Drawings 10 of 12.pdf
PDF 4 MB Posted
- Solicitation number
- RFQ 171 230000000791 2
- Issued by
- Barry County, Michigan
About this file
This file consists of mechanical construction drawings for a state facility maintenance project issued by the Department of Technology, Management and Budget, State of Michigan, State Facilities Administration, Design and Construction Division. The drawings depict piping and HVAC system installations for Buildings 29A, 29B, and 29C, with an issue date of September 14, 2023. The project includes installation of new variable air volume (VAV) boxes in specified locations, modification of existing piping systems, installation of new shutoff valves, balance valves, and control valves, and placement of new DDC flat plate sensors with associated wiring. The work encompasses upper attic piping plans for the base bid and Add Alternate #1 configurations, along with comprehensive mechanical details for heating coil installations, duct routing specifications, concrete pad requirements, and pressure relief valve assemblies. The contract order number is referenced as 472/LCFMAINTPROJ with a consultant job number of 20080.00 and funding code 472/19503.SMD.
The drawings provide detailed specifications for concrete pad construction including 4,000 PSI concrete with limestone mix and 6x6 W4.0 welded wire mesh reinforcement, with pads to be positioned minimum 4 inches above grade. The documents include specifications for multiple RTU (Rooftop Unit) installations with heating coil details, pump selections, and hot water supply/return piping configurations. Pressure relief valve specifications are detailed for steam systems, including Spirax Sarco Model 25P valves with inlet pressure of 90 PSIG and outlet pressure of 15 PSIG. The drawings reference coordination with existing mechanical prints and architectural plans for exact dimensions and construction details, with completion anticipated based on the September 2023 issuance date. No pricing, incumbency information, or explicit contract award dates are presented in these technical construction drawings.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
X-3" STM
X-3" STM
X-3" STM
X-3" STM
X-1-1/2" SC
X-1-1/2" SC
X-1-1/2" SC
X-1-1/2" SC
X-STM AND
X-SC DN
GENERAL NOTES
1. NO NEW PIPING WORK ON THIS PLAN.
file no.
checked by drawn by consultant contract order no.
472/LCFMAINTPROJ
consultant job no.
20080.00
M a t r ix
472/19503.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N issue date
KEY PLAN
9/14/2023 FOR CONSTRUCTION
M-606
BUILDING 29A UPPER ATTIC
PLAN - PIPING NEW
N BUILDING 29A UPPER ATTIC PLAN - PIPING NEW (BASE BID)
SCALE: 1/8" = 1'-0"
0 1 5 10 20
DBP
CAT
X-MAU
X-2" SC
X-3-1/2" STM
& 2" SC
X-2" SC DN TO
MECH ROOM
X-3-1/2" STM DN
TO MECH ROOM
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-2" SC
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-3" STM
X-3" STM
X-1-1/2" SC
X-1-1/2" SC
X-2-1/2" G
X-2" G
X-2" G
X-2-1/2"
G DN
X-MAU
VAV-B07
VAV-B08
VAV-B09
VAV-B12
VAV-B16
1 1
S
S
S
S
VAV-B26 1
S
PIPING KEY NOTES
INSTALL NEW VAV BOXES IN NEW LOCATIONS
SHOWN PER MANUFACTURE'S INSTALLATION
INSTRUCTIONS. MODIFY EXISTING PIPING AS
NEEDED FOR NEW VAV BOX INSTALLATION AND AS
NEEDED TO INSTALL NEW SHUTOFF VALVES,
BALANCE VALVE, AND CONTROL VALVE.
INSTALL NEW DDC FLAT PLATE SENSORS IN THE
AND ASSOCIATED DDC WIRING IN LOCATION SHOWN.
MOUNT NEW FLAT PLATE SENSORS USING TAMPER
PROOF SCREWS.
SEE M-604 FOR PIPING CONTINUATION.
GENERAL NOTES
1. SENSORS ARE LOCATED IN THE OCCUPIED
SPACE. THERMOSTATS SHOWN ON THIS PLAN
FOR CLARITY.
file no.
checked by drawn by consultant contract order no.
472/LCFMAINTPROJ
consultant job no.
