This document is a solicitation for a multiple award task order contract to provide services and products to the Department of the Air Force. The solicitation number is FA462024R0001 and offers opportunities for small businesses. Responses are due by June 26, 2018 with task orders to be awarded on a competitive basis between 2024-2029. Offerors will submit proposals for various professional and technical support services including engineering, logistics, and program management. Pricing is to be determined at the task order level with both fixed-price and cost-reimbursement type contracts available.
View the file
Other files for this federal contract opportunity
Show all 33
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fairchild AFB IFS
26JUNE2018
FAIRCHILD AIR FORCE BASE
INSTALLATION FACILITIES STANDARDS (IFS)
Installation Elements Site Development Facilities Exteriors Facilities Interiors
APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED
· . ANDERSON.MATTHEW.KARL.1156 o;gitally signed by
Signature Field 630167
ANDERsoN.MATTHEW.KARc.11s6630161
Date: 2018.09.1 0 08:25:53 -07'00'
FA462024R0001, Amendment 0004 Attachment 1A - Fairchild Air Force Base Installation Facilities Standards (IFS)
AIR FORCE
INSTALLATION
FACILITIES
STANDARDS
Fairchild Air Force Base IFS
Table of Contents
A. OVERVIEW .............................................................. s
A0l. Facility Hierarchy
A02. Facility Quality
A03. Facility Districts
B. INSTALLATION ELEMENTS
B0l. Comprehensive Planning
B0l .1. Installation Development Plan (IDP)
B0l .1.1. IFS Component Plan of IDP
B0l .1.2. Brief History of Base B0l .1.3. Future Development
B02. Street Envelope Standards
B02. l. Hierarchy of Streets
B02. l .1. Arterial Streets B02. l .2. Collector Streets
B02.1.3. Local Streets
B02.1.4. Special Routes
B02.2. Hierarchy of Intersections
B02.2. l. Arterials
B02.2.2. Arterial/Collector
B02.2.3. Collectors B02.2.4. Special Intersections B02.2.5. Street Frontage Requirements
B02.2.6. Sight Lines
B02.3. Street Elements
B02.3.1. Paving
B02.3.2. Curb and Gutter B02.3.3. Utility Service Elements
B02.3.4. Traffic Signs B02.3.5. Street Lighting
B02.3.6. Other
B03. Open Space / Public Space
B03.1. Plazas, Monuments and Static Displays
B03.1.1. Paved Plazas B03.1.2. Sculptures, Markers and Statuary B03.1.3. Static Display of Aircraft
B03.2. Grounds and Perimeters
B03.2.1. Parade Grounds B03.2.2. Parks
B03.2.3. Preserves B03.2.4. Perimeter Fence
C. SITE DEVELOPMENT
C0l. Site Design
COl .1. Site Design Considerations
C0l .2. Building Orientation
CO2. Utilities
CO2, 1. Utility Components
C03. Parking Areas
C03.1. Configurations and Design
C03.1.1. Paving and Striping C03.1.2. Curbing
C03.1.3. Internal Islands and Medians
C03.2. Parking Structures
C03.3. Connectivity
C04. Stormwater Management
C04.1. Stormwater Requirements
COS. Sidewalks, Bikeways and Trails
COS. l. Circulation and Paving
C0S.1.1. Ramps and Stairs C0S.1.2. Lighting
C06. Landscape
C06.1. Climate-based Materials
C06. l .1. Landscape Design Concept C06. l .2. Xeriscape Design Principles
C06. l .3. Minimizing Water Requirements
C06. l .4. Plant Material Selection
C06.1.5. Water Budgeting (Hydrozones) C06.1.6. Base Entrance Landscaping
C06.1.7. Streetscape Landscaping C06.1.8. Pedestrian Circulation Landscaping
C06.1.9. Parking Lot Landscaping C06.1.10. Screen/ Accent Landscaping C06.1.11. Other
C07. Site Furnishings
C07.1. Furnishings and Elements
Table of contents continued on next page
FA462024R0001, Amendment 0004
Table of contents continued
C07.2. Site Furnishings Products, Materials/ Color.. 42
C07.2.1. Barbeque Grills
C07.2.2. Benches
C07.2.3. Bike Racks C07.2.4. Bike Lockers
C07.2.5. Bollards
C07.2.6. Bus Shelters
C07.2.7. Drinking Fountains
C07.2.8. Dumpster Enclosures/ Gates C07.2.9. Fencing
C07.2.1 0. Flagpoles
C07.2.11. Lighting - Landscape/ Accent C07.2.12. Litter and Ash Receptacles
C07.2.13. Picnic Tables C07.2.14. Planters - Free Standing C07.2.15. Play Equipment C07.2.16. Screen Walls
C07.2.17. Tree Grates C07.2.18. Other
C08. Exterior Signs
C08.1. Colors and Types
C08.1.1. Materials and Color Specifications C08.1.2. Installation and Gate Identification Signs C08.1.3. Building Identification Signs
C08.1.4. Traffic Control Devices (Street Signs) C08.1.5. Directional and Wayfinding Signs
C08.1.6. Informational Signs
C08.1.7. Motivational Signs
C08.1.8. Parking Lot Signs C08.1.9. Regulatory Signs
C08.1.1 0. Other
C09. Lighting
C09.1. Fixtures and Lamping
C09.2. Light Fixture Types .................................................. 6 0
C09.2.1. Street Lighting
C09.2.2. Parking Lot Lighting
C09.2.3. Lighted Bollards C09.2.4. Sidewalk Lighting
C09.2.5. Walls/ Stairs Lighting
C09.2.6. Other
D. FACILITIES EXTERIORS
D01. Supporting the Mission
D02. Sustainability
D03. Architectural Features
D03.1. Orientation, Massing and Scale
D03.2. Architectural Character
D03.3. Details and Color
D03.3.1. Climate-based Data
D03.3.2. Natural Ventilation System
D03.3.3. Thermal Mass
D03.3.4. Thermal Shading D03.3.5. Renewable Heating/Cooling
D03.3.6. Solar Photovoltaic System D03.3.7. Solar Thermal System
D04. Building Entrances
D04.1. Primary Entrances
D04.2. Secondary Entrances
DOS. Wall Systems
D0S.1. Hierarchy of Materials
D05.2. Layout, Organization and Durability
D05.3. Equipment, Vents and Devices
D05.4 Wall Systems Materials
D05.4.1. Flat Metal Panels
