Drawings 8 of 12.pdf

PDF 5 MB Posted

Attached to
472/19503. SMD; Lakeland CF (SRF) - Building 29 HVAC Upgrades
Solicitation number
RFQ 171 230000000791 2
Issued by
Barry County, Michigan

About this file

Summary of Drawings 8 of 12 - Building 29 HVAC Mechanical Plans

This document contains architectural and mechanical drawings for HVAC system upgrades in Buildings 29A, 29B, and 29C at a State of Michigan facility under the Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division. The project involves installation of new rooftop units (RTU-4 and RTU-5) on concrete pads, new ductwork routing through newly constructed chases to attic penetrations, installation of new DDC (Direct Digital Control) VAV (Variable Air Volume) boxes at multiple locations, new horizontal heating coils, and modifications to existing ductwork throughout the buildings. The drawings indicate multiple supply diffusers, return grilles, and exhaust air components with specific CFM (cubic feet per minute) ratings documented on plan sheets M-402, M-403, M-404, M-405, and M-406. The project includes both a base bid and Add Alternate #1 scope, with the issue date of September 14, 2023, and contract order number 472/LCFMAINTPROJ.

The specifications require contractors to install new grade-mounted rooftop units per manufacturer specifications on concrete pads with dimensions noted, route new ductwork through newly constructed chases with access panels for maintenance, connect new DDC control panels to a dark network IT rack via purple CAT-6 cable through coordination with CommTech Design, balance all existing diffusers and grilles to new CFM requirements, and perform finishing work including patching, priming, and painting walls and ceilings where diffusers and grilles are removed. Additional work includes seeding disturbed areas with a specified seed mix (40% Kentucky bluegrass, 25% creeping fescue, 20% perennial ryegrass, 15% chewing fescue) at 8 pounds per 1,000 square feet or 350 pounds per acre, and applying 6 inches of topsoil over all disturbed areas. The project utilizes consultant job number 20080.00 with Matrix as the consulting firm and funding code 472/19503.SMD.

View the file

Other files

File Type Posted
Drawings 1 of 12.pdf PDF
Drawings 2 of 12.pdf PDF
Drawings 4 of 12.pdf PDF
Drawings 5 of 12.pdf PDF
Drawings 12 of 12.pdf PDF
47219503.SMD - Addendum 1 Write-Up.pdf PDF
Lakeland - Specifications.pdf PDF
Drawings 10 of 12.pdf PDF
Drawings 9 of 12.pdf PDF
Drawings 7 of 12.pdf PDF
LEIN Request 19503.pdf PDF
Walkthrough Sign-in Sheet.pdf PDF
MICHSpec Rev032022 V12 - 47219503.SMD.pdf PDF
Drawings 6 of 12.pdf PDF
DTMB Advertisement.pdf PDF
Drawings 3 of 12.pdf PDF
Drawings 11 of 12.pdf PDF
MICHSpec Rev032022 V12.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