20080.00
M a t r ix
472/19503.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N issue date
KEY PLAN
9/14/2023 FOR CONSTRUCTION
M-607
BUILDING 29B UPPER ATTIC
PLAN - PIPING NEW
N BUILDING 29B UPPER ATTIC PLAN - PIPING NEW (ADD ALTERNATE #1)
SCALE: 1/8" = 1'-0"
0 1 5 10 20
X-MAU
X-1-1/4"
STM
X-1" SC
X-3-1/2" STM
X-1" SC
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-3/4" HS
& HR DN
X-MAU
VAV-B16
VAV-C05VAV-C06
VAV-C17
VAV-C18
VAV-C16
VAV-C20
VAV-C19
1 1
VAV-C311
S
S
S
S
S
S
S
3 3
PIPING KEY NOTES
INSTALL NEW VAV BOXES IN NEW LOCATIONS
SHOWN PER MANUFACTURE'S INSTALLATION
INSTRUCTIONS. MODIFY EXISTING PIPING AS
NEEDED FOR NEW VAV BOX INSTALLATION AND AS
NEEDED TO INSTALL NEW SHUTOFF VALVES,
BALANCE VALVE, AND CONTROL VALVE.
INSTALL NEW DDC FLAT PLATE SENSORS IN THE
AND ASSOCIATED DDC WIRING IN LOCATION SHOWN.
MOUNT NEW FLAT PLATE SENSORS USING TAMPER
PROOF SCREWS.
SEE M-605 FOR PIPING CONTINUATION.
GENERAL NOTES
1. SENSORS ARE LOCATED IN THE OCCUPIED
SPACE. THERMOSTATS SHOWN ON THIS PLAN
FOR CLARITY.
file no.
checked by drawn by consultant contract order no.
472/LCFMAINTPROJ
consultant job no.
20080.00
M a t r ix
472/19503.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N issue date
KEY PLAN
9/14/2023 FOR CONSTRUCTION
M-608
BUILDING 29C UPPER ATTIC
PLAN - PIPING NEW
N BUILDING 29C UPPER ATTIC PLAN - PIPING NEW (ADD ALTERNATE #1)
SCALE: 1/8" = 1'-0"
0 1 5 10 20
28"Ø SA (RTU-3)
1 SECTION A MIDDLE ROUTING SOUTH CROSS SECTION
SCALE: NTS
18"x14" SA (RTU-2)18"x14" RA (RTU-2) 36"x24" RA (RTU-3)WALKWAY
2 SECTION A MIDDLE ROUTING NORTH CROSS SECTION
SCALE: NTS
28"Ø SA (RTU-1)
18"x14" SA (RTU-2)18"x14" RA (RTU-2) 36"x24" RA (RTU-1)WALKWAY
20"Ø SA (RTU-1)20"Ø SA (RTU-1) 20"x16" RA (RTU-1)20"x16" RA (RTU-1) WALKWAY
3 SECTION A NORTH WING CROSS SECTION
SCALE: NTS
20"Ø SA (RTU-1)20"Ø SA (RTU-1) 20"x16" RA (RTU-1)20"x16" RA (RTU-1) WALKWAY
4 SECTION A SOUTH WING CROSS SECTION
SCALE: NTS
5 SECTION B NEW MAIN DUCT ROUTING SOUTH CROSS SECTION
SCALE: NTS
24"Ø SA (RTU-4)
22"Ø RA (RTU-4)
24"Ø RA (RTU-4)
X-18x18 EAWALKWAY
22"Ø SA (RTU-4)
24x10 SA (RTU-4) 14x12 SA (RTU-4)
FRAME
VANED ELBOW
LOCKING LUG
2-1/4"R
4-1/2"R
TURNING VANE
NOTES:
1. LOCKING LUGS INTEGRAL WITH VANE
2. MAXIMUM UNSUPPORTED VANE LENGTH 48"
3. FRAMES - BOLTED OR RIVETED TO ELBOW
4. VANES AND FRAMES - SAME GAUGE AS ELBOW
2 1/4" 3 1/2"
9 TURNING VANES FORSQUARE ELBOW DETAIL
SCALE: NTS
HANGER STRAPS HANGER RODS
STRAP HANGER TRAPEZE HANGER
NO POP RIVETS ALLOWED, USE
SELF-TAPPING SHEETMETAL SCREWS
ONLY (TYP)
7 DUCT HANGER DETAIL
SCALE: NTS
RADIUS ELBOW
NOTE:
90° ELBOW SHOWN
SIMILAR RADIUS
CONSTRUCTION FOR
ALL ANGLES
R
R
OFFSET
ELBOW
FULL RADIUS
(R=W)
FLOW
AIR
TRANSITION - CONTRACTION FLOW
TRANSITION - DIVERGING FLOW
FLOW
AIR
W
W
R=1/ W
W
RECTANGULAR TRANSITIONS, OFFSETS, AND
ELBOWS
SCALE: NTS
6 SECTION C NEW MAIN DUCT ROUTING WEST CROSS SECTION
SCALE: NTS
22"Ø RA (RTU-5)
24"Ø RA (RTU-5)
24"Ø SA (RTU-5)
40x20 SA (RTU-5)
11 DUCT TRANSITION DETAIL
SCALE: NTS
VD
NOTES:
1. "ALTERNATE" FITTINGS SHALL BE
ACCEPTABLE ONLY WHEN DUCT HEIGHT
DOES NOT PERMIT THE USE OF
"PERMITTED" FULL SIZE BELLMOUTH
CONNECTION
2. THIS DETAIL APPLIES TO SINGLE TAKEOFFS
TO DIFFUSER AS WELL AS BRANCH
TAKEOFFS. IT ALSO APPLIES TO TAKEOFFS
IN THE HORIZONTAL AS WELL AS THE
VERTICAL DIRECTION.
