Drawing Vol 2-1 Telecommunication 614-700-TN-20231011.pdf

PDF 35 MB Posted

Attached to
Y1DA--614-22-700 EHRM Infrastructure Upgrades Construction Memphis TN Federal contract opportunity
Solicitation number
36C77624B0013_1
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document appears to be Drawing Vol 2-1 Telecommunication 614-700-TN-20231011.pdf, which is related to the federal contract opportunity Solicitation Number: 36C77624B0013_1, named "Y1DA--614-22-700 EHRM Infrastructure Upgrades Construction Memphis TN".

The solicitation is for EHRM (Electronic Health Record Modernization) Infrastructure Upgrades Construction at the Memphis, TN Veterans Affairs Medical Center (VAMC). The solicitation is being issued by the Department of Veterans Affairs Technology Acquisition Center in Austin. The contract will involve telecommunication-related construction and infrastructure upgrades. Key details are not provided in this specific document, as it appears to be a drawing rather than the full solicitation. The drawing may contain technical specifications or design details relevant to the telecommunication components of the overall infrastructure upgrade project.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--614-22-700 EHRM Infrastructure Upgrades Construction Memphis TN, newest first.
File Type Posted
614-700_Sheet List_20240702.pdf PDF
00 01 15 - List of Drawing Sheets.pdf PDF
36C77624B0013 Amendment 0004.docx DOCX document
614-700.ET_R21.pdf PDF
36C77624B0013 Amendment 0003.docx DOCX document
ENG FORM 4288-R 1-97.pdf PDF
CS501 Addendum _1.pdf PDF
Technical Questions Tracking Spreadsheet - Memphis IU Construction 6.20.24.docx DOCX document
S06 - 36C77624B0013 Amendment 0002.docx DOCX document
S06 - Wage rates Memphis 5.31.24.pdf PDF
Site Visit Sign-in Sheets - EHRM Infra - Memphis.pdf PDF
36C77624B0013 Amendment 0001.docx DOCX document
Drawing Vol 1-5-1 Architectural 614-700-AE-20231011.pdf PDF
Drawing Vol 1-5-5 Architectural 614-700-AE-20231011.pdf PDF
Specifications - Final.pdf PDF
Drawing Vol 1-2 Hazardous 614-700-HA-20231011.pdf PDF
Section 01 45 35 Statement of SI Template.xlsx XLSX spreadsheet
Site Visit Instructions.docx DOCX document
Wage Rates - Memphis 3.22.24.pdf PDF
VHA ICRA 614-22-700TR-03 EHRM Infrastructure TR Build-Out Level IV - High Risk.pdf PDF
VHA ICRA 614-22-700CD-03 EHRM Infrastructure Cable-Drops Level IV - High Risk.pdf PDF
VHA ICRA 614-22-700CD-02 EHRM Infrastructure Cable-Drops Level III - Medium Risk.pdf PDF
VHA ICRA 614-22-700CD-01 EHRM Infrastructure Cable-Drops Level II - Low Risk.pdf PDF
VHA ICRA 614-22-700TR-01 EHRM Infrastructure TR Build-Out Level II - Low Risk.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
Drawing Vol 1-5-4 Architectural 614-700-AE-20231011.pdf PDF
Drawing Vol 1-5-2 Architectural 614-700-AE-20231011.pdf PDF
Drawing Vol 1-1 General 614-700-GI-20231011.pdf PDF
Drawing Vol 1-5-6 Architectural 614-700-AE-20231011.pdf PDF
Drawing Vol 1-7 Fire Protection 614-700-FX-20231011.pdf PDF
Drawing Vol 1-4 Structural 614-700-SF-20231011.pdf PDF
Drawing Vol 2-2 Technology 614-700-TJ-20231011.pdf PDF
VHA ICRA 614-22-700CD-04 EHRM Infrastructure Cable-Drops Level IV - Highest Risk.pdf PDF
VHA ICRA 614-22-700TR-04 EHRM Infrastructure TR Build-Out Level IV - Highest Risk.pdf PDF
VHA PCRA 31May2023-EHRM Infrastructure.pdf PDF
Section 01 45 35 Schedule of Special Inspections.docx DOCX document
VHA ICRA 614-22-700TR-02 EHRM Infrastructure TR Build-Out Level III - Medium Risk.pdf PDF
Drawing Vol 1-8 Mechanical 614-700-MH-20231011.pdf PDF
Drawing Vol 1-6 Plumbing 614-700-PL-20231011.pdf PDF
Brand Name Justification Memphis EHRM.pdf PDF
36C77624B0013_1.docx DOCX document
Drawing Vol 1-5-3 Architectural 614-700-AE-20231011.pdf PDF
Drawing Vol 1-9 Electrical 614-700-EP-20231011.pdf PDF
Drawing Vol 1-3 Civil 614-700-CS-20231011.pdf PDF
Show all 44

