EAGLE_SPRINGS_OWNER_REVIEW_05.17.23.pdf
PDF 11 MB Posted
- Attached to
- ESGC Phase One Maintenance Building
- Solicitation number
- 25-19
- Issued by
- Walton County, Florida
About this file
The document is a comprehensive architectural and engineering design set for the Eagle Springs Golf Course Maintenance Building project in Walton County, Florida, prepared by Russell Johnson Architect and various consulting engineering firms. The project involves constructing a 9,600 square foot pre-engineered metal maintenance building with office spaces, equipment storage areas, restrooms, and support facilities. The design documents include detailed architectural plans, structural specifications, mechanical and HVAC layouts, plumbing schematics, and electrical system designs, adhering to the 2020 Florida Building Code and other relevant local and state regulations.
The project is designed as a single-story structure with specific attention to wind resistance (designed for 137 mph wind velocity), energy efficiency, and accessibility standards. The building will feature metal panel exteriors in light and dark grey, impact-rated windows and doors, and interior spaces with vinyl composition tile flooring and painted gypsum board walls. The design includes optional pricing for exterior metal panels, storage area floor finishes, and 8-foot high metal interior panels. The total occupant load is estimated at 39 people, with spaces for business and storage occupancies, and the design allows for potential future fire sprinkler system installation based on the Authority Having Jurisdiction's requirements.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A R
C H
IT
E C T U
E r a ja r c h m s n .c o m
R U S S E L L J
O H N S O N
C H
IT
E C T
P L
A - 100
PERFORMANCE STANDARDS
OUTSIDE DIAMETER
ON CENTER(S)OC
OD
GENERAL NOTES
FE
FDNAT
ACT
ACOUSTICAL TILEPLYWOODEARTH
MATERIAL SYMBOLS ABBREVIATIONS
FIRE EXTINGUISHER
FOUNDATION
SYMBOL LEGEND
SHOP DRAWINGS
EAGLE SPRINGS GOLF COURSE
NOTE:
RISER/RADIUS
ROOF DRAIN
CONTRACTOR ROUGH IN
OWNER FURNISHED
OWNER INSTALLED
OWNER FURNISHED
PLASTIC LAMINATE
PRESSURE TREATED
QUARRY TILE
OPPOSITE HAND
PAIR
OPPOSITE
PLATE
OVERHEAD
RD
R
OPH
QT
PT
PR
PL
OPP
OH
OFOI
PLAM
OFCRI
REVISE(SION)(D)
ROUGH OPENING
STAINLESS STEEL
SPECIFICATION(S)
SOLID CORE
STRUCTURAL
REINFORCE(D)(ING)
SYSTEM
ROOM
SIMILAR
SECTION
SQUARE
SOUTH
REQUIRED
RESILIENT
RECESSED
SS
SYS
RM
SQ
SIM
SECT
SC
S
RO
RES
REV
REQ
REC
STRUCT
SPEC
REINF
CONTRACTOR INSTALLED
THICK(NESS)
VINYL WALL COVERING
VENT THRU ROOF
WEST/WIDTH
WORK POINT
WITH
WITHOUT
VERTICAL
UNDERCUT
TOP OF
TYPICAL
W/
WPT
W/0
W
VCT
VTR
VWC
VERT
UON
UC
UL
TYP
TO
THK
UNDERWRITERS LABORATORY
UNLESS OTHERWISE NOTED
VINYL COMPOSITION TILE
T TREAD
HDW
HM
FTG
GWB
HA
GYP
GALV
GA
GL
FIXT
FO
FT
FL
FHC
FIN
FF
BRICKBRK
BUR
CEM PL
BOARD
BITUMINOUS
BUILDING
BLOCK
BLOCKING
BEAM
BOTTOM
BEARING
BLK
BLKG
BOT
BRG
BM
BLDG
BIT
BD
APPROXIMATE
AHU
APPROX
ARCH
AFF
AE
BUILT UP ROOFING
CEMENT PLASTER
ARCHITECT-ENGINEER
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
ARCHITECT(URAL)
HOUR
HVAC
HR
HT
MAX
LF
LAV
INSUL
INT
L
JT
IN
ID
JOINT
INCH
CT CERAMIC TILE
DETAIL
DEMO
DF
DET
CEILING
COLUMN
CONCRETE
CONTINUE(OUS)
CARPET(ED)
CONFERENCE
CENTER LINE
CONC
CONT
CPT
CONF
CMU
COL
CLG
CL
CHEMICAL
CFCI
CHEM
CJ
CONSTRUCTION JOINT
DRINKING FOUNTAIN
CONCRETE MASONRY UNIT
DEMOLISH(TION)
CONTRACTOR INSTALLED
CONTRACTOR FURNISHED
CONTROL JOINT/
BATT INSULATION
LATH
GWB/PLASTER/
STUCCO/GROUT
ACOUSTICAL OR
CERAMIC TILE
RIGID INSULATION
FIRE SAFING/
COMP FILLER
SCALE: 1"=1'-0"
DETAIL
BIT DAMPROOFING
BUILDING SECTION
DETAIL TITLE
NO
NTS
NOM
NIC
NA
N
MFR
MISC
MIN
MET
DR DOOR
EQUAL
EXISTING
EXPOSED
EQUIPMENT
EXP
EWC
EXIST
EQUIP
EQ
EAST
EACH
ELEVATION
ELECTRIC(AL)
ELEVATOR
DRAWING(S)
EA
ELEC
ELEV
EL
EJ
DWG
E
DIMENSION
DIVISION
DOWN
DIV
DN
DIM
ELECTRIC WATER COOLER
EXPANSION JOINT
EXTERIOREXT
INTERIOR
ELEVATION
FINISH FLOOR
ELEVATION
COLUMN REFERENCE
AND GRID LINES
2 A
12'-4"
SECTION CUTS
DIAMETERDIA MECH
ROUGH WOOD
(CONTINUOUS)
MASONRY UNIT
FINISHED WOOD
BRICK
CONCRETE
CONCRETE
GRANULAR FILL
A5.1
SHEET REFERENCE
SECTION NUMBER
A8.1
SHEET REFERENCE
DETAIL NUMBER
(NOT CONTINUOUS)
ROUGH WOOD
DOOR MARK
A9.1
SHEET REFERENCE
SECTION NUMBER
W3
B
NUMB
NAME ROOM NAME
WALL TYPE MARK
WINDOW MARK
ROOM NUMBER
GENERAL SYMBOLS
HARDWARE
HEATING, VENTILATING AND
HEIGHT/HIGH
AIR CONDITIONING
HOLLOW METAL
FIRE HOSE CABINET
GYPSUM WALL BOARD
HANDICAP ACCESSIBLE
FOOTING
GAGE/GAUGE
GALVANIZED
GLASS/GLAZING
GYPSUM
FINISHED FLOOR
FINISH(ED)
FIXTURE
FACE OF
FOOT/FEET
FLOOR
NOT TO SCALE
NOT IN CONTRACT
NOT APPLICABLE
MISCELLANEOUS
MANUFACTURE(R)
MECHANIC(AL)
LINEAL FEET
INSULATE(D)(ION)
INSIDE DIAMETER
NUMBER
NOMINAL
NORTH
METAL
MINIMUM
MAXIMUM
LAVATORY
INTERIOR
LENGTH
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE CODES
REFERENCED IN THESE DOCUMENTS AND AS ADPOTED AND
SUPPLEMENTED BY LOCAL REGULATIONS.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ACQUIRING
ALL BUILDING PERMITS FROM THE LOCAL BUILDING
DEPARTMENTS AS REQUIRED BY CITY/COUNTY REGULATIONS.
FEES FOR SUCH PERMITS SHALL BE PAID BY THE
CONTRACTOR AND A SET OF APPROVED DRAWINGS AND
ORIGINAL PERMITS SHALL BE RETAINED ON SITE FOR THE
DURATION OF THE PROJECT.
3. THE DESIGN INFORMATION SHOWN ON THE DRAWINGS
PROVIDES OVERALL DIMENSIONAL PARAMETERS AND
DESCRIBES ELEMENTS TO BE CONSTRUCTED. THE
CONTRACTOR SHALL ADJUST DIMENSIONS AND DETAILS AS
REQUIRED TO FIT EXISTING CONDITIONS. THE
ARCHITECT/ENGINEER SHALL BE NOTIFIED OF ALL PROPOSED
MODIFICATIONS.
4. NO CHANGES TO THE INFORMATION SHOWN ON THE
DRAWINGS SHALL BE MADE WITHOUT THE SPECIFIC WRITTEN
APPROVAL OF THE ARCHITECT OR ENGINEER, AS
APPICABLE.
5. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ANY
DISCREPANCIES ON THESE DOCUMENTS.
6. ALL EXTERIOR COMPONENTS SHALL HAVE FLORIDA
APPROVAL NUMBERS.
7. EXTERIOR GLAZING SHALL BE IMPACT RATED.
PROVIDE OPtional price for non-impact rated.
8. exterior doors shall be impact rated. provide optional price for non-impact rated.
9. FIRE SPINKLER / FIRE ALARM if required shall be
DESIGNed BY OTHERS AS REQUIRED TO MEET FBC 2020, NFPA, & FLORIDA FIRE PREVENTION CODE.
COPIES OF ALL SHOP DRAWINGS FOR STRUCTURAL OR LIFE
SAFETY RELATED COMPONENTS SHALL BE SUBMITTED TO THE
ARCHITECT & OWNER FOR APPROVAL..
THE CONTRACTOR SHALL SUBMIT DETAILED FABRICATION AND
INSTALLATION DRAWINGS AND PRODUCT LITERATURE FOR THE
FOLLOWING ITEMS. ARCHITECT REVIEW OF SHOP DRAWING IS FOR
COMPLIANCE OF THE PRODUCT WITH THE DESIGN CONCEPTS
DELINEATED IN THESE DOCUMENTS. THE CONTRACTOR AND/OR
PRODUCT MANUFACTURER SHALL BE RESPONSIBLE FOR THE
ACCURACY AND PERFORMANCE OF THE PRODUCT AND ITS
COORDINATION WITH THE OTHER TRADES.