DUCT SIZE:
(SEE PLANS)
PREFERRED
TAKE-OFF DETAIL
ALTERNATE 1
TAKE-OFF DETAIL
ALTERNATE 2
TAKE-OFF DETAIL
(WHEN OTHERS DO NOT FIT)
STANDARD
45° RECTANGULAR
DUCT CONNECTION
(SUPPLY SHOWN,
RETURN/EXHAUST SIMILAR)
RECTANGULAR TO ROUND
BOOT CONNECTIONMINI-BELLMOUTH CONNECTIONBELLMOUTH
CONNECTION
MANUAL VOLUME
DAMPER TYPICAL AT
ALL DUCT
TAKE-OFFS
VDVD
MAIN DUCT
AIR FLOW
6" min.
NOTES:
1. FLEXIBLE DUCTWORK SHALL NOT BE PERMITTED
UPSTREAM OF VAV BOXES.
2. DUCT TRANSITIONS SHALL BE A MINIMUM OF 3
DUCT DIAMETERS UPSTREAM OF ANY VAV BOX.
REDUCER OR INCREASER
IF REQUIRED
LINED SHEET METAL RUN-OUT
SIZE AS SHOWN ON PLAN 10 FT.
MIN. BEFORE TAKE OFF
SUPPLY DIFFUSER (SEE
SCHED. FOR TYPE)
COLLAR
FLEX ELBOW
DIFFUSER
NECK SIZE
FLEXIBLE DUCT
PROVIDE HANGER
CEILING
SHEET METAL RUN-OUT
SIZE AS SHOWN ON PLAN
BALANCE DAMPER
FLOW RING
VAV
SUPPLY AIR
DUCT
CONICAL TAP.
RUNOUT SIZE
PER PLAN
TRANSITION AS
REQUIRED
3 DUCT
DIA. MIN.
5 DUCT DIA. MIN.
6'-0" MAX.
10 VAV DUCT DETAIL
SCALE: NTS
12" DEEP 4,000 PSI W/6-8% AIR INTRADMENT LIMESTONE MIX
4.5 TO 6.5 SLUMP FIBER MESH CONCRETE PAD WITH #4 REBAR
TOP OF CONCRETE PAD TO BE MINIMUM 4" ABOVE GRADE
1" BY 1"
CHAMFER
(ALL ROUND)
GRADE
HOUSE KEEPING PADS SIZED AS
SHOWN ON NEW ARCHITECTURAL
PLANS AND PROVIDE A 1" X 1" CHAMFER
AROUND ALL EDGES. (TYP.)
12"
6"
GRADE
CONCRETE
1. CONCRETE MATERIAL SHALL BE:
1.1. ASTM C150 - TYPE 1 PORTLAND, COLOR SHALL MATCH EXISTING.
1.2. FINE AND COARSE AGGREGATES: ASTM C33, FINE MDOT DESIGNATED 2NS, COARSE MDOT
DESIGNATED 6AA.
1.3. WATER: CLEAN AND NOT DETRIMENTAL TO CONCRETE.
1.4. MIX CONCRETE IN ACCORDANCE WITH ASTM C94. MIXTURE SHALL BE HIGH-EARLY IN
ACCORDANCE WITH MDOT CONCRETE P-NC PER MDOT STANDARD SPECIFCATIONS FOR
CONSTRUCTION 2012, SECTION 603 AND 801.
2. THE CONCRETE DEPTH IS INDICATED ON THE DETAILS.
3. GRANULAR BASE SHALL BE 21AA CRUSHED LIMESTONE.
4. ADMIXTURES:
4.1. AIR ENTRAINMENT ASTM C260
4.2. CHEMICAL ASTM C494, TYPE B AND D ONLY, TYPE B - RETARDING TYPE D - WATER REDUCING
AND TESTING.