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A. REFER TO VA OIT "INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES VERSION 3.1"

FOR ADDITIONAL REQUIREMENTS INCLUDING MANUFACTURER AND MODEL NUMBERS FOR THE

BASIS OF DESIGN EQUIPMENT. ALL EQUIPMENT PROVIDED AS PART OF THIS PROJECT MUST BE

EQUIVALENT TO THE BASIS OF DESIGN EQUIPMENT LISTED.

B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM, INSTALLED BY A CERTIFIED INSTALLER, THAT IS

SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL

SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED

DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE

RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS

FOR LOCATIONS OF FIRE RATED WALLS.

C. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO

REMAIN CABLING.

D. PROVIDE ONE (1) CATEGORY 6A CABLE TO EACH UPS WITHIN PROJECT. CENTRALIZED UPS'S ARE

SHOWN ON THE ELECTRICAL DRAWING SET AND RACK MOUNTED UPS'S ARE SHOWN ON THE

TELECOMMUNICATIONS ROOM RACK ELEVATIONS FOR EACH ROOM. UPS'S SHALL BE CONNECTED

TOGETHER IN A CENTRALIZED UPS MONITORING SYSTEM.

E. PROVIDE ONE (1) CATEGORY 6A CABLE TO EACH NEW PANELBOARD, DISTRIBUTION BOARD, AND

SWITCHBOARD WITHIN PROJECT. PANELS SHALL BE CONNECTED TOGETHER IN A CENTRALIZED

ELECTRICAL METERING SYSTEM.

F. ALL CABLING, CONDUITS, CHASEWAYS, PANELS, BOXES AND EQUIPMENT ARE TO BE LABELED

UTILIZING THE LATEST IN BICSI/TIA STANDARDS.

G. ALL NEW CONSTRUCTION TRS ARE TO GET NEW ACCESS CONTROL PANELS FROM THE CURRENT VENDOR. THE CONTRACTOR WILL COORDINATE THE INSTALLATION OF THE NEW AC PANEL BY THE VENDOR WITH THE VA COR INTO THE NEW TR. THE CONTRACTOR IS TO REMOVE AND RE-USE CARD

READERS AND KEYPADS FROM DECOMMISSIONED TRS FOR NEW CONSTRUCTION TRS WHEREVER

POSSIBLE.

H. IT IS THE CONTRACTORS RESPONSIBILITY TO ENSURE ALL ENTRANCE, BACKBONE, AND

HORIZONTAL CABLING IS TERMINATED EACH END, TESTED, AND LABELED PER SPECIFICATIONS.

FIBER OPTIC CABLING SHALL BE TERMINATED WITHIN RACK MOUNT FIBER ENCLOSURES EACH END.

EXACT PART AND MODEL NO WILL NOT BE IDENTIFIED WITHIN RACK ELEVATIONS OR SCHEMATICS.

REFER TO SPECIFICATIONS. UTP CABLING SHALL BE TERMINATED EACH END ON SPECIFIED CAT 6A

PATCH PANELS WITHIN THE TRS AND SPECIFIED CAT 6A JACKS AT THE USER OUTLET.

