Drawings_Part7.pdf

PDF 7 MB Posted

Attached to
Upgrade Doors and Hardware - Iowa City VAMC
Solicitation number
36C26325B0015_1
Issued by

About this file

These are construction documents for the Upgrade Doors/Door Hardware project at the Iowa City VA Health Care System. The project involves upgrading doors and door hardware across multiple buildings (Buildings 1, 2, 7, and 50) within the VA medical complex. Key scope includes replacing door hardware, installing new electronic door operators, adding access control devices, updating power connections, and replacing or modifying existing doors and frames. The project documents include detailed floor plans for each building level, electrical diagrams, door hardware schedules, and specific installation instructions for each door. The construction documents are dated August 28, 2024, with the project being managed by Matthew Ruppenkamp and designed by Fourfront Design, Inc. The work appears to focus on improving building security, accessibility, and functionality through comprehensive door system upgrades.

View the file

Other files

File Type Posted
36C26325B0015 0004.docx DOCX document
636A8-23-102 Upgrade Doors Hardware QA_Revised 9.5.25.docx DOCX document
ICRA DOOR SCHEDULE_20240719.xlsx XLSX spreadsheet
Wage Determination IA20250068 8.22.25.pdf PDF
Site Visit Sign in Sheet.pdf PDF
36C26325B0015 0003.docx DOCX document
Specifications Revised 9.3.25.pdf PDF
636A8-23-102 Upgrade Doors Hardware QA.docx DOCX document
Final SOW_8.18.25.docx DOCX document
JA Honeywell - Lenel Fully_Redacted.pdf PDF
36C26325B0015 0002.docx DOCX document
Specifications Revised 8.18.25.pdf PDF
JA Best Access Systems - Cormax_Redacted.pdf PDF
Updated Door Schedule Dwg No. A6.00.pdf PDF
IFB Attachment - Site Visit Campus Map.pdf PDF
36C26325B0015 0001 (Amendment 0001).pdf PDF
Questions_Answers or Clarifications (Attachment).pdf PDF
Drawings_Part2.pdf PDF
SOW Final 6 pages.pdf PDF
Drawings_Part3.pdf PDF
Drawings_Part5.pdf PDF
Drawings_Part6.pdf PDF
Wage Determination 8-8-2025 7 pages.pdf PDF
Limitations on Subcontracting Certificate of Compliance 2 pages.pdf PDF
VA Handbook 6500.6 Appendix C.pdf PDF
Specifications 486 pages.pdf PDF
Safety or Environmental Violations and EMR Information 2 pages.pdf PDF
36C26325B0015_1.docx DOCX document
Drawings_Part1.pdf PDF
Drawings_Part4.pdf PDF
TMS 20939 VA Privacy Training.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP

4CE05

4CS04 4CS03

4S05

4W39

4CW07

4W54

4W52

C

W

C

4CS07A

4CS05A4CS05

C

S

A1.12

A1.12

A1.12

A1.12

A1.12

A1.12

A1.12

A1.12

A1.12

A1.12

A1.12

1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT

SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM

THE ARCHITECT.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE

PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND

PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL

TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR

DISCREPANCIES.

3. SEE ENLARGED AREA PLANS FOR KEYNOTES.

4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.

1-HOUR FIRE BARRIER

WALL RATING LEGEND:

2-HOUR FIRE BARRIER

SMOKE BARRIER

2-HOUR FIRE SMOKE

BARRIER

FIRE RATING

SMOKE AND FIRE RATING

1-HOUR FIRE SMOKE

BARRIER

SMOKE PARTITION

SMOKE RESISTIVE

CORRIDOR WALL

POINT OF EGRESS

SHEET LEGEND:

NORTH ARROW

PLAN NORTH

TRUE NORTH

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

FOUR FRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

STAMP: ARCHITECT/ENGINEER OF RECORD:

4F PROJECT NO: 19.2481.A26 40

/2 /2

:2

:1

P M

8/28/2024

BUILDING 1, FLOOR 4 PLAN

A1.05

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

KZKP

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

CONSTRUCTION DOCUMENTS

1/16" = 1'-0"

BUILDING 1, FLOOR 4

GENERAL NOTES:

SHEET SPECIFIC NOTES:

1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR

NEW DOOR HARDWARE.

C

S

E

A1.12

A1.12

1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT

SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM

THE ARCHITECT.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE

PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND

PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL

TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR

DISCREPANCIES.

3. SEE ENLARGED AREA PLANS FOR KEYNOTES.

4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.

1-HOUR FIRE BARRIER

WALL RATING LEGEND:

2-HOUR FIRE BARRIER

SMOKE BARRIER

2-HOUR FIRE SMOKE

BARRIER

FIRE RATING

SMOKE AND FIRE RATING

1-HOUR FIRE SMOKE

BARRIER

SMOKE PARTITION

SMOKE RESISTIVE

CORRIDOR WALL

POINT OF EGRESS

SHEET LEGEND:

NORTH ARROW

PLAN NORTH

TRUE NORTH

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

FOUR FRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

STAMP: ARCHITECT/ENGINEER OF RECORD:

4F PROJECT NO: 19.2481.A26 40

/2 /2

:2

:1

P M

8/28/2024

BUILDING 1, FLOOR 5 PLAN

A1.06

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

KZKP

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

CONSTRUCTION DOCUMENTS

1/16" = 1'-0"

BUILDING 1, FLOOR 5

GENERAL NOTES:

SHEET SPECIFIC NOTES:

1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR

DN

6CW03

A1.12

1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT

SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM

THE ARCHITECT.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE

PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND

PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL

TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR

DISCREPANCIES.

3. SEE ENLARGED AREA PLANS FOR KEYNOTES.

4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.

1-HOUR FIRE BARRIER

WALL RATING LEGEND:

2-HOUR FIRE BARRIER

SMOKE BARRIER

2-HOUR FIRE SMOKE

BARRIER

FIRE RATING

SMOKE AND FIRE RATING

1-HOUR FIRE SMOKE

BARRIER

SMOKE PARTITION

SMOKE RESISTIVE

CORRIDOR WALL

POINT OF EGRESS

SHEET LEGEND:

NORTH ARROW

PLAN NORTH

TRUE NORTH

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

FOUR FRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

STAMP: ARCHITECT/ENGINEER OF RECORD:

4F PROJECT NO: 19.2481.A26 40

/2 /2

:2

:1

P M

8/28/2024

BUILDING 1, FLOOR 6 PLAN

A1.07

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

KZKP

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

CONSTRUCTION DOCUMENTS

1/16" = 1'-0"

BUILDING 1, FLOOR 6

GENERAL NOTES:

SHEET SPECIFIC NOTES:

1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR

S

T

9ST03

A1.12

A1.12

1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT

SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM

THE ARCHITECT.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE

PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND

PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL

TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR

DISCREPANCIES.

3. SEE ENLARGED AREA PLANS FOR KEYNOTES.

4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.

