Drawings 12 of 12.pdf

PDF 1 MB Posted

Attached to
472/19503. SMD; Lakeland CF (SRF) - Building 29 HVAC Upgrades
Solicitation number
RFQ 171 230000000791 2
Issued by
Barry County, Michigan

About this file

This is an electrical riser diagram drawing prepared by the State of Michigan Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division for a facility maintenance project (Contract Order No. 472/LCFMAINTPROJ, Consultant Job No. 20080.00). The document presents two electrical riser diagrams—one showing existing equipment designated for demolition and a second showing the proposed new electrical configuration. The project involves modifications to the main distribution panel (MDP) rated at 2500A serving 120/208V three-phase, four-wire service, with work including the removal of a 50A breaker and installation of a 60A three-phase breaker to feed new equipment. The scope includes installation of new switchgear and breakers tied into the existing MDP, with the contractor required to match existing switchgear manufacturers and provide space for four spare 400A breakers. The project also requires installation of a new 1200A breaker in existing switchgear with arc flash reduction capability and coordination with the switchgear manufacturer.

The electrical modifications involve multiple distribution panels located in basements and attics, with connections to new rooftop units (RTU-1 through RTU-5) and existing HVAC systems, emergency power panels, UPS panels, and information system panels. New feeder circuits are specified with wire sizes ranging from 6 to 500KCMIL copper conductors with appropriate ground wires and conduit sizes. The project requires proper grounding integration with existing systems including water pipes, building steel, and footing steel grounds. The drawings were issued for construction on 9/14/2023 and reference comprehensive mechanical, electrical, and architectural sheet sets for the full project scope. The document was prepared by consultant JFS under the supervision of Director Adam P. Lach, RA, with drawing prepared by JKB.

View the file

Other files

File Type Posted
Drawings 1 of 12.pdf PDF
Drawings 2 of 12.pdf PDF
Drawings 8 of 12.pdf PDF
Drawings 4 of 12.pdf PDF
Drawings 5 of 12.pdf PDF
47219503.SMD - Addendum 1 Write-Up.pdf PDF
Lakeland - Specifications.pdf PDF
Drawings 10 of 12.pdf PDF
Drawings 9 of 12.pdf PDF
Drawings 7 of 12.pdf PDF
LEIN Request 19503.pdf PDF
Walkthrough Sign-in Sheet.pdf PDF
MICHSpec Rev032022 V12 - 47219503.SMD.pdf PDF
Drawings 6 of 12.pdf PDF
DTMB Advertisement.pdf PDF
Drawings 3 of 12.pdf PDF
Drawings 11 of 12.pdf PDF
MICHSpec Rev032022 V12.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GROUND BUS

EXISTING "MDP"

120/208V-3Ø, 4W 2500A

A/

3P

PANEL

EXISTING

BASEMENT 3

120/208V 3Ø, 4W

0A

/3P

SPARE

0A

/3P

PANEL

EXISTING

BASEMENT 2

120/208V 3Ø, 4W

0A

/3P

EXISTING

TO AC-2

0A

/3P

EXISTING

TO AC-3

0A

/3P

EXISTING

TO AC-1

0A

/3P

PANEL

EXISTING

A2 120/208V 3Ø, 4W

PANEL

EXISTING

A3 120/208V 3Ø, 4W

SECTION 1

2500A/3P

EXISTING

CUSTOMER

2400V : 120/208V, 3PH 4W

5A

/3P

TO EXISTING

EMERGENCY

POWER

PANEL

EXISTING

EMERGENCY

120/208V 3Ø, 4W

PANEL

EXISTING

EM2

120/208V 3Ø, 4W

5A

/3P

5A

/3P

PANEL

EXISTING

A6 120/208V 3Ø, 4W

PANEL

EXISTING

A7 120/208V 3Ø, 4W

5A

/3P

EXISTING

TO INFO

PANEL

A/

3P

A/

3P

0A

/3P

0A

/3P

0A

/3P

5A

/3P

5A

/3P

SECTION 2

5A

/3P

0A

/3P

5A

/3P

A/

3P

EXISTING

TO EAST AC

EXISTING

TO EAST AC

PANEL

EXISTING

ATTIC HVAC

120/208V 3Ø, 4W

PANEL

EXISTING

ATTIC A

120/208V

3Ø, 4W EXISTING

TO UPS

PANEL

EXISTING

A5 120/208V 3Ø, 4W

PANEL

EXISTING

ATTIC A5

120/208V 3Ø, 4W

EXISTING

TO INFO

PANEL

PANEL

EXISTING

BASEMENT 1

120/208V 3Ø, 4W

PANEL

EXISTING

A6 120/208V 3Ø, 4W

PANEL

EXISTING

FOOD TENT

120/208V

3Ø, 4W EXISTING

TO AC-A2

EXISTING EXISTING

EXISTING ELECTRICAL RISER DIAGRAM - DEMOLITION

SCALE: N.T.S.

