Attachment_7_-_LRAFB_Architectural_Design_Guide_Supplement.pdf

PDF 905 KB Posted

Attached to
LRAFB Multiple Award Construction Contract (MACC) Federal contract opportunity
Solicitation number
FA4460-16-R-0002
Issued by
Department of the Air Force Air Mobility Command

About this file

Attachment 7 - LRAFB Architectural Design Guide Supplement dated 28 April 2016.

View the file

Other files for this federal contract opportunity

Other files attached to LRAFB Multiple Award Construction Contract (MACC), newest first.
File Type Posted
Attachment_25_-_NKAK_15-1088_Rpr_Sus_Aircraft_MX_Shop_Restroom_Bldg_364_Revised_24_June_2016.pdf PDF
Attachment_27_-_ADA_Clarification.pdf PDF
FA4460-16-R-0002-0006.pdf PDF
Attachment_26_-_08_71_00_Door_Hardware.pdf PDF
Attachment_23_-_LRAFB_MACC_Site_Visit_Questions_ _Answers.pdf PDF
FA4460-16-R-0002-0005.pdf PDF
Attachment_24_-_B-364_Floorplans.pdf PDF
FA4460-16-R-0002-0004.pdf PDF
Attachment_21_-_Solicitation_Questions_ _Answers_2.pdf PDF
Attachment_22_-_Site_Visit_Attendance_Rosters.pdf PDF
FA4460-16-R-0002-0003.pdf PDF
Attachment_20_-_Solicitation_Questions_ _Answers.pdf PDF
NKAK_15-1088_Rpr_Acft_Mx_Shop_Restroom_B-364.pdf PDF
FA4460-16-R-0002-0002.pdf PDF
Attachment_19_-_Site_Visit_Attendee_Information.xlsx XLSX spreadsheet
FA4460-16-R-0002-U0001.pdf PDF
Attachment_18_-_LRAFB_Architectural_Compatibility_Guide.pdf PDF
Attachment_6_-_Seed_Project_Package.zip ZIP file
Attachment_4_-_Past_Performance_Package.docx DOCX document
Attachment_12_-_LRAFB_Fire_Detection_and_Alarm_Systems.pdf PDF
FA4460-16-R-0002.pdf PDF
Attachment_15_-_LRAFB_Section_26_05_04_Raceways.pdf PDF
Attachment_14_-_LRAFB_Section_09_06_89_Typical_Finish_Schedule.pdf PDF
Attachment_13_-_LRAFB_Mechanical_Design_Criteria.pdf PDF
Attachment_3_-_C D_Report.doc DOC document
Attachment_5_-_Financial_Institution_Reference_Sheet.docx DOCX document
Attachment_1_-_EMIS_Instruction_Guide.doc DOC document
Attachment_8_-_LRAFB_Civil_Design_Criteria.pdf PDF
Attachment_16_-_LRAFB_Information.pdf PDF
Attachment_17_-_Scheduled_Government_Furnished_Property.pdf PDF
MACC_Statement_of_Work.pdf PDF
Attachment_2_-_Environmental_MOA.doc DOC document
Attachment_10_-_LRAFB_Computer_Telephone_Systems.pdf PDF
Attachment_11_-_LRAFB_Building_Mass_Notification_System.pdf PDF
Attachment_7_-_LRAFB_Architectural_Design_Guide_Supplement.pdf PDF
Attachment_9_-_LRAFB_Electrical_Design_Standards.pdf PDF
Show all 36

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Little Rock Air Force Base

Architectural Design Guide Supplement

28 April 2016

This document does not take the place of the Little Rock Air Force Base Architectural Design Guide, but is intended as a supplement to provide additional insight to the Architectural Requirements and standards here at Little Rock Air Force Base. Any questions concerning this document may be addressed to the Little

Rock Air Force Base Architect.

All drawings shall include a graphic scale.

All plans shall include a “North” arrow for orientation.

Install corner guards at all outside corners in all public areas. Corner guards shall be 2” x 2” on extruded aluminum bracket and shall extend from floor to ceiling similar. Corner Guards shall be Koroguard G100/G10E or approved equal.

All exposed metals shall be painted. Red Iron primer is not a finished material and is not acceptable left exposed.

All exterior downspouts shall have concrete splash blocks. Splash blocks shall meet LRAFB

Standards. The minimum shall be 185 pound, 5” x 12” x 60” ” concrete splash blocks at each downspout. Splash block may also be fiber reinforced 6” x 24” x 60”cast‐in‐place 3500 psi concrete pads.