1-HOUR FIRE BARRIER

WALL RATING LEGEND:

2-HOUR FIRE BARRIER

SMOKE BARRIER

2-HOUR FIRE SMOKE

BARRIER

FIRE RATING

SMOKE AND FIRE RATING

1-HOUR FIRE SMOKE

BARRIER

SMOKE PARTITION

SMOKE RESISTIVE

CORRIDOR WALL

POINT OF EGRESS

SHEET LEGEND:

NORTH ARROW

PLAN NORTH

TRUE NORTH

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

FOUR FRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

STAMP: ARCHITECT/ENGINEER OF RECORD:

4F PROJECT NO: 19.2481.A26 40

/2 /2

:2

:1

P M

8/28/2024

BUILDING 1, FLOOR 9 PLAN

A1.08

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

KZKP

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

CONSTRUCTION DOCUMENTS

1/16" = 1'-0"

BUILDING 1, FLOOR 9

GENERAL NOTES:

SHEET SPECIFIC NOTES:

1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR

DN

UP

UP

1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT

SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM

THE ARCHITECT.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE

PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND

PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL

TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR

DISCREPANCIES.

3. SEE ENLARGED AREA PLANS FOR KEYNOTES.

4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.

C

A

A1.12

A1.12

A1.12

A1.12

POINT OF EGRESS

SHEET LEGEND:

NORTH ARROW

PLAN NORTH

TRUE NORTH

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

FOUR FRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

STAMP: ARCHITECT/ENGINEER OF RECORD:

4F PROJECT NO: 19.2481.A26 40

/2 /2

:2

:1

P M

8/28/2024

BUILDING 2, FLOOR 1 PLAN

A1.09

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

KZKP

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

CONSTRUCTION DOCUMENTS

GENERAL NOTES:

SHEET SPECIFIC NOTES:

1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR

NEW DOOR HARDWARE.

1/8" = 1'-0"

BUILDING 2, FLOOR 1

-7 A1.12

1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT

SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM

THE ARCHITECT.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE

PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND

PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL

TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR

DISCREPANCIES.

3. SEE ENLARGED AREA PLANS FOR KEYNOTES.

4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.

POINT OF EGRESS

SHEET LEGEND:

NORTH ARROW

PLAN NORTH

TRUE NORTH

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

FOUR FRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

STAMP: ARCHITECT/ENGINEER OF RECORD:

4F PROJECT NO: 19.2481.A26 40

/2 /2

:2

:1

P M

8/28/2024

BUILDING 7 FLOOR PLANS

A1.10

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

KZKP

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

CONSTRUCTION DOCUMENTS

1/8" = 1'-0"

BUILDING 7

GENERAL NOTES:

SHEET SPECIFIC NOTES:

1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR

1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT

SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM

THE ARCHITECT.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE

PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND

PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL

TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR

DISCREPANCIES.

3. SEE ENLARGED AREA PLANS FOR KEYNOTES.

4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.

1-HOUR FIRE BARRIER

WALL RATING LEGEND:

2-HOUR FIRE BARRIER

SMOKE BARRIER

2-HOUR FIRE SMOKE

BARRIER

FIRE RATING

SMOKE AND FIRE RATING

1-HOUR FIRE SMOKE

BARRIER

SMOKE PARTITION

SMOKE RESISTIVE

CORRIDOR WALL

BE24

09-01

08-01

09-02

09-01

B E

09-02

08-01

B E

09-02

08-01

B W

A

09-02

08-01

09-01 09-01

09-0109-01

B C

W

09-02

08-01

BS04

09-02

08-01

09-01

B W

09-0109-01

BCS03B

09-0109-01

08-72

B W

09-0109-01

08-72

B W

C

09-01

09-02

B W

09-01

09-02

08-01

09-01

1CN01A

1CN01

09-01

09-01

08-01

09-02

09-02

08-01

B W

09-01

08-01

09-02

09-01

B C

09-01

09-02

08-01

05-60

09-01

1E06

09-01

09-02

08-01

09-01

C

N

09-01

09-01

09-03

09-03

09-04

09-5009-50

09-01

W

08-71

09-01

TEMPORARY PARTITION

NEW CONSTRUCTION LEGEND:

PLAN NORTH

TRUE NORTH

NORTH ARROW

1C07

09-0109-01

09-01 09-01

1CW07

08-71

09-01

1W501CW07A

08-71 08-71

09-01

C

09-01

09-01

1CN03A

09-01

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

FOUR FRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

STAMP: ARCHITECT/ENGINEER OF RECORD:

4F PROJECT NO: 19.2481.A26 40

/2 /2

:2

:1

P M

8/28/2024

NEW CONSTRUCTION PLANS -

ENLARGED

A1.11

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

JEKP

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

CONSTRUCTION DOCUMENTS

05-60 UPDATE/REPLACE HARDWARE AS SPECIFIED, SEE DOOR SCHEDULE.

08-01 UPDATE/REINSTALL DOOR, SEE SPECS AND DOOR SCHEDULE

08-71 UPDATE DOOR OPERATOR, SEE SPECS.

08-72 UPDATE MOTION SENSOR, SEE SPECS.

09-01 PATCH AND REPAIR ANY DAMAGE AS A RESULT FROM THE REMOVAL

OF THE TEMPORARY PARTITION.

09-02 PATCH AND REPAIR ANY DAMAGE AS A RESULT FROM THE REMOVAL

OF THE DOOR FRAME.

09-03 PATCH AND REPAIR ANY DAMAGE AS A RESULT FROM THE REMOVAL

OF THE DOOR FRAME AND EXISTING WALL.

09-04 MATCH EXISTING FINISH.

09-50 EXTEND OR REPLACE CEILING AS NEEDED DUE TO DOOR

RELOCATION. MATCH EXISTING.

GENERAL NOTES:

KEYNOTES:

1/4" = 1'-0"

BUILDING 1 - DOOR BE24 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BE01 - ENLARGED

PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BE00 - ENLARGED

PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BW12A -

ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BCW02 -

ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BS04 - ENLARGED

PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BW101 -

ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BCS03B -

ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BW107 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BW110C -

ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BW114 -

ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOORS 1CN01 AND 1CN01A - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BW115 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR BC07 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 1E06 - ENLARGED

PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 1CN03 -

ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 1W36 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 1C07 - ENLARGED

PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 1CW07 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOORS 1W50 AND 1CW07A - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDINGS 50 - DOORS 50C101 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 1CN03A -

ENLARGED PLAN - NEW

THE ARCHITECT.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE

PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND

PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL

TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR

DISCREPANCIES.

3. SEE ENLARGED AREA PLANS FOR KEYNOTES.

4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.