5. REINFORCEMENT SHALL BE 6 X 6 W4.0 X W4.0 WELDED WIRE MESH.
6. FORMED JOINTS:
6.1. PLACE EXPANSION JOINT FILLER BETWEEN PAVING COMPENTS, AND BUILDING OR OTHER
APPURTENANCES, EXCEPT WHERE SIDEWALK ABUTS BITUMINOUS PAVEMENT. RECESS TOP
OF FILLER 1/2 INCH.
7. PSI OF THE CONCRETE SHALL BE A MINIMUM OF 4,000 W/6-8% AIR INTRADEMENT LIMESTONE MIX
4.5 TO 6.5 SLUMP FIBER MESH CONCRETE.
8. PLACING CONCRETE:
8.1. IN ACCORDANCE WITH ACI 301
8.2. ENSURE REINFORCEMENT, INSERTS, EMBEDDED PARTS AND FORMED JOINTS ARE NOT
DISTURBED DURING CONCRETE PLACEMENT.
8.3. POOR CONTINUOUSLY BETWEEN PREDETERMINED CONSTRUCTION JOINTS. DO NOT BREAK
OR INTERRUPT SUCCESSIVE POURS SUCH THAT COLD JOINTS OCCUR.
9. RESTORE GRADE AND PLANT GRASS TO MATCH EXISTING GRADE. REFER TO SEEDING
SCHEDULE ON SHEET M-401, M-402. & M-403.
10. SEALER:
10.1. PROVIDE AND INSTALL A PENETRATING SEALING COMPOUND ON BASES EQUAL TO PENTREAT
244-100.
10.1.1. DESIGN TO LIMIT THE INTRUSION OF MOISTURE AND CHLORIDES INTO THE SUBSTRATE.
10.1.2. REDUCES SPALLING.
10.1.3. PENETRATES DEEPLY FOR MAXIMUM PROTECTION.
10.1.4. MINIMIZES PENETRATION FROM DE-ICING CHEMICALS, SALT, WATER THAT MIGHT
DAMAGE CONCRETE SURFACES.
10.1.5. SEALS PORES AND CAPILLARIES OF SUBSTRATE, PREVENTING LIQUID ABSORPTION
WHILE ALLOWING EXCELLENT VAPOR TRANSMISSION.
10.1.6. LEAVES NO RESIDUE AND REQUIRES NO CLEANING AFTER APPLICATION.
1ST FLOOR
CONCRETE
PADDUCT SUPPORT, TYP. BASED ON
MIRO 8-DS OR APPROVED EQUAL
UNISTRUCT HORIZONTAL
DUCT SUPPORT FRAME
(TYP.) RTU
RA
RA
RA
48" TALL CURB
NOTES:
1. SIMILAR FOR RTU-1, RTU-3, RTU-4, AND RTU-5.
2. GRADE MOUNTED CURB 48" TALL WITH SA AND RA OPENINGS.
3. SEE NEW MECHANICAL PRINTS FOR RETURN AIR DUCT SIZES.
4. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT CHASE
DIMENSIONS AND CONSTRUCTION.
FLEXIBLE
CONNECTOR
CEILING
UNISTRUCT VERTICAL
DUCT SUPPORT FRAME
CONCRETE
PAD
DUCT SUPPORT, TYP. BASED ON
MIRO 8-DS OR APPROVED EQUAL
RTU
SA
48" TALL CURB
NOTES:
1. SIMILAR FOR RTU-1, RTU-3, RTU-4, AND RTU-5.
2. GRADE MOUNTED CURB 48" TALL WITH SA AND RA OPENINGS.
3. SEE NEW MECHANICAL PRINTS FOR SUPPLY AIR DUCT SIZES.
4. SEE NEW MECHANICAL PRINTS FOR HEATING COIL SELECTION.
INSTALL HEATING COIL APPROXIMATELY 48" ABOVE CONCRETE
PAD.
5. SEE NEW MECHANICAL PRINTS FOR NEW PUMP SELECTION AND
NEW HOT WATER SUPPLY AND HOT WATER RETURN SIZES.
INSTALL NEW PUMP AT APPROXIMATELY 60". FASTEN PIPING AND
PUMP T0 UNISTRUCT FRAME INSIDE CHASE.
6. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT CHASE
DIMENSIONS AND CONSTRUCTION.
7. TRANSITION DUCTWORK AS NEEDED TO ACCOMMODATE HEATING
COIL THAT IS LARGER THAN DUCT.
FLEXIBLE
CONNECTOR
HEATING
COIL
12 GRADE MOUNTED RTU-1, 3, 4, & 5 DETAIL
SCALE: NTS
PUMP
HS
HR
SA ELEVATIONRA ELEVATION
1ST FLOOR
UNISTRUCT HORIZONTAL
DUCT SUPPORT FRAME
(TYP.)