X-CUH

X-CUH

X-CUH

X-AC

X-AC

X-AC

X-AC

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-CU

RTU-4

CONCRETE PAD

X-SD 490

X-12x8 SA

X-SD 490

X-SD 470

X-12x8 SA

X-SD 450

X-SD 450

X-16x6 SA

X-16x6 SA

X-20x8

SA

X-8x10 SA

X-SD 435

X-SD 450

X-20x16

SA UP

X-22x10

SA

X-20x12

SA UP

X-26x8 RA UP

X-16x6 RA

X-RG 490

X-RG 450

X-RG 450

X-16x6 RA

X-18x8

RA

X-RG 490

X-12x8

RA UP

RG-1 630

16x16 ---

X-18x8 SA

X-10x12 SA X-16x6 SA

X-18x8 SA

X-18x8 RA UP

X-RG 450

X-RG 435

X-16x6 RA

X-SD 130

X-SD 130

X-12x12

SA UP

X-SD 200

X-10x8 SA X-10x6 SA

X-6x6 SA

X-6x6 SA

X-18x8

SA

X-EG 50

X-4x4 EA

X-16x8

EA

X-24x6 EA

X-EG 400

--- TYP.2

X-4x4

EA

X-12x6 EA

X-4x4 EA

X-EG 30

--- TYP. 2

X-16x6EA

X-EG 225

--- TYP.2

X-8x6

EA

X-EG 100

X-EG 205

X-8x6

RA

X-10x6 EA

X-16x8

EA UP

X-8x6

RA

X-SD 60

X-4x4 SA

X-6x4 SA X-SD 100

X-10x4 SA X-6x6 SA UP

X-RG 30

X-4x4 RA

X-10x4

RA UP

X-RG 100

X-SD 175

--- TYP.2

X-8x8 SA UPX-10x6 SA UP

X-SD 175

X-SD 70

X-6x4 SA

X-8x6 SA

X-10x6 SA

X-8x6 SA

X-8x8

SA UP

X-SD 175

X-SD 175

--- --- X-8x6 SA X-8x6 SA

X-12x6 SA

X-12x10

SA UP

X-SD 390

--- TYP.2

X-10x8 SA X-18x8 SA

X-30x8 RA

UP

X-RG 1780

36x16 ---

X-SD 705

20x10 ---

X-16x8 SA UP

X-RG 1780

36x14 ---

X-18x10

SA UP

X-SD 175

X-SD 110

X-6x6

SA

X-16x8 SA

X-4x6 SA

X-SD 160

X-6x6 SA

X-10x6 SA

X-SD 120

X-10x8 SA X-10x8 SA

X-4x6 SA

X-12x8 SA

X-4x8 SA

X-10x6 SA

X-SD 305

X-SD 160

X-12x8

SA UP

X-SD 100

X-SD 40

X-4x4 SA

X-RG 100

X-6x4 RA

X-RG 190

X-12x6 EA

X-8x6 EA

X-EG 70

X-6x6 EA

X-EG 150

X-EG 140

X-6x6 EA

X-RG 1200

X-4x6 EA X-8x6

EA

X-EG 190

X-EG 100

SD-1 220

12x12 TYP.2

X-10x10 SA UP

10x10

SA

X-10x8

SA UP

X-6x4 SA X-14x6

SA

X-EG 90

--- TYP. 2 X-EG 200

X-EG 205

--- ---X-6x4 EA

X-14x6 EA

X-24x12 EA

X-SD 60

X-EG 1780

X-8x6 EA

X-24x12

EA UP

X-18x8

EA UP

X-SD 460

--- TYP.4

X-SD 490

--- TYP.4

X-10x6 EA

X-EG 270

TYP. 3

X-SD 110

X-RG 850

X-12x12

RA UP

X-20x8

EA UP

X-SD 175

--- TYP.4

X-SD 175

X-SD 175

X-10x8 SA X-12x16 SA

X-8x16

RA

X-SD 210

X-8x6 SA

X-SD 210

X-16x8

SA

X-6x4 RA

X-24x10

SA UP

X-16x12

RA UP

X-18x12

EA UP

X-6x4 EA

X-10x6

EA UP

X-40x24 RA UPX-40x20 RA UP

X-SD 415

X-SD 175

VAV-B02

VAV-B03

VAV-B04

VAV-B10

VAV-B11

VAV-B06

VAV-B05

VAV-B13VAV-B14

VAV-B22

VAV-B23

VAV-B21

VAV-B20

VAV-B19

VAV-B18

VAV-B01

VAV-B17

VAV-

B24

42x28

SA UP

52x30

RA UP

X-8x8 EA

X-SD 70

X-SD 215

X-8x8

SA

X-8x6 SA

SD-1 375

12x12 ---

16x12

RA UP

X-RG 375

12x8 RA

SD-1 315

12x12 TYP. 2

10" SA

SD-1 120

6x6 ---

6x8 SA

6x8 SA

8x6 SA

SD-1 250

12x12 TYP. 2

12x6

SA

12x8

SA UP

RG-1 500

16x16 ---

16x12 RA

20x20

RA UP

RG-1 440

12x12 ---

SD-1 120

6x6 ---

SD-1 245

12x12 TYP. 2

SD-1 245

12x12 ---

SD-1 125

12x12 ---

SD-1 380

12x12 ---

SD-1 375

12x12 TYP. 4

SD-1 100

6x6 ---

SD-1 175

12x12 ---

14x12 SA UP 24x10

SA UP

EG-1 125

12x12 ---

RG-1 245

12x12 ---

RG-1 125

12x12 ---

RG-1 100

6x6 ---

RG-1 490

12x12 ---

RG-1 120

6x6 ---

RG-1 380

12x12 ---

RG-1 750

16x16 TYP. 2

30x14 RA UP 16x14 SA

20x16 SA

20x16 SA

20x12 SA

16x12 SA

16x10 SA

14x12

SA

30x14

RA

30x14

RA

30x12 RA

24x12 RA

14x8 RA

14x8

SA

12x10 SA

14x8

SA

10x10 SA

6x8 SA

6x8 RA 12x8 RA

20x8 RA

20x8 RA

14x8 RA

6x6 RA

14x8 RA

12x6 RA

10x12 SA

X-EG 30

SD-1 270

12x12 ---

6x12 SA

6x10

SA

HC-4

1 X-IT

RACK

12x8

RA

12x8

RA

VAV-B25

VAV-

B15

TYP. 3

6" SA (TYP.3)

8" SA

6x6 SA

10" SA

10" SA

8" SA

8" SA

12x12 SA

12x12 SA

8" SA

VAV-B285

12x14 SA

8x10 SA

6x6 SA

10" SA

10" SA

8" SA

10" SA

6x6

SA

10x10 SA

VAV-B27

SD-1 75

6x6 ---

8x8 SA

10" SA

8" SA

8x10 SA

6" SA

10x10 SA

8x8

SA

X-SD 220

27'-8"

RTU-4

CLEARANCE

'-1

0"

X-CUH

X-CUH

X-CUH

X-CUH

X-AC

X-AC

X-AC

X-AC

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-CU

INSTALL NEW GRADE MOUNTED ROOF TOP UNIT

PER MANUFACTURER'S INSTALLATION

INSTRUCTIONS ON MANUFACTURE PROVIDED

HORIZONTAL CURB. INSTALL NEW ROOF TOP

UNIT ON NEW CONCRETE PAD. PAD DIMENSIONS

ON PRINT. SEE M-800 FOR PAD THICKNESS AND

CONSTRUCTION.