1-HOUR FIRE BARRIER

WALL RATING LEGEND:

2-HOUR FIRE BARRIER

SMOKE BARRIER

2-HOUR FIRE SMOKE

BARRIER

FIRE RATING

SMOKE AND FIRE RATING

1-HOUR FIRE SMOKE

BARRIER

SMOKE PARTITION

SMOKE RESISTIVE

CORRIDOR WALL

4S05 08-01

08-7109-01

09-01

4CS05A

09-01

09-01

08-71

08-71

09-01 2 C

S

09-01

09-01

2W41 05-61

05-61

09-01

2W44

09-01

05-6105-61

09-01

09-01

4CE05

09-01

08-71

08-71

4CS04

09-0109-01

08-71

08-01

08-01

08-71

4CS07A

09-01

09-01

4CS05

C

S

09-01

09-01

09-01 09-01

08-71

08-71

08-7108-71

TEMPORARY PARTITION

NEW CONSTRUCTION LEGEND:

PLAN NORTH

TRUE NORTH

NORTH ARROW

4CS03

09-01

09-0108-01

08-71

08-71

08-01

C

09-01

08-71

09-01

4CW07

09-01 09-01

08-71

08-71

09-01

09-01

09-01

09-01

4W54

4W52

C

W

08-01

05-60

08-01

09-02

08-0108-01

09-02

09-01

09-01

4W39

09-01

09-01

08-71

08-71

C

S

09-01

09-01

08-0108-01

E

09-01

08-71

09-01

6CW03

09-0109-01

08-71

S

T

09-01

09-01

08-81

9ST03

09-01

09-01

08-81

C

3 09-01

09-01

SP103

09-0109-01 113

09-0109-01

08-01

08-71

A

09-01

08-01

02-11

-7

09-01

09-02

08-01

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

FOUR FRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

STAMP: ARCHITECT/ENGINEER OF RECORD:

4F PROJECT NO: 19.2481.A26 40

/2 /2

:2

:1

P M

8/28/2024

NEW CONSTRUCTION PLANS -

ENLARGED

A1.12

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

JEKP

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

CONSTRUCTION DOCUMENTS

02-11 PROVIDE AND INSTALL TEMPORARY VESTIBULE TO SEPERATE

AREAS OF CONSTRUCTION ACTIVITY FROM ADJACENT AREAS

THAT WILL REMAIN OCCUPIED AND OPERATIONAL.

05-60 UPDATE/REPLACE HARDWARE AS SPECIFIED, SEE DOOR

SCHEDULE.

05-61 UPDATE/REPLACE HINGES AS SPECIFIED, SEE SPECS.

08-01 UPDATE/REINSTALL DOOR, SEE SPECS AND DOOR SCHEDULE

08-71 UPDATE DOOR OPERATOR, SEE SPECS.

08-81 REPLACE DOOR GLAZING, SEE DOOR SCHEDULE.

09-01 PATCH AND REPAIR ANY DAMAGE AS A RESULT FROM THE

REMOVAL OF THE TEMPORARY PARTITION.

09-02 PATCH AND REPAIR ANY DAMAGE AS A RESULT FROM THE

REMOVAL OF THE DOOR FRAME.

GENERAL NOTES:

KEYNOTES:

1/4" = 1'-0"

BUILDING 1 - DOOR 4S05 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 4CS05A - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 2CS08 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 2W41 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 2W44 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 4CE05 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 4CS04 ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 4CS07A - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOORS 4CS05, 4CS06 -

ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOORS 4CS03 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 4C10 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 4CW07 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOORS 4W52, 4W54,

4CW10 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 4W39 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 5CS02 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 5E03 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 6CW03 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 9ST02 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 1 - DOOR 9ST03 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 2 - DOOR 1C03 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 2 - DOOR 103 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 2 - DOOR 113 - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 2 - DOOR 113A - ENLARGED PLAN - NEW

1/4" = 1'-0"

BUILDING 7 - DOOR 03-7 - ENLARGED PLAN - NEW

ALUM ALUMINUM

F FLUSH FULL

FG FULL GLASS

FRP FIBERGLASS REINFORCED POLYMER

FTF FACTORY TRANSPARENT FINISH

HM HOLLOW METAL

ME MATCH EXISTING

NV NARROW VIEW

PTE PAINT TO MATCH EXISTING

SG SPLIT GLASS

STE STAIN TO MATCH EXISTING

PIV PERSONAL IDENTITY VERIFICATION

VV VISION VIEW

WD WOOD

DOOR LEGEND:

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

FOUR FRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

STAMP: ARCHITECT/ENGINEER OF RECORD:

4F PROJECT NO: 19.2481.A26 40

/2 /2

:2

:1

P M

8/28/2024

DOOR SCHEDULES

A6.00

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

JEKP

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

CONSTRUCTION DOCUMENTS

DOOR SCHEDULE - BUILDING 1

Level

DOOR

NUMBER FIRE RATING

PANEL

WIDTH

PANEL

HEIGHT

PANEL

THICKNESS

PANEL

COUNT PANEL TYPE

PANEL

MATERIAL

PANEL

FINISH

GLAZING

TYPE

FRAME

TYPE

FRAME

MATERIAL FRAME FINISH HEAD JAMB SILL

HARDWARE

GROUP

NEW

OPERATOR

NEW

PIV PHASING NOT USED COMMENTS

BUILDING 1

BASEMENT BC07 --- 3' - 8" 7' - 0" --- 1 HG ALUM FTF --- AL-002 ALUM FTF 5/A6.01 10/A6.01 11/A6.01 02 NO NO COORDINATE WITH COR NEW ALUM DOOR AND FRAME REUSE ACCESS CONTROL AND OPERATOR, ADD INSIDE ACTUATOR / MAINTAIN MOTION SENSORS IN THE

PATH OF EGRESS

BASEMENT BCS03B 90 MIN. 3' - 0" 7' - 0" 1 3/4" 1 NV EXISTING PTE --- EXISTING HM PTE --- --- --- 03 NO NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS BW107, BW101, BCW02

ADD NEW MOTION SENSOR / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS

BASEMENT BCW02 90 MIN. 7' - 0" 7' - 0" 1 3/4" 2 NV HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 04 NO NO START FRIDAY NIGHT AND FINISH BY

SUNDAY NIGHT AND NOT AT THE SAME

TIME AS BCS03B, BW107, BW101

NEW DOOR, FRAME AND HARDWARE

BASEMENT BE00 --- 3' - 0" 6' - 0" 1 3/4" 1 F HM PTE --- HM-001 HM PTE 3/A6.01 8/A6.01 --- 01 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE FRAME SET IN BRICK VENEER WITH CONCRETE WALLS

BASEMENT BE01 --- 3' - 0" 7' - 0" 1 3/4" 1 F HM PTE --- 4 - SIDED HM PTE 4/A6.01 9/A6.01 --- 01 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE FRAME SET IN BRICK VENEER WITH CONCRETE WALLS

BASEMENT BE24 45 MIN. 6' - 0" 7' - 0" 1 3/4" 2 NV HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 05 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE RECONNECT ACCESS CONTROL

BASEMENT BS04 --- 4' - 0" 7' - 0" 1 3/4" 1 F WD STE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 06 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE

