These are construction documents for the Upgrade Doors/Door Hardware project at the Iowa City VA Health Care System. The project involves upgrading doors and door hardware across multiple buildings (Buildings 1, 2, 7, and 50) within the VA medical complex. Key scope includes replacing door hardware, installing new electronic door operators, adding access control devices, updating power connections, and replacing or modifying existing doors and frames. The project documents include detailed floor plans for each building level, electrical diagrams, door hardware schedules, and specific installation instructions for each door. The construction documents are dated August 28, 2024, with the project being managed by Matthew Ruppenkamp and designed by Fourfront Design, Inc. The work appears to focus on improving building security, accessibility, and functionality through comprehensive door system upgrades.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
4CE05
4CS04 4CS03
4S05
4W39
4CW07
4W54
4W52
C
W
C
4CS07A
4CS05A4CS05
C
S
A1.12
A1.12
A1.12
A1.12
A1.12
A1.12
A1.12
A1.12
A1.12
A1.12
A1.12
1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT
SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE
PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND
PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL
TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR
DISCREPANCIES.
3. SEE ENLARGED AREA PLANS FOR KEYNOTES.
4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.
1-HOUR FIRE BARRIER
WALL RATING LEGEND:
2-HOUR FIRE BARRIER
SMOKE BARRIER
2-HOUR FIRE SMOKE
BARRIER
FIRE RATING
SMOKE AND FIRE RATING
1-HOUR FIRE SMOKE
BARRIER
SMOKE PARTITION
SMOKE RESISTIVE
CORRIDOR WALL
POINT OF EGRESS
SHEET LEGEND:
NORTH ARROW
PLAN NORTH
TRUE NORTH
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOUR FRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
STAMP: ARCHITECT/ENGINEER OF RECORD:
4F PROJECT NO: 19.2481.A26 40
/2 /2
:2
:1
P M
8/28/2024
BUILDING 1, FLOOR 4 PLAN
A1.05
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
KZKP
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
CONSTRUCTION DOCUMENTS
1/16" = 1'-0"
BUILDING 1, FLOOR 4
GENERAL NOTES:
SHEET SPECIFIC NOTES:
1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR
NEW DOOR HARDWARE.
C
S
E
A1.12
A1.12
1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT
SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE
PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND
PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL
TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR
DISCREPANCIES.
3. SEE ENLARGED AREA PLANS FOR KEYNOTES.
4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.
1-HOUR FIRE BARRIER
WALL RATING LEGEND:
2-HOUR FIRE BARRIER
SMOKE BARRIER
2-HOUR FIRE SMOKE
BARRIER
FIRE RATING
SMOKE AND FIRE RATING
1-HOUR FIRE SMOKE
BARRIER
SMOKE PARTITION
SMOKE RESISTIVE
CORRIDOR WALL
POINT OF EGRESS
SHEET LEGEND:
NORTH ARROW
PLAN NORTH
TRUE NORTH
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOUR FRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
STAMP: ARCHITECT/ENGINEER OF RECORD:
4F PROJECT NO: 19.2481.A26 40
/2 /2
:2
:1
P M
8/28/2024
BUILDING 1, FLOOR 5 PLAN
A1.06
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
KZKP
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
CONSTRUCTION DOCUMENTS
1/16" = 1'-0"
BUILDING 1, FLOOR 5
GENERAL NOTES:
SHEET SPECIFIC NOTES:
1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR
DN
6CW03
A1.12
1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT
SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE
PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND
PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL
TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR
DISCREPANCIES.
3. SEE ENLARGED AREA PLANS FOR KEYNOTES.
4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.
1-HOUR FIRE BARRIER
WALL RATING LEGEND:
2-HOUR FIRE BARRIER
SMOKE BARRIER
2-HOUR FIRE SMOKE
BARRIER
FIRE RATING
SMOKE AND FIRE RATING
1-HOUR FIRE SMOKE
BARRIER
SMOKE PARTITION
SMOKE RESISTIVE
CORRIDOR WALL
POINT OF EGRESS
SHEET LEGEND:
NORTH ARROW
PLAN NORTH
TRUE NORTH
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOUR FRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
STAMP: ARCHITECT/ENGINEER OF RECORD:
4F PROJECT NO: 19.2481.A26 40
/2 /2
:2
:1
P M
8/28/2024
BUILDING 1, FLOOR 6 PLAN
A1.07
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
KZKP
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
CONSTRUCTION DOCUMENTS
1/16" = 1'-0"
BUILDING 1, FLOOR 6
GENERAL NOTES:
SHEET SPECIFIC NOTES:
1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR
S
T
9ST03
A1.12
A1.12
1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT
SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE
PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND
PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL
TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR
DISCREPANCIES.
3. SEE ENLARGED AREA PLANS FOR KEYNOTES.
4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.
1-HOUR FIRE BARRIER
WALL RATING LEGEND:
2-HOUR FIRE BARRIER
SMOKE BARRIER
2-HOUR FIRE SMOKE
BARRIER
FIRE RATING
SMOKE AND FIRE RATING
1-HOUR FIRE SMOKE
BARRIER
SMOKE PARTITION
SMOKE RESISTIVE
CORRIDOR WALL
POINT OF EGRESS
SHEET LEGEND:
NORTH ARROW
PLAN NORTH
TRUE NORTH
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOUR FRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
STAMP: ARCHITECT/ENGINEER OF RECORD:
4F PROJECT NO: 19.2481.A26 40
/2 /2
:2
:1
P M
8/28/2024
BUILDING 1, FLOOR 9 PLAN
A1.08
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
KZKP
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
CONSTRUCTION DOCUMENTS
1/16" = 1'-0"
BUILDING 1, FLOOR 9
GENERAL NOTES:
SHEET SPECIFIC NOTES:
1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR
DN
UP
UP
1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT
SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE
PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND
PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL
TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR
DISCREPANCIES.
3. SEE ENLARGED AREA PLANS FOR KEYNOTES.
4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.
C
A
A1.12
A1.12
A1.12
A1.12
POINT OF EGRESS
SHEET LEGEND:
NORTH ARROW
PLAN NORTH
TRUE NORTH
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOUR FRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
STAMP: ARCHITECT/ENGINEER OF RECORD:
4F PROJECT NO: 19.2481.A26 40
/2 /2
:2
:1
P M
8/28/2024
BUILDING 2, FLOOR 1 PLAN
A1.09
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
KZKP
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
CONSTRUCTION DOCUMENTS
GENERAL NOTES:
SHEET SPECIFIC NOTES:
1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR
NEW DOOR HARDWARE.
1/8" = 1'-0"
BUILDING 2, FLOOR 1
-7 A1.12
1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT
SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE
PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND
PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL
TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR
DISCREPANCIES.