ROUTE NEW SUPPLY AND RETURN DUCTWORK

UP THE SIDE OF THE BUILDING IN NEWLY

CONSTRUCTED CHASE TO NEW ATTIC

PENETRATIONS IN NEW ROOF GABLE.

INSTALL NEW SUPPLY/RETURN AIR DUCTWORK

AND ALL ASSOCIATED ACCESSORIES TO THE

EXTENTS SHOWN. MODIFY EXISTING

DUCTWORK AS NEEDED FOR NEW CONNECTION.

CONNECT EXISTING CABINET UNIT HEATER TO

NEW DDC CONROL PANEL.

INSTALL NEW DDC VAV BOX AT LOCATION

SHOWN. MODIFY DUCTWORK AS REQUIRED FOR

NEW CONNECTION. CONNECT NEW DDC VAV

BOXES TO NEW DDC CONTROL PANEL.

INSTALL NEW HORIZONTAL HEATING COIL IN

SUPPLY AIR DUCT RISER AT APPROXIMATELY

48" ABOVE CONCRETE PAD INSIDE NEWLY

CONSTRUCTED CHASE. INSTALL NEW

HORIZONTAL HEATING COIL PER

MANUFACTURE'S INSTALLATION INSTRUCTIONS.

NEW CHASE TO HAVE ACCESS PANEL FOR

MAINTENANCE AND ACCESSIBILITY.

EXISTING DUCT WORK CONTINUATION AND

SIZING SHOWN ON SHEET M-405.

RE-BALANCE EXISTING SUPPLY

DIFFUSER/RETURN GRILLE TO NEW CFM

SHOWN.

GENERAL NOTES

1. CONTRACTOR TO PATCH, PRIME, AND PAINT

WALLS/CEILINGS TO MATCH EXISTING WHERE

EXISTING SUPPLY DIFFUSERS AND RETURN

GRILLES WERE REMOVED AND NOT ENTIRELY

FILLED BY NEW SUPPLY DIFFUSERS AND

RETURN GRILLES. ONLY LOCATION OF WORK

NEEDS TO BE PAINTED NOT THE ENTIRE

WALL/CEILING.

2. CONTRACTOR TO PATCH, PRIME, AND PAINT

WALLS TO MATCH EXISTING WHERE EXISTING

THERMOSTATS WERE REMOVED AND NOT

COVERED BY NEW THERMOSTATS. ONLY

LOCATION OF WORK NEEDS TO BE PAINTED

NOT THE ENTIRE WALL.

3. ALL EXISTING DIFFUSERS & GRILLES TO BE

BALANCED TO EXISTING CFM AT THE END OF

CONSTRUCTION UNLESS OTHERWISE NOTED

ON DRAWINGS.

SEEDING SCHEDULE

CONTRACTOR TO SUPPLY 6" OF TOPSOIL OVER ALL

DISTURBED AREAS. SEED ALL DISTURBED AREAS

WITH THE FOLLOWING SEED MIX:

40% KENTUCKY BLUEGRASS

25% CREEPING FESCUE

20% PERENNIAL RYEGRASS

15% CHEWING FESCUE

APPLY AT A RATE OF 8 LBS PER 1,000 SQUARE FEET

OR 350 LBS PER ACRE.

ADD ALTERNATE #1:

HVAC KEY NOTES

BASE BID:

HVAC KEY NOTES

CONNECT NEW DDC CONTROL PANELS TO DARK

NETWORK IT RACK WITH PURPLE CAT-6 CABLE(S)

AS REQUIRED TO SEE THE BUILDING FROM THE

MAINTENANCE BUILDING IN DAVID KARNEY'S

OFFICE. HIRE AND COORDINATE CONNECTION TO

DARK NETWORK IT RACK WITH BRET EMERSON

FROM COMMTECH DESIGN (PHONE 616-433-7219).

file no.

checked by drawn by consultant contract order no.

472/LCFMAINTPROJ

consultant job no.