BASEMENT BW12A --- 3' - 0" 7' - 0" 1 3/4" 1 F HM PTE --- HM-001 HM PTE 3/A6.01 8/A6.01 --- 07 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE FRAME SET IN BRICK VENEER WITH CONCRETE WALLS

BASEMENT BW101 --- 7' - 0" 7' - 0" 1 3/4" 2 NV EXISTING EXISTING --- EXISTING EXISTING EXISTING --- --- --- 03 NO NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS BCS03B, BW107, BCW02

ADD NEW MOTION SENSOR

BASEMENT BW107 --- 6' - 0" 7' - 0" 1 3/4" 2 NV EXISTING PTE --- EXISTING EXISTING FTF --- --- --- 03 NO NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS BW101, BCW02, BCS03B

ADD NEW MOTION SENSOR / PAINT EXISITING HM DOOR AND FRAME

BASEMENT BW110C 45 MIN. 3' - 0" 7' - 0" 1 3/4" 1 F HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 08 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE RECONNECTING ACCESS CONTROL, NEW ELECTRIC STRIKE

BASEMENT BW114 45 MIN. 3' - 8" 7' - 0" 1 3/4" 1 NV HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 08 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE RECONNECTING ACCESS CONTROL, NEW ELECTRIC STRIKE, NARROW LIGHT GLASS

BASEMENT BW115 45 MIN. 3' - 8" 7' - 0" 1 3/4" 1 NV HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 08 NO NO COORDINATE WITH COR NEW DOOR AND FRAME / TO MATCH WARD / FIRE RATED GLASS / CLASSROOM W/ NARROW LIGHT

LEVEL 1 1C07 --- 3' - 6" 7' - 0" 1 3/4" 1 F EXISTING STE --- EXISTING EXISTING PTE --- --- --- 09 YES NO COORDINATE WITH COR ADD OPERATOR AND PUSH BUTTON OPENER AND TIE INTO EXISTING ACCESS CONTROL

LEVEL 1 1CN01 --- 12' - 6" 7' - 0" --- 2 ME ALUM ME --- AL-101 ALUM ME 2/A6.01 7/A6.01 --- SLIDER NO NO NIGHT OR WEEKEND, MAINTAIN EGRESS, FIREWATCH

NEW AUTO SLIDING DOORS / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS

LEVEL 1 1CN01A --- 12' - 6" 7' - 0" --- 2 ME ALUM ME --- AL-101 ALUM ME 2/A6.01 7/A6.01 --- SLIDER NO NO NIGHT OR WEEKEND, MAINTAIN EGRESS, FIREWATCH

NEW AUTO SLIDING DOORS / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS

LEVEL 1 1CN03 --- 5' - 8" 7' - 0" 1 3/4" 2 UNEVEN HG WD STE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 10 YES YES COORDINATE WITH COR NEW DOOR AND FRAME AND HARDWARE- 3'-8" PANEL WITH HALF GLASS AND SOLID PANEL FOR 2'-0" FLUSH PANEL WITH ELEC EXIT

DEVICE

LEVEL 1 1CN03A --- 4' - 0" 7' - 0" 1 3/4" 1 VV WD STE --- HM HM PTE 1/A6.01 6/A6.01 --- 28 YES YES COORDINATE WITH COR REPLACE DOOR AND FRAME ADD ACCESS CONTROL ADD OPERATOR

LEVEL 1 1CW07 --- 6' - 0" 7' - 0" 1 3/4" 2 FG EXISTING PTE --- EXISTING ALUM ALUM --- --- --- 15 YES NO NIGHT, MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS

LEVEL 1 1CW07A --- 6' - 4" 7' - 0" 1 3/4" 2 FG EXISTING PTE --- EXISTING ALUM FTF --- --- --- 15 YES NO NIGHT, MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS

LEVEL 1 1E06 --- 3' - 0" 7' - 0" 1 3/4" 1 F WD STE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 16 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE

LEVEL 1 1W36 SMOKE

BARRIER

3' - 6" 7' - 0" 1 3/4" 1 F EXISTING PTE --- EXISTING HM PTE --- --- --- 09 YES NO COORDINATE WITH COR ADD OPERATOR AND PUSH BUTTON OPENER AND TIE INTO EXISTING ACCESS CONTROL / MAINTAIN MOTION SENSORS IN THE PATH OF

EGRESS

LEVEL 1 1W50 --- 6' - 5 1/2" 7' - 0" 1 3/4" 2 FG EXISTING PTE --- EXISTING ALUM ALUM --- --- --- 15 YES NO NIGHT OR WEEKEND, MAINTAIN EGRESS, FIREWATCH

REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS

LEVEL 2 2CS08 --- 4' - 0" 7' - 0" 1 3/4" 1 FG EXISTING STE --- EXISTING HM PTE --- --- --- N/A YES NO NIGHT OR WEEKEND ADD OPERATOR, MOVE EXISTING SENSOR, ADD HIDDEN PUSH BUTTON AT RECEPTION DESK, COORDINATE LOCATION WITH COR. /

MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS

LEVEL 2 2W41 --- 5' - 8" 9' - 0" 1 3/4" 2 UNEVEN F WD - LEAD

LINED

STE --- HM - LEAD

LINED

HM PTE --- --- --- 21 NO NO NOT AT THE SAME TIME AS 2W44 REPLACE WOOD SLAB DOORS AND HARDWARE

LEVEL 2 2W44 --- 5' - 8" 9' - 0" 1 3/4" 2 UNEVEN F WD - LEAD

LINED

STE --- HM - LEAD

LINED

HM PTE --- --- --- 21 NO NO NOT AT THE SAME TIME AS 2W41 REPLACE WOOD SLAB DOORS AND HARDWARE

LEVEL 4 4C10 --- 4' - 0" 7' - 0" 1 3/4" 1 F EXISTING STE --- EXISTING HM PTE --- --- --- 18 YES NO MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS

LEVEL 4 4CE05 SMOKE

BARRIER

7' - 0" 7' - 0" 1 3/4" 2 F EXISTING STE --- EXISTING HM PTE 1/A6.01 6/A6.01 --- 24 YES NO MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR ADD SMOKE SEALS

LEVEL 4 4CS03 SMOKE

BARRIER

7' - 0" 7' - 0" 1 3/4" 2 F EXISTING STE --- EXISTING HM PTE 1/A6.01 6/A6.01 --- 25 YES NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS 4CS04

REMOVE AND REPLACE OPERATOR / ADD NEW UL ARMOR PLATES / SHIM DOOR TO MEET NFPA101 REQUIREMENTS / MAINTAIN MOTION

SENSOR IN THE PATH OF EGRESS

LEVEL 4 4CS04 --- 7' - 0" 7' - 0" --- 2 F EXISTING STE --- EXISTING HM PTE --- --- --- 25 YES NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS 4CS03

REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSOR IN THE PATH OF EGRESS

LEVEL 4 4CS05 SMOKE

BARRIER

7' - 0" 7' - 0" --- 2 F EXISTING STE --- EXISTING HM PTE --- --- --- 23 YES NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS 4CS06 OR 4CS05A,