SA
CEILING
UNISTRUCT VERTICAL
DUCT SUPPORT FRAME
file no.
checked by drawn by consultant contract order no.
472/LCFMAINTPROJ
consultant job no.
20080.00
M a t r ix
472/19503.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N issue date
9/14/2023 FOR CONSTRUCTION
M-800
MECHANICAL DETAILS
AHU HEATING COIL DETAIL
(2-WAY CONTROL VALVE)
SCALE: NTS
SHUT-OFF VALVE (TYP.)
UNION (TYP.)
STRAINIER(TYP.)
PUMP
HOSE END
DRAIN VALVE (TYP.)
HS
2-WAY MODULATING
CONTROL VALVE
P/T TAP (TYP.)
HR
BALANCE VALVE (TYP.)
MANUAL
AIR VENT
COIL
P P
PRESSURE GAUGE (TYP.) CHECK VALVE (TYP.)
THERMOMETER (TYP.)
SHUT-OFF VALVE (TYP.)
NOTES:
1. SIMILAR FOR HC-2, HC-3, HC-4, AND HC-5
2. SEE NEW PIPING PRINTS FOR PIPE SIZES.
3. SEE NEW MECHANICAL PRINTS FOR HEATING COIL SELECTION.
INSTALL HEATING COIL HORIZONTALLY APPROXIMATELY 60"
ABOVE CONCRETE PAD.
4. SEE NEW PIPING PRINTS FOR NEW PUMP SELECTION AND
INSTALL NEW PUMP AT APPROXIMATELY 72". FASTEN PIPING AND
PUMP T0 UNISTRUCT FRAME INSIDE CHASE.
COIL
HS
HR
SHUTOFF
VALVE
CIRCUIT SETTER
UNION (TYP)
MANUAL AIR VENT
P/T TAP (TYP.)
3/4" HOSE END DRAIN VALVE
2-WAY MODULATING
CONTROL VALVE
4 CABINET UNIT HEATER HEATING COIL DETAIL
SCALE: NTS
X-HR
X-HS
COIL
HS
HR
3/4" HOSE END
DRAIN VALVE 2-WAY MODULATING
CONTROL VALVE
STRAINER
CIRCUIT SETTER
UNION (TYP)
MANUAL AIR VENT
P/T TAP (TYP.)
3 VAV HEATING COIL DETAIL
SCALE: NTS
X-HR
X-HSSHUTOFF VALVE
TYPICAL VAV TERMINAL UNIT
HYDRONIC PIPING DIAGRAM
SCALE: NTS
2 HEAT EXCHANGER SKID DETAIL (HTP-1 & HTP-2)
SCALE: NTS
P
P
P
PT
P
P
PT X-HS
X-HR
FT
X-CD
X-STM
TO X-FD
P
X-MAKE UP CW
P
HEAT EXCHANGER
AIR SEPERATOR
EXPANSION TANK
PUMP (TYP.)
TRIPLE DUTY VALVE (TYP.)
PRESSURE/TEMPERATURE SENSOR (TYP.)
PRESSURE GUAGE (TYP.)
THERMOMETER (TYP.)
PRESSURE RELIEF VALVE (TYP.)
STRAINER (TYP.)
SHUTOFF VALVE (TYP.)
STEAM TRAP
PIPE CAP (TYP.)
SENSOR PORT (TYP.)
CHECK VALVE (TYP.)
PRESURE REDUCING VALVE
UNION (TYP.)
AIR VENT
PLUG VALVE
NOTES:
1. SIMILAR FOR HTP-1 & HTP-2
2. SEE NEW BASEMENT PIPING PRINTS FOR PIPE SIZES
CONNECTING TO HEAT TRANSFER SKID PACKAGE.
3. SEE HEAT TRANSFER SKID PACKAGE SCHEDULE FOR PUMP, AIR
SEPARATOR, EXPANSION TANK, AND HEAT EXCHANGER
INFORMATION AND BASIS OF DESIGN MODEL NUMBERS.
4. ALL COMPONENTS OF HEAT TRANSFER SKID PACKAGE TO BE
PRE-PIPED, PRE-WIRED, AND MOUNTED ON STURDY STEEL
FRAME.
5. HEAT TRANSFER SKID PACKAGE TO HAVE SINGLE 208/3/60 POWER
CONNECTION.
6. HEAT TRANSFER SKID PACKAGE TO INCLUDE ALL-INCLUSIVE
TOUCH SCREEN DDC CONTROL PANEL.