20080.00

M a t r ix

472/19503.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N issue date

KEY PLAN

9/14/2023 FOR CONSTRUCTION

BUILDING 29B LOWER ATTIC

PLAN - MECHANICAL NEW

N BUILDING 29B LOWER ATTIC PLAN - MECHANICAL NEW (BASE BID)

SCALE: 1/8" = 1'-0"

0 1 5 10 20

M-402

DBP

CAT

X-FIN TUBEX-FIN TUBEX-FIN TUBE X-FIN TUBE X-FIN TUBE X-FIN TUBE X-FIN TUBE X-FIN TUBE

X-FIN TUBEX-FIN TUBEX-FIN TUBEX-FIN TUBE X-FIN TUBEX-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-CUX-CU

X-AC

X-EF

RTU-5

CONCRETE PAD

X-SD 490

X-16x6 SA

X-RG 490

X-16x6 SA

X-18x16

RA UP

X-26x12

SA UP

X-10x8 SA

X-16x6 SA

X-16x10

RA

X-SD 480

X-SD 480

X-8x6 SA

X-SD 210

X-16x6

RA

X-12x8

EA UP

X-EG 210

--- TYP. 2

X-EG 30

X-10x8 EA

X-8x6 EA

X-4x4 EA

X-RG 480

X-RG 480

X-RG 210

X-10x6 RA X-16x6 RA

X-10x16

RA

X-16x10

SA

X-8x6 SA

X-EG 30

X-10x12

SA

X-8x16 RA

X-8x2 EA

X-SD 490

--- TYP. 2

X-SD 490

X-SD 490

--- TYP. 2

X-SD 400

X-SD 175

--- TYP. 4

X-SD 480

X-SD 475

X-SD 50

--- --- X-SD 175

X-SD 490

X-SD 160

X-SD 490

X-RG 400

X-10x8 RA

X-24x12

RA UP

X-RG 1770

48x12 ---

X-6x6 SA

X-8x8

SA UP

X-6x6 SA

X-SD 120

X-SD 160

X-RG 195

X-8x6 RA X-RG 90

X-6x4 RA

X-10x6 RA

X-20x16

RA UP

X-8x6 RA

X-RG 195

X-12x8 RA

X-22x10 RA

X-RG 1440

40x12 ---

X-20x8

RA

X-6x6 RA

X-RG 110

X-10x10

RA UP

X-RG 490

26x6 ---

X-12x8

SA UP

X-12x8 SA

X-10x8

SA

X-6x4 SA

X-SD 355

X-SD 80

X-6x6 SAX-6x6 SAX-6x6 SAX-8x6 SA X-12x6

SA

X-10x6 SAX-14x8 SA

X-SD 135

X-SD 200

X-RG 135

--- TYP. 2

X-RG 440

X-10x8 RA X-6x6 RAX-6x6 RA

X-12x8 RA

X-12x10

RA UP

X-10x10

EA UP

X-EG 80

X-12x8 EA X-14x8 SA

12x6

SA

SD-2 250

9x9 TYP.2

8" SA

12x10 SA 14x12 SA X-10x10 SA

X-20x10 SA

X-20x12 SA UP

12x8 SA

SD-2 380

12x12 ---

X-EG 230

X-8x6 EA

X-SD 210

--- --- X-8x6 SA

16x10 SA

X-SD 50

X-6x6

SA

X-SD 125

X-6x4 EA

X-EG 190

12x8 SA

X-8x6

SA

X-EG 80

RG-2 400

12x12 ---

10x10 RA

X-RG 200

X-RG 135

18x12 RA UP

RG-2 400

12x12 ---

X-8x6 RA

16x14

RA

X-6x6

RA

X-28x10

SA UP

X-14x10 SA UPX-14x10 SA

X-10x8 SA

X-SD 410

X-10x8 SA

X-SD 410

X-12x6

EA UP

X-EG 110

X-8x4 EA

X-EG 30

X-EG 30

X-4x4 EA

X-12x6 EA

X-6x4 EA

X-10"

EA UP

X-10"