MAINTAIN EGRESS

REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSOR IN THE PATH OF EGRESS

LEVEL 4 4CS05A --- 7' - 0" 7' - 0" --- 2 F EXISTING STE --- EXISTING HM PTE --- --- --- 23 YES NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS 4CS06 OR 4CS05,

MAINTAIN EGRESS

REMOVE AND REPLACE OPERATOR

LEVEL 4 4CS06 --- 7' - 0" 7' - 0" 1 3/4" 2 F EXISTING STE --- EXISTING HM PTE --- --- --- 26 YES NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS 4CS05 OR 4CS05A,

MAINTAIN EGRESS

REMOVE AND REPLACE OPERATOR AND ARMOR PLATES / MAINTAIN MOTIONSENSORS IN THE PATH OF EGRESS

LEVEL 4 4CS07A SMOKE

BARRIER

7' - 0" 7' - 0" 1 3/4" 2 F EXISTING STE --- EXISTING HM PTE --- --- --- 27 NO NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS 4CS05, 4CS05A, 4CS06,

MAINTAIN EGRESS

REMOVE AND REPLACE ARMOR PLATE

LEVEL 4 4CW07 --- 7' - 0" 7' - 0" 1 3/4" 2 NV EXISTING PTE --- EXISTING HM PTE --- --- --- 23 YES NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS 4W39, MAINTAIN EGRESS

REMOVE AND REPLACE OPERATOR

LEVEL 4 4CW10 --- 7' - 6" 7' - 0" 1 3/4" 2 F EXISTING PTE --- EXISTING HM PTE --- --- --- N/A NO NO ANYTIME REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSOR IN THE PATH OF EGRESS

LEVEL 4 4S05 --- 3' - 0" 7' - 0" 1 3/4" 1 VV WD - LEAD

LINED

STE LEAD LINED

TO MATCH

DOOR

HM - LEAD

LINED

HM PTE 1/A6.01 6/A6.01 --- 28 YES NO COORDINATE WITH COR REPLACE DOOR AND FRAME ACCESS CONTROL ADD OPERATOR LEAD LINED DOOR / 4'-7", ENSURE LEAD LINER OVERLAPS DRY WALL.

LEVEL 4 4W39 SMOKE

BARRIER

7' - 0" 7' - 0" 1 3/4" 2 F EXISTING PTE --- EXISTING HM PTE --- --- --- 15 YES NO NIGHT OR WEEKEND AND NOT AT THE

SAME TIME AS 4CW07, MAINTAIN

EGRESS

REMOVE AND REPLACE OPERATOR

LEVEL 4 4W52 --- 3' - 0" 7' - 0" 1 3/4" 1 NV WD STE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 32 NO YES COORDINATE WITH COR NEW FRAME, DOOR AND HARDWARE

LEVEL 4 4W54 45 MIN. 4' - 0" 7' - 0" 1 3/4" 1 F HM PTE --- EXISTING HM PTE --- --- --- 31 NO YES COORDINATE WITH COR EXISTING FRAME NEW DOOR AND HARDWARE

LEVEL 5 5CS02 --- 5' - 7 5/8" 7' - 0" 1 3/4" 2 UNEVEN NV HM PTE --- HM-002 HM PTE 1/A6.01 6/A6.01 --- 33 NO NO NIGHT OR WEEKEND, MAINTAIN EGRESS REPLACE DOOR FRAME AND HARDWARE RECONNECT ACCESS CONTROL

LEVEL 5 5E03 45 MIN. 3' - 0" 7' - 0" 1 3/4" 1 F EXISTING STE --- EXISTING HM PTE --- --- --- 18 YES NO ANYTIME REMOVE AND REPLACE OPERATOR

LEVEL 6 6CW03 --- 3' - 8" 7' - 0" 1 3/4" 1 SG EXISTING PTE --- EXISTING HM PTE --- --- --- 18 YES NO MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR

LEVEL 9 9ST02 90 MIN. 3' - 8" 7' - 0" 1 3/4" 1 NV EXISTING PTE CLEAR AND

RATED

EXISTING HM PTE 1/A6.01 6/A6.01 --- N/A NO NO MAINTAIN EGRESS REMOVE AND REPLACE FIRE RATED GLASS / 90 MIN.

LEVEL 9 9ST03 90 MIN. 3' - 8" 7' - 0" 1 3/4" 1 NV EXISTING PTE CLEAR AND

RATED

EXISTING HM PTE 3/A6.01 8/A6.01 --- N/A NO NO MAINTAIN EGRESS REMOVE AND REPLACE FIRE RATED GLASS / 90 MIN., ADD NEW SEALS

DOOR SCHEDULE - BUILDINGS 2, 7, AND 50

Level

DOOR

NUMBER FIRE RATING

PANEL

WIDTH

PANEL

HEIGHT

PANEL

THICKNESS

PANEL

COUNT PANEL TYPE

PANEL

MATERIAL

PANEL

FINISH

GLAZING

TYPE

FRAME

TYPE

FRAME

MATERIAL FRAME FINISH HEAD JAMB SILL

HARDWARE

GROUP

NEW

OPERATOR

NEW

PIV PHASING NOT USED COMMENTS

BUILDING 2

LEVEL 1 1C03 45 MIN. 7' - 4" 7' - 0" 1 3/4" 2 NV EXISTING PTE --- EXISTING HM PTE --- --- --- N/A YES NO NIGHT OR WEEKEND, MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR

LEVEL 1 103 45 MIN. 7' - 0" 7' - 0" 1 3/4" 2 F HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- YES YES NIGHT OR WEEKEND, MAINTAIN EGRESS NEW DOOR, FRAME AND OPERATOR

LEVEL 1 113 --- 3' - 0" 7' - 0" 1 3/4" 1 NV EXISTING STE --- EXISTING HM PTE --- --- --- 18 YES NO NIGHT OR WEEKEND REMOVE AND REPLACE OPERATOR

LEVEL 1 113A --- 3' - 0" 7' - 0" 1 3/4" 1 FG WD STE --- EXISTING HM PTE --- --- --- 34 NO NO ANYTIME REPLACE EXISTING DOOR WITH NEW SOLID CORE DOOR WITH NO WINDOW

BUILDING 7

LEVEL 1 03-7 --- 3' - 0" 7' - 0" 1 3/4" 1 F HM PTE --- HM-001 HM PTE 4/A6.01 9/A6.01 --- 35 NO NO MAINTAIN EGRESS REPLACE EXISTING DOOR, FRAME AND HARDWARE

BUILDING 50

LEVEL 1 50C101 --- 7' - 6 1/4" 7' - 0" 1 3/4" 1 AL-FG ALUM ALUM --- AL-001 ALUM ALUM 2/A6.01 7/A6.01 --- - YES YES MAINTAIN EGRESS NEW ALUMINUM DOOR W/ OPERATORS ADD PIV AND ACCESS CONTROL

THE ARCHITECT.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE

PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND

PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL

TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR

DISCREPANCIES.