3. SEE ENLARGED AREA PLANS FOR KEYNOTES.
4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.
POINT OF EGRESS
SHEET LEGEND:
NORTH ARROW
PLAN NORTH
TRUE NORTH
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOUR FRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
STAMP: ARCHITECT/ENGINEER OF RECORD:
4F PROJECT NO: 19.2481.A26 40
/2 /2
:2
:1
P M
8/28/2024
BUILDING 7 FLOOR PLANS
A1.10
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
KZKP
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
CONSTRUCTION DOCUMENTS
1/8" = 1'-0"
BUILDING 7
GENERAL NOTES:
SHEET SPECIFIC NOTES:
1. SEE THE DOOR HARDWARE SCHEDULE AND SPECIFICATIONS FOR
1. SHEET SIZE FOR PROPER SCALE IS 42X30. CONTRACTOR SHALL NOT
SCALE DRAWINGS BUT SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE
PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND
PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL
TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR
DISCREPANCIES.
3. SEE ENLARGED AREA PLANS FOR KEYNOTES.
4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.
1-HOUR FIRE BARRIER
WALL RATING LEGEND:
2-HOUR FIRE BARRIER
SMOKE BARRIER
2-HOUR FIRE SMOKE
BARRIER
FIRE RATING
SMOKE AND FIRE RATING
1-HOUR FIRE SMOKE
BARRIER
SMOKE PARTITION
SMOKE RESISTIVE
CORRIDOR WALL
BE24
09-01
08-01
09-02
09-01
B E
09-02
08-01
B E
09-02
08-01
B W
A
09-02
08-01
09-01 09-01
09-0109-01
B C
W
09-02
08-01
BS04
09-02
08-01
09-01
B W
09-0109-01
BCS03B
09-0109-01
08-72
B W
09-0109-01
08-72
B W
C
09-01
09-02
B W
09-01
09-02
08-01
09-01
1CN01A
1CN01
09-01
09-01
08-01
09-02
09-02
08-01
B W
09-01
08-01
09-02
09-01
B C
09-01
09-02
08-01
05-60
09-01
1E06
09-01
09-02
08-01
09-01
C
N
09-01
09-01
09-03
09-03
09-04
09-5009-50
09-01
W
08-71
09-01
TEMPORARY PARTITION
NEW CONSTRUCTION LEGEND:
PLAN NORTH
TRUE NORTH
NORTH ARROW
1C07
09-0109-01
09-01 09-01
1CW07
08-71
09-01
1W501CW07A
08-71 08-71
09-01
C
09-01
09-01
1CN03A
09-01
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOUR FRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
STAMP: ARCHITECT/ENGINEER OF RECORD:
4F PROJECT NO: 19.2481.A26 40
/2 /2
:2
:1
P M
8/28/2024
NEW CONSTRUCTION PLANS -
ENLARGED
A1.11
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
JEKP
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
CONSTRUCTION DOCUMENTS
05-60 UPDATE/REPLACE HARDWARE AS SPECIFIED, SEE DOOR SCHEDULE.
08-01 UPDATE/REINSTALL DOOR, SEE SPECS AND DOOR SCHEDULE
08-71 UPDATE DOOR OPERATOR, SEE SPECS.
08-72 UPDATE MOTION SENSOR, SEE SPECS.
09-01 PATCH AND REPAIR ANY DAMAGE AS A RESULT FROM THE REMOVAL
OF THE TEMPORARY PARTITION.
09-02 PATCH AND REPAIR ANY DAMAGE AS A RESULT FROM THE REMOVAL
OF THE DOOR FRAME.
09-03 PATCH AND REPAIR ANY DAMAGE AS A RESULT FROM THE REMOVAL
OF THE DOOR FRAME AND EXISTING WALL.
09-04 MATCH EXISTING FINISH.
09-50 EXTEND OR REPLACE CEILING AS NEEDED DUE TO DOOR
RELOCATION. MATCH EXISTING.
GENERAL NOTES:
KEYNOTES:
1/4" = 1'-0"
BUILDING 1 - DOOR BE24 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BE01 - ENLARGED
PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BE00 - ENLARGED
PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BW12A -
ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BCW02 -
ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BS04 - ENLARGED
PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BW101 -
ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BCS03B -
ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BW107 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BW110C -
ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BW114 -
ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOORS 1CN01 AND 1CN01A - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BW115 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR BC07 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 1E06 - ENLARGED
PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 1CN03 -
ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 1W36 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 1C07 - ENLARGED
PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 1CW07 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOORS 1W50 AND 1CW07A - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDINGS 50 - DOORS 50C101 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 1CN03A -
ENLARGED PLAN - NEW
THE ARCHITECT.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE
PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND
PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL
TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR
DISCREPANCIES.
3. SEE ENLARGED AREA PLANS FOR KEYNOTES.
4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.
1-HOUR FIRE BARRIER
WALL RATING LEGEND:
2-HOUR FIRE BARRIER
SMOKE BARRIER
2-HOUR FIRE SMOKE
BARRIER
FIRE RATING
SMOKE AND FIRE RATING
1-HOUR FIRE SMOKE
BARRIER
SMOKE PARTITION
SMOKE RESISTIVE
CORRIDOR WALL
4S05 08-01
08-7109-01
09-01
4CS05A
09-01
09-01
08-71
08-71
09-01 2 C
S
09-01
09-01
2W41 05-61
05-61
09-01
2W44
09-01
05-6105-61
09-01
09-01
4CE05
09-01
08-71
08-71
4CS04
09-0109-01
08-71
08-01
08-01
08-71
4CS07A
09-01
09-01
4CS05
C
S
09-01
09-01
09-01 09-01
08-71
08-71
08-7108-71
TEMPORARY PARTITION
NEW CONSTRUCTION LEGEND:
PLAN NORTH
TRUE NORTH
NORTH ARROW
4CS03
09-01
09-0108-01
08-71
08-71
08-01
C
09-01
08-71
09-01
4CW07
09-01 09-01
08-71
08-71
09-01
09-01
09-01
09-01
4W54
4W52
C
W
08-01
05-60
08-01
09-02
08-0108-01
09-02
09-01
09-01
4W39
09-01
09-01
08-71
08-71
C
S
09-01
09-01
08-0108-01
E
09-01
08-71
09-01
6CW03
09-0109-01
08-71
S
T
09-01
09-01
08-81
9ST03
09-01
09-01
08-81
C
3 09-01
09-01
SP103
09-0109-01 113
09-0109-01
08-01
08-71
A
09-01
08-01
02-11
-7
09-01
09-02
08-01
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOUR FRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
STAMP: ARCHITECT/ENGINEER OF RECORD:
4F PROJECT NO: 19.2481.A26 40
/2 /2
:2
:1
P M
8/28/2024
NEW CONSTRUCTION PLANS -
ENLARGED
A1.12
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
JEKP
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
CONSTRUCTION DOCUMENTS
02-11 PROVIDE AND INSTALL TEMPORARY VESTIBULE TO SEPERATE
AREAS OF CONSTRUCTION ACTIVITY FROM ADJACENT AREAS
THAT WILL REMAIN OCCUPIED AND OPERATIONAL.