EA DN

X-SD 160

X-8x6 SA X-4x4 EA DN

X-WALL CAP

X-4x4 EA

X-SD 175

X-SD 140

X-6x6 SA

X-8x6 SA X-12x8 SA

X-10x6 SA

X-EG 205

X-8x6 EA

X-20x10

RA UP

X-RG 680

24x8 ---

X-16x8 RA X-14x8 RA X-12x6 RA

X-RG 380

X-10x6 RA

X-RG 260

X-10x10

RA UP

X-SD 90

X-SD 70

X-6x6

SA

X-RG 120

X-6x6

RA X-RG 100

X-8x6 RA

X-10x10 RA

X-8x6

SA

X-RG 150

X-6x6 RA

X-RG 90

X-SD 210

X-8x6 SA

X-14x8 SA

X-SD 175

--- --- X-8x6 SA

X-14x10 SA

X-12x8 SA

X-20x12 SA UPX-12x12

SA

X-10x6 SA

X-20x10 SA

X-SD 130

X-6x6 SA

X-14x6 SA

X-SD 380

--- --- X-SD 365

X-12x6 SA X-14x6 SA

X-18x8

SA

X-12x8

SA X-SD 400

X-SD 130

X-6x6 SA

X-10x6 SA

X-SD 120

X-20x10

SA UP

X-8x8 SA X-12x8 SA

X-8x6 SA

X-SD 175

X-12x10 SA

X-16x10 SA

X-12x8 SA

X-10x6 SA

X-SD 285

X-8x6 SA

SD-2 300

12x12 ---

X-8x6 SA

X-SD 175

X-18x18

RA UP

X-RG 2300

48x16 ---

X-20x12 RA

X-RG 570

X-12x8

RA X-RG 145

X-30x18 RA

X-14x10 RA

X-RG 365

X-6x6

RA

X-RG 180

X-12x6 RA

X-12x8

RA

X-RG 400

X-SD 345

X-SD 175

--- TYP.4

X-8x6

SA UP

X-SD 490

X-SD 450

X-SD 450

X-SD 435

X-SD 450

X-8x6

EA

X-6x4 SA

X-SD 80

X-SD 80

X-EG 200

X-12x4 EA

X-6x6 EA

X-12x6 EA

X-EG 160

--- TYP.2

X-EG 160

X-6x4 EA

X-18x12

EA UP

X-18x12 EA

X-18x8 EA

X-EG 30

X-12x8 EA X-12x8 EA X-12x6

EA

X-10x6 EA

X-EG 270

EG-1 55

6x6 TYP. 3

X-EG 30

X-10x10

SA UP

X-SD 205

X-SD 170

X-SD 80

X-8x6 SA

X-8x8 SA

X-14x8 SA

X-6x6 SA

X-6x6 SA

X-6x4 SA

X-RG 270

X-RG 270

X-RG 140

X-RG 460

X-RG 520

X-RG 610

X-20x18

RA UP

X-14x8 RA

X-14x10 RA

X-10x10 RA

X-10x6 RA

X-10x6 RA

X-10x6 RA

X-20x10 RA

X-20x8

RA

X-12x8 RA

X-12x6 RA

X-8x6 RA

X-SD 490

X-SD 490

X-18x10

SA UP

X-8x6 SA

X-SD 110

X-SD 175

X-SD 175

X-8x6 SA

X-10x8 SA

X-16x8 SA X-18x8 SA

X-SD 270

X-14x10

SA UP

X-18x8 SA

X-10x6 RAX-10x6 RA

X-12x8 SA

X-8x8

SA UP

X-SD 80

X-8x6

EA UP

X-12x6

EA UP

X-SD 270

X-SD 270

X-RG 270

X-SD 100

X-4x4

EA

X-SD 135

X-SD 135

44x30

SA UP

60x30

RA UP

VAV-C02

VAV-C01

VAV-C03

VAV-C04

VAV-C07

VAV-C08VAV-C09

VAV-C10

VAV-C29

VAV-C28

VAV-C27 VAV-C26

VAV-C15

VAV-C21

VAV-C22

VAV-C23

VAV-C24

VAV-C25

VAV-C14

VAV-C13

VAV-C11

VAV-C12

2 2

10x8 SA

10x12 SA

10" SA

10x12 SA

10" SA

10" SA

SD-2 275

9x9 TYP.2

SD-2 310

12x12 ---

SD-2 310

12x12 ---

SD-1 270

12x12 ---

6x12 SA

5 5

HC-5

VAV-C30 57

7 7

26x12 SA

5 10" SA

10" SA

8" SA

SD-1 55

6x6 TYP. 38

6" SA (TYP.3)

6x6 SA

8x8

SA

8X-RG 550

3 3

RG-1 80

6x6 ---

'-8

46'-10"

RTU-5

CLEARANCE

X-CUH

X-CUH

X-FIN TUBEX-FIN TUBEX-FIN TUBE X-FIN TUBE X-FIN TUBE X-FIN TUBE X-FIN TUBE X-FIN TUBE

X-FIN TUBEX-FIN TUBEX-FIN TUBEX-FIN TUBE X-FIN TUBEX-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-FIN TUBE

X-CUX-CU

X-AC

X-EF

HVAC KEY NOTES

INSTALL NEW GRADE MOUNTED ROOF TOP UNIT

PER MANUFACTURER'S INSTALLATION

INSTRUCTIONS ON MANUFACTURE PROVIDED

HORIZONTAL CURB. INSTALL NEW ROOF TOP

UNIT ON NEW CONCRETE PAD. PAD DIMENSIONS

ON PRINT. SEE M-800 FOR PAD THICKNESS AND

CONSTRUCTION.

ROUTE NEW SUPPLY AND RETURN DUCTWORK

UP THE SIDE OF THE BUILDING IN NEWLY

CONSTRUCTED CHASE TO NEW ATTIC

PENETRATIONS IN NEW ROOF GABLE.

INSTALL NEW SUPPLY/RETURN/EXHAUST AIR

DUCTWORK, RETURN AIR DUCTWORK, AND ALL

ASSOCIATED ACCESSORIES TO THE EXTENTS

SHOWN. MODIFY EXISTING DUCTWORK AS

NEEDED FOR NEW CONNECTION.

CONNECT EXISTING CABINET UNIT HEATER TO

NEW DDC CONTROL PANEL.