I. CABLE QUANTITIES INDICATED FOR EACH BUILDING ARE APPROXIMATE BASED ON FIELD

OBSERVATIONS AND READINESS INFRASTRUCTURE SELF-ASSESSMENTS PROVIDED BY THE

VA. SOME LOCATIONS WERE UNABLE TO BE SURVEYED FOR EXISTING COMMUNICATIONS OUTLETS

AND CABLING DUE TO PATIENT CARE. CONTRACTOR SHALL ACCOUNT FOR ADDITIONAL CABLES

REQUIRED. CONTRACTOR SHALL ACCOUNT FOR AN ADDITIONAL 20% OF CABLES, DEVICES, AND

PATCH PANELS INDICATED ON DRAWINGS IN ORDER TO ACCOMMODATE THE FULL SCOPE OF THE

PROJECT WITHIN BASE BID.

J. EXISTING CEILINGS THROUGHOUT CORRIDORS AND ROOMS WITH EXISTING CABLING MAY NEED TO

BE REMOVED AND REPLACED TO ACCOMMODATE CONSTRUCTION. CONTRACTOR IS RESPONSIBLE

FOR IDENTIFICATION OF SCOPE OF WORK ASSOCIATED WITH THIS REMOVAL AND INSTALLATION WITHIN BASE BID. WHERE EXISTING CEILINGS ARE LAYIN TILE, GRID SYSTEM MAY REMAIN IN PLACE AND ONLY THE EXISTING TILES WILL REQUIRE REMOVAL AND REPLACEMENT. EXISTING CEILING

MOUNTED COMPONENTS SHALL BE TEMPORARILY SUPPORTED AND BE REINSTALLED IN NEW

CEILINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR COST OF REPLACEMENT OF CEILING

ELEMENTS THAT ARE DAMAGED OR DESTROYED DURING THE PROJECT. REFER TO ARCHITECTURAL

DRAWINGS FOR FURTHER INFORMATION. COORDINATE WITH OWNER FOR PROCUREMENT OF

REPLACEMENT CEILING TILES OR OTHER ELEMENTS.

K. ALL DECOMMISSIONED TR EQUIPMENT (RACKS, CABLE TRAY, SECURITY CAMERAS, CARD READERS, GROUND BUS BARS, HVAC SPLIT SYSTEMS) SHALL BE MOVED AND INSTALLED INTO NEW

CONSTRUCTION TRS AS NEEDED. EXCESS TR EQUIPMENT IS TO BE RETURNED TO THE VA.

L. ALL EXISTING VOICE CABLES AND WALL FIELD EQUIPMENT ARE TO REMAIN IN SERVICE AS IS.

M. ALL 2 POST RACKS TO BE REPLACED WITH 4 POST RACKS UNLESS OTHERWISE SPECIFIED IN SHEET

NOTES. THE 4 POST RACK IS SPECIFIED IN THE OIT INFRASTRUCTURE STANDARD 3.1 DOCUMENT.

N. THE CONTRACTOR IS RESPONSIBLE FOR MOVING OWNER FURNITURE TO ALLOW FOR EXISTING

DATA DROPS TO BE REPLACED. CONTRACTOR TO COORDINATE WITH THE OWNER FOR DATES AND

TIMES THAT THE FURNITURE CAN BE MOVED.

TELECOMMUNICATIONS GENERAL NOTES:

(GENERAL NOTES SHALL APPLY TO ALL SHEETS)

1. WORK RESTRICTIONS IN OPERATIONAL ROOMS: WORK WITHIN EXISTING ROOMS (ENTRANCE

FACILITY, MAIN COMPUTER ROOMS, TELECOMMUNICATIONS ROOMS) SHALL REQUIRE THE

PRESENCE OF A VA ESCORT WHILE THE EXISTING ROOM IS STILL OPERATIONAL AND ACTIVE. WORK WITHIN NEW ROOMS (ENTRANCE FACILITY, MAIN COMPUTER ROOM, TELECOMMUNICATIONS ROOMS)

SHALL REQUIRE THE PRESENCE OF A VA ESCORT ONCE THE NEW ROOM BECOMES OPERATIONAL

AND ACTIVE.

2. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR WORK RESTRICTIONS WITHIN EACH BUILDING FOR TIME OF DAY AVAILABILITY OF SPACES AND LEVEL OF INFECTION CONTROL

REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL ACCOUNT FOR OFF HOURS WORK

REQUIRED.