D05.4.2. Brick Veneer
D0S.4.3. Architectural Precast D05.4.4. Stucco Over Sheathing
D05.4.5. Curtain Wall
D05.4.6. Cast-in Place Concrete D05.4.7. Tilt-up Concrete D05.4.8. Ribbed Metal Sheeting
D05.4.9. EFIS
D05.4.1 0.GRFC
D05.4.11. Concrete Block D05.4.12. Fiber Cement Siding
D05.4.13. Other
D06. Doors and Windows
D06.1. Types
D06.2. Layout and Geometry
D06.3. Glazing and Shading
D06.4. Hardware
D06.5. Doors and Windows Materials
D06.5.1. Anodized Aluminum
D06.5.2. Hollow Metal D06.5.3. Aluminum-clad Wood D06.5.4. Other
D07. Roof Systems
D07.1. RoofType and Form
D07.2. Roof Slope
D07.3. Parapets and Copings
D07.4. Color and Reflectivity
D07.5. Gutters, Downspouts, Scuppers, Drains
D07.6. Roof Vents and Elements
D07.7. Clerestories and Skylights
D07.8. Vegetated Roof
Table of contents continued on next page
FA462024R0001, Amendment 0004
Table of contents continued
D07.9. Roof Systems Materials
D07.9.1. Standing Seam Metal D07.9.2. Membrane Single-ply D07.9.3. Built-up Multi-ply D07.9.4. Concrete Tile D07.9.5. Clay Tile D07.9.6. Slate Shingles D07.9.7. Vegetated System D07.9.8. Ribbed Metal Sheeting D07.9.9. Composite Shingles D07.9.10. Other
D08. Structural Systems
D08.1. Systems and Layouts
D08.2. Structural Systems Materials
D08.2.1. Concrete D08.2.2. Insulated Concrete Forming (ICF) D08.2.3. Steel D08.2.4. Pre-Engineered Steel D08.2.5. Masonry D08.2.6. Heavy Timber D08.2.7. Light-gauge Steel D08.2.8. Lumber Framing D08.2.9. Other
D09. Mechanical, Electrical and Plumbing
D09.1. Passive and Active Systems
D09.2. Functionality and Efficiency
E. FACILITIES INTERIORS
E0l. Building Configurations
E0l .1. Layout and Common Areas
E0l .1.1. Interior Design Process E0l .1.2. Codes and Regulations
E0l .2. Quality and Comfort
E02. Floors
E02. l. Floor Materials
E02. l .1. Prepared Slabs E02. l .2. Natural Stone and Terrazzo E02.1.3. Quarry Tile E02.1.4. Ceramic Tile E02. l .5. Resilient Floor E02.1.6. Carpet E02.1.7. Rapidly-Renewable Products E02.1.8. Other
E03. Walls
E03. l. Wall Materials
E03.1.1. Concrete E03.1.2. Masonry E03.1.3. Ceramic Tile E03.1.4. Gypsum Board E03.1.5. Metal Panels E03.1.6. Wood Paneling E03.1.7. Rapidly-Renewable Products E03.1.8. Other
E04. Ceilings
E04.1. Ceiling Materials
E04.1.1. Exposed Framing {Roof/ Floor Structure Above) E04.1.2. Exposed Concrete E04.1.3. Grid and Acoustical Tile E04.1.4. Gypsum Board E04.1.5. Metal Panels E04.1.6. Wood E04.1.7. Rapidly-Renewable Products E04.1.8. Other
E05. Doors and Windows
E05.1. Doors and Windows and Frames Materials
E05.1.1. Aluminum E05.1.2. Hollow Metal E05.1.3. Wood E05.1.4. Other
E06. Casework Systems
E06.1. Casework Materials
E06.1.1. Plastic Laminate E06.1.2. Solid Polymer Surface E06.1.3. Rapidly-Renewable Products E06.1.4. Metal
E06.2. Countertop Materials
E06.2. l. Plastic Laminate E06.2.2. Solid Polymer Surface E06.2.3. Natural Stone E06.2.4. Cast Stone E06.2.5. Metal
E07. Furnishings
E07.1. Durability and Serviceability
E07.2. Accessories
E08. Interior Signs
E08.1 Types and Color
E08.2. Interior Signs Materials
E09. Lighting, Power and Communication
E09.1. Functionality and Efficiency
E09.2. Types and Color
F.Appendices
G. Appendices
Version 02.00.02
FA462024R0001, Amendment 0004
A.OVERVIEW
Comply with Air Force Corporate Standards for Overview:
http:/ /afcfs.wbdg.org/index.html
This Installation Facilities Standards (IFS) document is part of the Air Force Corporate Facilities Standards (AFCFS) program to assist bases in implementing and maintaining facilities standards as appropriate for efficient operations within the respective climate region. IFS fully replaces, consolidates and simplifies existing facilities standards documents, such as the Architectural Compatibility Plan (ACP) or AC Gs, FEPs, etc., and organizes information using the same structure, or Table of Contents, as the AFCFS website.
IFS reflects the AFCFS' concepts of "Facility Hierarchy" (categorizing facilities into group numbers) and "Facility Quality" (assigning an appropriate level of quality to each group number) and applies these principles at the base level. Applicable DoD and Air Force criteria such as UFCs, AFls, Memoranda, and UFGSs (Guide Specs) are referenced and linked within IFS to ensure the document is always current.
Navigating within this IFS is efficient and straightforward. Please use the interactive Table of Contents to locate subject matter, and click on the title of a section to access it. From any page, click on the "Back to Table of Contents" footer to return. Content is organized into 4 major sections: Installation Elements, Site Development, Facilities Exteriors and Facilities Interiors.
This IFS document begins as a fill-in PDF form, which is fully editable, and becomes a "living document" that can be regularly updated by base-level personnel following a format that is consistent across the Air Force. While the format is standardized, IFS content is customized for base operations and the local climate to ensure mission success while emphasizing reduced maintenance and reduced initial costs, life-cycle costs, energy use, and water use.
1. Conformance to Air Force Corporate Facilities Standards (AFCFS) and Installation Facilities Standards (IFS) are required by Air
Force Instruction (AFI) 32-1023 and Air Force Memorandum. Please refer to the AFCFS website for links to documentation on current policy.