05-60 UPDATE/REPLACE HARDWARE AS SPECIFIED, SEE DOOR
SCHEDULE.
05-61 UPDATE/REPLACE HINGES AS SPECIFIED, SEE SPECS.
08-01 UPDATE/REINSTALL DOOR, SEE SPECS AND DOOR SCHEDULE
08-71 UPDATE DOOR OPERATOR, SEE SPECS.
08-81 REPLACE DOOR GLAZING, SEE DOOR SCHEDULE.
09-01 PATCH AND REPAIR ANY DAMAGE AS A RESULT FROM THE
REMOVAL OF THE TEMPORARY PARTITION.
09-02 PATCH AND REPAIR ANY DAMAGE AS A RESULT FROM THE
REMOVAL OF THE DOOR FRAME.
GENERAL NOTES:
KEYNOTES:
1/4" = 1'-0"
BUILDING 1 - DOOR 4S05 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 4CS05A - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 2CS08 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 2W41 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 2W44 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 4CE05 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 4CS04 ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 4CS07A - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOORS 4CS05, 4CS06 -
ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOORS 4CS03 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 4C10 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 4CW07 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOORS 4W52, 4W54,
4CW10 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 4W39 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 5CS02 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 5E03 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 6CW03 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 9ST02 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 1 - DOOR 9ST03 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 2 - DOOR 1C03 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 2 - DOOR 103 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 2 - DOOR 113 - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 2 - DOOR 113A - ENLARGED PLAN - NEW
1/4" = 1'-0"
BUILDING 7 - DOOR 03-7 - ENLARGED PLAN - NEW
ALUM ALUMINUM
F FLUSH FULL
FG FULL GLASS
FRP FIBERGLASS REINFORCED POLYMER
FTF FACTORY TRANSPARENT FINISH
HM HOLLOW METAL
ME MATCH EXISTING
NV NARROW VIEW
PTE PAINT TO MATCH EXISTING
SG SPLIT GLASS
STE STAIN TO MATCH EXISTING
PIV PERSONAL IDENTITY VERIFICATION
VV VISION VIEW
WD WOOD
DOOR LEGEND:
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOUR FRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
STAMP: ARCHITECT/ENGINEER OF RECORD:
4F PROJECT NO: 19.2481.A26 40
/2 /2
:2
:1
P M
8/28/2024
DOOR SCHEDULES
A6.00
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
JEKP
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
CONSTRUCTION DOCUMENTS
DOOR SCHEDULE - BUILDING 1
Level
DOOR
NUMBER FIRE RATING
PANEL
WIDTH
PANEL
HEIGHT
PANEL
THICKNESS
PANEL
COUNT PANEL TYPE
PANEL
MATERIAL
PANEL
FINISH
GLAZING
TYPE
FRAME
TYPE
FRAME
MATERIAL FRAME FINISH HEAD JAMB SILL
HARDWARE
GROUP
NEW
OPERATOR
NEW
PIV PHASING NOT USED COMMENTS
BUILDING 1
BASEMENT BC07 --- 3' - 8" 7' - 0" --- 1 HG ALUM FTF --- AL-002 ALUM FTF 5/A6.01 10/A6.01 11/A6.01 02 NO NO COORDINATE WITH COR NEW ALUM DOOR AND FRAME REUSE ACCESS CONTROL AND OPERATOR, ADD INSIDE ACTUATOR / MAINTAIN MOTION SENSORS IN THE
PATH OF EGRESS
BASEMENT BCS03B 90 MIN. 3' - 0" 7' - 0" 1 3/4" 1 NV EXISTING PTE --- EXISTING HM PTE --- --- --- 03 NO NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS BW107, BW101, BCW02
ADD NEW MOTION SENSOR / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS
BASEMENT BCW02 90 MIN. 7' - 0" 7' - 0" 1 3/4" 2 NV HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 04 NO NO START FRIDAY NIGHT AND FINISH BY
SUNDAY NIGHT AND NOT AT THE SAME
TIME AS BCS03B, BW107, BW101
NEW DOOR, FRAME AND HARDWARE
BASEMENT BE00 --- 3' - 0" 6' - 0" 1 3/4" 1 F HM PTE --- HM-001 HM PTE 3/A6.01 8/A6.01 --- 01 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE FRAME SET IN BRICK VENEER WITH CONCRETE WALLS
BASEMENT BE01 --- 3' - 0" 7' - 0" 1 3/4" 1 F HM PTE --- 4 - SIDED HM PTE 4/A6.01 9/A6.01 --- 01 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE FRAME SET IN BRICK VENEER WITH CONCRETE WALLS
BASEMENT BE24 45 MIN. 6' - 0" 7' - 0" 1 3/4" 2 NV HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 05 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE RECONNECT ACCESS CONTROL
BASEMENT BS04 --- 4' - 0" 7' - 0" 1 3/4" 1 F WD STE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 06 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE
BASEMENT BW12A --- 3' - 0" 7' - 0" 1 3/4" 1 F HM PTE --- HM-001 HM PTE 3/A6.01 8/A6.01 --- 07 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE FRAME SET IN BRICK VENEER WITH CONCRETE WALLS
BASEMENT BW101 --- 7' - 0" 7' - 0" 1 3/4" 2 NV EXISTING EXISTING --- EXISTING EXISTING EXISTING --- --- --- 03 NO NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS BCS03B, BW107, BCW02
ADD NEW MOTION SENSOR
BASEMENT BW107 --- 6' - 0" 7' - 0" 1 3/4" 2 NV EXISTING PTE --- EXISTING EXISTING FTF --- --- --- 03 NO NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS BW101, BCW02, BCS03B
ADD NEW MOTION SENSOR / PAINT EXISITING HM DOOR AND FRAME
BASEMENT BW110C 45 MIN. 3' - 0" 7' - 0" 1 3/4" 1 F HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 08 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE RECONNECTING ACCESS CONTROL, NEW ELECTRIC STRIKE
BASEMENT BW114 45 MIN. 3' - 8" 7' - 0" 1 3/4" 1 NV HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 08 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE RECONNECTING ACCESS CONTROL, NEW ELECTRIC STRIKE, NARROW LIGHT GLASS
