About this file

This is a technical specification and schematic document for the CLA-VAL Model 58-01/658-01 Combination Back Pressure and Solenoid Shut-Off Valve, prepared by CLA-VAL, a valve manufacturer headquartered in Newport Beach, California. The document provides comprehensive engineering specifications for an industrial valve designed to maintain constant back pressure while providing solenoid-controlled shut-off functionality. The valve is available in sizes ranging from 1 inch to 36 inches with threaded, flanged, or grooved end connections. Standard applications include maintaining minimum back pressure in systems while supplying water to reservoirs and electronic control service using timer-activated solenoid controls. The specification sheet includes schematic diagrams identifying five main components (Hytrol main valve, strainer and needle valve, pressure relief control, solenoid control, and reverse flow valve) along with optional features such as isolation valves, check valves, remote pilot sensing, and valve position indicators. Material options for the valve body and cover include ductile iron, cast steel, or bronze, with trim components available in cast iron, cast steel, or bronze and optional stainless steel selections.

The document provides detailed pressure ratings, dimensional specifications, and adjustment ranges across all valve sizes, with maximum recommended pressures varying from 285 psi for 150-class flanged ductile iron to 400 psi for 300-class options. The valve supports electrical ratings of 24, 48, 120, 240, or 480-volt AC at 60 Hz, or 6, 12, 24, 120, or 240-volt DC, with standard pilot system materials including bronze, stainless steel trim, and buna-n synthetic rubber. Adjustment range options include 0 to 75 psi, 20 to 105 psi, 20 to 200 psi, and 100 to 300 psi configurations, with water temperature capability to 180 degrees Fahrenheit. The specification establishes a ten-step ordering process requiring selection of valve size, pattern (globe or angle), pressure class, connection type, trim material, solenoid energization method, adjustment range, desired options, and electrical specifications. CLA-VAL maintains regional offices in Canada and Switzerland and provides technical support through their Newport Beach headquarters.

View the file

Other files

File Type Posted
Question#94_WHEELSTOP_DETAIL.pdf PDF
PCFR_Open_Burn_Permit.docx DOCX document
Question_52_UpdatedTable.pdf PDF
DCS.ctb —
2013RevisedDesignerManual_-_Part2_2152afa2d9.png PNG image
50183029_SURVEY_CONTROL_SHEET.dwg DWG drawing
COVER_SHEET.dwg DWG drawing
Dewberry-Title_Block_22x34_2705.dwg DWG drawing
EXISTING_CONDITIONS_PLAN.dwg DWG drawing
GENERAL_NOTES_AND_LEGEND.dwg DWG drawing
HIL2020_468223.sid SID file
KEY_SHEET.dwg DWG drawing
OP2017_NC_468223_24.sid SID file
OP2017_NC_468224_24.sid SID file
PLANTING_PLAN.dwg DWG drawing
PLAN_VIEW_RWM_ONLY.dwg DWG drawing
PRC#13013_McINTOSH_PRESERVE_12.17.24.pdf PDF
Sitework.Planting.Grass.Short.bump.jpg JPG image
Sitework.Planting.Grass.Thick.jpg JPG image
dewberry-master_template_22x34.dwt —
x-LIDAR_COPY.dwg DWG drawing
x-LIDAR_COPY_final_design_Parking_Water.dwg DWG drawing
x-MCINTOSH_PARKING_LOT.dwg DWG drawing
x-asbuilt_trails.dwg DWG drawing
x-existing_culverts.dwg DWG drawing
x-proposed_contours100%_final_design.dwg DWG drawing
50183029_DETAILS.dwg DWG drawing
50183029_GRADING_AND_DRAINAGE_PLANS.dwg DWG drawing
FDOT_DITCH_BOTTOM_INLET.pdf PDF
HIL2020_468224.sid SID file
McIntosh_Final_Design.txt TXT text file
OP2017_NC_468523_24.sid SID file
Concrete.Cast-In-Place.Flat.Broom.Grey.jpg JPG image
Hydrangea_Blue_Wave_01.jpg JPG image
S601.1.gif GIF image
Concrete.Cast-In-Place.Flat.Grey.1.jpg JPG image
HIL2023_468224.sid SID file
Hydrangea_Blue_Wave_01_mask.gif GIF image
Masonry.Stone.Fieldstone.Uncoarsed.Tight.jpg JPG image
Masonry.Unit_Masonry.Brick.Modular.Flemish_Cross.bump.jpg JPG image
PublishToWeb_PNG.pc3 —
Pre_Bid_Sign_In_-_26-048UO-IFB_-_Signed.pdf PDF
2026-08-19_McIntosh_Park_Wetland_Construction.pdf PDF
2022-02-03_LPA0038_Amendment_1.pdf PDF
053-2023_-_LPA0038_-_Amendment_2.pdf PDF
USAC_SAJ-2024-04226(SP-CM)_McIntoshPreserve.pdf PDF
Defend360_Digital-Owners-Manual_2025.pdf PDF
Safety_and_Site_Security.docx DOCX document
BidSheet_071626.xlsx XLSX spreadsheet
Polk_County_-_Bid_23-127_Bid_Package.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Combination Back Pressure & Solenoid Shut-Off Valve