1. STRUCTURAL STEEL
2. METAL STUD FRAMING
3. ROOF TRUSSES, LVL, & PRE-ENGINEERED BEAMS
4. REINFORCING STEEL
5. CONCRETE DESIGN MIXES
6. WATERPROOF MEMBRANES
7. RAILINGS & HANDRAILS
8. ARCHITECTURAL PRE-CAST OR PRE-FORMED COLUMNS
9. APPLIED FOAM TRIM, WINDOW/DOOR HEADS, AND
ARCHITECTURAL DETAILING
10. BATHROOM ACCESSOIRES & MIRRORS
11. ALL FOOR, WALL , AND CEILING FINISHES
12. ALL CABINETRY
13. ELEVATORS
14. STAIRS AND HANDRAILS
15. ALL HEATING & VENTILATING EQUIPMENT
16. ELECTRICAL FIXTURES & EQUIPMENT
17. ALL PLUBMING FIXTURES
18. DOORS, WINDOWS, AND ALL HARDWARE
19. FIREPLACES
20. APPLIANCES
ALL MATERIALS, PRODUCTS AND THEIR INSTALLAITON SHALL MEET THE
PRODUCT APPROVAL OF AND BE INSTALLED IN ACCORDANCE WITH THE
STANDARDS ESTABLISHED BY THE FOLLOWING AGENCIES, AS APPICALBE:
ASTM AMERCIAN SOCIETY OF TESTING MATERIALS
ACI - AMERICAN CONCRETE INSTITUE
AF&PA - AMERICAN FOREST & PAPER ASSSOCIATION
AISC - AMERICAN INSTITURE OF STEEL CONSTRUCTION
AWI - AMERICAN WOODWORK INSTITUTE
AWPB - AMERICAN WOOD PERSERVATIVES BUREAU
ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE
AAMA - ARCHITECTURAL ALUMINUM MANUFACTURE'RS ASSOCIATION
FBC - FLORIDA BUILDING CODE
GA - GYPSUM ASSOCIATION
LSC - LIFE SAFETY CODE
NER - NATIONAL EVALUATION SERVICE INC
NFPA - NATIONAL FIRE RPOTECTION ASSOCIATION
NDW - NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION
OSHA - OCCKUPATIONAL SAFETY AND HEALTH ACT
SJI - STEEL JOIST INSTITUE
TCA - TILE COUNCIL OF AMERICA
UL - UNERWRITERS LABORATORIES
FIRE EXTINGUISHER CABINETFEC OWNER FURNISHEDOFCIAREA DRAINAD
ARCHITECT NOT RESPSONIBLE FOR ANY CIVIL WORK, SITE WORK,
LANDSCAPE DESIGN, FIRE SUPPRESSION SYSTEMS, OR ANY
OTHER WORK NOT SPECIFICALLY ADDRESSED BY THESE
DOCUMENTS.
OWNER REVIEW
05.17.23
METAL BUILDING - EQUIPMENT STORAGE AND OFFICE SPACE
THIS PROJECT IS A PRE-FAB METAL BUILDING. COORDINATE ALL
DIMENSIONS WITH METAL BUILDING SHOP DRAWINGS. PROVIDE
FULL SHOP DRAWINGS SIGNED AND SEALED BY AN ENGINEER
REGISTERED IN THE STATE OF FLORIDA.
provide full shop drawings with all loading and reactions to structural engineer for foundation design verification prior to any construction activity.
WALTON COUNTY FLORIDA
TOTAL SF = 9.600 SF
e a g l e s p r in g s g o l f c o u r s e m a in t e n a n c e b u il d in g w a l t o n c o u n t y f l o r id a
MAINTENANCE BUILDING
BUILDING DESIGN DATA
APPLICABLE CODES
INDEX OF DRAWINGS
MAIN BUILDING
A100 COVER
A101 FLOOR PLAN
A102 ELEVATIONS
A103 ELEVATIONS
A104 BUILDING SECTION
A105 ENLARGED BATHROOMS
STRUCTURAL DRAWINGS
S001 SPECIFICATIONS / NOTES
S101 FOUNDATION PLAN
S501 DETAILS
MECHANICAL / PLUMBING
M001 SCHEDULES
M100 HVAC PLAN
M101 HVAC DETAILS
M102 HVAC DETAILS
P001 NOTES AND DETAILS
P100 BELOW FLOOR SANITARY
P101 ABOVE FLOOR PLUMBING PLAN
P102 PARTIAL PLUMBING PLAN
P103 SANITARY SEWER RISER
ELECTRICAL ENGINEERING
E100 ELECTRICAL NOTES
E101 NOTES
E1002 ELECTRICAL PLANS
2020 florida building code, building, 7th edition
2020 florida building code, accessibility, 7th edition
2020 florida building code, energy conservation, 7th edition
2020 florida building code, plumbing, 7th edition
2020 florida building code, mechanical, 7th edtion, 2020 florida builidng code, fuel gas, 7th edition florida fire prevention code national electrical code 2017 nfpa 101 life safety code 2020 w/ amendments florida statutes florida administrative code refer to other drawings for other applicable codes
PROJECT DATA
RUSSELL JOHNSON, ARCHITECT
P.O. BOX 1399
(850) 630.4483
AR 0012593
PANAMA CITY, FL. 32401
APEX ENGINEERING GROUP, PLLC
78-A RICKER AVENUE
(850) 231.4540
SANTA ROSA BEACH, FL 32459
rajarch@msn.com www.apexengineeringgroup.net
WELCON ELECTRICAL CONSULTANTS , PLLC
14116 CUSTOMS BLVD, SUITE #111
(228).822.8000
GULFPORT, MS 39503
STEPHENS MECHANICAL ENG, LLC
925 TOMMY MUNRO DR
BILOXI, MS 39532
SUITE B
(228) 207-3322
1. FIRE EXTINGUISHER NOTES:
1.1. THE LOCATION, SIZE, AND CLASS OF FIRE EXTINGUISHERS SHALL BE DETERMINED
PER NFPA REQUIREMENTS BY THE FIRE EXTINGUISHER SUPPLIER AND AS
APPROVED BY THE FIRE MARSHALL / INSPECTOR.
1.2. THE INSTALLATION OF THE PORTABLE FIRE EXTINGUISHERS SHALL BE PER A FIRE
PROTECTION CONTRACTOR IN CONJUNCTION WITH THE GENERAL CONTRACTOR.
1.3. SUBMIT FIRE EXTINGUISHER LAYOUT, SIZE, AND CLASS TO THE APPROPRIATE FIRE
MARSHALL / INSPECTOR FOR REVIEW AND APPROVAL INDICATING THE FIRE
EXTINGUISHER HAZARD CLASSIFICATIONS, SIZES, PLACEMENTS AND TRAVEL
DISTANCES PRIOR TO INSTALLATION.
occupant loads:
business occupancy = 1,920 sf / 150 sf / occ = 13 occ.
storage s2 occ. = 7,680 sf / 300 sf/occ = 26 occ total occupant load = 39 occ.
fire sprinkler note: based on the allowable area for non-sprinklered s2 occupancy ( 13,500 sf allowed), a fire sprinkler system is not required. however, the ahj, authority having jurisdiction, may require a fire sprinkler system/alarm based on the actual storage materials and equipment that the owner places in the storage area. contractor shall coordinate fire sprinkler requirements w/ the owner and ahj. if a fire sprinkler/alarm is required, it shall be designed by others and shall meet the requirements of fbc 2020, nfpa codes, and the florida fire prevention code.
options for pricing:
Contractors shall provide optional pricing as follows:
1. exterior metal panels as indicated on elevations
2. storage area floor finishes as indicated on finish schedule
3. STORAGE AREA - 8 FT HIGH METAL INTERIOR PANELS.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT #
AutoCAD SHX Text
REVIEWED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
ARCHITECT
AutoCAD SHX Text
STRUCTURAL ENGINEER
AutoCAD SHX Text
ELECTRICAL ENGINEER
AutoCAD SHX Text
MECHANICAL ENGINEER
MEN
WOMEN
120'-0" equipment storage supervisor assistant break ROOM mechanic grinder & office parts ROOM office office
24'-0" 24'-0" 24'-0" 24'-0" 24'-0"
120'-0"
17'-0" 8'-4"
16'-0" 22'-11" 7'-6" 11'-11" 17'-4" foyer
A R
C H
IT
E C T U ja r c h m s n .c o m
R U S S E L L J
O H N S
C H
IT
E
A - 101 e a g l e s p r in g s g o l f c o u r s e
FLOOR PLAN
SCALE: 3/16" = 1'-0"
m a in t e n a n c e b u il d in g w a l t o n c o u n t y f l o r id a
D1 W1 D2 D1D2W1 W1
W1
D2
D2
W1
D1
D1D1 W1W1W1W1W1W1
W1
D1
W1
D2
D2
12'-0" 7'-4" 16'-8" 22'-0" 3'-6" 12'-10" 25'-6" 8'-2" 12'-0"
7'-6" 4'-6" 24'-0" 24'-0" 24'-0" 24'-0" 4'-6" 7'-6"
D3 D3 D3 D3 D3
D4
D4
D5 D5 D5
D5
D6
D6
D4
D7 bathroom restroom restroom bathroom bathroom closet
2'-2"
2' -4
/8
7' -8
/4
2'-2"
7'-9"
2'-6"
/2
/4
/4
UL 419 2 HRUL 419 2 HRUL 419 2 HR UL 419 2 HRUL 419 2 HRUL 419 2 HR
7' -6
/8
/8
7' -4
/1
1/
36 X 36
ADA SHWR
36 X 36
ADA SHWR
ADA DF
mechanical
2'-4 3/4" 7'-9"
8'-9 3/4"
UL 419 2 HR
D3
D8
REFRIG
SINK
ICE
MACHINEMW
indicates 2 hr wall assembly ul 419 or approved equal ada threshold ada threshold ada threshold ada thresholdada threshold ada threshold mop sink - provide s.s. mop and broom wall mounted holders cl of door /window typical steel frame by pemb -typical all locations interior walls to be 3 5/8" metal studs @ 16" oc w/ 5/8" painted gyp bd each side. stud ga and blocking per manufacturer's requirements.