BASEMENT BW115 45 MIN. 3' - 8" 7' - 0" 1 3/4" 1 NV HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 08 NO NO COORDINATE WITH COR NEW DOOR AND FRAME / TO MATCH WARD / FIRE RATED GLASS / CLASSROOM W/ NARROW LIGHT
LEVEL 1 1C07 --- 3' - 6" 7' - 0" 1 3/4" 1 F EXISTING STE --- EXISTING EXISTING PTE --- --- --- 09 YES NO COORDINATE WITH COR ADD OPERATOR AND PUSH BUTTON OPENER AND TIE INTO EXISTING ACCESS CONTROL
LEVEL 1 1CN01 --- 12' - 6" 7' - 0" --- 2 ME ALUM ME --- AL-101 ALUM ME 2/A6.01 7/A6.01 --- SLIDER NO NO NIGHT OR WEEKEND, MAINTAIN EGRESS, FIREWATCH
NEW AUTO SLIDING DOORS / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS
LEVEL 1 1CN01A --- 12' - 6" 7' - 0" --- 2 ME ALUM ME --- AL-101 ALUM ME 2/A6.01 7/A6.01 --- SLIDER NO NO NIGHT OR WEEKEND, MAINTAIN EGRESS, FIREWATCH
NEW AUTO SLIDING DOORS / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS
LEVEL 1 1CN03 --- 5' - 8" 7' - 0" 1 3/4" 2 UNEVEN HG WD STE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 10 YES YES COORDINATE WITH COR NEW DOOR AND FRAME AND HARDWARE- 3'-8" PANEL WITH HALF GLASS AND SOLID PANEL FOR 2'-0" FLUSH PANEL WITH ELEC EXIT
DEVICE
LEVEL 1 1CN03A --- 4' - 0" 7' - 0" 1 3/4" 1 VV WD STE --- HM HM PTE 1/A6.01 6/A6.01 --- 28 YES YES COORDINATE WITH COR REPLACE DOOR AND FRAME ADD ACCESS CONTROL ADD OPERATOR
LEVEL 1 1CW07 --- 6' - 0" 7' - 0" 1 3/4" 2 FG EXISTING PTE --- EXISTING ALUM ALUM --- --- --- 15 YES NO NIGHT, MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS
LEVEL 1 1CW07A --- 6' - 4" 7' - 0" 1 3/4" 2 FG EXISTING PTE --- EXISTING ALUM FTF --- --- --- 15 YES NO NIGHT, MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS
LEVEL 1 1E06 --- 3' - 0" 7' - 0" 1 3/4" 1 F WD STE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 16 NO NO COORDINATE WITH COR NEW DOOR, FRAME AND HARDWARE
LEVEL 1 1W36 SMOKE
BARRIER
3' - 6" 7' - 0" 1 3/4" 1 F EXISTING PTE --- EXISTING HM PTE --- --- --- 09 YES NO COORDINATE WITH COR ADD OPERATOR AND PUSH BUTTON OPENER AND TIE INTO EXISTING ACCESS CONTROL / MAINTAIN MOTION SENSORS IN THE PATH OF
EGRESS
LEVEL 1 1W50 --- 6' - 5 1/2" 7' - 0" 1 3/4" 2 FG EXISTING PTE --- EXISTING ALUM ALUM --- --- --- 15 YES NO NIGHT OR WEEKEND, MAINTAIN EGRESS, FIREWATCH
REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS
LEVEL 2 2CS08 --- 4' - 0" 7' - 0" 1 3/4" 1 FG EXISTING STE --- EXISTING HM PTE --- --- --- N/A YES NO NIGHT OR WEEKEND ADD OPERATOR, MOVE EXISTING SENSOR, ADD HIDDEN PUSH BUTTON AT RECEPTION DESK, COORDINATE LOCATION WITH COR. /
MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS
LEVEL 2 2W41 --- 5' - 8" 9' - 0" 1 3/4" 2 UNEVEN F WD - LEAD
LINED
STE --- HM - LEAD
LINED
HM PTE --- --- --- 21 NO NO NOT AT THE SAME TIME AS 2W44 REPLACE WOOD SLAB DOORS AND HARDWARE
LEVEL 2 2W44 --- 5' - 8" 9' - 0" 1 3/4" 2 UNEVEN F WD - LEAD
LINED
STE --- HM - LEAD
LINED
HM PTE --- --- --- 21 NO NO NOT AT THE SAME TIME AS 2W41 REPLACE WOOD SLAB DOORS AND HARDWARE
LEVEL 4 4C10 --- 4' - 0" 7' - 0" 1 3/4" 1 F EXISTING STE --- EXISTING HM PTE --- --- --- 18 YES NO MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSORS IN THE PATH OF EGRESS
LEVEL 4 4CE05 SMOKE
BARRIER
7' - 0" 7' - 0" 1 3/4" 2 F EXISTING STE --- EXISTING HM PTE 1/A6.01 6/A6.01 --- 24 YES NO MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR ADD SMOKE SEALS
LEVEL 4 4CS03 SMOKE
BARRIER
7' - 0" 7' - 0" 1 3/4" 2 F EXISTING STE --- EXISTING HM PTE 1/A6.01 6/A6.01 --- 25 YES NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS 4CS04
REMOVE AND REPLACE OPERATOR / ADD NEW UL ARMOR PLATES / SHIM DOOR TO MEET NFPA101 REQUIREMENTS / MAINTAIN MOTION
SENSOR IN THE PATH OF EGRESS
LEVEL 4 4CS04 --- 7' - 0" 7' - 0" --- 2 F EXISTING STE --- EXISTING HM PTE --- --- --- 25 YES NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS 4CS03
REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSOR IN THE PATH OF EGRESS
LEVEL 4 4CS05 SMOKE
BARRIER
7' - 0" 7' - 0" --- 2 F EXISTING STE --- EXISTING HM PTE --- --- --- 23 YES NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS 4CS06 OR 4CS05A,
MAINTAIN EGRESS
REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSOR IN THE PATH OF EGRESS
LEVEL 4 4CS05A --- 7' - 0" 7' - 0" --- 2 F EXISTING STE --- EXISTING HM PTE --- --- --- 23 YES NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS 4CS06 OR 4CS05,
MAINTAIN EGRESS
REMOVE AND REPLACE OPERATOR
LEVEL 4 4CS06 --- 7' - 0" 7' - 0" 1 3/4" 2 F EXISTING STE --- EXISTING HM PTE --- --- --- 26 YES NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS 4CS05 OR 4CS05A,
MAINTAIN EGRESS
REMOVE AND REPLACE OPERATOR AND ARMOR PLATES / MAINTAIN MOTIONSENSORS IN THE PATH OF EGRESS
LEVEL 4 4CS07A SMOKE
BARRIER
7' - 0" 7' - 0" 1 3/4" 2 F EXISTING STE --- EXISTING HM PTE --- --- --- 27 NO NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS 4CS05, 4CS05A, 4CS06,
MAINTAIN EGRESS
REMOVE AND REPLACE ARMOR PLATE
LEVEL 4 4CW07 --- 7' - 0" 7' - 0" 1 3/4" 2 NV EXISTING PTE --- EXISTING HM PTE --- --- --- 23 YES NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS 4W39, MAINTAIN EGRESS
REMOVE AND REPLACE OPERATOR
LEVEL 4 4CW10 --- 7' - 6" 7' - 0" 1 3/4" 2 F EXISTING PTE --- EXISTING HM PTE --- --- --- N/A NO NO ANYTIME REMOVE AND REPLACE OPERATOR / MAINTAIN MOTION SENSOR IN THE PATH OF EGRESS
LEVEL 4 4S05 --- 3' - 0" 7' - 0" 1 3/4" 1 VV WD - LEAD
LINED
STE LEAD LINED
TO MATCH
DOOR
HM - LEAD
LINED
HM PTE 1/A6.01 6/A6.01 --- 28 YES NO COORDINATE WITH COR REPLACE DOOR AND FRAME ACCESS CONTROL ADD OPERATOR LEAD LINED DOOR / 4'-7", ENSURE LEAD LINER OVERLAPS DRY WALL.
