01, Section 26 32
14.00 10.
Drawings and Specifications
E‐602&E‐603 new generator.
Specification 40 95 00 Appendix 40 95 00.00‐1 Description of operations (3.9.28 page 1 of 2)
Appendix 40 95 00.00‐1(3.9.28) generator date: rating 630kw/450kva. E‐ 602&E‐603 generator rate 360kw, 450kva pf=0.8 Which is correct?
The generator ratings shown on E‐602 and E‐603 are correct. Refer to Specifications Section 26 32 14.00 10, included in Addendum 01.
141 Drawings E‐605.
item number 9 420V/120V transformer. Japanese F1 and F2 voltage is 100V, if 120V F1&F2 repair material is specific and high price.
"Power Cabinet" Item Number 9 does identify the Control Power Transformer (CPT) as being 420/100V. The notation on the one‐line diagram as "420/120V" is a typographical error.
142 General
Range of guarantee. We understand that the required guarantee of our scope of supply is to install the equipment based on your specification. If there are any other requirements, please let us know.
In regards to warranty of construction, refer to FAR 52.246‐21, "Warranty of Construction" available at URL: http://farsite.hill.af.mil.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
143 General
Range of guarantee. If the performance guarantee will be required in our scope of supply, please clarify and provide us 1) design capacity, 2) raw water quality, 3) treated water quality, 4) capacity calculation.
See Addendum 02.
144 General
Equipment detail and Request. We deemed that the equipment with the Japanese standards should be preferable for this project, and the capacity, caluculation of each equipment and specification will be required.
Please clarify and provide us the above information.
Japanese manufacturers are not excluded, provided the equipment is equal to the specified equipment. A detailed description is provided in the individual specification section.
145 General
Equipment detail and Request. The detailed civil construction information
(ex. Piping layout, quantity calculationdate of size, length to be replaced) will be required .Please clarify and provide us.
Drawings DS101 and DP141 cover the process piping. Two water lines and one sanitary line are covered in drawings C‐102 and C‐103.
146 RFP General Bid Date. Please extend bid date for 3 months for design and estimate of cost.
Solicitation submission due date was changed from "12 Jun 15" to "31 Jul 15" with Amendment No. 0001 issued on 4 Jun 15, and it is posted on the FedBizOpps.
147 General
Method of re‐construction. It was informed at the site visit that we CANNOT stop the operation while we are replacing the plant.
If you have the plan for the replacing process for each equipment, please let us know.
However there is only one receiving tank, so we have to stop for replacing such as the automatic coarse screens and the pumps. And also final settling tank is only one, so we have to stop as well for replaceing equipment in the tank.
Refer to Section 01 11 00, Summary of Work, Paragraph 1.1.1.1
148 RFP Section F
Contract term. Please set the cap for liquid damage with 3% of contract price.
Refer to Section F, FAR 52.211‐12 "Liquidated Damages ‐ Construction", page 7 of the solicitation, Liquidated Damages is determined to be ¥146,076 for the first calendar day of delay and ¥130,622 for each additional calendar day of delay and thereafter. No upper limitation is set for the amount of Liquidated Damages.
149 RFP
Section L 52.216‐1
Firm‐Fixed‐price. The contract term is difined firm‐fixed‐price in RFQ, however please clarify that the price will be changed in the following conditions.
A) RFQ terms and scope of supply are changed after contract.
B) The actual site condition is different from RFQ terms and specification.
C) RFQ and scope of supply are changed by any discussion after contract.
In a case where a change in the terms of a contract is required (e.g.
change in specification/drawing, differing site condition and etc), the contract amount may be changed by issuing a modification.
Query No. Target Document Reference Question Submitted by Prospective Offerors Gov't Response / Clarification
Consolidated List of Prospective Offerors' Submitted Questionnaire and U.S. Government Response / Clarification
150 Drawings D‐631 & SB140
Anaerobic and aerobic treatment process. We will replace each anaerobic and aerobic treatment process one by one, and treated water condition may not be stable when the plant re‐start up.
Therefore we would like to review whether it is the mixture of treated water by existing plant and by replaced plant is under the required water condition by regulation.
Please clarify and provide us the data of the treated water by existing plant.
Refer to Section 01 11 00, Summary of Work, Paragraph 1.1.1.1
151 Drawings Drawing No. EF~
Switch board. Regarding a switch board, please clarify which board we have to replace or remain.
(Ex.) Are EF600~ circled doublet for replacement ?
Are LP ‐34, 35, 36, 41, 51, 53, 50A, 50B for replacement ?
The Local Panels listed in the question are new. Refer to Drawing EF600, which shows a schedule of new Local Panels, and who each panel is to be furnished by.
152 Drawings ED640~
Drawing on cable. Regarding cable drawing, our understanding is below.
A)REMAIN → re‐use B)DEMOLISH → have to remove Please clarify.
Drawing ED640 is not a "Cable Drawing;" it is a schedule of existing motors and special outlets.