All exterior downspouts shall have a cast iron downspout boots/shoes to protect lower portions of each down spout from grounds maintenance high speed mower impacts.

Provide prefinished metal louvers (same color as siding and/or roof) for ventilation systems sized and constructed to meet exhaust needs. Louvers shall have bird screen and insect netting.

Where pipe bollards are required, provide six inch diameter steel pipe bollards filled with concrete. If at a door location provide bollards on each side of door, inside and out.

A common problem here at LRAFB is bird nesting and insect control. Open Structures, bar joist, I beams, lintels, exposed structure, etc. is not allowed. All building structure must be wrapped in the finish materials of the proposed structure without allowing any protruding ledges that would promote bird nesting. Care should be taken to ensure that all gaps in materials are properly flashed or sealed to prevent nesting areas for insects and or birds.

All new ceiling tile shall be fine fissured, 2’ x 2’ panels, with a tegular edge. All field cuts shall be beveled and field painted to match per manufactures instructions

Cellulose/newspaper type insulation and loose fill type insulation is not acceptable.

Installing insulation on suspended ceiling tile and grid is not acceptable.

Provide all necessary blocking and backing for window blinds, curtains, toilet accessories, towel bars, robe hooks, mirrors, etc.

Provide a knock down finish, primer coat and minimum of two paint coats for areas to receive painting.

Provide a GA 214 level five finish for all areas to receive vinyl wall coverings.

All Vinyl wall covering shall be breathable and or micro‐vented to prevent the buildup of mold.

Use only adhesives that do not promote mold growth.

Provide mechanically attached room number signage and directional signage. Room number signage shall have room number and blank window for slide‐in name and unit symbol. Provide and install building signage system to include directional signage and directories.

All carpeting shall meet or exceed the requirements of the USAF Unaccompanied Housing

Design Guide, the Air Force Carpet Handbook, ETL 07‐04 and UFC 3‐120‐10. Carpeting shall be at a minimum heavy traffic/heavy wear rated carpeting. Carpeting shall also have a geometric pattern and shall be a branded fiber. Density shall be no less than 7000 average pile density. All areas with carpeting shall also have 4 inch high seamed edge carpeted wall base from matching roll stock.

Vinyl base is acceptable in areas without carpet or ceramic tile. Vinyl base shall be continuous roll stock, not 4’ lengths and shall be installed in the longest lengths possible. Piecemealing small lengths is not acceptable.

Base shall match floor unless noted otherwise. Examples: carpet floor = carpet base, VCT floor = vinyl or rubber base, CT floor = CT base, Porcelain tile = Porcelain base, Epoxy floor = epoxy base. Areas that require floors to contain spills and liquids shall have coved base.

Provide base on all gyp board wall construction.

Carpet tile is the basis for design. Broadloom shall only be installed in areas specified by the

Statement of Work. All carpet tile shall be of the non‐glue down variety. Carpe tile manufacturer’s standard method of installation shall include a non‐glue down method. Using a different manufacturer’s installation method for another manufacturer’s tile is not acceptable.

Carpet and installation method shall be by the same manufacturer.

Provide an approximately 5/16” thick, non‐skid abrasive strip, extruded aluminum stair treads, nosing and riser system. Treads, nosing’s, risers and tile, and base in matching color, pattern, and style for stairwells for a complete and uniform system. New wall base shall not be vinyl or rubber wall base in stairwells.

Provide thin set, 6” x 6” non‐skid porcelain ceramic floor tile on floor of all bathrooms, in all laundry rooms, kitchen area, lobby area, vestibules, and public restrooms and at water fountain alcove, in color groups 2 & 3.

Provide and install 6” high matching porcelain ceramic tile wall base in all areas with floor tile.

Provide 6” x 6” or 6” x 8” glazed wall tile on concrete board on all wet walls from floor to ceiling.

This is a minimum size only. Larger tiles may be used where appropriate based on room size.

When laying out tile, layout of tile shall start from the center of the room to prevent small pieces of tile at the wall.

Provide 2” – 4” wide extruded aluminum transition thresholds at all changes in floor coverings.

Transition thresholds shall be mechanically and adhesively attached. Vinyl and rubber transition strips are not acceptable.