LEVEL 4 4W39 SMOKE
BARRIER
7' - 0" 7' - 0" 1 3/4" 2 F EXISTING PTE --- EXISTING HM PTE --- --- --- 15 YES NO NIGHT OR WEEKEND AND NOT AT THE
SAME TIME AS 4CW07, MAINTAIN
EGRESS
REMOVE AND REPLACE OPERATOR
LEVEL 4 4W52 --- 3' - 0" 7' - 0" 1 3/4" 1 NV WD STE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- 32 NO YES COORDINATE WITH COR NEW FRAME, DOOR AND HARDWARE
LEVEL 4 4W54 45 MIN. 4' - 0" 7' - 0" 1 3/4" 1 F HM PTE --- EXISTING HM PTE --- --- --- 31 NO YES COORDINATE WITH COR EXISTING FRAME NEW DOOR AND HARDWARE
LEVEL 5 5CS02 --- 5' - 7 5/8" 7' - 0" 1 3/4" 2 UNEVEN NV HM PTE --- HM-002 HM PTE 1/A6.01 6/A6.01 --- 33 NO NO NIGHT OR WEEKEND, MAINTAIN EGRESS REPLACE DOOR FRAME AND HARDWARE RECONNECT ACCESS CONTROL
LEVEL 5 5E03 45 MIN. 3' - 0" 7' - 0" 1 3/4" 1 F EXISTING STE --- EXISTING HM PTE --- --- --- 18 YES NO ANYTIME REMOVE AND REPLACE OPERATOR
LEVEL 6 6CW03 --- 3' - 8" 7' - 0" 1 3/4" 1 SG EXISTING PTE --- EXISTING HM PTE --- --- --- 18 YES NO MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR
LEVEL 9 9ST02 90 MIN. 3' - 8" 7' - 0" 1 3/4" 1 NV EXISTING PTE CLEAR AND
RATED
EXISTING HM PTE 1/A6.01 6/A6.01 --- N/A NO NO MAINTAIN EGRESS REMOVE AND REPLACE FIRE RATED GLASS / 90 MIN.
LEVEL 9 9ST03 90 MIN. 3' - 8" 7' - 0" 1 3/4" 1 NV EXISTING PTE CLEAR AND
RATED
EXISTING HM PTE 3/A6.01 8/A6.01 --- N/A NO NO MAINTAIN EGRESS REMOVE AND REPLACE FIRE RATED GLASS / 90 MIN., ADD NEW SEALS
DOOR SCHEDULE - BUILDINGS 2, 7, AND 50
Level
DOOR
NUMBER FIRE RATING
PANEL
WIDTH
PANEL
HEIGHT
PANEL
THICKNESS
PANEL
COUNT PANEL TYPE
PANEL
MATERIAL
PANEL
FINISH
GLAZING
TYPE
FRAME
TYPE
FRAME
MATERIAL FRAME FINISH HEAD JAMB SILL
HARDWARE
GROUP
NEW
OPERATOR
NEW
PIV PHASING NOT USED COMMENTS
BUILDING 2
LEVEL 1 1C03 45 MIN. 7' - 4" 7' - 0" 1 3/4" 2 NV EXISTING PTE --- EXISTING HM PTE --- --- --- N/A YES NO NIGHT OR WEEKEND, MAINTAIN EGRESS REMOVE AND REPLACE OPERATOR
LEVEL 1 103 45 MIN. 7' - 0" 7' - 0" 1 3/4" 2 F HM PTE --- HM-001 HM PTE 1/A6.01 6/A6.01 --- YES YES NIGHT OR WEEKEND, MAINTAIN EGRESS NEW DOOR, FRAME AND OPERATOR
LEVEL 1 113 --- 3' - 0" 7' - 0" 1 3/4" 1 NV EXISTING STE --- EXISTING HM PTE --- --- --- 18 YES NO NIGHT OR WEEKEND REMOVE AND REPLACE OPERATOR
LEVEL 1 113A --- 3' - 0" 7' - 0" 1 3/4" 1 FG WD STE --- EXISTING HM PTE --- --- --- 34 NO NO ANYTIME REPLACE EXISTING DOOR WITH NEW SOLID CORE DOOR WITH NO WINDOW
BUILDING 7
LEVEL 1 03-7 --- 3' - 0" 7' - 0" 1 3/4" 1 F HM PTE --- HM-001 HM PTE 4/A6.01 9/A6.01 --- 35 NO NO MAINTAIN EGRESS REPLACE EXISTING DOOR, FRAME AND HARDWARE
BUILDING 50
LEVEL 1 50C101 --- 7' - 6 1/4" 7' - 0" 1 3/4" 1 AL-FG ALUM ALUM --- AL-001 ALUM ALUM 2/A6.01 7/A6.01 --- - YES YES MAINTAIN EGRESS NEW ALUMINUM DOOR W/ OPERATORS ADD PIV AND ACCESS CONTROL
THE ARCHITECT.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE
PROJECT AND VERIFY EXISTING CONDITIONS/DIMENSIONS AND
PROPOSED CONDITIONS. COORDINATE DEMOLITION BETWEEN ALL
TRADES. NOTIFY A/E IMMEDIATELY OF ANY CONFLICTS OR
DISCREPANCIES.