INSTALL NEW DDC VAV BOX AT LOCATION

SHOWN. MODIFY DUCTWORK AS REQUIRED FOR

NEW CONNECTION. CONNECT NEW DDC VAV

BOXES TO NEW DDC CONTROL PANEL.

INSTALL NEW HORIZONTAL HEATING COIL IN

SUPPLY AIR DUCT RISER AT APPROXIMATELY

48" ABOVE CONCRETE PAD INSIDE NEWLY

CONSTRUCTED CHASE. INSTALL NEW

HORIZONTAL HEATING COIL PER

MANUFACTURE'S INSTALLATION INSTRUCTIONS.

NEW CHASE TO HAVE ACCESS PANEL FOR

MAINTENANCE AND ACCESSIBILITY.

EXISTING DUCT WORK CONTINUATION AND

SIZING SHOWN ON SHEET M-406.

RE-BALANCE EXISTING SUPPLY

DIFFUSER/RETURN GRILLE TO NEW CFM

SHOWN.

GENERAL NOTES

1. CONTRACTOR TO PATCH, PRIME, AND PAINT

WALLS/CEILINGS TO MATCH EXISTING WHERE

EXISTING SUPPLY DIFFUSERS AND RETURN

GRILLES WERE REMOVED AND NOT ENTIRELY

FILLED BY NEW SUPPLY DIFFUSERS AND

RETURN GRILLES. ONLY LOCATION OF WORK

NEEDS TO BE PAINTED NOT THE ENTIRE

WALL/CEILING.

2. CONTRACTOR TO PATCH, PRIME, AND PAINT

WALLS TO MATCH EXISTING WHERE EXISTING

THERMOSTATS WERE REMOVED AND NOT

COVERED BY NEW THERMOSTATS. ONLY

LOCATION OF WORK NEEDS TO BE PAINTED

NOT THE ENTIRE WALL.

3. ALL EXISTING DIFFUSERS & GRILLES TO BE

BALANCED TO EXISTING CFM AT THE END OF

CONSTRUCTION UNLESS OTHERWISE NOTED

ON DRAWINGS.

SEEDING SCHEDULE

CONTRACTOR TO SUPPLY 6" OF TOPSOIL OVER ALL

DISTURBED AREAS. SEED ALL DISTURBED AREAS

WITH THE FOLLOWING SEED MIX:

40% KENTUCKY BLUEGRASS

25% CREEPING FESCUE

20% PERENNIAL RYEGRASS

15% CHEWING FESCUE

APPLY AT A RATE OF 8 LBS PER 1,000 SQUARE FEET

OR 350 LBS PER ACRE.

file no.

checked by drawn by consultant contract order no.

472/LCFMAINTPROJ

consultant job no.

20080.00

M a t r ix

472/19503.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N issue date

KEY PLAN

9/14/2023 FOR CONSTRUCTION

BUILDING 29C LOWER ATTIC

PLAN - MECHANICAL NEW

N BUILDING 29C LOWER ATTIC PLAN - MECHANICAL NEW (ADD ALTERNATE #1)

SCALE: 1/8" = 1'-0"

0 1 5 10 20

M-403

X-CUPOLA

(ON ROOF)

X-CUPOLA

(ON ROOF)

26x34

SA DN

26x34

RA DN

26x34

SA DN

26x34 RA DN

26x34

SA DN

26x34

RA DN

26x34

SA DN

24x18

SA DN

24x18

RA UP

24x18

RA DN

24x18

SA DN

24x14

EA UP

26x34

RA DN

HVAC KEY NOTES

ROUTE NEW SUPPLY AND RETURN DUCTWORK

UP THE SIDE OF THE BUILDING IN NEWLY

CONSTRUCTED CHASE TO NEW ATTIC

PENETRATIONS IN NEW ROOF GABLE.

ROUTE NEW EXHAUST AIR DUCT WORK UP TO

EXISTING CUPOLA ON ROOF.

file no.

checked by drawn by consultant contract order no.

472/LCFMAINTPROJ

consultant job no.

20080.00

M a t r ix

472/19503.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N issue date

KEY PLAN

9/14/2023 FOR CONSTRUCTION

BUILDING 29A UPPER ATTIC

PLAN - MECHANICAL NEW

N BUILDING 29A UPPER ATTIC PLAN - MECHANICAL NEW (BASE BID)

SCALE: 1/8" = 1'-0"