When re‐using existing windows, install fragmentation retention film and catch bars on all exterior windows that are to remain to meet Anti‐Terrorism and Force Protection requirements, UFC 4‐010‐01 Department of Defense Minimum Antiterrorism Standards for Buildings.

All new exterior windows, doors, and storefronts shall meet the requirements of UFC 4‐010‐01

Department of Defense Minimum Antiterrorism Standards for Buildings. This includes transferring the blast loads to the building structure as needed so the window, frame, and wall remain intact in case of an explosion.

When re‐using existing door frames ‐ Provide surface preparation, welding, grinding of all steel door frames and install filler, primer and paint coats to restore all steel door frames to a like new appearance and function.

If renovating a facility and planning to re‐use the existing frames, remove all wood door frames and replace with 16 gauge welded corner steel door frames, grouted full with masonry or concrete and mechanically anchored to existing structure. Wood door frames are not acceptable and shall not be allowed to remain.

Remove all existing wood doors and replace with bonded staved solid core birch face factory finished stain grade doors.

Remove all existing hollow metal doors and replace with new 16 Gauge hot dipped galvanized and factory primed hollow metal doors. Paint as required for new finish. See Section 08 11 13

STEEL DOOR AND FRAMES.

Paint all door frames. This includes all edges, sides, and top.

Provide and install 6” high white reflective vinyl lettering above the kick plate of all fire exit doors reading “FIRE EXIT”.

All new doors, interior or exterior, shall at a minimum be a 3070 door, unless called out different in SOW.

Ensure all interior doors include the following hardware and are the same/matching throughout.

o Bonded staved solid core birch face factory finished stain grade doors. Provide rating as required.

o 5” x 20” lites where existing and/or required.

o Welded corner steel frames with silencers.

o Brushed aluminum or stainless steel kick plates.

o Ball bearing hinges.

o Curved return lever handle locksets.

o Locksets shall match the function of the room. For instance, Classroom locksets shall be installed on Classroom doors and Office locksets shall be installed on Office doors. Any variation of this shall be done only with coordination through the LRAFB Architect during the design process.

o Keyed Deadbolts on all doors with locksets.

o Card Key Access System that will work with the existing CAC Card system, with manual override on occupant rooms only. Where required.

o Wall stops.

o Adjustable force door closers.

o ICU peep viewers with covers on occupant rooms only. Where required.

o Touch‐Bar panic hardware on all egress doors.

o See also Section 08 71 00 Door Hardware.

All exterior doors shall be protected from the weather with an overhang or canopy that provides adequate protection from the weather.

Provide a concrete slab at all exterior door locations.

Provide an exterior light at all exterior door locations.

Provide solid surface Corian type window sills and stools at all windows. Solid surface material shall be burn resistant, and shall have geometric and speckled patterns to choose from.

Provide and install 2” deep solid plastic commercial vertical blinds at all windows.

CABINETRY

Provide and install a minimum 20 gauge metal stud and 5/8” gypsum board soffit above wall cabinets. Soffit shall extend above the drop ceiling.

Provide solid stain grade wood cabinetry. All base cabinets shall have solid wood stain grade toe‐kick base. 3/4” furniture grade plywood is acceptable for drawer, sides, bottoms, backs and for backs of cabinets and adjustable shelving. MDF, OSB, particle board and other similar products are not acceptable for use in cabinetry. Concealed hinges, ball bearing slides and non‐ snagging pulls shall be used for all hardware. Stain grade cabinetry grain and color shall match grain and color of birch face doors.

Provide integral coved 4” backsplash and 2” bull nose solid surface countertops with integral lavatory sinks at vanities and double bowl deep stainless steel sinks at all kitchen cabinetry.

Solid surface material shall be burn resistant, and shall have geometric, speckled and marbleized patterns to choose from.

BATHROOMS

Provide shower pan liner in all showers.

Provide pre‐cast terrazzo shower pans.

Provide 5/8” concrete board (durock) on all walls, shower ceiling and floor and sealed with

Laticrete 9235 waterproofing membrane, (“Red Guard”, “green board”, “blue board” and

“moisture resistant board” are not acceptable products).

Provide thin‐set 6” x 6”, 6” x 8” (minimum size) glazed ceramic wall tile on walls in color group 2

& 3 full height in showers and bathrooms. Shower ceiling to be ceramic tile with shower light.

Replace all water closets and flush valve assemblies with hands free operation.

Provide new commercial grade towel bars, toilet tissue dispensers, robe hooks, wash cloth holders, soap dish shelf in showers, mirrors, et cetera.

