The contractor must furnish and install foundations, bases, and supports for mechanical equipment not specifically provided by other subcontractors. All concrete foundations, bases, and supports shall be reinforced concrete, while steel bases and supports must receive a prime coat of zinc chromate or red metal primer, followed by a final gray enamel coat upon completion. Concrete bases (housekeeping pads) shall be nominally 4 inches thick and extend 3 inches on all sides of equipment, or 6 inches larger than the factory base. When a base is located less than 12 inches from a wall, the base must extend to the wall to prevent dirt accumulation. The contractor shall provide all concrete materials and workmanship conforming to Portland Cement Association standards, reinforced with 6"x6", W1.4-W1.4 welded wire fabric, with concrete capable of withstanding 3,000 pounds compression per square inch at 28 days. Centrifugal pumps are identified as equipment requiring bases under this specification.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PIP-II F37 Pump Room
FOUNDATIONS, BASES, AND SUPPORTS
A. Basic Requirements:
1. Furnish and install foundations, bases, and supports (not specifically indicated on the Drawings or in the Specifications of either the General Construction or Mechanical work as provided by another subcontractor) for mechanical equipment.
2. All concrete foundations, bases and supports, shall be reinforced. All steel bases and supports shall receive a prime coat of zinc chromate or red metal primer. After completion of work, give steel supports a final coat of gray enamel.
B. Concrete Bases (Housekeeping Pads):
1. Unless shown otherwise on the drawings, concrete bases shall be nominal 4 inches thick and shall extend 3 inches on all sides of the equipment (6 inches larger than factory base).
2. Where a base is less than 12 inches from a wall, extend the base to the wall to prevent a “dirt-trap”.
3. Concrete materials and workmanship required for the subcontractor's work shall be provided by him. Materials and workmanship shall conform to the applicable standards of the Portland Cement Association.
Reinforce with 6”x6”, W1.4-W1.4 welded wire fabric. Concrete shall withstand 3,000 pounds compression per square inch at 28 days.
4. Equipment requiring bases is as follows:
a. Centrifugal Pumps