provide 3" batt insulation for bathrooms and mechanical spaces
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT #
AutoCAD SHX Text
REVIEWED
DATE
C H
IT
E C T U ja r c h m s n .c o m
R U S S E L L J
O H N S
C H
IT
E
A - 102 e a g l e s p r in g s g o l f c o u r s e elevations
SCALE: 3/16" = 1'-0"
m a in t e n a n c e b u il d in g w a l t o n c o u n t y f l o r id a
GUTTER, DOWNSPOUT - WHITE, & CONC. SPLASHBLOCK
front elevation right side elevation
METAL ROOF PANELS BY PEMB, LIGHT GREY COLORC
D
A TYPE 1, DARK GREY COLOR, PEMB METAL WALL PANELS
TYPE 2, LIGHT GREY COLOR, PEMB METAL WALL PANELS
D
C
D
A
H METAL TRIM BAND - WHITE, BY PEMB
GUTTER WHITEG
GGGGGG
H
G
7' -6
D1
D2
D3
D4
D5
D6
D7
D8
METAL ROOF PANELS BY PEMB, LIGHT GREY COLOR
TYPE 2, LIGHT GREY COLOR, PEMB METAL WALL PANELS
METAL ROOF PANELS BY PEMB, LIGHT GREY COLORC
GUTTER WHITE
TYPE 2, LIGHT GREY COLOR, PEMB METAL WALL PANELS
METAL TRIM BAND - WHITE, BY PEMB
TYPE 1, DARK GREY COLOR, PEMB METAL WALL PANELS
GUTTER, DOWNSPOUT - WHITE, & CONC. SPLASHBLOCKG
Q Q
METAL ROOF FASCIA BY PEMB, WHITE
METAL ROOF FASCIA BY PEMB, WHITE
METAL DOOR & TRIM - WHITE, TYPICAL
WINDOW TRIM - WHITE, TYPICAL
OH DOOR & TRIM - WHITE, TYPICAL
METAL ROOF FASCIA BY PEMB, WHITE
3.75
1.63
LEGEND
TYPE 1, COLOR 1, PEMB METAL WALL PANELS
STEEL PEMB FRAME
METAL ROOF PANELS BY PEMB
TYPE 2, COLOR 2, PEMB METAL WALL PANELS
PEMB Z-GIRTS
IN COMPLIANCE W/ FBC ENERGY CODE -
GUTTER, DOWNSPOUT, & CONC. SPLASHBLOCK
METAL TRIM BAND / FLASHING BY PEMB
INTERIOR FINISH - COORDINATE W/ OWNER
CEILING - 5/8" TYPE X PAINTED GYP BD, COORDINATE W/ OWNER
CONCRETE FOUNDATION - REFER TO STRUCTURAL
3-5/8" METAL STUDS (6" @ PLUMBING WALLS IF REQUIRED)
CONCRETE FLOOR SLAB - REFER TO STRUCTURAL, PROVIDE VAPOR BARRIER
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
@ 16" OC W/ 5/8" TYPE X PAINTED GYP BD
SHOP DRAWINGS FROM THE METAL STUD MANUFACTURER
METAL STUD GAUGE, BRACING, ETC SHALL BE PER SIGNED AND SEALED
8 FT H METAL PANELS BY PEMB IN STORAGE AREA
5/8" PAINTED GYP BOARD OTHER SPACES
BUILDING SIGNAGE PER OWNER'S SPECIFICATIONS
R
WALL INSULATION W/ VAPOR RETARDER -
4" VINYL BASE ALL SPACES - EXCEPT STORAGE AREA
VINYL FLOOR TILE ALL SPACES EXCEPT STORAGE AREA
PROVIDE 3.5" BATT INSULATION ALL INTERIOR WALLS THAT ABUTT THE
MAIN STORAGE AREA AND ALL MECHANICAL AND BATHROOMS.
ON 6" 18 GA CEILING JOISTS @ 16" OC.
IN COMPLIANCE W/ FBC ENERGY CODE -
ROOF INSULATION W/ VAPOR RETARDER -
PROVIDE 2 HOUR WALL ASSEMBLY WHERE INDICATED ON PLAN
PROVIDE UL APPROVED FIRE CAULKING SYSTEM MATCHING FIRE RATING
OF WALL @ STEEL BEAM PENETRATIONS
LOUVERS - COORDINATE W/ MECHANICAL DRAWINGS
TYPICAL ALL SPACES EXCEPT MAIN STORAGE AREA
PROVIDE UL APPROVED 2HR ASSEMBLY UL I 506 OR APPROVED EQUAL
(2) LAYERS 5/8" TYPE ULIX GYP BD, LOOSELY LAID ON TOP OF MIN 6" D
STEEL JOISTS @16" OC AND (3) LAYERS TYPE ULIX GYP BD ATTACHED
TO THE BOTTOM OF THE STEEL CEILING JOISTS.
BASE - EQUAL TO MERCER #207 4" VINYL
INTERIOR WALLS -
OFFICES / BREAK ROOMS / RESTROOMS ETC. PAINTED GYP BD, PRIME COAT, (2)
COATS OF FINISH, COLOR PER OWNER, EPOXY PAINT IN RESTROOMS, MECH
SPACES, AND SURFACES EXPOSED TO STORAGE AREA
STORAGE AREA - 8 FT HIGH METAL PANELS BY PEMB MANUFACTURER - OPTIONAL
PRICE TO DELETE FOR OWNER COORDINATION
EXPOSED METAL FRAMES TO BE PAINTED AFTER REMOVING ALL RUST - USE
PRIMER AND PAINT DESIGNED FOR METAL - SUBMIT PAINT TO OWNER FOR
APPROVAL
INTERIOR DOOR FRAMES TO RECEIVE TNEMEC "GRAY COURT" #GR22.
STORAGE AREA FLOORS - PROVIDE OPTIONAL PRICES FOR:
1. SEALED CONCRETE W/ A NON-SLIP FINISH
2. PRIME COAT TNEMEC 201 PRIMER - 6-8 MILS
SECOND COAT TNEMEC 281 COAT - 8-12 MILS
TOP COAT TNEMEC 248 TOP COAT - 2-3 MILS
APPROVED EQUALS ARE ACCEPTABLE, COORDINATE WITH OWNER
CEILINGS - PAINTED GYP BD, 1 COAT PRIMER 2 COATS FINISH (EXCEPT
STORAGE AREA)
FINISH SCHEDULE
NOTE: FINISHES SHALL BE COORDINATED WITH OWNER
PRIOR TO PURCHASING AND CONSTRUCTION. SUBMIT
SAMPLES FOR OWNER APPROVAL.
EQUAL TO AZROCK V783
NOTE: PROVIDE 3" SOUND BATT IN BATHROOM AND
MECHANICAL ROOM WALLS.
FLOORING - (OFFICES, BREAK ROOM, BATHROOMS, HALLWAY, ETC) VINYL COMPOSITION TILE
room finish notes:
1. all floor finishes shall be in compiance w/ fbc accessibility chapter 3. exposed / polished concrete shall have slip-resistant finishes in compliance w/ fbc accessibility and the concrete polishing council. all flooring shall meet or exceed the floor dynamic coefficient of friction (dcof) as per accessibility codes for non-slip / slip resistant standards.
2. all gyp bd shall be 5/8" min. thickness. all exposed gyp bd shall be painted. moisture resistant gyp bd shall be "proroc" by certaineed or approved equal. FOR ALL MOISTURE RESISTANT CEILINGS, provide 2 x blocking @ 12" oc e.W.
3. INTERIOR WALLS AND CEILINGS IN THE RESTROOMS SHALL BE PAINTED AS FOLLOWS:
3.1 PRIMER: TNEMEC SERIES 151 ELASTO-GRIP FC APPLIED @ 1.0 MIL DRY FILM THICKNESS INTERMEDIATE: TNEMEC SERIES 113 TNEME-TUFCOAT APPLIED @ 4.0-6.0 MIL DRY FILM THICKNESS
FINISH: TNEMEC SERIES 113 TNEME-TUFCOAT APPLIED @ 4.0-6.0 MIL DRY FILM THICKNESS
4. CHANGES IN LEVEL: ALL FLOOR CHANGES IN LEVEL SHALL MEET FBC 2020 ACCESSIBILITY CODE. VERTICAL CHANGES IN LEVEL BETWEEN
1/4" HIGH MAX ARE PERMITTED TO BE VERTICAL . CHANGES IN LEVEL BETWEEN 1/4" HIGH AND 1/2" HIGH MAX SHALL BE BEVELED WITH A
SLOPE NOT STEEPER THAN 1:2 CHANGES IN LEVEL GREATER THAN 1/2" HIGH SHALL BE RAMPED AND SHALL COMPLY W/ SECTIONS 405 & 406.
DESCRIPTIONCODE
WINDOW SCHEDULE
3'-4" W X 4'-8" H IMPACT RATED WINDOW
NOTE: THE BASIS OF DESIGN FOR THE WINDOWS SHALL BE
"KAWNEER" NX3800, W/ THERMAL BREAK, ARGON GAS,
SOLAR BAN 70, AND AN .09 INNER LAYER. THE FRAME SHALL
ALUMINUM - FRAME COLOR AS SELECTED BY OWNER FROM
MANUFACTURER'S STANDARD COLORS. APPROVED EQUALS
ARE ACCEPTED IF APPROVED BY OWNER DURING BIDDING.
W1
NOTE: PROVIDE OWNER WITH AN OPTIONAL PRICE TO
REPLACE TYPE 1 PEMB WALL PANEL WITH A CONTINUATION
OF TYPE 2 PEMB WALL PANEL AND DELETE TRIM BAND H
EXTERIOR METAL WALL PANELS
O
12" H X 8 ' L ALUM BACKING W/ 8" H ALUM LETTERS
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT #
AutoCAD SHX Text
REVIEWED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
DOOR SCHEDULE
AutoCAD SHX Text
OFFICE DOOR, INTERIOR
AutoCAD SHX Text
RESTROOM DOOR
AutoCAD SHX Text
W/ CLOSERS & ADA COMPLIANT LOCKSETS/HANDLES
AutoCAD SHX Text
PAINTED METAL, HM FRAME
AutoCAD SHX Text 3-0 W, 6-8 H
AutoCAD SHX Text
PAINTED GALV STEEL, HM FRAME
AutoCAD SHX Text
EXTERIOR DOOR
AutoCAD SHX Text
IMPACT RATED W/ CLOSERS & ADA COMPLIANT LOCKSETS/HANDLES
AutoCAD SHX Text 12-0 W, 14-0 H
AutoCAD SHX Text
PAINTED GALV STEEL, HM FRAME
AutoCAD SHX Text
IMPACT RATED
AutoCAD SHX Text
OH DOOR - ELECTRIC
AutoCAD SHX Text
PERSONEL DOOR, INTERIOR
AutoCAD SHX Text 3-0 W, 6-8 H
AutoCAD SHX Text
PAINTED METAL, HM FRAME
AutoCAD SHX Text
W/ CLOSERS & ADA COMPLIANT LOCKSETS/HANDLES, SMOKE GASKET, DOOR SWEEP
AutoCAD SHX Text
BATHROOM DOOR
AutoCAD SHX Text
W/ CLOSERS & ADA COMPLIANT LOCKSETS/HANDLES
AutoCAD SHX Text 3-0 W, 6-8 H
AutoCAD SHX Text
PAINTED METAL, HM FRAME
AutoCAD SHX Text
KEYED ON THE EXTERIOR SIDE W/ PRIVACY TURN BUTTON ON INTERIOR SIDE
AutoCAD SHX Text 3-0 W, 6-8 H
AutoCAD SHX Text 3-0 W, 6-8 H
AutoCAD SHX Text
CLOSET DOOR
AutoCAD SHX Text
W/ CLOSERS & ADA COMPLIANT LOCKSETS/HANDLES
AutoCAD SHX Text
PAINTED WOOD, WD FRAME
AutoCAD SHX Text (2)1-6 W, 6-8 H
AutoCAD SHX Text
KEYED ON THE EXTERIOR SIDE W/ PRIVACY TURN BUTTON ON INTERIOR SIDE
AutoCAD SHX Text
MINERAL FIBER INSULATION
AutoCAD SHX Text
MINERAL FIBER INSULATION
AutoCAD SHX Text
PRIVACY PUSH BUTTON ON INSIDE, INSIDE BUTTON LOCKS OUTSIDE LEVER. TURNING
AutoCAD SHX Text
INSIDE LEVER RELEASES INDIDE BUTTON AND UNLOCKS LOCKSET.