2. The IFS is a component plan of the Installation Development Plan (IDP) per Air Force Instruction (AFI) 32-7062 (replacing the
Architectural Compatibility Plan). All military construction projects and Non-Appropriated Funds (NAF) facilities are required to comply with the IDP and its IFS component plan by AFI 32-1023. The Base Civil Engineer (BCE) maintains and implements the IDP and its component plans, to include the IFS.
3. Please refer to the AFCFS website as a portal to reference materials and requirements documents for design and construction projects (via links). Specific references to current DoD memoranda and Air Force criteria are updated periodically to provide the most current guidance and requirements. Programming, design and contract documents should list"current edition"for all reference and requirements documents. The documents in force at the date of execution of the design and/or construction contract shall be the governing version.
4. Advanced Modeling Requirements:
For all Air Force projects requiring advanced modeling, to include 30 visualization, Building Information Modeling (BIM), facility data, quantity take-off, geospatial, etc., follow the Army standards. Refer to USACE Minimum Model Matrix (M3) and Project
Execution Plan (PxP) which outline required model uses. Refer to CAD BIM Technology Center (Contract Requirements) for more information on M3 and PxP.
5. Joint Bases shall implement IFS under their Joint-Base designation with volume numbers for individual installations following the IFS Development Tool template. For example, for Joint Base Langley-Eustis, provide: Vol. 1 Langley AFB and Vol. 2 Fort Eustis.
A.01. FACILITY HIERARCHY
Comply with AF Corporate Standards for Facility Hierarchy (and subsections):
http://afcfs.wbdg.org/facility-hierarchy/index.html
A.02. FACILITY QUALITY
Comply with AF Corporate Standards for Facility Quality (and subsections):
http://afcfs.wbdg.org/facility-guality/index.html
A.03. FACILITY DISTRICTS
Comply with AF Corporate Standards for Facility Districts (and subsections):
http:// af cfs. wbd g .org/faci I ity-d istricts/i n dex.htm I
Fairchild Air Force Base IFS Page 5 of 122
FA462024R0001, Amendment 0004
Fairchild Air Force Base IFS Overview Map:
.FAIRCH]LD AFB
FACILITY DISTRICTS MAP
LEGENID
1 Basewide 2 Brown Brick
3 Flightline/lndustrial 4 Family Hous·ng1
2000 ft .... , ___ ..,.
Note: Apply the base-wide standards in this IFS for Installation Elements, Site Development, Facilities Exteriors and Facilities Interiors
(products, materials, color, etc.). Following application of the base-wide standards, refer to the Appendix and apply any additional requirements specifically related to the Facility District.
Fairchild Air Force Base IFS Page6 of 122
FA462024R0001, Amendment 0004
B. INSTALLATION ELEMENTS
Comply with Air Force Corporate Standards for Installation Elements:
http:/ /afcfs. wbdg .orq/i nsta I lation-elements/i ndex.htm I
B.01. COMPREHENSIVE PLANNING
Comply with Air Force Corporate Standards for Comprehensive Planning:
http://afcfs.wbdg.org/installation-elements/comprehensive-planninq/index.html
B01.1. Installation Development Plan (IDP)
(e Applicable r N/A Large graphics r Applicable (e N/A Small graphics
A plica ion of DoD an Air Force Facilities C iteria
DoD Criteri�
....,,.c,,.,,:,u,its<Alm!A [Ul'C), t91;HiffRf-� AHO
:Mr.!IITA.IKMJU!! 8UI.OIH<:I
Jl;l[(MMDllHH:
UFCs, Memoranda, UFGS
Air Force Criiteria
AFls, ETLs, AfCFS, Memoranda
Department of Defense, Department of the Air Force and Air Force Base Criteria
AF Base IDP
AF Base IFS
1. The Base Civil Engineer is responsible for developing, maintaining and implementing the installation's Comprehensive Planning documents and to ensure that the Installation Development Plan (IDP) is prepared, maintained, and implemented following AFI 32-7062. The base is also required to provide and maintain Installation Facilities Standards (IFS) as a Component Plan of the base's Installation Development Plan (IDP).
B01.1.1. IFS Component Plan of IDP r Applicable (e N/A Large graphics r Applicable (e N/A Small graphics
The IFS is a multipurpose tool that shall be used throughout the entire planning, programming, and design process, from inception to project completion for any project on base. While architectural designers are the primary users of the plan, it must
Fairchild Air Force Base IFS Page 7 of 122
FA462024R0001, Amendment 0004 also be used by project managers, programmers, planners, engineers, maintenance and operations personnel, self-help personnel, and the Architectural Compatibility Review Board (ACRB). Any items purchased for the exterior of buildings - including those purchased with impact cards - must conform to the requirements prescribed in the IFS.
Fairchild AFB has a foundation for architectural unity. The existing architecture depicts a predominant materials palette and a consistency of material detailing. The following design standards are applicable to the entire installation, to both host and tenant organizations.
The goal is to design excellent facilities that satisfy all of these priorities: The first priority is to achieve architectural compatibility for Fairchild Air Force Base as a whole. The second priority is compatibility within an architectural setting or sub-area.
Outstanding designs for individual buildings or facilities are the third priority.
Site planning and site development issues contribute significantly to the architectural context. Building setbacks and the scale and definition of space are as fundamental to creating architectural compatibility as consistent facade designs. Develop exterior spaces to promote pedestrian use and activity and to connect buildings and the landscape. Use the landscape with other visual elements to create greater continuity.
About the Architectural Compatibility Review Board (ACRB):
• The ACRB is the installation approval authority for all designs and visual features on the installation. Projects with design features or proposals that compete with standards or methods as prescribed by the IFS or would otherwise establish a new precedent, require ACRB approval.
• The ACRB is organized by the Base Civil Engineer (BCE).
• The chair person as appointed.
• Members include the base architects, community planner, engineering flight chief, operations flight chief, project manager, and others as determined by the chair person.
• The base architect, engineering disciplines, and project manager review designs regardless of ACRB involvement.
• The ACRB meets as required.
• Most projects, regardless of size, must be approved by the ACRB. (The chairperson makes the determination on review requirements).