Schematic Diagram

Item Description 1 Hytrol (Main Valve) 2 X42N-3 Strainer & Needle Valve 3 CRL Pressure Relief Control 4 CS3 Solenoid Control 5 100-01 Hytrol (Reverse Flow)

Optional Features

Item Description B Shutoff Isolation Valve - Isolates Pilot System D Check Valves with Isolation Valve F Remote Pilot Sensing H Drain to Atmosphere P X141 Pressure Gauge S CV Speed Control (Opening) V X101 Valve Position Indicator

Electrode

Pump Gound

Storage

Tank

Supply System

CLA-VAL

58-01/658-01 Combination Back Pressure and Solenoid Shut-Off Valve

High Pressure System

Time Clock

Low Pressure

System

CLA-VAL

58-01/658-01 Combination Back

Pressure and Solenoid Shut-Off Valve

• Accurate Pressure Control

• Wide Adjustment Ranges

• Optional Check Feature Available

• Quick Acting Solenoid Shut-Off

• Easy Installation and Maintenance

The Cla-Val Model 58-01/658-01 valve performs two separate functions. It maintains a constant back pressure by discharging excess pressure downstream and when the solenoid is activated the valve closes drip-tight.

In operation, the valve is actuated by hydraulic line pressure through the pilot control system. When inlet pressure is greater than the control setting, the valve opens. When inlet pressure is equal to the control setting, the pilot modulates the valve, maintaining the preselected back pressure. When inlet pressure is less than the control setting, the pilot system closes the valve drip tight. Changing the pressure setting simply involves turning an adjusting screw on the pilot control.

The solenoid control is available in energize to open or de-energize to open models.

Back Pressure Maintenance Service A frequent application of this valve is to maintain minimum back pressure in the system while supplying water to a reservoir. The electrode in the storage tank activates the solenoid shutoff feature when the tank reaches a preset level.

Electronic Control Service Using a timer connected to the solenoid control of the valve, flow from the high pressure system to the low pressure system can be controlled at certain times during the day.

Typical Applications

The "D" feature on a vertically installed 6" and larger valve must be horizontally oriented.

58-39

MODEL

KC-NSF61 EPOXY

desser Highlight desser Highlight desser Highlight desser Highlight desser Highlight desser Highlight desser Highlight

Note: The top two flange holes on valve size 36 are threaded to 1 1/2"-6 UNC.

Model 58-01 (Uses Basic Valve Model 100-01) Dimensions (In inches)

Model 58-01 Dimensions (In Inches)

Component Standard Material Combinations

Body & Cover Ductile Iron Cast Steel Bronze

Available Sizes 1" - 36" 1" - 16" 1" - 16"

Disc Retainer & Diaphragm Washer Cast Iron Cast Steel Bronze

Trim: Disc Guide, Seat & Cover Bearing

Bronze is Standard Stainless Steel is Optional

Disc EPDM Diaphragm EPDM Stem, Nut & Spring Stainless Steel

For material options not listed, consult factory.