AutoCAD SHX Text
W/ CLOSERS & ADA COMPLIANT LOCKSETS/HANDLES, SMOKE GASKET, DOOR SWEEP
AutoCAD SHX Text
KEYED ON THE EXTERIOR SIDE W/ PRIVACY TURN BUTTON ON INTERIOR SIDE
AutoCAD SHX Text
MECH CLOSET
AutoCAD SHX Text
NOTE: PROVIDE OPTION PRICE FOR NON - IMPACT RATING FOR EXTERIOR DOORS & WINDOWS.
AutoCAD SHX Text
(2) 3-0 W, 6-8 H
AutoCAD SHX Text
PAINTED METAL, HM FRAME
AutoCAD SHX Text
1.5 HOUR FIRE RATED UL ASSEMBLY
AutoCAD SHX Text
W/ CLOSERS & ADA COMPLIANT LOCKSETS/HANDLES, SMOKE GASKET, DOOR SWEEP
AutoCAD SHX Text
KEYED ON THE EXTERIOR SIDE W/ PRIVACY TURN BUTTON ON INTERIOR SIDE
AutoCAD SHX Text
1.5 HOUR FIRE RATED UL ASSEMBLY
AutoCAD SHX Text
PRIVACY PUSH BUTTONS, INSIDE PUSH BUTTON LOCKS OUTSIDE LEVER
AutoCAD SHX Text
PROVIDE COAT HOOK
AutoCAD SHX Text
PROVIDE COAT HOOK
AutoCAD SHX Text
PAINTED METAL, HM FRAME
AutoCAD SHX Text
NOTE: PROVIDE OPTION PRICE FOR NON IMPACT RATING FOR EXTERIOR DOORS & WINDOWS.
MINERAL FIBER INSULATION
C H
IT
E C T U ja r c h m s n .c o m
R U S S E L L J
O H N S
C H
IT
E
A - 103 e a g l e s p r in g s g o l f c o u r s e m a in t e n a n c e b u il d in g w a l t o n c o u n t y f l o r id a
GUTTER, DOWNSPOUT, & CONC. SPLASHBLOCKG
G
GUTTER, DOWNSPOUT, & CONC. SPLASHBLOCKG
G
GUTTER, DOWNSPOUT, & CONC. SPLASHBLOCKG
G
GUTTER, DOWNSPOUT, & CONC. SPLASHBLOCKG
G
GUTTER, DOWNSPOUT, & CONC. SPLASHBLOCKG
G
GUTTER, DOWNSPOUT, & CONC. SPLASHBLOCKG
G elevations
SCALE: 3/16" = 1'-0"
rear elevation left side elevation
INSULATION SYSTEM
1. INSULATION SYSTEM SHALL BE "SIMPLE SAVER SYSTEM" W/ OSHA
COMPLIANT FALL PROTECTION OR APPROVED EQUAL.
2. INSULATION SHALL BE IN COMPLIANCE W/ FBC 2020 ENERGY CODE
FOR METAL BUILDING, CLIMATE ZONE 2, ALL OTHER CATEGORY.
Q Q
3.75
1.63
NOTE: PROVIDE OWNER WITH AN OPTIONAL PRICE TO
REPLACE TYPE 1 PEMB WALL PANEL WITH A CONTINUATION
OF TYPE 2 PEMB WALL PANEL AND DELETE TRIM BAND H
EXTERIOR METAL WALL PANELS
LEGEND
TYPE 1, COLOR 1, PEMB METAL WALL PANELS
STEEL PEMB FRAME
METAL ROOF PANELS BY PEMB
TYPE 2, COLOR 2, PEMB METAL WALL PANELS
PEMB Z-GIRTS
IN COMPLIANCE W/ FBC ENERGY CODE -
GUTTER, DOWNSPOUT, & CONC. SPLASHBLOCK
METAL TRIM BAND / FLASHING BY PEMB
INTERIOR FINISH - COORDINATE W/ OWNER
CEILING - 5/8" TYPE X PAINTED GYP BD, COORDINATE W/ OWNER
CONCRETE FOUNDATION - REFER TO STRUCTURAL
3-5/8" METAL STUDS (6" @ PLUMBING WALLS IF REQUIRED)
CONCRETE FLOOR SLAB - REFER TO STRUCTURAL, PROVIDE VAPOR BARRIER
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
@ 16" OC W/ 5/8" TYPE X PAINTED GYP BD
SHOP DRAWINGS FROM THE METAL STUD MANUFACTURER
METAL STUD GAUGE, BRACING, ETC SHALL BE PER SIGNED AND SEALED
8 FT H METAL PANELS BY PEMB IN STORAGE AREA
5/8" PAINTED GYP BOARD OTHER SPACES
BUILDING SIGNAGE PER OWNER'S SPECIFICATIONS
R
WALL INSULATION W/ VAPOR RETARDER -
4" VINYL BASE ALL SPACES - EXCEPT STORAGE AREA
VINYL FLOOR TILE ALL SPACES EXCEPT STORAGE AREA
PROVIDE 3.5" BATT INSULATION ALL INTERIOR WALLS THAT ABUTT THE
MAIN STORAGE AREA AND ALL MECHANICAL AND BATHROOMS.
ON 6" 18 GA CEILING JOISTS @ 16" OC.
IN COMPLIANCE W/ FBC ENERGY CODE -
ROOF INSULATION W/ VAPOR RETARDER -
PROVIDE 2 HOUR WALL ASSEMBLY WHERE INDICATED ON PLAN
PROVIDE UL APPROVED FIRE CAULKING SYSTEM MATCHING FIRE RATING
OF WALL @ STEEL BEAM PENETRATIONS
LOUVERS - COORDINATE W/ MECHANICAL DRAWINGS
TYPICAL ALL SPACES EXCEPT MAIN STORAGE AREA
PROVIDE UL APPROVED 2HR ASSEMBLY UL I 506 OR APPROVED EQUAL
(2) LAYERS 5/8" TYPE ULIX GYP BD, LOOSELY LAID ON TOP OF MIN 6" D
STEEL JOISTS @16" OC AND (3) LAYERS TYPE ULIX GYP BD ATTACHED
TO THE BOTTOM OF THE STEEL CEILING JOISTS.
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT #
AutoCAD SHX Text
REVIEWED
C H
IT
E C T U ja r c h m s n .c o m
R U S S E L L J
O H N S
C H
IT
E
A - 104
BUILDING SECTION
NTS
e a g l e s p r in g s g o l f c o u r s e m a in t e n a n c e b u il d in g w a l t o n c o u n t y f l o r id a
B C
E
K
N
I
3.75
A
E
E
F
G
D
H
J
L L
B
M
J
F
B
M
J
F
C
1/ 2"
1.63 top of pemb frame top of pemb frame top of pemb frame top of pemb frame
16'-0"
B
EE
F
G
G
I
I
L
FXD.FXD.
REFRIGERATOR
9'- 6" (FIELD ADJUST)
SCALE: NTS
BREAK ROOM CABINET ELEVATIONS
4" TOE KICK -
MATCH WALL BASE
COORDINATE SIZE
W/ OWNER'S SELECTION
(1) ADJUSTABLE SHELF
PER CABINET
NO SHELF
THIS CABINET
TOP OF
COUNTER
NOTE:
1. COORDINATE CABINET DESIGN WITH OWNER - SUBMIT
SHOP DRAWINGS FOR OWNER APPROVALS PRIOR
TO PURCHASE / CONSTRUCTION OF CABINETS.
2. CABINETS TO BE PLASTIC LAMINATE OVER 3/4" PLYWOOD.
3. HARDWARE TO BE STAINLESS STEEL, COMMERCIAL GRADE
SINK
UL 419 2 HR
P
Q Q
R
2"
L L L
MW
ICE
MAKER
DEMISING WALL - U419 or approved equal
1. 3 5/8 " METAL STUDS - @ 16" OC - gauge and blocking per manufacturer's requirements - 25 ga min.
2. (2) layers of 5/8 " sheetrock firecode core panels EACH SIDE OF WALL - provide r19 insulation.