3. SEE ENLARGED AREA PLANS FOR KEYNOTES.

4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.

ALUM ALUMINUM

F FLUSH FULL

FG FULL GLASS

FRP FIBERGLASS REINFORCED POLYMER

FTF FACTORY TRANSPARENT FINISH

HM HOLLOW METAL

ME MATCH EXISTING

NV NARROW VIEW

PTE PAINT TO MATCH EXISTING

SG SPLIT GLASS

STE STAIN TO MATCH EXISTING

PIV PERSONAL IDENTITY VERIFICATION

VV VISION VIEW

WD WOOD

DOOR LEGEND:

EXISTING METAL STUD WALL

HOLLOW METAL DOOR FRAME,

FILL WITH LIGHTWEIGHT

PLASTER

DOOR, SEE SCHEDULE

SEALANT, EACH SIDE

EXISTING METAL STUD WALL

HOLLOW METAL FRAME, FILL

WITH LIGHTWEIGHT PLASTER

SEALANT, EACH SIDE

DOOR, SEE SCHEDULE

SEALANT, BOTH SIDES

HOLLOW METAL FRAME,

GROUT SOLID

DOOR, SEE SCHEDULE

EXISTING WALL SYSTEM

PATCH INTERIOR

FINISH AS REQUIRED

SEALANT, BOTH SIDES

HOLLOW METAL FRAME,

GROUT SOLID

DOOR, SEE SCHEDULE

EXISTING WALL SYSTEM

PATCH INTERIOR

FINISH AS REQUIRED

S E

E S

C H

E D

U

LE

7'

2" O

R

SEE SCHED.

2" 2"

AL-001

FRP-001

HM-001

13' - 0"

7'

6' - 10 3/8"

2" SEE SCHED.

3' - 8"

2"

2' - 8 3/8"

2"

8" 2'

2"

3'

2"

1'

2"

1'

2"

S E

E S

C H

E D

U

LE

7'

AL-101

BLANK PANELS

BEHIND

EXISTING SIGN

AL-002

WD-VV

3'

0"

2'

8"

7'

SEE SCHED.

6" 8"

SEE SCHED.

8" 8"

8" 2'

3'

0"

7'

FRP-NV

HM-NV

WD-NV

FRP-HG

HM-HG

WD-HG

SEE SCHED.

7'

FRP-F

HM-F

WD-F

3' - 0"

5'

1'

8"

7'

AL-FG

8" 8"

SEE SCHED.

1'

1'

7'

ALUMINUM FRAME

1" INSULATED GLASS OR

1/4" TEMPERED GLASS

EXISTING WALL

ALUMINUM DOOR

ALUMINUM FRAME

1/4" TEMPERED GLASS

OR 1" INSULATED GLASS

EXISTING WALL

DOOR, SEE SCHEDULE

ALUMINUM

DOOR, SEE

SCHEDULE

FACE OF EXISTING

WALL BEYOND

THRESHOLD, SET IN

SEALANT

EXISTING CONCRETE

SLAB

EXISTING METAL STUD WALL

ALUMINUM FRAME

1/4" TEMPERED GLASS

OR 1" INSULATED GLASS

DOOR, SEE SCHEDULE

EXISTING METAL STUD WALL

ALUMINUM FRAME

1" INSULATED GLASS OR

1/4" TEMPERED GLASS

ALUMINUM DOOR

SEALANT, BOTH SIDES

HOLLOW METAL FRAME,

GROUT SOLID

DOOR, SEE SCHEDULE

EXISTING WALL SYSTEM

SEALANT, BOTH SIDES

HOLLOW METAL FRAME,

GROUT SOLID

DOOR, SEE SCHEDULE

EXISTING WALL SYSTEM

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

FOUR FRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

STAMP: ARCHITECT/ENGINEER OF RECORD:

4F PROJECT NO: 19.2481.A26 40

/2 /2

:2

:2

P M

8/28/2024

DOOR ELEVATIONS AND DETAILS

A6.01

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

JEKP

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

CONSTRUCTION DOCUMENTS

GENERAL NOTES:

3" = 1'-0"

DOOR HEAD DETAIL AT METAL STUD

3" = 1'-0"

DOOR JAMB DETAIL AT METAL STUD

3" = 1'-0"

DOOR HEAD DETAIL AT CONCRETE WALL AND CMU AND METAL STUD

3" = 1'-0"

DOOR JAMB DETAIL AT CONCRETE WALL AND CMU AND METAL STUD

1/4" = 1'-0"

DOOR FRAME ELEVATIONS

1/4" = 1'-0"

DOOR PANEL ELEVATIONS

3" = 1'-0"

EXTERIOR DOOR HEAD DETAIL ALUMINUM AT EXTERIOR WALL

3" = 1'-0"

EXTERIOR DOOR JAMB DETAIL ALUMINUM AT EXTERIOR WALL

3" = 1'-0"

DR-ALUM-SILL

3" = 1'-0"

DOOR JAMB DETAIL ALUMINUM AT METAL STUD

3" = 1'-0"

DOOR HEAD DETAIL ALUMINUM AT METAL STUD

3" = 1'-0"

EXTERIOR DOOR JAMB DETAIL AT CMU AND BRICK

3" = 1'-0"

EXTERIOR DOOR HEAD DETAIL AT CMU AND BRICK

ELECTRICAL ABBREVIATIONS

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

CABLE

ACC ACCESSIBLE

ADO AUTOMATIC DOOR OPENER

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE

FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

AMP AMPERE

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAS BUILDING AUTOMATION SYSTEM

BFF BELOW FINISH FLOOR

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR

INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

INSTALLED

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

DAS DISTRIBUTED ANTENNA SYSTEM

DB DECIBEL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMERGENCY MONITORING CONTROL

PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLT FLOODLIGHT

FLUOR FLUORESCENT

FLUOR FIX FLUORESCENT FIXTURE

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G OR GND GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF

NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MVA MEGAVOLT-AMPERE

MW MEGAWATT MICROWAVE

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OF OWNER FURNISHED

OF/CI OWNER FURNISHED/CONTRACTOR

INSTALLED

OF/OI OWNER FURNISHED/OWNER INSTALLED

OL OVERLOAD

OS OCCUPANCY SENSOR

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SPDT SINGLE POLE, DOUBLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

VS VACANCY SENSOR

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

SWITCH, MULTIPOSITION

SWITCH, NORMALLY CLOSED FLOAT

SWITCH, NORMALLY CLOSED FOOT OPERATED

SWITCH, NORMALLY CLOSED LIMIT

SWITCH, NORMALLY CLOSED TIME DELAY

SWITCH, NORMALLY OPEN FLOAT

SWITCH, NORMALLY OPEN LIMIT

SWITCH, NORMALLY OPEN TEMPERATURE ACTIVATED

SWITCH, NORMALLY OPEN TIME DELAY

SWITCH, SINGLE BREAK

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

MOLDED CASE CIRCUIT BREAKER

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

HIGH-VOLTAGE OIL CIRCUIT BREAKER

HIGH-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

O.C.B.