• Design projects are submitted to the ACRB by the base-assigned project manager
B01.1.2. Brief History of Base r Applicable (e N/A Large graphics
(e Applicable r N/A Small graphics
The arrival of Gen. Fairchild Gen. Fairchild Portrait Unveiling Dedication Ceremony, 1951
Since 1942, Fairchild Air Force Base has been an integral part of our nation's defense strategy; first as a key WWII repair and supply depot, then as a Strategic Air Command bomber, tanker and ICBM wing during the Cold War and, finally, as an Air Mobility
Command air refueling wing supporting contingency operations around the world. Today, Fairchild's aircraft and personnel make up the backbone of the Air Force's tanker fleet on the west coast. This Center of Excellence for Air Refueling is the home of the Air
Fairchild Air Force Base IFS Page8 of 122
FA462024R0001, Amendment 0004
Force's premier tanker base and survival training school house. However, it must be noted that it was the vision of Spokane's city leaders and the support of the people of Spokane that made the base a reality.
The 92d Air Refueling Wing, the 141 st Air Refueling Wing, the 336th Training Group, and the associate units at Fairchild, and the Spokane community have forged an impressive relationship over the years. This team, "Team Fairchild," has earned a well deserved reputation for excellence. Team Fairchild will continue to meet future challenges in its usual fashion, and in so doing will preserve the legacy of excellence that began over 75 years ago by providing responsive, precise air refueling and operational support for a full range of military operations.
B01.1.3. Future Development r Applicable (i' N/A Large graphics l Applicable (i' N/A Small graphics
1. Follow AFI 32-7062 for Air Force Comprehensive Planning, the Comprehensive Planning Process, Comprehensive Planning Requirements, and Geospatial Mapping.
2. Address all future development under the Installation Development Plan (IDP).
B02. STREET ENVELOPE STANDARDS
Comply with Air Force Corporate Standards for Installation Elements:
http://afcfs.wbdg.org/i nsta I lation-elements/i ndex.htm I
Comply with AF Corporate Standards for Street Envelope Standards:
http://afcfs.wbdg.org/installation-elements/street-envelope-standards/index.html
B02.1. Hierarchy of Streets r Applicable (i' N/A Large graphics l Applicable (e' N/A Small graphics
1. Develop and evolve a hierarchical transportation network of arterial, collector and local streets following UFC 3-201-01 and its industry references.
2. Provide consistent functionality throughout the installation and a level of visual quality relating to the adjacent Facility Group number.
3. Routes along facilities in Group 1 may have materials, finishes and features with a higher visual quality than Groups 2, 3 and 4. Reduce maintenance requirements by installing highly durable materials and finishes in routes along Group 3 industrial facilities.
4. Special routes may have a visual quality comparable to those along facilities in Group 1.
5. Create and maintain arterials with two lanes of traffic in each direction with landscaped or paved medians as applicable to the local climate and adjacent facility group designation / land use.
6. Minimize stops and turns along arterials. Eliminate on-street parking along arterials and collector streets.
7. Connect arterials to local streets with appropriately scaled collector streets.
8. Provide appropriate landscape setbacks and pedestrian buffers along all streets.
9. Minimize and consolidate curb cuts along streets.
Fairchild Air Force Base IFS Page 9 of 122
FA462024R0001, Amendment 0004 l
10. Ensure access for emergency and service vehicles.
11. Define bicycle traffic routes in the Installation Development Plan or its applicable component plans.
12. Define appropriate force protection features, site furnishings, signs, lighting, utilities, and paving in the IFS.
802.1.1. Arterial Streets
(i' Applicable r NIA Large graphics
(i' Applicable r NIA Small graphics
CU BAND �
J GU R'
te} ½ l � t t
• G¥D l 'SElBACK SIDJiWAtK/ TM.Ve\. TRAVEl.. MEOl:e.N OR' TRAVFil. TRAVEL S DEWALiv' SETBACK
LANOSCA!lE LANE 1,ANE LEFT TURN LANE LANE LANE LANOSCAl>E t� (ll) (,!!J "(b,) ) (a) {di
Travel Lane {a): 12' Median {b): 12' Curb and Gutter {c): 2' Sidewalk I Landscape {d): 12') Setback {f): Min. 35' or per ATFP
UFtlOJI PAftERN, "l':AJl, COLM'f'f,lllt j,«! :,�
Paved Median
PLAM
SEOTION
ft
Primary roadways are developed as boulevards and contain two lanes of traffic in each direction often with planted medians.
Fairchild Air Force Base IFS Page 10 of 122
I
FA462024R0001, Amendment 0004
FA462024R0001, Amendment 0004
UFC 3-201-01, UFC 3-250-01
B02.1.4. Special Routes r Applicable (i' N/A Large graphics r Applicable (i' N/A Small graphics
1. Develop all special routes consistently with those adjacent to Group 1 facilities.
2. Service drives provide access for service vehicles to certain parts of a building or site.
3. Combine service drives for several facilities where possible.
4. Sidewalks can double as service drives; size and design accordingly.
5. Maintain a setback between the building and service drive.
6. Minimize the visual impact of service drives through correct placement of drives and landscape screening.
B02.2. Hierarchy of Intersections r Applicable (i' N/A Large graphics r Applicable (i' N/A Small graphics
1. Provide a hierarchy of intersections to include arterial, arterial-collector, collector, collector-local and local following UFC 3-201-01 and its industry references.
2. Passive systems such as traffic circles are preferred to active systems such as signalized intersections. Aggressively pursue passive systems to lower maintenance requirements and reduce energy use.
3. Use a level of visual quality for an intersection equal to the quality found in the related streetscape, which corresponds to the adjacent Facility Group number.
B02.2.1. Arterials r Applicable (i' N/A Large graphics r Applicable (i' N/A Small graphics
UFC 3-201-01, UFC 3-250-01
B02.2.2. Arterial/Collector r Applicable (i' N/A Large graphics r Applicable (i' N/A Small graphics
UFC 3-201-01, UFC 3-250-01
Fairchild Air Force Base IFS Page 14 of 122
FA462024R0001, Amendment 0004
B02.2.3. Collectors
(' Applicable (i' N/A Large graphics
(' Applicable (i' N/A Small graphics
UFC 3-201-01, UFC 3-250-01
B02.2.4. Special Intersections
(' Applicable (i' N/A Large graphics
(' Applicable (i' N/A Small graphics
1. Develop all special intersections consistently with those adjacent to Group 1 facilities.
B02.2.5. Street Frontage Requirements
(' Applicable (i' N/A Large graphics
(' Applicable (i' N/A Small graphics
1. Consistently maintain open space buffers following B03.2.3. Preserves.
2. Refer to C06.1.7. Streetscape Landscaping for planting and screen wall requirements along street frontage.
B02.2.6. Sight Lines
(' Applicable (i' N/A Large graphics
(' Applicable (i' N/A Small graphics
1. Provide adequate sight lines for an effective and safe traffic operation per American Association of State Highway and Transportation Officials (AASHTO) standards and local municipality guidelines.