3. provide ul approved fire rated assembly at all voids & penetrations
LEGEND
TYPE 1, COLOR 1, PEMB METAL WALL PANELS
STEEL PEMB FRAME
METAL ROOF PANELS BY PEMB
TYPE 2, COLOR 2, PEMB METAL WALL PANELS
PEMB Z-GIRTS
IN COMPLIANCE W/ FBC ENERGY CODE -
GUTTER, DOWNSPOUT, & CONC. SPLASHBLOCK
METAL TRIM BAND / FLASHING BY PEMB
INTERIOR FINISH - COORDINATE W/ OWNER
CEILING - 5/8" TYPE X PAINTED GYP BD, COORDINATE W/ OWNER
CONCRETE FOUNDATION - REFER TO STRUCTURAL
3-5/8" METAL STUDS (6" @ PLUMBING WALLS IF REQUIRED)
CONCRETE FLOOR SLAB - REFER TO STRUCTURAL, PROVIDE VAPOR BARRIER
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
@ 16" OC W/ 5/8" TYPE X PAINTED GYP BD
SHOP DRAWINGS FROM THE METAL STUD MANUFACTURER
METAL STUD GAUGE, BRACING, ETC SHALL BE PER SIGNED AND SEALED
8 FT H METAL PANELS BY PEMB IN STORAGE AREA
5/8" PAINTED GYP BOARD OTHER SPACES
BUILDING SIGNAGE PER OWNER'S SPECIFICATIONS
R
WALL INSULATION W/ VAPOR RETARDER -
4" VINYL BASE ALL SPACES - EXCEPT STORAGE AREA
VINYL FLOOR TILE ALL SPACES EXCEPT STORAGE AREA
PROVIDE 3.5" BATT INSULATION ALL INTERIOR WALLS THAT ABUTT THE
MAIN STORAGE AREA AND ALL MECHANICAL AND BATHROOMS.
ON 6" 18 GA CEILING JOISTS @ 16" OC.
IN COMPLIANCE W/ FBC ENERGY CODE -
ROOF INSULATION W/ VAPOR RETARDER -
PROVIDE 2 HOUR WALL ASSEMBLY WHERE INDICATED ON PLAN
PROVIDE UL APPROVED FIRE CAULKING SYSTEM MATCHING FIRE RATING
OF WALL @ STEEL BEAM PENETRATIONS
LOUVERS - COORDINATE W/ MECHANICAL DRAWINGS
TYPICAL ALL SPACES EXCEPT MAIN STORAGE AREA
PROVIDE UL APPROVED 2HR ASSEMBLY UL I 506 OR APPROVED EQUAL
(2) LAYERS 5/8" TYPE ULIX GYP BD, LOOSELY LAID ON TOP OF MIN 6" D
STEEL JOISTS @16" OC AND (3) LAYERS TYPE ULIX GYP BD ATTACHED
TO THE BOTTOM OF THE STEEL CEILING JOISTS.
APPLIANCE SCHEDULE:
COORDINATE W/ OWNER FOR FINAL SELECTIONS.
APPROVED EQUALS ARE ACCEPTABLE
GE 27.8 cu ft FRENCH DOOR REFRIGERATOR w/ Ice Maker S
S
T
U
Stainless Steel
GE Profile 2.2 cu. ft. Countertop Sensor MICROWAVE OVEN T
Model # PES7227SLSS
EDGESTAR IB250SS 15" wide 20 lb Built-In ICE MAKER U
Model # IB250SS
SHELF FOR
MICROWAVE
Model #PFE28KYNFS
Stainless Steel
Stainless Steel
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT #
AutoCAD SHX Text
REVIEWED
B A
BATHROOM - MOUNTING HEIGHTS
E
D
TOILET ACCESSORIES
A TOILET TISSUE DISPENSER
B ADA SHWR GRAB BARS
C ADA MIRROR
D SOAP DISPENSER
E PAPER TOWEL DISPENSER & WASTE RECEPTACLE
F 36" ADA GRAB BAR
G 42" ADA GRAB BAR
H 18" VERTICAL ADA GRAB BAR
I ADA LAVATORY
J ADA WCFG
H
I
JJ
F
NOTES:
1. COORDINATE TOILET ACCESSORIES WITH OWNER.
SUBMIT FULL SHOP DRAWINGS / CUT SHEETS FOR
OWNER APPROVAL DURING BIDDING.
2. COORDINATE MOUNTING HEIGHTS OF
ACCESSORIES WITH MANUFACTURER'S DATA FOR
ADA COMPLIANCE.
1'-0"
3'-6"
3'-4"
8"
1'
1/
3'-0"
MEN
WOMEN
7'-6"
D1
D4
D4
D5
D6
D6 restroom restroom bathroom bathroom 2'-6"
/2
/4
/4
7' -6
/8
/8
36 X 36
ADA SHWR
36 X 36
ADA SHWR
ADA DF
mechanical
2'-4 3/4" 7'-9"
D3
D8D8
A R
C H
IT
E C T U ja r c h m s n .c o m
R U S S E L L J
O H N S
C H
IT
E
A - 105 e a g l e s p r in g s g o l f c o u r s e m a in t e n a n c e b u il d in g w a l t o n c o u n t y f l o r id a
BATHROOM ACCESSORY PRODUCT SELECTION SCHEDULE
NOTE: Specified products listed are for design intent/quality control, approved equals are accepted as approved by owner. Submit complete shop drawings and specs for owner review and approval.
COAT HOOK Bobrick B-6707 satin finished stainless steel finished single utility/coat hook.
Mirror - Bobrick B-292 1830 seried welded satin stainless steel finish framed mirror with 5" shelf, 18" x 30".
PTC; Bobrick B-262 classic series satin stainless steel finished surface mounted paper towel cabinet for folded paper.
SDISP, Bobrick B-2111 classic series surface mounted soap dispensers with satin stainless steel finish.
TPH; Bobrick B-6867 classic series surface mounted satin stainless steel finish two roll toilet paper holder.
ADA COMPLIANT LAV ( exposed piping shall be insulated per ada requirements)
ADA COMPLIANT WATER CLOSET -
ADA COMPLIANT WALL MOUNTED URINAL - kohler Steward Hybrid K-5244-ET-0 or owner approved equal
GB; Bobrick B-6806.99 series peened satin stainless steel finished grab bars for accessible toilet size 42" L side wall, 36" L back wall
Bobrick B 2260 satin stainless steel floor standing waste receptacle
K COAT HOOK, S.S.
TYPICAL
A
A
A
B
B
L ADA FOLDING SEAT
L
L
C
C
C
(3 LOCATIONS)
D
D
D
E
E
E
F
F
G
G
H
H
H
I
I
J
J
K
K
K
ENLARGED RESTROOM FLOOR PLAN
11'-3"
COORDINATE WALL THICKNES
W/ PLUMBING DRAWINGS
SD-1
CONTROL
VALVE
BY MECH
CONTROL
WALL
WATER
SUPPLY
CURTAIN
ROD
GB
ACCESSIBLE SHOWER - TRANSFER TYPE SHOWER WITH SEAT
7" 9"
4"
2"
GB
1'-6"
1'
GB
SIDE BACK PLAN
3'-0"
SIDE
FSB
1'
3'-0"
1'-0"
SHOWER
ACCESS
CLEARANCE
FSB
1'
3'-0"
" 6
1. 36" X 36" CLEAR ACCESSIBLE TRANSFER TYPE SHOWER. DIMENSIONS ARE ABSOLUTE CLEAR INSIDE INCLUDING FINISHES.
2. PROVIDE HAND HELD SHOWER WITH SLIDE BAR, ADJUSTABLE MECHANISE AND BE OPERABLE WITH ONE HAND WITHOUT TIGHT GRASPING OR
TWISTING OF THE WRIST. MAX. 5 LB FORCE TO OPERATE.
3. GB BLKG TO BE DESIGNED FOR 250 LB LAT. AND DEAD LOADS.
4. HAND HELD SHOWER MUST HAVE A NON-POSITIVE SHUT OFF AND A HOSE THAT IS 59" LONG MIN.
1'-5"
3/8" = 1'-0"
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT #
AutoCAD SHX Text
REVIEWED
N.T.S.
STRUCTURAL GENERAL
NOTES
S001
AB ANCHOR BOLT
ADDL ADDITIONAL
ALT ALTERNATE
ALUM ALUMINUM
ARCH ARCHITECTURAL or ARCHITECT
B/ BOTTOM OF
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOS BOTTOM OF STEEL
BRG BEARING
B/S BOTTOM SIDE
BTM or (B) BOTTOM, "BOT" SIM
BTW BETWEEN
CB CARRIAGE BOLT
CFS COLD FORMED STEEL
CIP CAST IN PLACE
C.J. CONTROL JOINT
CL or (℄) CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
C.O. CASED OPENING
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUE or CONTINUOUS
CSJ CONSTRUCTION JOINT
CTR CENTERED, "CNTR'd" SIM
DET DETAIL
DBL DOUBLE
DIA or (∅) DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIR DIRECTION
D.L. DEAD LOAD
DN DOWN
DWG DRAWING
DWL DOWEL
EA EACH
E.E. EACH END
E.F. EACH FACE
EJ EXPANSION JOINT
ELEV ELEVATION
EMBED EMBEDDED or EMBEDMENT
EOS EDGE OF SLAB
E.G. EXISTING GRADE
E.S. EACH SIDE
EQ EQUAL
E.W. EACH WAY
EX EXISTING
EXPB EXPANSION BOLT
EXT EXTERIOR
F.F. FAR FACE
FFE FINISHED FLOOR ELEVATION
F.G. FINISHED GRADE
FIN FINISH
FL FLOOR
FLG FLANGE
FND FOUNDATION
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FOS FACE OF STUD
FP FULL PENETRATION
F/S FAR SIDE
FT FOOT OR FEET
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GDR GIRDER
GP GUSSET PLATE
HAS HEADED ANCHOR STUD
HD HOLDOWN
HDG HOT DIP GALVANIZED
HDR HEADER
HK HOOK
HORZ HORIZONTAL
HSB HIGH STRENGTH BOLT
H.S.S. HEADED SHEAR or "NELSON" STUD HSS HOLLOW STL SECTION or TUBE
I.F. INSIDE FACE
IN INCH OR INCHES
INT. INTERIOR
INV INVERT
JST JOIST
JT JOINT
K KIP (1,000 POUNDS)
LB POUNDS
L.E. LEFT END
L.L. LIVE LOAD
LLD LONG LEG DOWN
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LVL LAMINATED VENEER LUMBER
LWC LIGHT WEIGHT CONCRETE
MAS MASONRY
MAX MAXIMUM
MB MACHINE BOLT
MFGR MANUFACTURER
MID or (M) MIDDLE
MIN MINIMUM
MISC MISCELLANEOUS
M.R.D. METAL ROOF DECK
MTL METAL
MTRL MATERIAL
N.F. NEAR FACE
NOM NOMINAL
NO. NUMBER OR #
N/S NEAR SIDE
NS NON-SHRINK
N.T.S. NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
O.C. ON CENTER, "C.C." SIM
O.D. OVERALL DIM. "O/O" SIM
O.F. OUTSIDE FACE
OPP OPPOSITE
OVS OVERSIZED
PCC PRECAST CONCRETE
PEN PENETRATION
PERP PERPENDICULAR
P.L. POINT LOAD
PL PLATE
PSL PARALLEL STRAND LUMBER
PT POINT
P.T. PRESSURE TREATED or POST-TENSION
P.U. RIGHT END
REINF REINFORCING
REF REFERENCE
RET RETURN
REQ REQUIRED
R.L.L. ROOF LIVE LOAD
R.O. ROUGH OPENING
SC SLIP CRITICAL
SCHED SCHEDULE
S.D.N. STRUCTURAL DESIGN NOTES
SIM SIMILAR
SOG SLAB ON GRADE
S.E. STUD PACK
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL, "S.S." SIM
STAG STAGGERED
STD STANDARD
STIFF STIFFENER
STL STEEL
STR STRUCTURAL, "STRUCT" SIMILAR
S.W. SHEAR WALL
SYM SYMMETRICAL
T or (T) TOP
T&B TOP AND BOTTOM
T&S TEMPERATURE & SHRINKAGE REINF.
