This is an Instrumentation Specification document for the PIP-II F37 Low Conductivity Water (LCW) System, issued by Fermi National Accelerator Laboratory as part of the Proton Improvement Plan-II Building Infrastructure procurement package.

The specification details instrumentation and process filters required for procurement and installation in the F37 Pump Room. Equipment requirements include three Ashcroft B Series differential pressure switches (¼" FNPT, 30IW - 10 psi setpoint, epoxy coated aluminum enclosure); three Ashcroft Model 45-1127-SD-02-L-XSG-15# differential pressure gages (4-1/2" dial, 316SS, ¼" Male NPT, 0-15 psig); two Rosemount 8800 Reducer Vortex flow meters (2-inch and 6-inch models); one Rosemount 8705 flanged magnetic flow meter sensor (6-inch) with 8732E transmitter; three Metler Toledo dissolved oxygen sensors (5-1,000 ml/min sample rate, 0-10,000 ppb range); one Kodiak Controls Sure Site level transmitter (48" indication length, 4-20MA output); two Metler Toledo conductivity meters (0.02-50,000 µs/CM range); ten Noshok 100 Series pressure transmitters (0-200 psi); fifteen McMaster Carr pressure gages (0-200 PSI, 4-1/2" dial); six Reotemp RTD temperature transmitters with stainless steel thermowells; and three particulate filters (Parker 0.5-micron, Parker 20-micron, and Keckley 6-inch strainer with .125" basket). The document was initially released for review in May 2025 and issued for bid in January 2026 (Revision A). Reference documents include P&IDs (F10151066 SH01/SH02) and 2D installation drawings (F10170043).

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PIP-II F37 Low Conductivity Water (LCW) System Instrumentation Specification

Document number: ED0042584

Document Approval

Signatures Required Date Approved

Originator: Mike Hanson, Sr Fluids Engineer

Reviewer: Matt Slabaugh, BLDGI L3 Manager

Approver: Jerry Leibfritz, Linac Installation & Commissioning L2 Manager

PIP-II Template

Fermi National Accelerator Laboratory 2

Revision History

Revision Date of Release Description of Change May 2025 Initial Release for Review A January 2026 Issue for Bid

Fermi National Accelerator Laboratory 3

Table of Contents

1. Purpose

2. Acronyms ............................................................................................. Error! Bookmark not defined.

3. Reference Documents

4. Topic 1 ................................................................................................. Error! Bookmark not defined.

5. Topic 2 ................................................................................................. Error! Bookmark not defined.

6. Conclusion ........................................................................................... Error! Bookmark not defined.

Fermi National Accelerator Laboratory 4

1. Purpose

This document is part of the Proton Improvement Plan-II (PIP-II) Building Infrastructure procurement package for the Low Conductivity Water (LCW) System. It contains a detailed description of the instrumentation and process filters that will be procured and installed in the F37 Pump Room portion of the PIP-II LCW System. This document can be found in Teamcenter under #ED0042585.

2. Reference Documents

# Reference Document #

1 P&ID’s (for reference only) F10151066

SH01/SH02

2 2D installation drawings F10170043

3. Equipment Specification for Linac Gallery

Item Requirement Statement Quantity Differential Pressure Switch

• Ashcroft B Series

• Pipe Size: ¼” FNPT

• Epoxy coated aluminum enclosure

• 30IW - 10 psi setpoint

Differential Pressure Gage

• Part Number: Ashcroft Model 45-1127-SD-02-L-XSG-15#

• 4-1/2” Dial

• 316SS Process Connection

• ¼” Male NPT

• 0-15 psig gage

Flow Transmitter • ROSEMOUNT 8800 REDUCER VORTEX FLOW METER, 2 INCH

(DN50)

• Part Number 8800DR020SA1N1D1M5

Flow Transmitter • ROSEMOUNT 8800 REDUCER VORTEX FLOW METER, 6 INCH

(DN150)

• Part Number 8800DR060SA1N1D1M5

Flow Transmitter • ROSEMOUNT 8705 FLANGED MAGNETIC FLOW METER

SENSOR, 6 INCH (DN150)

• Part Number 8705TSA060C1M0

• ROSEMOUNT 8732E MAGNETIC FLOW METER TRANSMITTER

• Part Number 8732EMR1A1M4

Fermi National Accelerator Laboratory 5

Dissolved Oxygen Sensor

• Metler Toledo #58037407

• 5-1000 ml/min sample rate

• 0-10,000 ppb range

Level Transmitter • Kodiak Controls Sure Site

• Type BA connection

• Plastic Flag Material

• Stainless Housing and Float Material

• S5 Side Connection, weld neck flange

• Length of Indication – 48”

• 4-20MA signal output – loop powered

Conductivity Meter • Metler Toledo #58031404

• 1.34” Insertion Length

• 0.02 – 50,000 µs/CM

• .1 Titanium Cell Construction

Pressure Transmitter • Noshok 100 Series

• 0-200 psi

Pressure Gage • McMaster Carr Part Number 9880T23

• High-Clarity Vibration-Resistant Pressure Gauge with Seal

• Stainless Steel ¼” NPT Male Bottom Connection

• 4-1/2" Dial

• 0-200 PSI

Temperature Transmitter

• Reotemp RTD including stainless steel thermowell

• 100 ohm 3-wire with 4” dial

Particulate Filter - F1 • Parker Model #4LFE6-3-3F-SS with 0.5-micron cartridge 1 Particulate Filter – F2 • Parker FULFLO® BSSB Single Cartridge Filter Vessel, Part#

100837 with 20-micron cartridge

Particulate Filter – F3 • 6", Keckley Model SGFV, carbon steel body, single basket Strainer, with .125” basket

1. Purpose
2. Reference Documents
3. Equipment Specification for Linac Gallery