3. SEE ENLARGED AREA PLANS FOR KEYNOTES.
4. EXISTING AREAS NOT IN CONTRACT SHOWN SHADED FOR CLARITY.
ALUM ALUMINUM
F FLUSH FULL
FG FULL GLASS
FRP FIBERGLASS REINFORCED POLYMER
FTF FACTORY TRANSPARENT FINISH
HM HOLLOW METAL
ME MATCH EXISTING
NV NARROW VIEW
PTE PAINT TO MATCH EXISTING
SG SPLIT GLASS
STE STAIN TO MATCH EXISTING
PIV PERSONAL IDENTITY VERIFICATION
VV VISION VIEW
WD WOOD
DOOR LEGEND:
EXISTING METAL STUD WALL
HOLLOW METAL DOOR FRAME,
FILL WITH LIGHTWEIGHT
PLASTER
DOOR, SEE SCHEDULE
SEALANT, EACH SIDE
EXISTING METAL STUD WALL
HOLLOW METAL FRAME, FILL
WITH LIGHTWEIGHT PLASTER
SEALANT, EACH SIDE
DOOR, SEE SCHEDULE
SEALANT, BOTH SIDES
HOLLOW METAL FRAME,
GROUT SOLID
DOOR, SEE SCHEDULE
EXISTING WALL SYSTEM
PATCH INTERIOR
FINISH AS REQUIRED
SEALANT, BOTH SIDES
HOLLOW METAL FRAME,
GROUT SOLID
DOOR, SEE SCHEDULE
EXISTING WALL SYSTEM
PATCH INTERIOR
FINISH AS REQUIRED
S E
E S
C H
E D
U
LE
7'
2" O
R
SEE SCHED.
2" 2"
AL-001
FRP-001
HM-001
13' - 0"
7'
6' - 10 3/8"
2" SEE SCHED.
3' - 8"
2"
2' - 8 3/8"
2"
8" 2'
2"
3'
2"
1'
2"
1'
2"
S E
E S
C H
E D
U
LE
7'
AL-101
BLANK PANELS
BEHIND
EXISTING SIGN
AL-002
WD-VV
3'
0"
2'
8"
7'
SEE SCHED.
6" 8"
SEE SCHED.
8" 8"
8" 2'
3'
0"
7'
FRP-NV
HM-NV
WD-NV
FRP-HG
HM-HG
WD-HG
SEE SCHED.
7'
FRP-F
HM-F
WD-F
3' - 0"
5'
1'
8"
7'
AL-FG
8" 8"
SEE SCHED.
1'
1'
7'
ALUMINUM FRAME
1" INSULATED GLASS OR
1/4" TEMPERED GLASS
EXISTING WALL
ALUMINUM DOOR
ALUMINUM FRAME
1/4" TEMPERED GLASS
OR 1" INSULATED GLASS
EXISTING WALL
DOOR, SEE SCHEDULE
ALUMINUM
DOOR, SEE
SCHEDULE
FACE OF EXISTING
WALL BEYOND
THRESHOLD, SET IN
SEALANT
EXISTING CONCRETE
SLAB
EXISTING METAL STUD WALL
ALUMINUM FRAME
1/4" TEMPERED GLASS
OR 1" INSULATED GLASS
DOOR, SEE SCHEDULE
EXISTING METAL STUD WALL
ALUMINUM FRAME
1" INSULATED GLASS OR
1/4" TEMPERED GLASS
ALUMINUM DOOR
SEALANT, BOTH SIDES
HOLLOW METAL FRAME,
GROUT SOLID
DOOR, SEE SCHEDULE
EXISTING WALL SYSTEM
SEALANT, BOTH SIDES
HOLLOW METAL FRAME,
GROUT SOLID
DOOR, SEE SCHEDULE
EXISTING WALL SYSTEM
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOUR FRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
STAMP: ARCHITECT/ENGINEER OF RECORD:
4F PROJECT NO: 19.2481.A26 40
/2 /2
:2
:2
P M
8/28/2024
DOOR ELEVATIONS AND DETAILS
A6.01
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
JEKP
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
CONSTRUCTION DOCUMENTS
GENERAL NOTES:
3" = 1'-0"
DOOR HEAD DETAIL AT METAL STUD
3" = 1'-0"
DOOR JAMB DETAIL AT METAL STUD
3" = 1'-0"
DOOR HEAD DETAIL AT CONCRETE WALL AND CMU AND METAL STUD
3" = 1'-0"
DOOR JAMB DETAIL AT CONCRETE WALL AND CMU AND METAL STUD
1/4" = 1'-0"
DOOR FRAME ELEVATIONS
1/4" = 1'-0"
DOOR PANEL ELEVATIONS
3" = 1'-0"
EXTERIOR DOOR HEAD DETAIL ALUMINUM AT EXTERIOR WALL
3" = 1'-0"
EXTERIOR DOOR JAMB DETAIL ALUMINUM AT EXTERIOR WALL
3" = 1'-0"
DR-ALUM-SILL
3" = 1'-0"
DOOR JAMB DETAIL ALUMINUM AT METAL STUD
3" = 1'-0"
DOOR HEAD DETAIL ALUMINUM AT METAL STUD
3" = 1'-0"
EXTERIOR DOOR JAMB DETAIL AT CMU AND BRICK
3" = 1'-0"
EXTERIOR DOOR HEAD DETAIL AT CMU AND BRICK
ELECTRICAL ABBREVIATIONS
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
CABLE
ACC ACCESSIBLE
ADO AUTOMATIC DOOR OPENER
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
AMP AMPERE
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAS BUILDING AUTOMATION SYSTEM
BFF BELOW FINISH FLOOR
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DAS DISTRIBUTED ANTENNA SYSTEM
DB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL
PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
FLUOR FLUORESCENT
FLUOR FIX FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF
NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MVA MEGAVOLT-AMPERE
MW MEGAWATT MICROWAVE
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OWNER FURNISHED
OF/CI OWNER FURNISHED/CONTRACTOR
INSTALLED
OF/OI OWNER FURNISHED/OWNER INSTALLED
OL OVERLOAD
OS OCCUPANCY SENSOR
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SPDT SINGLE POLE, DOUBLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
VS VACANCY SENSOR
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
SWITCH, MULTIPOSITION
SWITCH, NORMALLY CLOSED FLOAT
SWITCH, NORMALLY CLOSED FOOT OPERATED
SWITCH, NORMALLY CLOSED LIMIT
SWITCH, NORMALLY CLOSED TIME DELAY
SWITCH, NORMALLY OPEN FLOAT
SWITCH, NORMALLY OPEN LIMIT
SWITCH, NORMALLY OPEN TEMPERATURE ACTIVATED
SWITCH, NORMALLY OPEN TIME DELAY
SWITCH, SINGLE BREAK
FUSE WITH RATING
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
MOLDED CASE CIRCUIT BREAKER
LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
HIGH-VOLTAGE OIL CIRCUIT BREAKER
HIGH-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
O.C.B.