T/ TOP OF
T/S TOP SIDE
TDR THREADED ROD
TEMP. "T&S" FOR REINF, ELSE TEMPORARY
THK THICK OR THICKNESS
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE, "U.N.O." SIM
UWA UNDER WALL ABOVE, "U.W.A." SIM
VERT VERTICAL
W/ WITH
WF WIDE FLANGE
WP WORKING POINT
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
ABBREVIATIONS
STRUCTURAL GENERAL NOTES
MINIMUM LAP SPLICE LENGTH (IN.) - 3000 PSI CONCRETE
No. 3
6-in CMU WALL
8-in CMU WALL
12-in CMU WALL
No. 4 No. 5 No. 6 No. 7
39 81
DETAILING
21 23 29 37 50
RECOMMENED END HOOKS ANCHORAGE LENGTH (IN.) - 3000 PSI CONCRETE
No. 3
A or G
No. 4 No. 5 No. 6 No. 7 No. 8
6 8 10 12 14 16
D 2.25 3.00 3.75 4.50 5.25 6.00
MINIMUM LAP SPLICE LENGTH (IN.) - 1500 PSI NORMAL WEIGHT CMU
No. 8
1. GENERAL NOTES:
1.1. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH PROJECT SPECIFICATIONS
AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND SITE DRAWINGS. CONSULT
THESE DRAWINGS FOR OPENINGS, DEPRESSIONS, EQUIPMENT WEIGHTS AND LOCATIONS,
EMBEDDED ITEMS AND OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.
1.2. DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANY DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF THE ENGINEER OF RECORD BEFORE PROCEEDING WITH
THE AFFECTED PART OF THE WORK.
1.3. NO STRUCTURAL MEMBER OR COMPONENT SHALL BE CUT, NOTCHED, OR OTHERWISE
ALTERED UNLESS APPROVED IN WRITING BY THE ENGINEER OF RECORD. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR ANY AND ALL COSTS INCURRED BY THE ENGINEER OF RECORD
FOR REVIEW OF ANY SUCH DEVIATIONS.
1.4. DO NOT SCALE DRAWINGS.
1.5. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS
COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES
AND SEQUENCE TO ENSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING
ERECTION. THIS INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY
BRACING, AND TIEDOWNS.
1.6. DETAILS LABELED "TYPICAL DETAILS" ON THE DRAWINGS SHALL APPLY TO ALL SITUATIONS
OCCURRING ON THE PROJECT THAT ARE THE SAME OR SIMILAR TO THOSE SPECIFICALLY
DETAILED. THE APPLICABILITY OF THE DETAIL TO ITS LOCATION ON THE DRAWINGS CAN BE
DETERMINED BY THE TITLE OF DETAIL. SUCH DETAILS SHALL APPLY WHETHER OR NOT THEY
ARE REFERENCED AT EACH LOCATION. QUESTIONS REGARDING APPLICABILITY OF TYPICAL
DETAILS SHALL BE DETERMINED BY THE ENGINEER OF RECORD.
1.7. THE GENERAL CONTRACTOR SHALL COMPARE THE ARCHITECTURAL, MECHANICAL,
ELECTRICAL, PLUMBING, CIVIL AND STRUCTURAL DRAWINGS AND REPORT ANY
DISCREPANCIES BETWEEN EACH SET OF DRAWINGS AND WITHIN EACH SET OF DRAWINGS TO
THE ARCHITECT AND ENGINEER OF RECORD PRIOR TO THE FABRICATION AND INSTALLATION
OF ANY STRUCTURAL MEMBERS.
1.8. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE, AND DO NOT INDICATE THE METHOD OR MEANS OF CONSTRUCTION. THE
CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE SOLELY
RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES,
SEQUENCE AND SAFETY. THE ENGINEER DOES NOT HAVE CONTROL OR CHARGE OF, AND
SHALL NOT BE RESPONSIBLE FOR, CONSTRUCTION MEANS, METHODS, TECHNIQUES,
SEQUENCES, OR PROCEDURES, FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION
WITH THE WORK, FOR THE ACTS OR OMISSION OF THE CONTRACTOR, SUBCONTRACTOR OR
ANY OTHER PERSONS PERFORMING ANY OF THE WORK, OR FOR THE FAILURE OF ANY OF
THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
1.9. THE REVIEW OF SUBMITTALS AND/OR SHOP DRAWINGS BY THE STRUCTURAL ENGINEER DOES
NOT RELIEVE THE CONTRACTOR OF THE SOLE RESPONSIBILITY TO REVIEW AND CHECK SHOP
DRAWINGS PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER. THE CONTRACTOR
REMAINS SOLELY RESPONSIBLE FOR ERRORS AND OMISSIONS ASSOCIATED WITH THE
PREPARATION OF SHOP DRAWINGS AS THEY PERTAIN TO MEMBER SIZES, DETAILS, AND
DIMENSIONS SPECIFIED IN THE CONTRACT DOCUMENTS. THE CONTRACTOR ALSO SHALL BE
RESPONSIBLE FOR MEANS, METHOD, TECHNIQUES, SEQUENCES, AND PROCEDURES OF
CONSTRUCTION.
1.10. PERIODIC SITE OBSERVATION BY FIELD REPRESENTATIVES OF ATLAS ENGINEERING AND
CONSULTING, LLC IS SOLELY FOR THE PURPOSE OF DETERMINING IF THE WORK OF THE
CONTRACTOR IS PROCEEDING IN GENERAL ACCORDANCE WITH THE STRUCTURAL CONTRACT
DOCUMENTS. THIS LIMITED SITE OBSERVATION SHALL NOT BE CONSTRUED AS EXHAUSTIVE
OR CONTINUOUS TO CHECK THE QUALITY OR QUANTITY OF THE WORK.
1.11. ALL STRUCTURES REQUIRE PERIODIC MAINTENANCE TO EXCEED LIFE SPAN AND TO ENSURE
STRUCTURAL INTEGRITY FROM EXPOSURE TO THE ENVIRONMENT. A PLANNED PROGRAM OF
MAINTENANCE SHALL BE ESTABLISHED BY THE OWNER. THIS PROGRAM SHALL INCLUDE
ITEMS SUCH AS, BUT NOT LIMITED TO, PAINTING OF STRUCTURAL STEEL, PROTECTIVE
COATINGS FOR CONCRETE, SEALANTS, CAULKED JOINTS, EXPANSION JOINTS, CONTROL
JOINTS, SPALLS AND CRACKS IN CONCRETE, AND PRESSURE WASHING OF EXPOSED
STRUCTURAL ELEMENTS EXPOSED TO SALT ENVIRONMENT OR OTHER HARSH CHEMICALS.
1.12. STRUCTURAL ENGINEER OF RECORD IS NOT RESPONSIBLE FOR THE DESIGN OF STEEL STAIRS, HANDRAILS, CURTAIN WALL/WINDOW WALL SYSTEMS, COLD-FORMED STEEL FRAMING, OR
OTHER SYSTEMS NOT SHOWN IN THE STRUCTURAL DOCUMENTS. SUCH SYSTEMS SHALL BE
DESIGNED, FURNISHED, AND INSTALLED AS REQUIRED BY OTHER PORTIONS OF THE
CONTRACT DOCUMENTS.
1.13. ALL CONSTRUCTION SHALL CONFORM TO THE FLORIDA BUILDING CODE 7TH EDITION (2020).
REFERENCE TO OTHER CODES OR STANDARD SPECIFICATIONS REFER TO THE LATEST EDITION
OF SUCH CODES OR SPECIFICATIONS, UNLESS STATED OTHERWISE.
1.14. NO PROVISIONS HAVE BEEN MADE FOR VERTICAL OR HORIZONTAL EXPANSION EXCEPT AS
SHOWN ON CONTRACT DOCUMENTS.
1.15. FINISH FLOOR ELEVATION (FIRST FLOOR) OF 0"-0" IS USED AS A REFERENCE ELEVATION. SEE
CIVIL DRAWINGS FOR ACTUAL ELEVATION.
1.16. THE USE OF REPRODUCTIONS OF THESE CONTRACT DOCUMENTS AND USE OF CAD FILES BY
ANY CONTRACTOR, SUBCONTRACTOR, ERECTOR, FABRICATOR OR MATERIAL SUPPLIER IN LIEU
OF PREPARATION OF SHOP DRAWINGS IS PROHIBITED UNLESS PRIOR WRITTEN APPROVAL IS
OBTAINED FROM ENGINEER OF RECORD.
1.17. IN THE EVENT THAT THE STRUCTURAL CONTRACTS DRAWINGS AND SPECIFICATIONS
CONFLICT ON INFORMATION, THE STRUCTURAL CONTRACT DRAWINGS SHALL SUPERSEDE
THE SPECIFICATIONS.
2. CODE DESIGN:
2.1. STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE 2020 FLORIDA BUILDING CODE.
2.2. FLOOD DESIGN DATA:
FLOOD ZONE = X
BFE = N/A
PANEL NO = 12131C0260G
3. FOUNDATIONS:
3.1. THE FOUNDATIONS ARE DESIGNED FOR AN ANTICIPATED ALLOWABLE SOIL BEARING
PRESSURE OF 2,000 PSF ON COMPACTED FILL IF GEOTECHNICAL INVESTIGATION HAS NOT
BEEN CONDUCTED.
3.2. REGARDLESS OF WHETHER OR NOT A GEOTECHNICAL INVESTIGATION IS PERFORMED, NO
WARRANTIES, EXPRESSED OR IMPLIED, ARE MADE BY ATLAS ENGINEERING AND CONSULTING,
LLC FOR THE PERFORMANCE OF THE FOUNDATION.