MODULATING CONTROL
VALVE (BY MANU.)
5 GRADE MOUNTED RTU-2 DETAIL
SCALE: NTS
12" DEEP 4,000 PSI W/6-8% AIR INTRADMENT LIMESTONE MIX
4.5 TO 6.5 SLUMP FIBER MESH CONCRETE PAD WITH #4 REBAR
TOP OF CONCRETE PAD TO BE MINIMUM 4" ABOVE GRADE
1" BY 1"
CHAMFER
(ALL ROUND)
GRADE
HOUSE KEEPING PADS SIZED AS
SHOWN ON NEW ARCHITECTURAL
PLANS AND PROVIDE A 1" X 1" CHAMFER
AROUND ALL EDGES. (TYP.)
12"
6"
GRADE
CONCRETE
1. CONCRETE MATERIAL SHALL BE:
1.1. ASTM C150 - TYPE 1 PORTLAND, COLOR SHALL MATCH EXISTING.
1.2. FINE AND COARSE AGGREGATES: ASTM C33, FINE MDOT DESIGNATED 2NS, COARSE MDOT
DESIGNATED 6AA.
1.3. WATER: CLEAN AND NOT DETRIMENTAL TO CONCRETE.
1.4. MIX CONCRETE IN ACCORDANCE WITH ASTM C94. MIXTURE SHALL BE HIGH-EARLY IN
ACCORDANCE WITH MDOT CONCRETE P-NC PER MDOT STANDARD SPECIFCATIONS FOR
CONSTRUCTION 2012, SECTION 603 AND 801.
2. THE CONCRETE DEPTH IS INDICATED ON THE DETAILS.
3. GRANULAR BASE SHALL BE 21AA CRUSHED LIMESTONE.
4. ADMIXTURES:
4.1. AIR ENTRAINMENT ASTM C260
4.2. CHEMICAL ASTM C494, TYPE B AND D ONLY, TYPE B - RETARDING TYPE D - WATER REDUCING
AND TESTING.
5. REINFORCEMENT SHALL BE 6 X 6 W4.0 X W4.0 WELDED WIRE MESH.
6. FORMED JOINTS:
6.1. PLACE EXPANSION JOINT FILLER BETWEEN PAVING COMPENTS, AND BUILDING OR OTHER
APPURTENANCES, EXCEPT WHERE SIDEWALK ABUTS BITUMINOUS PAVEMENT. RECESS TOP
OF FILLER 1/2 INCH.
7. PSI OF THE CONCRETE SHALL BE A MINIMUM OF 4,000 W/6-8% AIR INTRADEMENT LIMESTONE MIX
4.5 TO 6.5 SLUMP FIBER MESH CONCRETE.
8. PLACING CONCRETE:
8.1. IN ACCORDANCE WITH ACI 301
8.2. ENSURE REINFORCEMENT, INSERTS, EMBEDDED PARTS AND FORMED JOINTS ARE NOT
DISTURBED DURING CONCRETE PLACEMENT.
8.3. POOR CONTINUOUSLY BETWEEN PREDETERMINED CONSTRUCTION JOINTS. DO NOT BREAK
OR INTERRUPT SUCCESSIVE POURS SUCH THAT COLD JOINTS OCCUR.
9. RESTORE GRADE AND PLANT GRASS TO MATCH EXISTING GRADE. REFER TO SEEDING
SCHEDULE ON SHEET M-401, M-402. & M-403.
10. SEALER:
10.1. PROVIDE AND INSTALL A PENETRATING SEALING COMPOUND ON BASES EQUAL TO PENTREAT
244-100.
10.1.1. DESIGN TO LIMIT THE INTRUSION OF MOISTURE AND CHLORIDES INTO THE SUBSTRATE.
10.1.2. REDUCES SPALLING.
10.1.3. PENETRATES DEEPLY FOR MAXIMUM PROTECTION.
10.1.4. MINIMIZES PENETRATION FROM DE-ICING CHEMICALS, SALT, WATER THAT MIGHT
DAMAGE CONCRETE SURFACES.
10.1.5. SEALS PORES AND CAPILLARIES OF SUBSTRATE, PREVENTING LIQUID ABSORPTION
WHILE ALLOWING EXCELLENT VAPOR TRANSMISSION.
10.1.6. LEAVES NO RESIDUE AND REQUIRES NO CLEANING AFTER APPLICATION.
1ST FLOOR
CONCRETE
PADDUCT SUPPORT, TYP. BASED ON
MIRO 8-DS OR APPROVED EQUAL
UNISTRUCT HORIZONTAL
DUCT SUPPORT FRAME
(TYP.)