SWITCH AND FUSE UNIT
FUSED DRAWOUT POTENTIAL TRANSFORMER
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
DELTA CONNECTION
TRANSFORMER
WYE CONNECTION
EARTH GROUND
JUNCTION BOX
PULL BOX
PRESSURE SWITCH-CLOSE ON INCREASE
PRESSURE SWITCH-OPEN ON INCREASE
FUSIBLE LINK
TIME CLOCK
GENERATOR, POWERG
BATTERY
CAPACITOR
LIGHTNING ARRESTOR
R
RECTIFIER, CATHODIC PROTECTION SANITARY
INSTANTANEOUS OVERCURRENT RELAY
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
POTHEAD
STRESS CONE
M METER
A AMMETER
V VOLTMETER
W WATTMETER
WH WATT-HOUR METER
J
PB
R
AC-TIME OVERCURRENT RELAYR
AC-DIRECTIONAL OVERCURRENT RELAYR
LOCKING OUT RELAYR
TC
SYMBOL
SWITCH, NORMALLY CLOSED
TEMPERATURE ACTIVATED
DESCRIPTION
ELECTRICAL LEGEND
(DETAILS)
DUCT, CELL FLOOR HEADER
T T DUCT, TROLLEY
DUCT, UNDERFLOOR JUNCTION BOX
RC RIGID CONDUIT LINE = RC
SUBSTATION
DISTRIBUTION PANEL
LIGHTING PANEL
PANELBOARD CABINET, FLUSH MOUNTED
PANELBOARD CABINET, SURFACE MOUNTED
C RECEPTACLE, CLOCK HANGER
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX ON EMERGENCY POWER
RECEPTACLE, GFCI DUPLEX
RECEPTACLE, QUADRAPLEX
DB DIRECT BURIAL CABLE = DB
P POWER DUCT = P
HI VOLTAGE SWITCH ON CONCRETE PAD
LOW VOLTAGE SWITCH ON CONCRETE PAD
DUAL POWER AND TELECOMMUNICATIONS MANHOLE
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
TRANSFORMER
WYE CONNECTION
EARTH GROUND
JUNCTION BOX
PULL BOX
J
PB
SYMBOL DESCRIPTION
ELECTRICAL LEGEND
(FLOORPLAN)
C C LADDER CABLE TRAY
BRANCH CIRCUIT HOMERUN. LINES INDICATE
NUMBER OF CIRCUITS, NEUTRAL, AND SWITCH LEG
CONDUCTORS. ONE SEPARATE GREEN GROUNDING
CONDUCTOR SHALL BE PROVIDED FOR EACH
HOMERUN; NOT SHOWN
W W WIREWAY
T P
LVS
HVS
S
B B BUSWAY
LP
DP#__
A
B
C
D
RECEPTACLE, SPECIAL PURPOSE 208V,
20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
RECEPTACLE, SPECIAL PURPOSE 120V,
30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
RECEPTACLE, SPECIAL PURPOSE 208V,
30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
RECEPTACLE, SPECIAL PURPOSE 120V,
20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
VENTILATOR OR FAN COIL UNIT OUTLET
SWITCH, SPST
VARIABLE FREQUENCY DRIVE
TIME CLOCK
R
RECTIFIER, CATHODIC PROTECTION SANITARY
INSTANTANEOUS OVERCURRENT RELAY
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
R
AC-TIME OVERCURRENT RELAYR
AC-DIRECTIONAL OVERCURRENT RELAYR
LOCKING OUT RELAYR
TC
SYMBOL DESCRIPTION
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm]
CENTERS OR AS DESIGNATED ON DRAWINGS), MTD
3'-6" [1067mm] AFF OR AS INDICATED.
VFD
CONDUIT TERMINATED W/COUPLING
(FLUSH W/FINISHED FLOOR) FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
CONDUIT TERMINATED 6" [152mm] AFF IN STANDARD
BOX FOR EXTENSION TO EQUIPMENT AS DIRECTED.
SWITCH, DPST2
SWITCH, FUSEDF
SWITCH, KEY OPERATEDK
SWITCH, LOCKL
SWITCH, LOW VOLTAGE MASTERLM
SWITCH, MANUAL MOTOR STARTINGM
SWITCH, MOMENTARY CONTACTMC
MP
SWITCH, WITH PILOT LIGHTP
SWITCH, PUSH BUTTONPB
SWITCH, REMOTE CONTROLRC
SWITCH, WEATHER PROOFWP
SWITCH, EXPLOSION PROOFX
SWITCH, THREE WAY3
SWITCH, THREE WAY DIMMER3D
SWITCH, THREE WAY OCCUPANCY SENSOR3OS
SWITCH, FOUR WAY4
SWITCH, DIMMERD
SWITCH, DOOR JAMBDOOR
SWITCH, FOUR WAY OCCUPANCY SENSOR4OS
SWITCH, OCCUPANCY SENSOROS
SWITCH, PHOTOCELLPH
SWITCH, OCCUPANCY SENSOR DIMMEROSD
SWITCH, MOTOR SNAP WITH
PILOT LIGHT (THERMAL TYPE)
E
RECEPTACLE, SPECIAL PURPOSE 208V,
60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV
FIBEROPTICS LINE = FO
COMMUNICATIONS FLOOR RECEPTACLE
PAGING SPEAKER, CEILING MOUNTED
PAGING SPEAKER, WALL MOUNTED
CATV
CCTV
FO
COMMUNICATIONS WALL RECEPTACLE
COMMUNICATIONS LINE = COMCOM
INTERCOM LINE = II
NURSE CALL LINE = NCNC
NCS NURSE'S CALL MASTER STATION
NCT NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
D = DUTY STATION. MTD 5' AFF
E = MTD 6' AFF FOR SHOWER LOCATION
MTD 4'-6" AFF FOR TUB LOCATION
MTD 3' AFF FOR TOILET LOCATION
P = PSYCHIATRIC CORRIDOR STATION WITH KEY
SWITCH
S = AUDIO VISUAL STAFF STATION MTD 5' AFF
U = UTILITY CALL STATION, MTD 5' AFF
NURSE CALL STATION.
D = CORRIDOR DOME LIGHT MTD 6" ABOVE DOOR
I = AUXILIARY INTERSECTIONAL DOME LIGHT
TELECOMMUNICATIONS TERMINAL CABINET
TELECOMMUNICATIONS BACKBOARD (WALL MTD)
TELECOMMUNICATIONS MANHOLE
COMMUNICATIONS CEILING RECEPTACLE
TELEVISION FLOOR RECEPTACLE
C = CAMERA (CCTV SYSTEM)
M =MONITOR (CATV SYSTEM).