3.3. AT A MINIMUM, SITE PREPARATION WORK SHALL INCLUDE:
3.3.1. STRIPPING AND GRUBBING OF THE BUILDING FOOTPRINT PLUS A MARGIN OF 5 FEET
AROUND THE BUILDING, REMOVING ALL ORGANIC MATERIALS.
3.3.2. PROOF ROLLING THE BUILDING SITE TO LOCATE ANY UNFORESEEN SOFT AREAS. ANY
SOFT AREAS SHALL BE\ EXCAVATED AND REPLACED WITH CLEAN FILL. A DENSITY OF AT
LEAST 95% FOR A DEPTH OF 2 FEET IS REQUIRED UNDER THE BUILDING FOOTPRINT.
3.3.3. ALL FILL SHALL BE CLEAN SAND AND FREE OF ORGANIC MATERIALS. COMPACT FILL IN 12
INCH (UNCOMPACTED THICKNESS) LIFTS TO A MINIMUM OF 95% OF THE MODIFIED
PROCTOR MAXIMUM DRY DENSITY VALUE.
3.3.4. EXCAVATIONS FOR FOUNDATIONS SHALL BE COMPACTED TO 95% FOR A DEPTH OF AT
LEAST 2 FEET BELOW THE BOTTOM OF THE FOUNDATION.
3.3.5. DEWATERING MAY BE REQUIRED TO ACHIEVE THE REQUIRED COMPACTION VALUES, AND
IF USED, SHOULD DRAW DOWN THE WATER LEVEL TO AT LEAST 2 FEET BELOW THE
BOTTOM OF THE EXCAVATION.
3.4. SLABS ON GRADE SHALL BE PLACED OVER A 15 MIL, CLASS "B" VAPOR RETARDER. VAPOR
RETARDER SHALL BE LAPPED A MINIMUM OF 6", OR AS RECOMMENDED BY THE
MANUFACTURER (WHICHEVER IS GREATER) AND TAPED AT ALL JOINTS. ALL PUNCTURES IN
THE VAPOR RETARDER SHALL BE REPAIRED PER MANUFACTURER'S WRITTEN INSTRUCTIONS.
ALL PENETRATIONS THROUGH THE VAPOR RETARDER (COLUMNS, PLUMBING, CONDUITS, ETC)
SHALL BE SEALED PER MANUFACTURER'S WRITTEN INSTRUCTIONS. VAPOR RETARDER SHALL
BE CONTINUOUS UNDER WALL FOUNDATIONS OR SEALED TO EXTERIOR WALLS PER
MANUFACTURER'S WRITTEN INSTRUCTIONS.
4. CONCRETE:
4.1. CONCRETE SHALL BE PLACED AND CURED ACCORDING TO ACI STANDARDS AND
SPECIFICATIONS.
4.2. UNLESS NOTED OTHERWISE, ALL CONCRETE SHALL BE NORMAL WEIGHT AND HAVE THE
FOLLOWING MINIMUM 28 DAY COMPRESSIVE STRENGTHS:
4.2.1. FOUNDATIONS & SLAB-ON-GRADE 3,000 PSI
4.2.2. STRUCTURAL SLABS 4,000 PSI
4.2.3. CIP BEAMS, COLUMNS & WALLS 4,000 PSI
4.2.4. EXTERIOR RETAINING WALLS 4,000 PSI
4.3. SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELD CYLINDER OR LAB TESTS FOR REVIEW
PRIOR TO USE. MIX SHALL BE UNIQUELY IDENTIFIED BY MIX NUMBER OR OTHER POSITIVE
IDENTIFICATION. MIX SHALL MEET THE REQUIREMENTS OF ASTM C33 FOR COARSE
AGGREGATE.
4.4. CONCRETE SHALL COMPLY WITH THE REQUIREMENTS OF ASTM STANDARD C94 FOR
MEASURING, MIXING, TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE TIME STAMPED
WHEN CONCRETE IS BATCHED.
4.5. THE MAXIMUM TIME ALLOWED FROM THE TIME THE MIXING WATER IS ADDED UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED ONE AND ONE HALF (1-1/2) HOURS. IF
FOR ANY REASON THERE IS A LONGER DELAY THAN THAT STATED ABOVE, THE CONCRETE
SHALL BE DISCARDED. IT SHALL BE THE RESPONSIBILITY OF THE TESTING LAB TO NOTIFY THE
OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY NONCOMPLIANCE WITH THE
ABOVE.
4.6. CALCIUM CHLORIDES SHALL NOT BE UTILIZED; OTHER ADMIXTURES MAY BE USED ONLY WITH
THE APPROVAL OF THE ENGINEER.
4.7. CONCRETE MIX DESIGNS SHALL INCLUDE A WRITTEN DESCRIPTION INDICATING WHERE EACH
PARTICULAR MIX IS TO BE PLACED WITHIN THE STRUCTURE.
4.8. CONDUITS, PIPES AND SLEEVES SHALL BE PLACED AND SPACED IN ACCORDANCE WITH ACI
318, 20.6.
4.9. CONCRETE DESIGN MIX SUBMITTALS SHALL INCLUDE TESTED, STATISTICAL BACK-UP DATA AS
PER 26.4.4 OF ACI 318.
4.10. CONCRETE SLABS ON GRADE SHALL BE REINFORCED WITH 6x6 W1.4xW1.4 STEEL MESH OR
SYNTHETIC FIBERS AT A MINIMUM RATE OF 3.0 LBS/CY, OR AS RECOMMENDED BY THE FIBER
MANUFACTURER FOR CONTROL OF TEMPERATURE AND SHRINKAGE/CRACKING, WHICHEVER
IS GREATER. UNLESS NOTED OTHERWISE.
4.11. WHEN WATER-BASED ADHESIVE ARE BEING USED ON CONCRETE SURFACES, THE
CONTRACTOR SHALL VERIFY THAT THE WATER CONTENT OF THE CONCRETE IS WITHIN THE
ALLOWABLE RANGE BEFORE INSTALLATION.
4.12. CHAMFER OR ROUND ALL EXPOSED CORNERS A MINIMUM OF 3/4".
5. REINFORCING STEEL
5.1. SHALL BE ASTM A615 GRADE 60 DEFORMED BARS, FREE FROM OIL, SCALE AND RUST AND
PLACED IN ACCORDANCE WITH THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF
ACI STANDARDS AND SPECIFICATIONS.
5.2. REINFORCING STEEL SHALL HAVE THE FOLLOWING CONCRETE CLEAR COVER UNO (PER ACI
318-05 PAR.7.7.1)
5.2.1. CONCRETE CAST AGAINST EARTH: 3"
5.2.2. FORMED CONCRETE EXPOSED
TO EARTH OR WEATHER: 2" (#6 BARS & LARGER)
1-1/2" (#5 BARS & SMALLER)
5.2.3. CONCRETE NOT EXPOSED
TO EARTH OR WEATHER: 3/4" (SLABS)
1" (WALLS)
1-1/2" (STIRRUPS & TIES)
5.3. SECURE APPROVAL OF SHOP DRAWINGS PRIOR TO COMMENCING FABRICATION.
5.4. PROVIDE STANDARD HOOKS AT DISCONTINUOUS ENDS OF ALL TOP BARS.
5.5. WHERE REINFORCING IS SHOWN CONTINUOUS, SPLICE BOTTOM BARS OVER SUPPORTS AND
TOP BARS AT CENTER OF SPAN. ALL OTHER LAP SPLICES SHALL BE IN ACCORDANCE WITH
SPLICE TABLES AND DETAILS SHOWN ON DRAWINGS.
5.6. PROVIDE DOWELS INTO FOOTINGS, PILE CAPS, SUPPORT BEAMS, ETC. TO MATCH VERTICAL
BARS WITH CLASS B TENSION LAP SPLICES, U.N.O.
5.7. WHERE HOOKS ARE SHOWN ON THE PLANS OR DETAILS, HOOKS SHALL BE DETAILED TO
EXTEND DEEP ENOUGH INTO SUPPORTING STRUCTURE TO DEVELOP THE FULL STRENGTH OF
THE HOOKED BAR. PROVIDE ADDITIONAL TIES OR STIRRUPS IN SUPPORTING STRUCTURE AS
REQUIRED TO SATISFY ACI 318 HOOK DEVELOPMENT, CONFINEMENT, AND ANCHORAGE
CRITERIA.
5.8. ALL REINFORCEMENT SHALL BE BENT COLD, UNLESS OTHERWISE APPROVED BY THE
STRUCTURAL EOR.
5.9. SHOP DRAWINGS SHOWING ALL FABRICATION DIMENSIONS AND LOCATIONS FOR PLACING
REINFORCING STEEL IN MAT SLABS, CAST-IN-PLACE WALLS, AND STRUCTURAL SLABS SHALL
BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO FABRICATION.
5.10. ALL CONCRETE REINFORCEMENT SHALL BE DETAILED, FABRICATED, LABELED, SUPPORTED
AND SPACED IN FORMS AND SECURED IN PLACE IN ACCORDANCE WITH THE PROCEDURES
AND REQUIREMENTS FOR REINFORCED CONCRETE, "ACI 318" AND THE "MANUALS OF
STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES," ACI 315 (LATEST
EDITION).
5.11. ALL REINFORCING STEEL AND EMBEDMENTS SHALL BE SECURELY TIED AND SUFFICIENTLY
SUPPORTED TO MAINTAIN THE POSITION WITHIN SPECIFIED TOLERANCES DURING ALL
CONSTRUCTION ACTIVITIES. "WET STICKING” DOWELS INTO CONCRETE IS NOT PERMITTED.
5.12. CONTINUOUS REINFORCEMENT SHALL BE PROVIDED WHEREVER POSSIBLE. REINFORCEMENT
SHALL BE SPLICED ONLY AS SHOWN OR NOTED IN THE STRUCTURAL CONTRACT DOCUMENTS.
STAGGER SPLICES WHERE POSSIBLE; USE FULL TENSION SPLICE (CLASS "B") UNLESS NOTED
OTHERWISE. DOWELS SHALL MATCH THE SIZE AND SPACING OF THE SPECIFIED
REINFORCEMENT AND SHALL BE LAPPED WITH FULL TENSION SPLICES (CLASS "B") UNLESS
NOTED OTHERWISE. TERMINATE BARS WITH STANDARD HOOKS.