RTU
RA
RA
RA
NOTES:
1. CONFIGURATION SHOWN FOR RTU-2
2. GRADE MOUNTED ROOF CURB
3. SEE NEW MECHANICAL PRINTS FOR RETURN AIR DUCT SIZES.
4. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT CHASE
DIMENSIONS AND CONSTRUCTION.
FLEXIBLE
CONNECTOR
CEILING
UNISTRUCT VERTICAL
DUCT SUPPORT FRAME
SA
NOTES:
1. CONFIGURATION SHOWN FOR RTU-2
2. GRADE MOUNTED STANDARD ROOF CURB
3. SEE NEW MECHANICAL PRINTS FOR SUPPLY AIR DUCT SIZES.
4. SEE NEW MECHANICAL PRINTS FOR HEATING COIL SELECTION.
INSTALL HEATING COIL APPROXIMATELY 60" ABOVE CONCRETE
PAD.
5. SEE NEW MECHANICAL PRINTS FOR NEW PUMP SELECTION AND
NEW HOT WATER SUPPLY AND HOT WATER RETURN SIZES.
INSTALL NEW PUMP AT APPROXIMATELY 72". FASTEN PIPING AND
PUMP T0 UNISTRUCT FRAME INSIDE CHASE.
6. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT CHASE
DIMENSIONS AND CONSTRUCTION.
HEATING
COIL
PUMP
HS
SA ELEVATIONRA ELEVATION
STANDARD ROOF CURB 1ST FLOOR
CONCRETE
PADDUCT SUPPORT, TYP. BASED ON
MIRO 8-DS OR APPROVED EQUAL
UNISTRUCT HORIZONTAL
DUCT SUPPORT FRAME
(TYP.)
RTU
SA
SA
FLEXIBLE
CONNECTOR
CEILING
UNISTRUCT VERTICAL
DUCT SUPPORT FRAME
STANDARD ROOF CURB
HR
X-
HR
X-
HS
X-SHUTOFF
VALVE X-CIRCUIT SETTER
X-MANUAL AIR VENT
X-UNION
X-FINTUBE/CUH COIL
NOTE:
1. CONTRACTOR TO REMOVE EXISTING
VALVES AS SHOWN IN DETAIL FOR
ALL EXISTING FIN TUBE.
X-HOT WATER
SUPPLY
X-HOT WATER
RETURN
TYPICAL FIN TUBE/CABINET UNIT HEATER
COIL DETAIL - DEMOLITION
SCALE: NTS
X-
HR
X-
HS
SHUTOFF
VALVE (TYP.)
2-WAY DDC MODULATING
CONTROL VALVE
CIRCUIT SETTER
X-MANUAL AIR VENT
X-UNION (TYP.)
X-FINTUBE/CUH COIL
NOTE:
1. CONTRACTOR TO INSTALL ALL NEW
VALVES AS SHOWN IN DETAIL FOR
ALL EXISTING FIN TUBE.
2. SEE NEW PLANS FOR EXISTING PIPE
SIZES. COORDINATE CONTROL VALVE
SIZE WITH EXISTING PIPE SIZE.
X-HOT WATER
SUPPLY
X-HOT WATER
RETURN
TYPICAL FIN TUBE/CABINET UNIT HEATER
COIL DETAIL - NEW
SCALE: NTS
AHU HEATING COIL DETAIL
(3-WAY CONTROL VALVE)
SCALE: NTS
SHUT-OFF VALVE (TYP.)
UNION (TYP.)
STRAINIER(TYP.)
PUMP
HOSE END
DRAIN VALVE (TYP.)
HS
3-WAY MODULATING
CONTROL VALVE
P/T TAP (TYP.)
HR
BALANCE VALVE (TYP.)
MANUAL
AIR VENT
COIL
P P
PRESSURE GAUGE (TYP.)
CHECK VALVE (TYP.)
THERMOMETER (TYP.)
SHUT-OFF VALVE (TYP.)
NOTES:
1. CONFIGURATION FOR HC-1
2. SEE NEW PIPING PRINTS FOR PIPE SIZES.
3. SEE NEW MECHANICAL PRINTS FOR HEATING COIL SELECTION.
INSTALL HEATING COIL HORIZONTALLY APPROXIMATELY 60"
ABOVE CONCRETE PAD.
4. SEE NEW PIPING PRINTS FOR NEW PUMP SELECTION AND
INSTALL NEW PUMP AT APPROXIMATELY 72". FASTEN PIPING AND
PUMP T0 UNISTRUCT FRAME INSIDE CHASE.