SWITCH AND FUSE UNIT

FUSED DRAWOUT POTENTIAL TRANSFORMER

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

DELTA CONNECTION

TRANSFORMER

WYE CONNECTION

EARTH GROUND

JUNCTION BOX

PULL BOX

PRESSURE SWITCH-CLOSE ON INCREASE

PRESSURE SWITCH-OPEN ON INCREASE

FUSIBLE LINK

TIME CLOCK

GENERATOR, POWERG

BATTERY

CAPACITOR

LIGHTNING ARRESTOR

R

RECTIFIER, CATHODIC PROTECTION SANITARY

INSTANTANEOUS OVERCURRENT RELAY

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

POTHEAD

STRESS CONE

M METER

A AMMETER

V VOLTMETER

W WATTMETER

WH WATT-HOUR METER

J

PB

R

AC-TIME OVERCURRENT RELAYR

AC-DIRECTIONAL OVERCURRENT RELAYR

LOCKING OUT RELAYR

TC

SYMBOL

SWITCH, NORMALLY CLOSED

TEMPERATURE ACTIVATED

DESCRIPTION

ELECTRICAL LEGEND

(DETAILS)

DUCT, CELL FLOOR HEADER

T T DUCT, TROLLEY

DUCT, UNDERFLOOR JUNCTION BOX

RC RIGID CONDUIT LINE = RC

SUBSTATION

DISTRIBUTION PANEL

LIGHTING PANEL

PANELBOARD CABINET, FLUSH MOUNTED

PANELBOARD CABINET, SURFACE MOUNTED

C RECEPTACLE, CLOCK HANGER

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, GFCI DUPLEX

RECEPTACLE, QUADRAPLEX

DB DIRECT BURIAL CABLE = DB

P POWER DUCT = P

HI VOLTAGE SWITCH ON CONCRETE PAD

LOW VOLTAGE SWITCH ON CONCRETE PAD

DUAL POWER AND TELECOMMUNICATIONS MANHOLE

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

TRANSFORMER

WYE CONNECTION

EARTH GROUND

JUNCTION BOX

PULL BOX

J

PB

SYMBOL DESCRIPTION

ELECTRICAL LEGEND

(FLOORPLAN)

C C LADDER CABLE TRAY

BRANCH CIRCUIT HOMERUN. LINES INDICATE

NUMBER OF CIRCUITS, NEUTRAL, AND SWITCH LEG

CONDUCTORS. ONE SEPARATE GREEN GROUNDING

CONDUCTOR SHALL BE PROVIDED FOR EACH

HOMERUN; NOT SHOWN

W W WIREWAY

T P

LVS

HVS

S

B B BUSWAY

LP

DP#__

A

B

C

D

RECEPTACLE, SPECIAL PURPOSE 208V,

20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.

RECEPTACLE, SPECIAL PURPOSE 120V,

30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.

RECEPTACLE, SPECIAL PURPOSE 208V,

30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.

RECEPTACLE, SPECIAL PURPOSE 120V,

20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.

VENTILATOR OR FAN COIL UNIT OUTLET

SWITCH, SPST

VARIABLE FREQUENCY DRIVE

TIME CLOCK

R

RECTIFIER, CATHODIC PROTECTION SANITARY

INSTANTANEOUS OVERCURRENT RELAY

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

R

AC-TIME OVERCURRENT RELAYR

AC-DIRECTIONAL OVERCURRENT RELAYR

LOCKING OUT RELAYR

TC

SYMBOL DESCRIPTION

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm]

CENTERS OR AS DESIGNATED ON DRAWINGS), MTD

3'-6" [1067mm] AFF OR AS INDICATED.

VFD

CONDUIT TERMINATED W/COUPLING

(FLUSH W/FINISHED FLOOR) FOR

EXTENSION TO EQUIPMENT AS DIRECTED.

CONDUIT TERMINATED 6" [152mm] AFF IN STANDARD

BOX FOR EXTENSION TO EQUIPMENT AS DIRECTED.

SWITCH, DPST2

SWITCH, FUSEDF

SWITCH, KEY OPERATEDK

SWITCH, LOCKL

SWITCH, LOW VOLTAGE MASTERLM

SWITCH, MANUAL MOTOR STARTINGM

SWITCH, MOMENTARY CONTACTMC

MP

SWITCH, WITH PILOT LIGHTP

SWITCH, PUSH BUTTONPB

SWITCH, REMOTE CONTROLRC

SWITCH, WEATHER PROOFWP

SWITCH, EXPLOSION PROOFX

SWITCH, THREE WAY3

SWITCH, THREE WAY DIMMER3D

SWITCH, THREE WAY OCCUPANCY SENSOR3OS

SWITCH, FOUR WAY4

SWITCH, DIMMERD

SWITCH, DOOR JAMBDOOR

SWITCH, FOUR WAY OCCUPANCY SENSOR4OS

SWITCH, OCCUPANCY SENSOROS

SWITCH, PHOTOCELLPH

SWITCH, OCCUPANCY SENSOR DIMMEROSD

SWITCH, MOTOR SNAP WITH

PILOT LIGHT (THERMAL TYPE)

E

RECEPTACLE, SPECIAL PURPOSE 208V,

60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.

CABLE TELEVISION LINE = CATV

CLOSED CIRCUIT TELEVISION LINE = CCTV

FIBEROPTICS LINE = FO

COMMUNICATIONS FLOOR RECEPTACLE

PAGING SPEAKER, CEILING MOUNTED

PAGING SPEAKER, WALL MOUNTED

CATV

CCTV

FO

COMMUNICATIONS WALL RECEPTACLE

COMMUNICATIONS LINE = COMCOM

INTERCOM LINE = II

NURSE CALL LINE = NCNC

NCS NURSE'S CALL MASTER STATION

NCT NURSE CALL TERMINAL CABINET.

NURSE CALL STATION.

D = DUTY STATION. MTD 5' AFF

E = MTD 6' AFF FOR SHOWER LOCATION

MTD 4'-6" AFF FOR TUB LOCATION

MTD 3' AFF FOR TOILET LOCATION

P = PSYCHIATRIC CORRIDOR STATION WITH KEY

SWITCH

S = AUDIO VISUAL STAFF STATION MTD 5' AFF

U = UTILITY CALL STATION, MTD 5' AFF

NURSE CALL STATION.

D = CORRIDOR DOME LIGHT MTD 6" ABOVE DOOR

I = AUXILIARY INTERSECTIONAL DOME LIGHT

TELECOMMUNICATIONS TERMINAL CABINET

TELECOMMUNICATIONS BACKBOARD (WALL MTD)

TELECOMMUNICATIONS MANHOLE

COMMUNICATIONS CEILING RECEPTACLE

TELEVISION FLOOR RECEPTACLE

C = CAMERA (CCTV SYSTEM)

M =MONITOR (CATV SYSTEM).