B02.3. Street Elements
(' Applicable (i' N/A Large graphics
(' Applicable (i' N/A Small graphics
1. Emulate the streetscape area's pre-development hydrology using passive and active design features to help sustain the adjacent regionally appropriate landscape. Coordinate with the base Stormwater Management Plan.
2. Employ systems, materials and techniques to maximize streetscape sustainability. Consider pervious paving and reflectivity of surfaces appropriate for the local climate.
3. Install at-grade curbing and/or raised-profile curb and gutter as applicable to direct stormwater to bioswales and rain gardens as source water for vegetation. Do not paint concrete curbing.
Fairchild Air Force Base IFS Page 15 of 122
FA462024R0001, Amendment 0004
4. Provide all on-site utility service lines and equipment below grade when adjacent to Facility Group 1. In routes along Group 2, 3 and 4, when mounting elements such as utility cabinets, communications equipment and water valves above grade is unavoidable, paint these consistently and provide visual screening following Installation Facilities Standards (IFS).
5. Provide traffic control devices including access control point/entry control facility signs, speed limit signs and street name signs following the current edition of the Manual on Uniform Traffic Control Devices (MUTCD) per UFC 3-120-01.
6. Follow UFC 3-120-01 for directional and wayfinding signs and address both vehicular and pedestrian traffic.
7. Reduce energy consumption and reduce maintenance requirements by providing street lighting only when functionally required to ensure safety and to address antiterrorism following UFC 4-010-01. Ensure the quality and quantities of lighting and fixtures are appropriate for the adjacent Facility Group number.
B02.3.1. Paving r Applicable (i' N/A Large graphics l Applicable (i' N/A Small graphics
1. Use asphalt paving for all primary, secondary, and access roadways.
2. Use concrete paving in loading areas, dumpster enclosures, and sites used by heavy vehicles.
3. Gravel surfacing may be used on patrol roads and outlying sites only.
4. Incorporate a concrete apron where gravel roads meet paved roads.
5. All patching shall match adjacent materials.
B02.3.2. Curb and Gutter r Applicable (i' N/A Large graphics
("' Applicable (i' N/A Small graphics
1. Comply with base CE standards for all 6-inch integrated concrete curb and gutter for all roadways in developed areas.
2. Patrol roads and service drives in outlying areas may not require curb and gutter, with ACRB approval.
3. Wheel stops in lieu of curbs are not allowed.
4. Do not paint concrete curbs.
B02.3.3. Utility Service Elements
("' Applicable (i' N/A Large graphics r Applicable (i' N/A Small graphics
Fairchild Air Force Base IFS Page 16 of 122
FA462024R0001, Amendment 0004
1. Provide all utility service lines below grade; when mounting elements (such as utility cabinets, communications equipment and water valves) above grade is unavoidable, paint these consistently and provide visual screening following Site Development, Landscaping.
2. Do not cut pavements to install utilities. Avoid free standing utility structures, and use underground vaults for equipment where possible.
3. Locate fire hydrants at least 5 feet away from other structures. Maintain a 30-inch clear area. Fire Hydrants shall be painted based on flow rates.
4. Locate pad-mounted equipment in less visible areas and screen with landscaping or screen walls.
B02.3.4. Traffic Signs
(' Applicable (i' N/A Large graphics
(' Applicable (i' N/A Small graphics
1. Refer to Exterior Signs, Colors and Types for Traffic Control Devices, which includes signs.
B02.3.5. Street Lighting
(' Applicable (i' N/A Large graphics
(' Applicable (i' N/A Small graphics
1. Refer to the Lighting section for appropriate applications along streets.
B02.3.6. Other
(' Applicable (i' N/A Large graphics
(' Applicable (i' N/A Small graphics
Crosswalks and Ramps:
1. Ensure that all paths lead to the safest crossing point possible, and cross roadways at 90-degree angles.
2. Incorporate ADA accessible curb ramps and crosswalk markings into all crosswalks.
3. Crosswalks should be designated with striping.
4. Construct all concrete curb ramps with a waffle stamp pattern and flared curb ramps.
5. Provide for adequate drainage away from the ramp or by drainage grates.
UFC 3-201-01, UFC 3-250-01
B03. OPEN SPACE/ PUBLIC SPACE
Comply with Air Force Corporate Standards for Installation Elements:
http://afcfs.wbdg.org/installation-elements/index.html
Fairchild Air Force Base IFS Page 17 of 122
FA462024R0001, Amendment 0004
Comply with AF Corporate Standards for Open Space I Public Space:
http://afcfs.wbdg.org/installation-elements/open-space-public-space/index.html
B03.1. Plazas, Monuments and Static Displays
("' Applicable (i' N/A Large graphics
(i' Applicable ("' N/A Small graphics
In Memoriam Monument Cold War Memorial Flagpole Monument
1. Natural features and culturally or historically significant features or events may be recognized and acknowledged with physical elements such as plazas, monuments and static displays. However, limit these elements on the base to ensure judicious use of resources and to reduce ongoing maintenance requirements.
2. Design highly durable plazas, monuments and static displays with a level of quality comparable to Facility Group 1.
3. Link plazas, monuments and static displays to the pedestrian circulation system. Install landscaping, site furnishings and lighting appropriate for the application and local climate following Installation Facilities Standards (IFS).
4. Select systems, products and materials for paving, walls, and structures following IFS.
B03.1.1. Paved Plazas r Applicable (i' N/A Large graphics
("' Applicable (i' N/A Small graphics
1. Mitigate heat island by providing high-albedo, shaded plazas. Pervious pavers shall be used on all plazas and courtyards in Facility Groups 1 and 2 not subject to severe freeze-thaw cycles. The designer shall incorporate appropriate expansion and construction joints.
2. Use standard brick pavers or colored concrete as a unifying theme for plazas and courtyard paving. Use manufacturer standard patterns for concrete pavers.