0 1 5 10 20

M-404

X-6x6

SA DN

X-20x16

SA DN

X-20x12

SA DN

X-12x8

RA DN

X-18x8 RA DN

X-18x8 RA DN

X-12x12

SA DN

X-16x8 EA

DN

X-10x4 RA

DN

X-10x6 SA DN X-8x8

SA DN

X-12x10

SA DN

X-30x8 RA

DN

X-16x8

SA DN

X-12x10

SA DN

X-12x8

SA DN

X-10x10 SA DN

X-10x8 SA DN

X-24x12

EA DN

X-20x12 RA

X-20x16 RA

X-20x20 RA X-20x20 RA

X-16x20 RA X-20x20 RA

X-20x14

RA

X-12x12

RA DN

X-20x16 RA

X-10x6 RAX-10x4 RA

X-INTAKELOUVER

X-14x8 RA

X-40x20

RA DN

X-24x12 EA

X-10x18 EA

X-8x18 EAX-20x12 EA

X-12x6 EA

X-16x8 EA

X-20x8

EA DN

X-18x18

EA

X-18x18 EA X-24x22 EA

X-18x26 EA

X-10"ø SA X-10"ø SA

X-14"ø SA X-14"ø SA

X-10x14

SA

X-10x14 SA

X-18x14 SA X-10x8

SA

X-18x16

SA

X-18x18

SA

X-12x32

SA

X-32x20 SAX-36x24 SAX-22x24 SA

X-24x16 SA

X-24x8

SA

X-16x16 SA X-10x8 SA

X-14x8 SA

X-24x12 SAX-20x10

SA

X-20x8 SAX-18x8 SAX-14x8 SA

X-14x8 SA

X-14x6 SA

X-10x8

SA

X-8x6 SA

X-6x8SA

X-24x28 SAX-20x24 SA

X-20x22 SA

X-20x16 SA

X-26x12 SA

X-8x6 SAX-24x12 SA

X-24x8 SA X-24x8 SAX-14x8 SA

X-12x8 SAX-12x8 SA

X-8x6 SA

X-12x8 SA

X-12x8 SA

X-30x12 SA X-10x12

SA

X-20x8 SA

X-8x6 SA

X-12"ø SA

X-10"ø SA

X-10"ø SA

X-8"ø SA

X-38x32 SA

X-20x12 SA

X-20x12 SA

X-EXHAUST

LOUVER

X-12x6 RA

X-6x4 RA DN

X-6x4 RA

X-12x6 EA

DN

X-28x10

SA DN

X-18x8

EA DN

X-14x6

SA DN

X-8x6

SA DN

X-24x10

SA

X-12x12

SA DN

X-12x12

SA DN

X-12x12

SA DN

X-12x12

SA DN

X-8x8

SA DN

X-8x8

SA DN

X-8x8

SA DN

X-10x6

EA DN

X-8x8

SA DN

X-EF-9

X-18x18 EA

X-8x6

SA DN

X-12x8

SA DN

X-12x8

SA DN

X-12x8

SA DN

X-12x8

SA DN

X-8x6

SA DN

X-12x6

RA DN

X-16x16

SA DN

X-MAU

X-SF-12

X-16x16

SA

X-16x16

SA

X-6x6

SA DN

X-20x16

SA DN

X-20x12

SA DN

X-12x8

RA DN

X-18x8 RA DN

X-18x8 RA DN

X-12x12

SA DN

X-16x8 EA

DN

X-10x4 RA

DN

X-10x6 SA DN X-8x8

SA DN

X-12x10

SA DN

X-30x8 RA

DN

X-16x8

SA DN

X-12x10

SA DN

X-12x8

SA DN

X-10x10 SA DN

X-10x8 SA DN

X-24x12

EA DN

X-20x12 RA

X-20x16 RA

X-20x20 RA X-20x20 RA

X-16x20 RA X-20x20 RA

X-20x14

RA

X-12x12

RA DN

X-20x16 RA

X-10x6 RAX-10x4 RA

X-INTAKELOUVER

X-14x8 RA

X-40x20

RA DN

X-24x12 EA

X-10x18 EA

X-8x18 EAX-20x12 EA

X-12x6 EA

X-16x8 EA

X-20x8

EA DN

X-18x18

EA

X-18x18 EA X-24x22 EA

X-18x26 EA

X-10"ø SA X-10"ø SA

X-14"ø SA X-14"ø SA

X-10x14

SA

X-10x14 SA

X-18x14 SA X-10x8

SA

X-18x16

SA

X-18x18

SA

X-12x32

SA

X-32x20 SAX-36x24 SAX-22x24 SA

X-24x16 SA

X-24x8

SA

X-16x16 SA X-10x8 SA

X-14x8 SA

X-24x12 SAX-20x10

SA

X-20x8 SAX-18x8 SAX-14x8 SA

X-14x8 SA

X-14x6 SA

X-10x8

SA

X-8x6 SA

X-6x8SA

X-24x28 SAX-20x24 SA

X-20x22 SA

X-20x16 SA

X-26x12 SA

X-8x6 SAX-24x12 SA

X-24x8 SA X-24x8 SAX-14x8 SA

X-12x8 SAX-12x8 SA

X-8x6 SA

X-12x8 SA

X-12x8 SA

X-30x12 SA X-10x12

SA

X-20x8 SA

X-8x6 SA

X-12"ø SA

X-10"ø SA

X-10"ø SA

X-8"ø SA

X-38x32 SA

X-20x12 SA

X-20x12 SA

X-EXHAUST

LOUVER

X-12x6 RA

X-6x4 RA DN

X-6x4 RA

X-12x6 EA

DN

X-28x10

SA DN

X-18x8

EA DN

X-14x6

SA DN

X-8x6

SA DN

X-24x10

SA

X-12x12

SA DN

X-12x12