AV= AUDIO VISUAL (CONFERENCE ROOM

CONNECTION RECEPTACLES)

M

M

M

S

S

AUDIO VISUAL LINE = AVAV

TTB

N D

N D

RECEPTACLE, SWITCHED DUPLEXS

F

G

H

RECEPTACLE, SPECIAL PURPOSE 208V,

30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.

RECEPTACLE, SPECIAL PURPOSE 208V,

50A, 3 PHASE, 3 POLE, 4W, NEMA 15-50R.

RECEPTACLE, SPECIAL PURPOSE 208V,

60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,

GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN

FLEXIBLE CORD (CENTER LINE OF OUTLET: 6'-6"

[1981mm] AFF. MINIMUM).

TELEVISION WALL RECEPTACLE

C = CAMERA (CCTV SYSTEM)

M =MONITOR (CATV SYSTEM).

AV= AUDIO VISUAL (CONFERENCE ROOM

CONNECTION RECEPTACLES)

TELEVISION CEILING RECEPTACLE

C = CAMERA (CCTV SYSTEM)

M =MONITOR (CATV SYSTEM).

AV= AUDIO VISUAL (CONFERENCE ROOM

CONNECTION RECEPTACLES)

SYMBOL DESCRIPTION

J

RECEPTACLE, SPECIAL PURPOSE 208V,

20A, 3 PHASE, 3 POLE, 4W, NEMA 15-20R.

EH ELECTRIC POWER TRANSFER HINGE

ES ELECTRONIC STRIKE

DOOR CONTACT / DOOR POSITION SWITCH

MAGNETIC DOOR LOCKING DEVICE

C CAMERA

C 360 CAMERA

CARD ACCESS READER; LETTER INDICATES AS

FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN

M-MULLION P-PEDESTAL R-RACK S-SURFACE

W-WALL

T=TECHNOLOGY/TYPE

B-BARCODE M-MAG STRIP

F-ELEVATOR FLOOR CALL P-PROXIMITY

H-ELEVATOR HALL CALL S-SMART CARD

T-TOKEN

DURESS/PANIC ALARM PUSH BUTTON

M

T

M

T

M

T

ELECTROMAGNETIC TYPE DOOR HOLDER OUTLETDH

ELECTRONIC LOCK; LETTER INDICATES AS

FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN

M-MULLION P-PEDESTAL R-RACK S-SURFACE

W-WALL

T=TECHNOLOGY/TYPE

D-DEADBOLT H-HYBRID L-LATCH SET

M-MAGNETIC S-STRIKE

INTERCOM; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN

M-MULLION P-PEDESTAL R-RACK S-SURFACE

W-WALL

T=TECHNOLOGY/TYPE

M-MASTER S-SUBSTATION

ITEMS SHOWN IN GRAY ARE EXISTING TO REMAIN

DEMOLITION PLANS: SOLID DARK ITEMS ARE TO BE

REMOVED OR MODIFIED.

NEW PLANS: SOLID DARK ITEMS ARE TO BE

ADDED OR MODIFIED.

DASHED ITEMS ARE INSTALLED BELOW REFERENCED

PLAN

CONNECT TO EXISTING

ELECTRONIC DOOR OPERATOR

DOOR ACTUATOR SWITCH / POSITION SWITCH

PIR EGRESS SENSOR

MAGNETIC DOOR HOLD OPEN

MID MOTION INTRUSION DETECTOR

SSTV SECURITY SURVEILLANCE TELEVISION

DC

MAG

EDO

DAS

PES

DH

A. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO

MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT

HOMERUN SHALL HAVE A SEPERATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

B. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES

AND TYPES OF EMERGENCY AND NORMAL BRANCH

WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN

DEVICES.

C. REFER TO CEILING PLANS FOR LOCATION OF CEILING

AND WALL MOUNTED DEVICES, AS REQUIRED.

D. MINIMUM SIZE CONDUIT FOR CONTROL CIRCUITS

SHALL BE 3/4"

E. GENERAL CONTRACTOR TO FURNISH AND INSTALL

ACCESS DOORS IN WALLS AND CEILINGS WHERE ACCESS

TO CONCEALED ELECTRICAL BOXES AND DEVICES IS

REQUIRED.

H. ARMORED CABLE (AC) MAY BE USED FOR LAY-IN

FIXTURE PIGTAILS. ARMORED CABLE (AC) SHALL NOT BE

USED FOR BRANCH CIRCUIT HOMERUNS. ARMORED

CABLE (AC) SHALL NOT BE USED WHERE MORE THAN

THREE CONDUCTORS (PHASE/NEUTRAL/GROUND) ARE

REQUIRED, WHERE EXPOSED; OR IN LENGTHS

EXCEEDING 20 FEET EXCEPT FOR TEMPORARY WIRING.

I. COORDINATE ALL OUTAGES WITH VHA COR PER

SPECS PRIOR TO WORK BEING DONE.

GENERAL ELECTRICAL NOTES

A. WHERE EXISTING EQUIPMENT IS BEING REMOVED,

ALL UNUSED CONDUITS AND WIRING ARE TO BE

REMOVED IN THEIR ENTIRETY. NO BOXES, CONDUIT OR

WIRING IS TO BE ABANDONED IN PLACE.

B. DISCONNECT AND REMOVE ALL WIRES BACK TO THE

OVERCURRENT DEVICE AND RELABEL AS A SPARE.

REUSE EXISTING CONDUIT IN COMPLIANCE WITH NEC.

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL

CONDUITS AND CONDUCTORS PASSING THROUGH

RENOVATED AREAS AND SERVICING UNDISTURBED

AREAS.

ELECTRICAL GENERAL NOTES - DEMOLITION

ELECTRICAL LEGENDS AND

ABBREVIATIONS

E0.00

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COMFOURFRONT

D E S I G N I N C.

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

COR / Project Engineer

CONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 of

Office of Construction and Facilities Management

Department of Veterans Affairs

Phase

CO056R7C6+O0 DOC7ME065

STAMP: ARCHITECT/ENGINEER OF RECORD:

08/28/2024

UPGRADE DOORS/DOOR

HARDWARE AT IOWA CITY VA

HEALTH CARE SYSTEM

WSWW

IOWA CITY, IOWAMATTHEW RUPPENKAMP

CONSTRUCTION

DOCUMENTS

636A8-23-102

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text No. 91134PE 91134PE91134PE

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text

WILLIAM WANGEN

CABLE TO SECURITY PANEL BY DIVISION 28

CONTRACTOR; POWER BY DIVISION 26 TO

BE AT SECURITY PANEL. COORDINATE

POWER REQUIREMENTS

WITH DIVISION 28 CONTRACTOR.

JUNCTION BOX

ABOVE ACCESSIBLE CEILING

DC DC

EH EH

BY…