3. Concrete may be stamped to accent the design.
Fairchild Air Force Base IFS Page 18 of 122
FA462024R0001, Amendment 0004
B03.1.2. Sculptures, Markers and Statuary r Applicable (i' N/A Large graphics l Applicable (i' N/A Small graphics
1. Relate new sculpture, markers and statuary to the base's architectural design theme. Generally limit these elements to frequently used locations adjacent to Facility Group 1 and highly traveled community pedestrian spaces.
2. Consider entry gates as possible sites for new displays.
3. All proposed memorials shall follow AFI 36-3108 and be limited to highly deserving individuals or groups as deemed appropriate by the installation leadership. Living memorials {tree plantings/ etc.) are discouraged due to added maintenance requirements.
4. When sculpture requires a base, match the materials and/ or color palette of adjacent buildings.
5. Use direct or indirect lighting to accentuate features or enhance an intended effect.
6. Ensure that all sculpture, markers and statuary are honorable and inspiring, provide a sense of place, positively contribute to the base's visual quality, and encourage pride for the community and the US Air Force.
B03.1.3. Static Display of Aircraft r Applicable (i' N/A Large graphics
(i' Applicable r N/A Small graphics
C-47D Skytrain Commemorative Plaque Various Aircraft
1. Follow IFS base-wide standards for all elements of the display area with specific attention to traffic sight lines, pedestrian circulation, site furnishings, signs, and lighting. Address requirements for the Facility District as well.
2. Generally locate concrete base/foundation structures for static displays below grade.
3. At static displays where pedestrian paths are provided, a minimum of one trash receptacle and one bench shall be provided. Receptacle and bench design must conform to IFS requirements.
Fairchild Air Force Base IFS Page 19 of 122
FA462024R0001, Amendment 0004
B03.2. Grounds and Perimeters
(i' Applicable (' N/A Small graphics
Open Green Space Park and Recreational Areas Provide areas of rest
1. Provide formal spaces for parade and review functions, recreational areas and parks following the base's Installation Development Plan (IDP) and Installation Facilities Standards (IFS). Refer to the Site Furnishings topic for additional information.
2. Maintain preservation areas following the IDP and IFS.
3. Comply with UFC 4-010-01 DoD Minimum Antiterrorism Standards for Buildings and UFC 4-022-03 Security Fences and Gates for all elements associated with the base's gates and perimeter fence.
4. Identify and describe base-wide utility corridors in the IDP.
5. Base-wide utility infrastructure shall be inconspicuous. Bury all utility service lines below grade.
6. Follow the requirements of this IFS regarding all utility structures and service lines located above grade that visually impact the installation.
7. Where screening of utility equipment and structures is provided, allow adequate and proper clearance for safety and maintenance.
8. Reduce visual clutter and visual impact of the following items through a combination of careful placement, screen walls, landscaping and painting:
• Electrical switch-stations.
• Sewage lift stations.
• Water well pumps, storage tanks and/or related structures.
• Gas piping, meters and similar incidental items.
• Above ground fuel storage tanks.
• Any ground-mounted freestanding utility item exposed to view.
9. Larger structures such as electrical switch-stations, sewage lift stations, fuel storage tanks and mechanical/electrical equipment shall be screened from view, using materials, forms, and colors in the screen walls which match those respective design elements present at adjacent buildings.
10. Paint above-ground equipment and associated components such as electrical piping or exposed plumbing lines dark bronze.
11. Maintain currently buried utility service lines as a visual asset.
Fairchild Air Force Base IFS Page 20 of 122
FA462024R0001, Amendment 0004
12. Bury the following exposed above-grade items in future projects when economically feasible:
• Electrical power grid and service lines.
• Telephone lines.
• Cable TV lines.
• Communications lines.
• Exterior lighting service lines.
• Any similar system of above-ground lines serving the base.
13. Consolidate and enclose service utility lines in underground utility corridors when feasible. Create routes along the inside edge of parking lot islands.
B03.2.1. Parade Grounds r Applicable (i' N/A Large graphics r Applicable Ci' N/A Small graphics
1. Follow UFC 3-201-02, Appendix B for the planning and design process and criteria for parade grounds.
2. Establish and maintain parade grounds only where there is a confirmed need and provide landscape materials appropriate for the locale following IFS.
3. Bleachers may be installed only when there is a documented requirement at parade grounds. Nonferrous metals that do not require painting or going maintenance are preferred. The Base Civil Engineer shall determine quantities, sizes, and products on a case basis.
B03.2.2. Parks r Applicable Ci' N/A Large graphics
(i' Applicable r NIA Small graphics
Shaded Areas for Gathering Unobstructed Pedestrian Pathways Decorative Paving
1. Bleachers may be installed only when there is a documented requirement at parks and fields for recreational events.
Follow guidance under Parade Grounds.
2. Picnic pavilions may be provided in parks where there is a documented need. Locate pavilions centrally among facilities being served to create multipurpose use.
3. Construct new pavilions with brick columns and low-sloped gable, standing seam dark brown metal roofs at high-visibility locations.
Fairchild Air Force Base IFS Page 21 of 122
FA462024R0001, Amendment 0004
4. Use manufactured pavilions in low-visibility locations with ACRB approval only.
Wood gazebos are not allowed.
803.2.3. Preserves
r Applicable (i' N/A Large graphics r Applicable (i' N/A Small graphics
1. Preserve areas adjacent to runways, taxiways, aprons, golf course roughs, storage areas, antenna facilities, and ammunition storage areas, as open space.
2. Provide minimal maintenance with mowing as needed for controlling bird behavior for airfield safety, or eliminating fire hazards.
803.2.4. Perimeter Fence
r Applicable (i' N/A Large graphics r Applicable (i' N/A Small graphics
1. Design, install and maintain the base's perimeter fence following UFC 4-022-03.
2. Perimeter fencing shall respond to the site context and use combinations of vinyl-covered chain link, decorative metal, or brick per ACRB direction.
3. Stringently comply with AT/ FP requirements following UFC 04-010-01 for all spaces adjacent to the base's perimeter fence and all gates.
4. Fencing, gates and other elements that are associated with the main gates shall be a level of quality equivalent to Facility Group 1. Wrought iron fencing may be used for high visibility sites.