AV= AUDIO VISUAL (CONFERENCE ROOM
CONNECTION RECEPTACLES)
M
M
M
S
S
AUDIO VISUAL LINE = AVAV
TTB
N D
N D
RECEPTACLE, SWITCHED DUPLEXS
F
G
H
RECEPTACLE, SPECIAL PURPOSE 208V,
30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
RECEPTACLE, SPECIAL PURPOSE 208V,
50A, 3 PHASE, 3 POLE, 4W, NEMA 15-50R.
RECEPTACLE, SPECIAL PURPOSE 208V,
60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,
GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN
FLEXIBLE CORD (CENTER LINE OF OUTLET: 6'-6"
[1981mm] AFF. MINIMUM).
TELEVISION WALL RECEPTACLE
C = CAMERA (CCTV SYSTEM)
M =MONITOR (CATV SYSTEM).
AV= AUDIO VISUAL (CONFERENCE ROOM
CONNECTION RECEPTACLES)
TELEVISION CEILING RECEPTACLE
C = CAMERA (CCTV SYSTEM)
M =MONITOR (CATV SYSTEM).
AV= AUDIO VISUAL (CONFERENCE ROOM
CONNECTION RECEPTACLES)
SYMBOL DESCRIPTION
J
RECEPTACLE, SPECIAL PURPOSE 208V,
20A, 3 PHASE, 3 POLE, 4W, NEMA 15-20R.
EH ELECTRIC POWER TRANSFER HINGE
ES ELECTRONIC STRIKE
DOOR CONTACT / DOOR POSITION SWITCH
MAGNETIC DOOR LOCKING DEVICE
C CAMERA
C 360 CAMERA
CARD ACCESS READER; LETTER INDICATES AS
FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN
M-MULLION P-PEDESTAL R-RACK S-SURFACE
W-WALL
T=TECHNOLOGY/TYPE
B-BARCODE M-MAG STRIP
F-ELEVATOR FLOOR CALL P-PROXIMITY
H-ELEVATOR HALL CALL S-SMART CARD
T-TOKEN
DURESS/PANIC ALARM PUSH BUTTON
M
T
M
T
M
T
ELECTROMAGNETIC TYPE DOOR HOLDER OUTLETDH
ELECTRONIC LOCK; LETTER INDICATES AS
FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN
M-MULLION P-PEDESTAL R-RACK S-SURFACE
W-WALL
T=TECHNOLOGY/TYPE
D-DEADBOLT H-HYBRID L-LATCH SET
M-MAGNETIC S-STRIKE
INTERCOM; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN
M-MULLION P-PEDESTAL R-RACK S-SURFACE
W-WALL
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
ITEMS SHOWN IN GRAY ARE EXISTING TO REMAIN
DEMOLITION PLANS: SOLID DARK ITEMS ARE TO BE
REMOVED OR MODIFIED.
NEW PLANS: SOLID DARK ITEMS ARE TO BE
ADDED OR MODIFIED.
DASHED ITEMS ARE INSTALLED BELOW REFERENCED
PLAN
CONNECT TO EXISTING
ELECTRONIC DOOR OPERATOR
DOOR ACTUATOR SWITCH / POSITION SWITCH
PIR EGRESS SENSOR
MAGNETIC DOOR HOLD OPEN
MID MOTION INTRUSION DETECTOR
SSTV SECURITY SURVEILLANCE TELEVISION
DC
MAG
EDO
DAS
PES
DH
A. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO
MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT
HOMERUN SHALL HAVE A SEPERATE GREEN INSULATED
EQUIPMENT GROUNDING CONDUCTOR.
B. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES
AND TYPES OF EMERGENCY AND NORMAL BRANCH
WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN
DEVICES.
C. REFER TO CEILING PLANS FOR LOCATION OF CEILING
AND WALL MOUNTED DEVICES, AS REQUIRED.
D. MINIMUM SIZE CONDUIT FOR CONTROL CIRCUITS
SHALL BE 3/4"
E. GENERAL CONTRACTOR TO FURNISH AND INSTALL
ACCESS DOORS IN WALLS AND CEILINGS WHERE ACCESS
TO CONCEALED ELECTRICAL BOXES AND DEVICES IS
REQUIRED.
H. ARMORED CABLE (AC) MAY BE USED FOR LAY-IN
FIXTURE PIGTAILS. ARMORED CABLE (AC) SHALL NOT BE
USED FOR BRANCH CIRCUIT HOMERUNS. ARMORED
CABLE (AC) SHALL NOT BE USED WHERE MORE THAN
THREE CONDUCTORS (PHASE/NEUTRAL/GROUND) ARE
REQUIRED, WHERE EXPOSED; OR IN LENGTHS
EXCEEDING 20 FEET EXCEPT FOR TEMPORARY WIRING.
I. COORDINATE ALL OUTAGES WITH VHA COR PER
SPECS PRIOR TO WORK BEING DONE.
GENERAL ELECTRICAL NOTES
A. WHERE EXISTING EQUIPMENT IS BEING REMOVED,
ALL UNUSED CONDUITS AND WIRING ARE TO BE
REMOVED IN THEIR ENTIRETY. NO BOXES, CONDUIT OR
WIRING IS TO BE ABANDONED IN PLACE.
B. DISCONNECT AND REMOVE ALL WIRES BACK TO THE
OVERCURRENT DEVICE AND RELABEL AS A SPARE.
REUSE EXISTING CONDUIT IN COMPLIANCE WITH NEC.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL
CONDUITS AND CONDUCTORS PASSING THROUGH
RENOVATED AREAS AND SERVICING UNDISTURBED
AREAS.
ELECTRICAL GENERAL NOTES - DEMOLITION
ELECTRICAL LEGENDS AND
ABBREVIATIONS
E0.00
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
COR / Project Engineer
CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
Office of Construction and Facilities Management
Department of Veterans Affairs
Phase
CO056R7C6+O0 DOC7ME065
STAMP: ARCHITECT/ENGINEER OF RECORD:
08/28/2024
UPGRADE DOORS/DOOR
HARDWARE AT IOWA CITY VA
HEALTH CARE SYSTEM
WSWW
IOWA CITY, IOWAMATTHEW RUPPENKAMP
CONSTRUCTION
DOCUMENTS
636A8-23-102
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text No. 91134PE 91134PE91134PE
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text
WILLIAM WANGEN
CABLE TO SECURITY PANEL BY DIVISION 28
CONTRACTOR; POWER BY DIVISION 26 TO
BE AT SECURITY PANEL. COORDINATE
POWER REQUIREMENTS
WITH DIVISION 28 CONTRACTOR.
JUNCTION BOX
ABOVE ACCESSIBLE CEILING
DC DC
EH EH
BY…