5.13. REINFORCING STEEL SHALL NOT BE WELDED OR TACK WELDED UNLESS APPROVED BY THE
STRUCTURAL EOR.
5.14. ALL STEEL REINFORCING USED IN SLAB-ON-GRADE CONSTRUCTION IS REQUIRED TO BE
SUPPORTED IN THE CENTER TO UPPER ONE THIRD OF THE SLAB.
6. WELDED WIRE FABRIC:
6.1. SHALL CONFORM TO ASTM A-185, FREE FROM OIL, SCALE AND RUST AND PLACED IN
ACCORDANCE WITH THE TYPICAL PLACING DETAILS OF ACI STANDARDS AND SPECIFICATIONS.
6.2. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES.
6.3. ALL WELD WIRE MESH USED IN SLAB-ON-GRADE CONSTRUCTION IS REQUIRED TO BE
SUPPORTED IN THE CENTER TO UPPER ONE THIRD OF THE SLAB.
7. WOOD:
7.1. STRUCTURAL GLUED LAMINATED TIMBER SHALL BE PRODUCED IN ACCORDANCE WITH THE
AMERICAN INSTITUTE OF TIMBER CONSTRUCTION (AITC). MINIMUM ALLOWABLE BENDING
STRESS SHALL BE 2,400 PSI (DRY CONDITIONS).
7.2. PROVIDE DRESSED SEASONED LUMBER, S4S, WITH A MAXIMUM MOISTURE CONTENT OF 19%
AT TIME OF DRESSING AS LISTED BELOW.
7.2.1. INTERIOR AND EXTERIOR LOAD-BEARING WALLS:
SOUTHERN PINE, NO. 2 GRADE.
7.2.2. LINTELS, FLOOR JOISTS AND BEAMS:
SOUTHERN PINE, NO. 2 GRADE.
7.2.3. WOOD IN CONTACT WITH CONCRETE OR MASONRY SHALL BE FOUNDATION GRADE
PRESSURE-TREATED. USE GALVANIZED NAILS IN PRESSURE-TREATED WOOD. THE
PROTECTIVE COATING ON LIGHT GAUGE STEEL CONNECTIONS IN CONTACT W/
PRESSURE-TREATED WOOD SHALL BE IN ACCORDANCE WITH THE CONNECTOR
MANUFACTURERS RECOMMENDATIONS.
7.3. ENGINEERED LUMBER PRODUCTS
7.3.1. PARALLEL STRAND LUMBER (PSL) SHALL HAVE THE FOLLOWING MINIMUM ALLOWABLE
STRESSES AND PROPERTIES:
ALLOWABLE BENDING STRESS F/B = 2900 PSI
COMPRESSION PERPENDICULAR TO GRAIN F/C┴ = 750 PSI
COMPRESSION PARALLEL TO GRAIN F/C││ = 2900 PSI
HORIZONTAL SHEAR F/V = 290 PSI
MODULUS OF ELASTICITY E = 2,000,000 PSI
7.3.2. LAMINATED VENEER LUMBER (LVL) SHALL HAVE THE FOLLOWING MINIMUM ALLOWABLE
STRESSES AND PROPERTIES:
ALLOWABLE BENDING STRESS F/B = 2600 PSI
COMPRESSION PERPENDICULAR TO GRAIN F/C┴ = 750 PSI
COMPRESSION PARALLEL TO GRAIN F/C││ = 2510 PSI
HORIZONTAL SHEAR F/V = 285 PSI
MODULUS OF ELASTICITY E = 2,000,000 PSI
7.3.3. LAMINATED STRAND LUMBER (LSL) SHALL HAVE THE FOLLOWING MINIMUM ALLOWABLE
STRESSES AND PROPERTIES:
ALLOWABLE BENDING STRESS F/B = 1700 PSI
COMPRESSION PERPENDICULAR TO GRAIN F/C┴ = 710 PSI
COMPRESSION PARALLEL TO GRAIN F/C││ = 1835 PSI
HORIZONTAL SHEAR F/V = 425 PSI
MODULUS OF ELASTICITY E = 1,300,000 PSI
7.3.4. GLULAM BEAMS SHALL HAVE THE FOLLOWING MINIMUM ALLOWABLE STRESSES AND
PROPERTIES:
ALLOWABLE BENDING STRESS F/B = 3000 PSI
COMPRESSION PERPENDICULAR TO GRAIN F/C┴ = 805 PSI
TENSION PARALLEL TO GRAIN F/T││ = 1350 PSI
HORIZONTAL SHEAR F/V = 300 PSI
MODULUS OF ELASTICITY E = 2,100,000 PSI
7.3.5. PRESERVED GLULAM BEAMS SHALL HAVE THE FOLLOWING MINIMUM ALLOWABLE
STRESSES AND PROPERTIES:
ALLOWABLE BENDING STRESS F/B = 2400 PSI
COMPRESSION PERPENDICULAR TO GRAIN F/C┴ = 740 PSI
HORIZONTAL SHEAR F/V = 300 PSI
MODULUS OF ELASTICITY E = 1,800,000 PS
7.4. STRUCTURAL PANELS
7.4.1. FLOOR PANELS SHALL BE CONSTRUCTED WITH TONGUE AND GROOVE APA RATED,
EXPOSURE 1, 23
32" PLYWOOD. FLOOR PANELS SHALL BE GLUED AND NAILED W/ 10D RING
SHANK NAILS @ 4" O/C AT PANEL EDGES AND AT 6" O/C IN THE FIELD.
7.4.2. WALL PANELS SHALL BE CONSTRUCTED WITH APA RATED, EXPOSURE 1, 15 32" SHEATHING, SHEATHING SHALL BE ATTACHED WITH 10D COMMON NAILS @ 3" O/C AT PANEL EDGES
AND 6" O/C IN THE FIELD. ALL PANEL EDGES SHALL BE BLOCKED.
7.4.3. ROOF PANELS SHALL BE CONSTRUCTED WITH APA RATED, EXPOSURE 1, 19 32" SHEATHING.
SHEATHING SHALL BE ATTACHED WITH 10D RING SHANK NAILS @ 4" O/C AT PANEL EDGES
AND AT 6" O/C IN THE FIELD. ALL PANEL EDGES SHALL BE BLOCKED OR ATTACHED WITH
SIMPSON PSCA PANEL SHEATHING CLIPS. NAIL HEADS SHALL NOT PENETRATE THE
OUTER SURFACE OF SHEATHING.
7.5. FABRICATED WOOD TRUSSES
7.5.1. DESIGN OF WOOD TRUSSES SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
SUBMIT SHOP DRAWINGS, DESIGN LOAD DATA, AND SUPPORT REACTIONS SEALED BY AN
ENGINEER LICENSED IN THE PROJECT STATE. REVIEW OF SHOP DRAWINGS SHALL BE FOR
CONFORMANCE WITH THE CONTRACT DOCUMENTS WITH REGARD TO TRUSS
CONFIGURATION, AND THE CONTRACTOR'S INTERPRETATION OF DESIGN LOADS AND
DETAILS. SUCH REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF THE FULL
RESPONSIBILITY FOR THE DESIGN OF THE TRUSSES OR TRUSS CONNECTIONS NOT
SPECIFICALLY DETAILED IN THE CONTRACT DOCUMENTS.
7.5.2. ERECTION AND TEMPORARY BRACING OF PREFABRICATED WOOD TRUSSES SHALL BE IN
CONFORMANCE WITH THE RECOMMENDATIONS OF THE TRUSS MANUFACTURER AND
THE TRUSS PLATE INSTITUTE'S "BRACING WOOD TRUSSES: COMMENTARY AND
RECOMMENDATIONS".
7.5.3. SECURE EACH COMMON ROOF TRUSS/RAFTER TO TOP PLATE WITH SIMPSON H-10 OR H-7
HURRICANE CLIP AT ALL BEARING POINTS. USE SIMPSON H-7 AT GIRDER TRUSSES.
PROVIDE A MINIMUM OF TWO STUDS UNDER GIRDER TRUSS END BEARING.
7.5.4. TRUSSES ON SITE PRIOR TO INSTALLATION SHALL BE STORED IN A VERTICAL POSITION
WITH SUPPORT POINTS PROVIDED AT FINAL BEARING POINTS AND BRACED TO AVOID
TIPPING.
7.5.5. INSTALLATION OF ALL TRUSSES SHALL BE DONE USING A SPREADER BAR WITH A THREE
POINT VERTICAL PICK AND CARE IS TO BE USED IN LIFTING TO MINIMIZE HORIZONTAL
BENDING.
7.5.6. IMPROPER HANDLING OF THE TRUSSES AS NOTED ABOVE AND IN THE SPECIFICATIONS
SHALL MEAN REMOVAL OF THE TRUSSES FROM THE JOB SITE.
7.5.7. DOUBLE TRUSSES SHALL BE NAILED TOGETHER W/ 10D @12" O.C. EACH SIDE, TOP AND
BOTTOM CHORDS & WEBS.
7.5.8. TRUSS TO TRUSS CONNECTIONS SHALL BE VERIFIED BY THE TRUSS DESIGNER.
7.5.9. CONTRACTOR TO REFER TO "STANDARD FOR HURRICANE RESISTANT CONSTRUCTION
SSTD 10-99 FOR FRAMING REQUIREMENTS OF WOOD FRAMED WALL SYSTEMS.
7.5.10. FLOOR TRUSS LOADS:
FLOOR TRUSSES SHALL BE DESIGNED FOR THE FOLLOWING LOADS
UNLESS A SPECIAL LOADING PATTERN IS PROVIDED BY THE
STRUCTURAL ENGINEER OF RECORD.
TOP CHORD LIVE LOAD 40 PSF
TOP CHORD DEAD LOAD 20 PSF
BOTTOM CHORD DEAD LOAD 10 PSF
TOTAL 70 PSF
7.5.11. ROOF TRUSS LOADS:
ROOF TRUSSES SHALL BE DESIGNED FOR THE FOLLOWING LOADS
UNLESS A SPECIAL LOADING PATTERN IS PROVIDED BY THE
STRUCTURAL ENGINEER OF RECORD.
TOP CHORD LIVE LOAD 20 PSF
TOP CHORD DEAD LOAD 20 PSF
BOTTOM CHORD DEAD LOAD 10 PSF
TOTAL 40 PSF
7.6. CONNECTIONS
7.6.1. CONNECTIONS FOR STRUCTURAL TIMBER SHALL BE GALVANIZED…