5. Maintain a positive visual quality along the traffic corridor on both sides of the main gates. Specifically address pedestrian access, circulation and common areas.
6. Wood or white vinyl is allowed only in the Facility Group 4.
Fairchild Air Force Base IFS Page 22 of 122
FA462024R0001, Amendment 0004
C. SITE DEVELOPMENT
Comply with Air Force Corporate Standards for Site Development:
http://afcfs.wbdg.org/site-development/index.html
C01. SITE DESIGN
Comply with Air Force Corporate Standards for Site Development:
http://afcfs.wbdg.org/site-development/index.html
Comply with AF Corporate Standards for Site Design / NEPA:
http://afcfs.wbdg.org/site-development/site-design-nepa/index.html
C01.1. Site Design Considerations r Applicable (i' N/A Large graphics r Applicable (i' N/A Small graphics
1. Collect documentation to validate approvals and completion of the NEPA process.
2. Ensure site design compliance with the Installation Development Plan (IDP) and its component plans and Installation Facilities Standards (IFS).
3. Develop a strong relationship between buildings and exterior spaces. Articulate building facades to create areas of shade and shadow.
4. Promote integrated design with on-site solutions such as engineered small-scale hydrologic controls verses base-wide infrastructure; consider open space, natural features, bioswales, building roofs, streets, and paved surfaces.
5. Limit the impact of development on land and water resources. All site elements and infrastructure shall reinforce an image of sustainability, with reduced energy demand, renewable-energy usage, and water conservation.
6. Consider energy conservation during site design for the following categories: building and site lighting, auxiliary systems and equipment (refrigerators, elevators, etc.), building envelope, electric power and distribution, HVAC systems and equipment, service hot water, energy management (metering, EMCS).
7. Coordinate on-site renewable-energy systems and components to minimize area requirements and maximize efficiencies.
Appropriately buffer and screen these and other mechanical systems and equipment.
8. New building projects should preserve open space and protect natural habitat.
9. Conform to existing topography to the greatest extent possible and use slopes to increase site and building efficiencies.
Design sites to minimize irrigation and impacts to stormwater runoff.
10. Carefully study new project sites to identify the character of adjacent buildings, streets, landscaping, and site design elements. Reinforce the existing character in new site design.
11. Consider relationships to adjacent facilities and district / centralized heating and cooling infrastructure and cost effectively connect building systems to harvest heat, grey water or other beneficial byproducts.
12. Minimize existing and planned obstructions from landscaping, structures, topography, and adjacent developments to preserve solar access and natural ventilation.
13. Purposefully integrate service access, receiving and storage areas to eliminate the need for visual screening. Combine functions whenever possible to avoid a proliferation of small independent structures.
14. Appropriately connect to the base network of streets, sidewalks and trails using drive aisles, parking areas, walkways, paths, and bicycle routes addressing both vehicles and pedestrians.
Fairchild Air Force Base IFS Page 23 of 122
FA462024R0001, Amendment 0004
15. Applicably coordinate heat island mitigation in paving and roof designs when implementing an integrated approach to stormwater management.
16. Consider the location of "Designated Tobacco Areas."
C01.2. Building Orientation
(i' Applicable r N/A Large graphics
(i' Applicable r N/A Small graphics
ORMNG, FAClOR.S
•�--�ollllolMldl'!t; • -llio�&�-
• IWo-1-�- •$ �-"---
• �v,,�..r ,,.,.,l<?Q • �<i'll!,o'9ilio<lllc;'--_Aild>
' lflo(lho '"""'""flfi'ltlodoildbtl!!<•
•��•lll!l'�onlll
•O�.� • �,..��loff
Site Option 1
Site OptJo:n i
CONCEPTI.JAL DIAGRAM
Conceptual Site Analysis and Site Design Diagram
Local Solar Data Local Climate Data
Fairchild Air Force Base IFS Page 24 of 122
•Ovliloot·�,-�
• �.jl'� ... _,o;
Sitt Fo..-�e.s .Pi.iigr.\1"11
1111:
' !I•
�,-41,-----,ii't._,."'.:J.-w"�
Site Data
FA462024R0001, Amendment 0004
East-West Axis
� z• · � ��I
• ---- I
�--J� Optimum Solar Control Optimized Shading
1. Ensure the site will accommodate optimum requirements for building orientation, which is with the long axis parallel to the east/west direction for rectilinear CONUS buildings.
2. Meet Installation Facilities Standards (IFS) requirements for the locations of the building's passive and renewable-energy systems and exterior shading systems as applicable.
3. Locate the building(s) and permitted ancillary structures to promote solar gain, solar shading, natural ventilation, rainwater harvesting, wind buffering and other beneficial passive systems. Consider natural ventilation during the design of HVAC systems.
4. Consider relationships to adjacent sites and their facilities and infrastructure, and cost effectively integrate building systems to harvest heat, grey water or other beneficial byproducts.
5. Consider the "public side" of the building, its views and the location of the main entrance.
CO2. UTILITIES
Comply with AF Corporate Standards for Site Development:
http://afcfs.wbdg.org/site-development/index.html
Comply with AF Corporate Standards for Utilities:
http://afcfs.wbdg.org/site-development/utilities/index.html
Fairchild Air Force Base IFS Page 25 of 122
FA462024R0001, Amendment 0004
C02.1. Utility Components
(i' Applicable r N/A Small graphics
Vegetation helps break up hardscape Utility components hidden by vegetation Transformer hidden by landscape screening
1. Provide all on-site utility service lines below grade; when mounting elements (such as utility cabinets, communications equipment and water valves) above grade is unavoidable, paint these consistently with their hosting wall colors and provide visual screening following Installation Facilities Standards (IFS). Exterior surface-mounted utility con lines, or equipment are NOT allowed (except meters and control devices).
2. Provide installation of utility infrastructure to support near term and future electric vehicle charging stations.
3. Define all service entry points into the building and route distribution below grade into an interior space within the facility;
exposed conduits, cables and wires on exterior walls are not permitted for Facility Group 1.
4. Include consideration of appropriate placement of meters in support of Automated Revenue Management Services (ARMS). Locate mechanical equipment on the least public side of the building.
5. Limit exterior mechanical distribution systems such as exterior steam, chilled water, and hot water distribution to Group 3 facilities; when required for Group 1 and 2 facilities integrate with the architecture and provide visual screens following
IFS.