Cla-Val manufactures valves in more than 50 different alloys.

Materials

GGGG

DDDDInlet

AAAA

X

100-01 Grooved

EE

CC

(MAX)

K

J

H

Inlet Outlet

B (Diameter)

Y

Z

G

GG

GGG

DInlet

DD

DDD

F

FF

X

100-01 Threaded &

Flanged

A

E

C

(MAX)

K

J

H

Inlet Outlet

AA

AAA

B (Diameter)

Valve Body & Cover Pressure Class

Flanged Grooved Threaded

Grade Material

ANSI

Standards*

Class

Class

Class End‡

Details

ASTM A536 Ductile Iron B16.42 250 400 400 400

ASTM A216-WCB Cast Steel B16.5 285 400 400 400

ASTM B62 Bronze B16.24 225 400 400 400

Note: * ANSI standards are for flange dimensions only.

Flanged valves are available faced but not drilled.

‡ End Details machined to ANSI B2.1 specifications.

Valves for higher pressure are available; consult factory for details

Pressure Ratings (Recommended Maximum Pressure - psi)

Valve Size (Inches) 1 1 1/4 1 1/2 2 2 1/2 3 4 6 8 10 12 14 16 18 20 24 30 36 A Threaded 7.25 7.25 7.25 9.38 11.00 12.50 — — — — — — — — — — — — AA 150 ANSI — — 8.50 9.38 11.00 12.00 15.00 20.00 25.38 29.75 34.00 39.00 41.38 46.00 52.00 61.50 63.00 76.00 AAA 300 ANSI — — 9.00 10.00 11.62 13.25 15.62 21.00 26.38 31.12 35.50 40.50 43.50 47.64 53.62 63.24 64.50 76.00 AAAA Grooved End — — 8.50 9.00 11.00 12.50 15.00 20.00 25.38 — — — — — — — — — B Dia. 5.62 5.62 5.62 6.62 8.00 9.12 11.50 15.75 20.00 23.62 28.00 32.75 35.50 41.50 45.00 53.16 56.00 66.00 C Max. 5.50 5.50 5.50 6.50 7.56 8.19 10.62 13.38 16.00 17.12 20.88 24.19 25.00 39.06 41.90 43.93 54.60 61.50 CC Max. Grooved End — — 4.75 5.75 6.88 7.25 9.31 12.12 14.62 — — — — — — — — — D Threaded 3.25 3.25 3.25 4.75 5.50 6.25 — — — — — — — — — — — — DD 150 ANSI — — 4.00 4.75 5.50 6.00 7.50 10.00 12.69 14.88 17.00 19.50 20.81 — — 30.75 — — DDD 300 ANSI — — 4.25 5.00 5.88 6.38 7.88 10.50 13.25 15.56 17.75 20.25 21.62 — — 31.62 — — DDDD Grooved End — — — 4.75 — 6.00 7.50 — — — — — — — — — — — E 1.12 1.12 1.12 1.50 1.69 2.06 3.19 4.31 5.31 9.25 10.75 12.62 15.50 12.95 15.00 17.75 21.31 24.56 EE Grooved End — — 2.00 2.50 2.88 3.12 4.25 6.00 7.56 — — — — — — — — — F 150 ANSI — — 2.50 3.00 3.50 3.75 4.50 5.50 6.75 8.00 9.50 10.50 11.75 15.00 16.50 19.25 22.50 25.60 FF 300 ANSI — — 3.06 3.25 3.75 4.13 5.00 6.25 7.50 8.75 10.25 11.50 12.75 15.00 16.50 19.25 24.00 25.60 G Threaded 1.88 1.88 1.88 3.25 4.00 4.50 — — — — — — — — — — — — GG 150 ANSI — — 4.00 3.25 4.00 4.00 5.00 6.00 8.00 8.62 13.75 14.88 15.69 — — 22.06 — — GGG 300 ANSI — — 4.25 3.50 4.31 4.38 5.31 6.50 8.50 9.31 14.50 15.62 16.50 — — 22.90 — — GGGG Grooved End — — — 3.25 — 4.25 5.00 — — — — — — — — — — — H NPT Body Tapping .375 .375 .375 .375 .50 .50 .75 .75 1 1 1 1 1 1 1 1 2 2 J NPT Cover Center Plug .25 .25 .25 .50 .50 .50 .75 .75 1 1 1.25 1.5 2 1.5 1.5 1.5 2 2 K NPT Cover Tapping .375 .375 .375 .375 .50 .50 .75 .75 1 1 1 1 1 1 1 1 2 2 Stem Travel 0.4 0.4 0.4 0.6 0.7 0.8 1.1 1.7 2.3 2.8 3.4 4.0 4.5 5.1 5.63 6.75 7.5 8.5 Approx. Ship Wt. Lbs. 15 15 15 35 50 70 140 285 500 780 1165 1600 2265 2982 3900 6200 7703 11720 X Pilot System 11 11 11 13 14 15 17 29 31 33 36 40 40 43 47 68 79 85 Y Pilot System 9 9 9 9 10 11 12 20 22 24 26 29 30 32 34 39 40 45 Z Pilot System 9 9 9 9 10 11 12 20 22 24 26 29 30 32 34 39 42 47 desser Highlight desser Highlight desser Highlight desser Highlight desser Highlight desser Highlight