1 3 5 7 9 11 13 15 17 19 21 2 4 6 8 10 12 14 16 18 20 22

GROUND BUS

EXISTING "MDP"

120/208V-3Ø, 4W 2500A

A/

3P

PANEL

EXISTING

BASEMENT 3

120/208V 3Ø, 4W

0A

/3P

SPARE

0A

/3P

PANEL

EXISTING

BASEMENT 2

120/208V 3Ø, 4W

0A

/3P

TO NEW

RTU-3

0A

/3P

TO NEW

RTU-1

0A

/3P

0A

/3P

PANEL

EXISTING

A2 120/208V 3Ø, 4W

PANEL

EXISTING

A3 120/208V 3Ø, 4W

SECTION 1

2500A/3P

EXISTING

CUSTOMER

2400V : 120/208V, 3PH 4W

5A

/3P

TO EXISTING

EMERGENCY

POWER

PANEL

EXISTING

EMERGENCY

120/208V 3Ø, 4W

PANEL

EXISTING

EM2

120/208V 3Ø, 4W

5A

/3P

5A

/3P

PANEL

EXISTING

A6 120/208V 3Ø, 4W

PANEL

EXISTING

A7 120/208V 3Ø, 4W

5A

/3P

EXISTING

TO INFO

PANEL

A/

3P

A/

3P

0A

/3P

0A

/3P

0A

/3P

5A

/3P

5A

/3P

SECTION 2

5A

/3P

0A

/3P

5A

/3P

A/

3P

PANEL

EXISTING

ATTIC HVAC

120/208V 3Ø, 4W

PANEL

EXISTING

ATTIC A

120/208V

3Ø, 4W EXISTING

TO UPS

PANEL

EXISTING

A5 120/208V 3Ø, 4W

PANEL

EXISTING

ATTIC A5

120/208V 3Ø, 4W

EXISTING

TO INFO

PANEL

PANEL

EXISTING

BASEMENT 1

120/208V 3Ø, 4W

PANEL

EXISTING

A6 120/208V 3Ø, 4W

PANEL

EXISTING

FOOD TENT

120/208V

3Ø, 4W EXISTING

TO AC-A2

EXISTING EXISTING

EXISTING ELECTRICAL RISER DIAGRAM - NEW

SCALE: N.T.S.

1 3 5 7 9 11 13 15 17 19 21 2 4 6 8 10 12 14 16 18 20 22

EXISTING EQUIPMENT TO REMAIN.

DISCONNECT EQUIPMENT FOR REMOVAL BY OTHERS. CONDUIT AND WIRE

TO REMAIN, MODIFY AS REQUIRED TO FEED NEW EQUIPMENT.

DISCONNECT EQUIPMENT FOR REMOVAL BY OTHERS. REMOVE ASSOCIATED

CONDUIT AND WIRE.

DEMOLITION NOTES

1 1

1 1 1 1

1 1 1

1 1

12 3 3 3 3

SPARE SPARE

ELECTRICAL KEY NOTES

REMOVE EXISTING 50A BREAKER AND PROVIDE AND INSTALL A 60A-3P

BREAKER TO FEED NEW EQUIPMENT.

CONTRACTOR SHALL PROVIDE AND INSTALL A NEW SECTION OF

SWITCHGEAR AND BREAKERS, TIE INTO EXISTING MDP. MATCH EXISTING

SWITCHGEAR MANUFACTURE. PROVIDE ENOUGH SPACE IN SWITCHGEAR TO

HOUSE (4) SPARE 400A BREAKERS.

TIE GROUND INTO EXISTING GROUNDING, WATER PIPE, BUILDING STEEL

AND FOOTING STEEL GROUNDS.

PROVIDE AND INSTALL NEW 1200A BREAKER IN EXISTING SWITCHGEAR.

COORDINATE INSTALLATION WITH SWITCHGEAR MANUFACTURE. BREAKER

MUST HAVE ARC FLASH REDUCTION.

TO NEW

RTU-2

0A

/3P

GROUND BUS

SECTION 3 "MDP-S3"

NEW

TO NEW

RTU-4

0A

/3P

TO NEW

RTU-5

SPACE

(4) 400KCMIL

(1) #3 GND

3" CND

(4) 500KCMIL

(1) #3 GND

3" CND

(4) 3/0

(1) #6 GND

2" CND

(4) 3/0

(1) #6 GND

2" CND

(4) 6

(1) #10 GND

1" CND

EXISTING

750KVA

EXISTING

750KVA

EX

EX

A/ 3P

4 SETS OF

(4) 350KCMIL

(1) 3/0 GND

3" CND

file no.

checked by drawn by consultant contract order no.

472/LCFMAINTPROJ

consultant job no.

20080.00

M a t r ix

472/19503.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N issue date

9/14/2023 FOR CONSTRUCTION

E-600

JKB

JFS

ELECTRICAL

RISER

DIAGRAM

Sheets and Views
M-000-2008000-T-000
M100-2008000-M-100
M300-2008000-M-300
M301-2008000-M-301
M302-2008000-M-302
M303-2008000-M-303
M304-2008000-M-304
M305-2008000-M-305
M306-2008000-M-306
M307-2008000-M-307
M308-2008000-M-308
M309-2008000-M-309
M310-2008000-M-310
M311-2008000-M-311
M312-2008000-M-312
M313-2008000-M-313
M314-2008000-M-314
M315-2008000-M-315
M316-2008000-M-316
M317-2008000-M-317
M318-2008000-M-318
M319-2008000-M-319
M320-2008000-M-319
M400-2008000-M-400
M401-2008000-M-401
M402-2008000-M-402
M403-2008000-M-403
M404-2008000-M-404
M405-2008000-M-405
M406-2008000-M-406
M600-2008000-M-600
M601-2008000-M601
M602-2008000-M602
M603-2008000-M603
M604-2008000-M604
M605-2008000-M605
M606-2008000-M606
M607-2008000-M607
M608-2008000-M608
M609-2008000-M-609
M610-2008000-M-610
M611-2008000-M-611
M800-2008000-M-800
M801-2008000-M-801
M802-2008000-M-802
M900-2008000-M-900
Elec.pdf
Sheets and Views
E100-2008000-30x42
E300-200800-30x42
E301-2008000-30x42
E302-2008000-30x42
E303-2008000-30x42
E304-2008000-30x42
E305-2008000-30x42
E500-2008000-30x42
E501-2008000-30x42
E502-2008000-30x42
E503-2008000-30x42
E600-2008000-30x42

File details come from the government source that posted it. Updated .