6. Direct roof drainage to underground collection when feasible or provide splash blocks/ paved channels to intercept roof drainage at grade.
7. In remote locations, paint freestandpipes and above-ground utility system components Spanish Moss.
8. Fire hydrants shall be painted in accordance with UFC 3-600-01.
9. Collocate coaxial and telephone extecomponents and entry points. Align all communication components with one another on the horizontal and vertical plane.
C03. PARKING AREAS
Comply with AF Corporate Standards for Site Development:
http://afcfs.wbdg.org/site-development/index.html
Comply with AF Corporate Standards for Parking Areas:
http://afcfs.wbdg.org/site-development/parking-areas/index.html
Fairchild Air Force Base IFS Page 26 of 122
FA462024R0001, Amendment 0004
C03.1. Configurations and Design r Applicable Ce N/A Large graphics
(e Applicable r NIA Small graphics
Small Lot Configuration l�H Ii lH II I! 11110 .� � \ 11, 11' ! I � 11 ! 11 Dt
S.ep.,rated ingress fe,g,ress �rives for � 20 spac.es
Large Lot Configuration Facility Group 1 Configuration
1. Evaluate adjacent sites and cost-effectively consolidate parking areas to maximize efficient use; ensure that all areas meet accessibility guidelines. Parking layout must address accessibility, maintenance, snow removal, and safety issues.
2. Generally envision on-site parking as a series of small connected singular areas selectively placed around the facility served, rather than a single large area; buffer parking areas from the facility main entrance with a transition space and provide drop-offs to decrease close-in parking. Comply with IFS standards while meeting ATFP requirements. Reduce large parking areas with landislands and planting strips.
3. Integrate at-grade and raised-profile curbing, permeable paved areas, and parking islands with the stormwater system and direct stormwater to bio-swales and rain gardens as source water for regionally appropriate native vegetation.
4. Define pedestrian access with approved hardscape and provide shading along the primary path from the parking area to the main entrance of the building.
5. Coordinate suitable landscape or barriers integrated with walls and fences to ensure adequate force protection.
6. Accessible parking spaces shall be marked according to UFC 3-120-01 and its references in ABAAS and the MUTCD. Use the 90-degree parking configuration when possible.
7. Consider locations and requirements of near term and future electric vehicle charging stations.
8. Designate preferred parking spaces for electric vehicles and carpools near the main entrance.
9. Reserved parking is discouraged except for Facility Group 1. Reserved parking shall be designated by rank or title with curb-mounted signs.
10. On-street parking is discouraged except in multi-use areas. When used, provide approved on-street parking configurations following UFC 3-201-01.
11. Access and service drives should accommodate the largest vehicle serving the facility.
C03.1.1. Paving and Striping r Applicable Ce N/A Large graphics r Applicable (e N/A Small graphics
Fairchild Air Force Base IFS Page 27 of 122
FA462024R0001, Amendment 0004
Facility Group 1 paving materials shall be as follows.
Primary: Asphaltic concrete
Secondary: Concrete
Accent: N/A
Facility Group 2 paving materials shall be as follows.
Primary: Asphaltic Concrete
Secondary: N/A
Accent: N/A
Facility Group 3 paving materials shall be as follows.
Primary: Concrete where operationally required
Secondary: Asphaltic Concrete
Accent: N/A
Facility Group 4 paving materials shall be as follows.
Primary: Concrete
Secondary: N/A
Accent: N/A
1. All new parking lots in Groups 1 and 2 shall be constructed of asphalt paving. Concrete paving shall be used in Groups 3, and where required for heavy vehicles, motorcycle parking, and where fuel spills may occur
2. Cost-effectively provide light-colored concrete to reduce heat island effect; otherwise install asphaltic concrete paving.
Dirt, gravel, and grass lots are not allowed.
3. Use consistent striping, angles and stall sizes in all parking areas.
4. All parking shall be marked with white stripes of paint or applied vinyl coatings. Red or yellow markings shall only be used for safety purposes and must be kept to a minimum. All lines shall be four inches (4") wide.
C03.1.2. Curbing r Applicable (i' N/A Large graphics
(i' Applicable r N/A Small graphics
"Rolled" Curb
Fairchild Air Force Base IFS s•
Header Cu11b
Conventional Barrier Curb
FA462024R0001, Amendment 0004
Facility Group 1 curbing/ edging materials shall be as follows.
Primary: Concrete, rolled curb
Secondary: N/A
Accent: N/A
Facility Group 2 curbing/ edging materials shall be as follows.
Primary: Concrete, rolled curb
Secondary: N/A
Accent: N/A
Basewide curbing shall consist of concrete rolled curbing.
Facility Group 3 curbing/ edging materials shall be as follows.
Primary: Concrete, rolled curb
Secondary: N/A
Accent: N/A
Facility Group 4 curbing/ edging materials shall be as follows.
Primary: Concrete, rolled curb
Secondary: N/A
Accent: N/A
1. Define all parking lots with either raised profile or at-grade curbing to promote drainage and protect paving edges. All raised curbs shall be concrete, and shall be the rolled (mountable) type. Do not paint concrete curbs.
2. Integrate curbing to direct stormwater to bioswales and rain gardens as source water for regionally appropriate native vegetation.
3. Wheel stops are not permitted except at locations where car bumpers could contact adjacent items such as poles, signs or pedestrians.
4. Asphalt curbs, wood timbers, and precast wheel stops are prohibited.
C03.1.3. Internal Islands and Medians r Applicable (i' N/A Large graphics
(i' Applicable r N/A Small graphics
Median serves as a visual break
1. Install landscape islands and medians as visual breaks, to reduce heat island effects and to accommodate bioswales and rain gardens with consideration for snow removal. Coordinate suitable landscape or barriers integrated with walls and fences to ensure adequate force protection.
2. Provide planting medians for every four rows of vehicles and paver islands for every 20 stalls. Coordinate with snow removal operations.
Fairchild Air Force Base IFS Page 29 of 122
FA462024R0001, Amendment 0004
3. When lighting is necessary, contain fixture bases within medians or internal landscape islands. Coordinate layout for light poles with the islands and minimize their number to provide the required illumination.
4. Provide designated areas for pedestrian cross traffic.
C03.2. Parking Structures r Applicable (i' N/A Large graphics r Applicable (i' N/A Small graphics
1. Parking structures are not used at Fairchild AFB due to…