9 STEAM PRESSURE REDUCING VALVE DETAIL - NEW
SCALE: NTS
PRV-1
P
P
PRV-2
P
6" VTR
SHUTOFF
VALVE (TYP.)
STRAINER
(TYP.)
PRESSURE
GAUGE (TYP.)
REDUCER (TYP.)
PRESSURE
RELIEF VALVE
PIPING KEY NOTES
INSTALL NEW PRESSURE RELIEF VALVE IN THE
LOCATION SHOWN.
PRESSURE RELIEF VALVE SPECS:
MANUFACTURER: SPIRAX SARCO
MODEL: SV74
SIZE: 4"
SET PRESSURE: 25 PSI
INSTALL NEW PRV-1 AS IN THE LOCATION SHOWN.
PRESSURE RELIEF VALVE SPECS:
MANUFACTURER: SPIRAX SARCO
MODEL: 25P
INLET PRESSURE: 90 PSIG
OUTLET PRESSURE: 15 PSIG
CAPACITY: 2740 LB/HR
INSTALL NEW PRV-2 AS IN THE LOCATION SHOWN.
PRESSURE RELIEF VALVE SPECS:
MANUFACTURER: SPIRAX SARCO
MODEL: 25P
INLET PRESSURE: 90 PSIG
OUTLET PRESSURE: 15 PSIG
CAPACITY: 1360 LB/HR
4" STM
2" STM
3" STM4" STM 6" STM
STEAM PRV NOTES:
, TYPICAL FOR BOTH PRV ASSEMBLIES.
1. ALLOW AT LEAST 10 PIPE DIAMETERS OF
STRAIGHT PIPE.
2. ALL PIPING VALVING ETC. ON HIGH PRESSURE
SIDE OF PRV'S SHALL BE WELDED OR FLANGED.
3. ALL ACCESSORY PIPING ON HIGH PRESSURE
SIDE OF PRV'S SHALL BE SCREWED AND BACK
WELDED.
4. PRV'S SHALL BE SIZED FOR 1/3 & 2/3 CAPACITY.
ONE PRV SHALL BE SET AT 1 PSI GREATER
THAN THE OTHER PRV.
5. TOTAL PRV CAPACITY 4,100# FOR INLET
PRESSURE OF 90 PSI AND OUTLET PRESSURE
OF 15 PSI.
6. PRV-1: 2,740# FOR INLET PRESSURE OF 90 PSI
AND OUTLET PRESSURE OF 15 PSI, SELF
OPERATED, 3" VALVE.
7. PRV-2: 1,360# FOR INLET PRESSURE OF 90 PSI
AND OUTLET PRESSURE OF 15 PSI, SELF
OPERATED, 2" VALVE.
file no.
checked by drawn by consultant contract order no.
472/LCFMAINTPROJ
consultant job no.
20080.00
M a t r ix
472/19503.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N issue date
9/14/2023 FOR CONSTRUCTION
M-801
MECHANICAL DETAILS
| Sheets and Views |
| M-000-2008000-T-000 |
| M100-2008000-M-100 |
| M300-2008000-M-300 |
| M301-2008000-M-301 |
| M302-2008000-M-302 |
| M303-2008000-M-303 |
| M304-2008000-M-304 |
| M305-2008000-M-305 |
| M306-2008000-M-306 |
| M307-2008000-M-307 |
| M308-2008000-M-308 |
| M309-2008000-M-309 |
| M310-2008000-M-310 |
| M311-2008000-M-311 |
| M312-2008000-M-312 |
| M313-2008000-M-313 |
| M314-2008000-M-314 |
| M315-2008000-M-315 |
| M316-2008000-M-316 |
| M317-2008000-M-317 |
| M318-2008000-M-318 |
| M319-2008000-M-319 |
| M320-2008000-M-319 |
| M400-2008000-M-400 |
| M401-2008000-M-401 |
| M402-2008000-M-402 |
| M403-2008000-M-403 |
| M404-2008000-M-404 |
| M405-2008000-M-405 |
| M406-2008000-M-406 |
| M600-2008000-M-600 |
| M601-2008000-M601 |
| M602-2008000-M602 |
| M603-2008000-M603 |
| M604-2008000-M604 |
| M605-2008000-M605 |
| M606-2008000-M606 |
| M607-2008000-M607 |
| M608-2008000-M608 |
| M609-2008000-M-609 |
| M610-2008000-M-610 |
| M611-2008000-M-611 |
| M800-2008000-M-800 |
| M801-2008000-M-801 |
| M802-2008000-M-802 |
| M900-2008000-M-900 |
File details come from the government source that posted it. Updated .