TL CDRL A021 Cathodic Prot Bklet Samplev2.pdf
PDF 58 KB Posted
- Solicitation number
- FA461027R0001
About this file
This is a Contractor Data Requirements List (CDRL) sample document for cathodic protection system documentation and monitoring. The document presents a tabular inventory of cathodic protection systems protecting above-ground water storage tanks and fire water tanks at a facility. The table tracks two systems: facility 1829 (fire water tank, equipment M29LVCP001) and facility OM066 (water tank, equipment OMCLVCP430), both utilizing impressed current protection systems manufactured by COREPRO with TASCA 30-8CJ model rectifiers installed in 2008.
The monitoring data indicates specific operational parameters for each system, including rectifier voltage and amperage measurements, test potentials in millivolts DC, and system status classifications. Facility 1829 operates at normal status with a test potential of -948 mVDC, rectifier voltage of 2.6 VDC and 0.7 amperage. Facility OM066 displays a "Low Amperage" status with 0 amperage output at 2 VDC and a test potential of -975 mVDC. Both systems were last tested on December 25 with next test dates scheduled for January 2026 and February 2026 respectively. The document serves as a compliance and maintenance tracking tool for cathodic protection system performance monitoring under the identified CDRL requirement.
View the file
Other files
Show 40 more
Latest 50 of 124 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CDRL A021 Cathodic Protection Booklet- Sample
FACILITY PROTECTED ASSET
EQUIPMENT
NUMBER
SYSTEM
TYPE
MANUFACTURE
R
MODEL
SERIAL
NUMBE
R
YEAR
INSTALLE
D
LAST
TEST
DATE
NEXT TEST
DATE
RECTIFIER
VOLTAGE
(VDC)
RECTIFIER
AMPERAGE
(A)
TEST
POTENTIAL
(mVDC)
SYSTEM
STATUS
SYSTEM NOTES
ABOVE-GROUND
FIRE WATER TANK
M29LVCP001
IMPRESSED
CURRENT
COREPRO TASCA 30-8CJ C-081993 2008 Dec-25 Jan-26 2.6 0.7 -948 NORMAL
OM066
ABOVE GROUND
WATER TANK
OMCLVCP430
IMPRESSED
CURRENT
COREPRO TASCA 30-8CJ C-051226 2008 Dec-25 Feb-26 2 0 -975 Low Amperage
Page 1 CDRL A021 Cathodic Protection Booklet- Sample