Adjustment Ranges 0 to 75 psi

20 to 105 psi 20 to 200 psi* 100 to 300 psi *Supplied unless otherwise specified Other ranges available, please consult factory

Temperature Range

Water: to 180°F

Electrical Ratings:

Voltage:

24, 48, 120, 240, 480 – 60 Hz. VAC

6, 12, 24, 120, 240 VDC

Materials Standard Pilot System Materials

Pilot Control: Bronze ASTM B62 Trim: Stainless Steel Type 303

Rubber: Buna-N® Synthetic Rubber Tubing & Fittings: Copper and Bronze

Optional Pilot System Materials Pilot Systems are available with optional Aluminum, Stainless Steel or Monel materials.

Pilot System Specifications When Ordering, Please Specify

1. Catalog No. 58-39

2. Valve Size

3. Pattern - Globe or Angle

4. Pressure Class

5. Threaded or Flanged

6. Trim Material

7. Energized or De-energized to

Open Main Valve

8. Adjustment Range

9. Desired Options

10. Electrical Selection

11. When Vertically Installed

PO Box 1325 Newport Beach CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441

CLA-VAL

CLA-VAL CANADA CLA-VAL EUROPE

4687 Christie Drive Beamsville, Ontario Canada L0R 1B4 Phone: 905-563-4963 Fax: 905-563-4040

Chemin dés Mesanges 1 CH-1032 Romanel/ Lausanne, Switzerland Phone: 41-21-643-15-55 Fax: 41-21-643-15-50

©COPYRIGHT CLA-VAL 2013 Printed in USA Specifications subject to change without notice. www.cla-val.com E-58-01/658-01 (R-1/2013)

Represented By:

58-39 Valve

Selection

100-01 Pattern: Globe (G), Angle (A), End Connections: Threaded (T), Grooved (GR), Flanged (F) Indicate Available Sizes

Inches 1 11⁄4 11⁄2 2 21⁄2 3 4 6 8 10 12 14 16 18 20 24 30 36 mm 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750 900

Basic Valve 100-01

Pattern G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G G G, A G G

End Detail T T T, F, Gr*

T, F, Gr

T, F, Gr*

T, F, Gr

F, Gr

F, Gr*

F, Gr*

F F F F F F F F F

Suggested Flow (gpm)

Maximum 55 93 125 210 300 460 800 1800 3100 4900 7000 8400 11000 14000 17000 25000 42000 50000

Maximum Surge 120 210 280 470 670 1000 1800 4000 7000 11000 16000 19000 25000 31000 39000 56500 63000 85000

Suggested Flow

(Liters/Sec)

Maximum 3.5 6 8 13 19 29 50 113 195 309 442 530 694 883 1073 1577 2650 3150

Maximum Surge 7.6 13 18 30 42 63 113 252 441 693 1008 1197 1577 1956 2461 3560 3975 5360

100-01 Series is the full internal port Hytrol. *Globe Grooved Only