SA DN

X-12x12

SA DN

X-12x12

SA DN

X-8x8

SA DN

X-8x8

SA DN

X-8x8

SA DN

X-10x6

EA DN

X-8x8

SA DN

X-EF-9

X-18x18 EA

X-8x6

SA DN

X-12x8

SA DN

X-12x8

SA DN

X-12x8

SA DN

X-12x8

SA DN

X-8x6

SA DN

X-12x6

RA DN

X-16x16

SA DN

X-MAU

X-SF-12

X-16x16

SA

X-16x16

SA

42x28 SA DN

52x30 RA DN

24x10

SA DN

40x24

RA DN

VAV-B07

VAV-B08

VAV-B09

VAV-B12

VAV-B16

X-16x12

RA DN

X-12x8

SA DN4

20x20 RA DN 4 30x20 RA

14x12 SA DN

X-30x14

RA DN

40x24 RA

24"Ø SA

38x32

SA

M-800

22"Ø RA

42x28 SA

42x38 RA

24"Ø RA

24"Ø RA

22"Ø RA

24"Ø SA

22"Ø SA

24"Ø

SA

22"Ø

SA

24"Ø RA

22"Ø RA

VAV-B26 1

HVAC KEY NOTES

INSTALL NEW DDC VAV BOX AT LOCATION

SHOWN. MODIFY DUCTWORK AS REQUIRED FOR

NEW CONNECTION. CONNECT NEW DDC VAV

BOXES TO NEW DDC CONTROL PANEL.

ROUTE NEW SUPPLY AND RETURN DUCTWORK

UP THE SIDE OF THE BUILDING IN NEWLY

CONSTRUCTED CHASE TO NEW ATTIC

PENETRATIONS IN NEW ROOF GABLE.

CONNECT EXISTING MAKE UP AIR UNIT AND

SUPPLY FAN TO NEW DDC CONTROL PANEL.

CONNECT NEW SUPPLY AIR DUCTWORK,

RETURN AIR DUCTWORK, AND ALL ASSOCIATED

ACCESSORIES TO EXISTING DUCTWORK AS

SHOWN. MODIFY EXISTING DUCTWORK AS

NEEDED FOR NEW CONNECTION.

CONNECT EXISTING EXHAUST FAN TO NEW DDC

CONTROL PANEL.

GENERAL NOTES

1. SEE M-800 SHEET FOR DETAILS SHOWING NEW

TRUNK LINE SUPPLY AND RETURN DUCT

ROUTING AND ORIENTATION THROUGH JOIST

OPENINGS. ONLY LARGEST TRUNK LINE DUCT

SIZE SHOWN ON DETAIL. CONTINUATION OF

DUCT ROUTING TO USE SIMILAR ROUTING PATH

THROUGH JOIST OPENINGS AT SIZES SHOWN.

2. ALL EXISTING DIFFUSERS & GRILLES TO BE

BALANCED TO EXISTING CFM AT THE END OF

CONSTRUCTION UNLESS OTHERWISE NOTED

ON DRAWINGS.

file no.

checked by drawn by consultant contract order no.

472/LCFMAINTPROJ

consultant job no.

20080.00

M a t r ix

472/19503.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N issue date

KEY PLAN

9/14/2023 FOR CONSTRUCTION

BUILDING 29B UPPER ATTIC

PLAN - MECHANICAL NEW

N BUILDING 29B UPPER ATTIC PLAN - MECHANICAL NEW (ADD ALTERNATE #1)

SCALE: 1/8" = 1'-0"

0 1 5 10 20

M-405

Sheets and Views
M-000-2008000-T-000
M100-2008000-M-100
M300-2008000-M-300
M301-2008000-M-301
M302-2008000-M-302
M303-2008000-M-303
M304-2008000-M-304
M305-2008000-M-305
M306-2008000-M-306
M307-2008000-M-307
M308-2008000-M-308
M309-2008000-M-309
M310-2008000-M-310
M311-2008000-M-311
M312-2008000-M-312
M313-2008000-M-313
M314-2008000-M-314
M315-2008000-M-315
M316-2008000-M-316
M317-2008000-M-317
M318-2008000-M-318
M319-2008000-M-319
M320-2008000-M-319
M400-2008000-M-400
M401-2008000-M-401
M402-2008000-M-402
M403-2008000-M-403
M404-2008000-M-404
M405-2008000-M-405
M406-2008000-M-406
M600-2008000-M-600
M601-2008000-M601
M602-2008000-M602
M603-2008000-M603
M604-2008000-M604
M605-2008000-M605
M606-2008000-M606
M607-2008000-M607
M608-2008000-M608
M609-2008000-M-609
M610-2008000-M-610
M611-2008000-M-611
M800-2008000-M-800
M801-2008000-M-801
M802-2008000-M-802
M900-2008000-M-900

File details come from the government source that posted it. Updated .