Provide temperature adjustable/control mixer valves in each shower. Provide hand held shower, slide bar and hose assembly in each shower. Plastic parts shall be limited. Majority of all parts shall be chrome plated bronze or brass.

PUBLIC RESTROOMS

Minimum requirements include toilet with seat and hands free operation flush, lavatory with hands free faucet, stainless steel mirror (one per lavatory), toilet paper dispenser (one per toilet) that allows for an 9” jumbo roll with reserve capacity, Foam soap dispenser (one per lavatory unless there are two in a room, then one dispenser per two lavatories is acceptable), a roll type paper towel dispenser (one per lavatory unless there are two in a room, then one dispenser per two lavatories is acceptable), and a stainless steel trash disposal unit. Provide ceramic tile floor and walls with a lay‐in ceiling. Wall tile on wet wall shall be on concrete board.

All toilet partitions shall be floor mounted, overhead braced, solid plastic toilet partitions with an integral continuous stop and hinge as manufactured by Hadrian Toilet Partitions, ARCH

Series, or Eclipse Partitions Privacy by Design.

All toilet paper dispensers, paper towel dispensers, and foam soap dispensers shall accept the supplies provided by the Base Custodial Contract unless specifically changed by the User. The

A/E Firm shall confirm who supplies the products with the User to ensure during the design process.

o San Jamar Simplicity or Georgia Pacific ‐ Mechanical Hands Free Dispenser.

o Foam Clean Foam Soap Dispensers.

o Bobrick B‐2892 ClassicSeries® ‐ Surface‐Mounted Twin Jumbo‐Roll Toilet Tissue

Dispenser (2 – 9” rolls with 3” cores).

LAUNDRY ROOMS – Where required.

Provide sound isolation between laundry rooms and occupant rooms. Provide washer and dryer connections in pre‐manufactured housings with no exposed plumbing.

Provide and install floor drain(s) near washers and ice machine for spill containment.

Provide curbed corner floor sink with hot and cold water. Provide mop holders above for dripping into sink.

Provide glazed ceramic wall tile on concrete board on all wet walls, floor to ceiling.

In masonry construction.

o In all occupied public areas, all exterior corners are to be bull nosed block.

o All door openings to be bull nosed block.

o All colored masonry block or brick shall have integrally colored mortar, unless noted otherwise.

All transformers, panel boxes, conduits, and electrical equipment shall be painted “Satin

Bronzetone” from Sherwin Williams ProMar Bronzetone Enamel Custom Colors, or “SW 2080

“Naturel” depending upon location. Coordinate with LRAFB Architect for correct color selection.

All exterior HVAC units, condensers, etc. shall be factory finished “Satin Bronzetone” from

Sherwin Williams ProMar Bronzetone Enamel Custom Colors, or “SW 2080 “Naturel” depending upon location. Coordinate with LRAFB Architect for correct color selection.

All exterior HVAC ducts shall be painted “Satin Bronzetone” from Sherwin Williams ProMar

Bronzetone Enamel Custom Colors, or “SW 2080 “Naturel” depending upon location. Coordinate with LRAFB Architect for correct color selection.

When any excavation takes place (trenches, utilities, etc.) ground surface is to be restored to better than original condition. Solid sod all disturbed soil and ensure that original elevations and slopes are maintained.

When placing maintenance slabs next to buildings, keep in mind grounds maintenance. If the slab does not allow room for a riding mower between the maintenance slab and building (less than 6’), or has surface mounted conduits and lines that connect it to the facility, extend the slab up to the edge of the facility.

All exterior Electrical boxes and exterior conduits shall be painted “Satin Bronzetone” from

Sherwin Williams ProMar Bronzetone Enamel Custom Colors, or “SW 2080 “Naturel” depending upon location. Coordinate with LRAFB Architect for correct color selection.

All roof top penetrations shall be painted to match the roof of the facility. Typically, this is either

“Satin Bronzetone” from Sherwin Williams ProMar Bronzetone Enamel Custom Colors, or “SW

2080 “Naturel” depending upon location. Coordinate with LRAFB Architect for correct color selection.

When using the description “Stain Grade”, it refers to the quality of the materials and the actual final finish of the materials which shall include a stained finish. Coordinate final color selection with LRAFB Architect for approval.

When interior finishes are being replaced, this shall also include counter tops and millwork finish.