TL HPGSA-PV-230-VTE-01242024v2.pdf
PDF 696 KB Posted
- Solicitation number
- FA461027R0001
About this file
This is an Exterior Pressure Vessel Inspection Report for the LOSC ISI Program, completed on 1/24/2024 by Inspector Brett Strickland (Level II) for client Call Henry Inc. The report documents inspection findings for vessel PV-230, a horizontal pressure vessel manufactured by Taylor Forge with serial number 750400-1V8, rated for 6,000 PSI maximum allowable working pressure and located at the High Pressure Gas Storage Area (HPGSA) on SLC-4 at Space X facility. The vessel stores gaseous nitrogen at temperatures ranging from -25 to 140°F.
The inspection identified multiple deficiencies requiring attention. Significant code violations include: dissimilar metals on bolt/flange assemblies (galvanized steel washers in contact with stainless steel studs and nuts), violating AFSPCMAN 91-710 11.3.1.5.6; relief valves missing system reference designators, violating AFSPCMAN 91-710 LOSC Tailored 11.2.1.7.6.7; and a missing U-bolt on the pipe support. Additional findings include moderate corrosion on the isolation valve, a 7/8-inch offset and 1.25-1.5 inch gap in concrete foundations, replacement gauges missing "No Calibration Required" stickers, relief valves outside the one-year calibration period, and vegetation growth around foundation gaps. Most vessel components including heads, shell, welds, and attachments (except bolts/flanges rated as rejectable) received acceptable or acceptable-with-reservation ratings. The report recommends corrective action for corrosion, gauge registration, vegetation removal, and continued monitoring of the foundation offset.
View the file
Other files
Show 40 more
Latest 50 of 124 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOSC ISI Program
Bld. Number
N/A
A/R/F/O
Acceptable
Acceptable
Acceptable
Acceptable
N/A
Acceptable
A/R/F/O
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
A/R/F/O
Rejectable
Acceptable
N/A
Other
Drain
Other Moderate corrosion on isolation valve, pipe support missing
No Comments
Evidence of Leakage
Dents/Deformations
Insulation/CUI
Paint
Condition of Shell No Comments
Comments
No Comments
Welds
Head to Shell Welds
No Comments
Areas of minor corrosion, chipped/cracked paint
No Comments
No Comments
No Comments
No Comments
No CommentsGrayloc Connection
Skirt/Band Welds
Additional Component Welds
Bolts/Flanges
No Comments
No Comments
Comments
Dissimilar metals
Attachments
Longitudinal Weld(s)
Nozzle Welds
Support/Saddle Welds
The vessel was located at the High Pressure Gas Storage Area (HPGSA) on SLC-4. Access must be set up in advance with the facility operator, Space X.
Previous Inspection Documentation
Manufacturer & Year Built
Taylor Forge
Inspector/Level
Brett Strickland / II
Client
Call Henry Inc.
National Board Number
N/A
MAWP Temp. Range
6,000 PSI
Vessel ID
Location/Area
SLC-4/HPGSA
Commodity
Gaseous Nitrogen
Required Equipment
Exterior Pressure Vessel Inspection Report Number: CHI-PV-230-VTE-2024
No Comments
No Comments
Date
1/24/2024
Serial Number
750400-1V8
PV-230
Vessel Type
Horizontal Pressure Vessel
Exam Type
External
Ladder, flashlight, mirror, bubble leak, picks, hammer, ruler, camera
Condition of Heads
Room Number
-25 to 140 °F
VTE: 2023
GP-R-142002 (2010)
Access Notes
Vessel Inspection
CommentsPrimary
N/A
A/R/F/O
Acceptable
Acceptable
Acceptable
Acceptable
N/A
Other
Acceptable
N/A
N/A
N/A
N/A
A/R/F/O
Other
N/A
N/A
Rejectable
Acceptable
N/A
Inspection Findings/Code Violations
No Comments
No Comments
Additional Notes/Recommendations
The vessel isolation valve has areas of moderate corrosion. This item should be addressed before the corrosion impacts the function of the valve. The gauges on the panel were replaces and no longer have "No Calibration Required" (NCR) stickers on them. As these gauges are identical and serving an identical function as the previous gauges that had NCR this item has been listed as "Other". It is still recommended that the site owner register these new gauges as NCR and affix the NCR stickers to them. There was a fair amount of vegetation growing around and in the gaps of the vessel foundations. It is recommended that this be removed and controled as plant life/growth can cause damage to foundations.
Other
There was a slight offset of 7/8" between the concrete foundations and a gap of 1.25"-1.5". It is recommended that this continue to be monitored. There was not notable change in the offset severity from the previous years inspection. The relief valves were missing system reference designators. This is a violation of AFSPCMAN 91-710 LOSC Tailored
11.2.1.7.6.7. There were dissimilar metals on the bolt\flange assemblies that were not mutually isolated from each other.
It appeared that galvanized steel washers were in contact with stainless steel studs and nuts. This is a violation of
AFSPCMAN 91-710 11.3.1.5.6. The pipe support was missing the U-bolt that supports it. The relief valves are outside the traditional one year calibration period.
Comments
Missing CNR sticker, @4,700 PSI
No Comments
No Comments
Vessel Inspection Cont. Vessel SN: 750400-1V8
Missing system designators
Comments
No Comments
No Comments
No Comments
Gauges
Sensors/Transducer
Sight Glass/Liquid Level
Relief Valve
Grounding
Anchor Bolting
Saddle/Steel Support Structure
Supports
Platforms
Grating
Handrails/Kickplates
Auxiliary Equipment
Pedestal/Grouting
Concrete Pad
Foundation
Containment
Ladders/Stairs
No Comments
No Comments
Offset/gap between foundations
No Comments
No Comments
No Comments
No Comments
No Comments
Skirts/Bands
Area Overview Vessel Overview
Nameplate Pressure Gauges/Relief Valves
External Pressure Vessel Inspection
External Photographs Vessel SN: 750400-1V8
Dissimilar Metals Corrosion on Valve
External Pressure Vessel Inspection
External Photographs Vessel SN: 750400-1V8
Offset Foundation Missing U-Bolt