WORK RESTRICTION NOTES:

(GENERAL NOTES SHALL APPLY TO ALL SHEETS)

A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF TELECOMMUNICATIONS

DEMOLITION WORK. PROVIDE DEMOLITION FOR ITEMS AS SHOWN.

B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).

C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION.

SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO

PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE

ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID

SUBMITTAL.

D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES

SALVAGE, CONTRACTOR IS RESPONSIBLE FOR THE LEGAL AND RESPONSIBLE DISPOSAL.

E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED TELECOMMUNICATIONS EQUIPMENT

SHALL BE REMOVED. SEE ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON

CONCEALED CONDUITS WHERE WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED

WHERE AVAILABLE. WHERE EXISTING CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CABLES AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING CONDUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CABLES SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT.

REMOVE AND PATCH WHERE BOXES ARE NOT REUSED.

F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL TELECOMMUNICATIONS DEMOLITION ITEMS.

DISCONNECT AND REMOVE TELECOMMUNICATIONS DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC

ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE

ARCHITECT.

G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES.

MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE.

DO NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION.

INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING

JUNCTION BOXES THAT BECOME INACCESSIBLE DUE TO NEW WORK.

H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY SERVICES AS

REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.

I. PROTECT EXISTING TELECOMMUNICATIONS EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL

CAPACITY, QUALITY, AND FUNCTIONALITY.

J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED TELECOMMUNICATIONS DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND

FINISH. SEE ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.

K. THIS PROJECT WILL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS.

SYSTEM SERVICES TO AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE MAINTAINED AT

ALL TIMES.

L. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO

MATCH ADJACENT SURFACE.

M. ALL UNLABELED TELECOMMUNICATIONS DEVICES SHALL BE TRACED AS NEEDED WITH A LABEL

PROVIDED.

N. CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT OF ALL CABLING, PATHWAYS, AND SYSTEMS

LOCATED ABOVE CEILING THAT ARE REQUIRED TO BE MODIFIED AS A PART OF THE PROJECT.

CONTRACTOR SHALL REPLACE ANY ITEMS DAMAGED FROM TEMPORARY SUPPORT.

O. EXISTING ANALOG DEVICES ACTIVELY SERVING EQUIPMENT SHALL BE EXISTING TO REMAIN REGARDLESS IF SHOWN AS BEING REMOVED. CONNECTIONS INCLUDE BUT ARE NOT LIMITED TO THE

FOLLOWING. THE CONTRACTOR SHALL FIELD VERIFY DURING CONSTRUCTION.

a. FAX, ELEVATORS, PATIENT TELEPHONES, BLUE PHONES, CODE BLUE DEVICES, FIRE ALARM, MEDICAL

ANALOG EQUIPMENT, PANIC DURESS, ETC.

P. WITHIN EXISTING SPACES THAT ARE TO BE DEMOLISHED TO BE CONVERTED INTO A TR OR MCR, REROUTE ANY EXISTING LOW VOLTAGE CABLING OUTSIDE THE ROOM. SPLICE AND EXTEND

CONDUCTORS AS REQUIRED. REPLACE ANY CATEGORY CABLES NEEDING TO BE REROUTED.

Q. ALL CATEGORY 5E AND LOWER DATA CABLES THAT ARE REMOVED FROM THE RACK ARE TO BE REMOVED ENTIRELY TO THE WORK AREA. THE WORK AREA WALL PLATES AND JACKS ARE ALSO PART OF THE DEMOLITION. OLD DATA CABLES CANNOT BE DOMOLISHED UNTIL NEW CAT6A CABLES HAVE BEEN INSTALLED AND THE CLIENT IS ACTIVELY USING THE NEW DATA DROP. SEE THE SEQUENCING NOTES FOR

ADDITIONAL DETAIL.

R. FIBER CABLES THAT ARE IN TRS TO BE DEMOLISHED ARE TO BE REMOVED ENTIRELY BACK TO THE SERVER ROOM. ANY CODUIT USED BY THE EXISTING FIBER WILL REMAIN AND POTENTIALLY BE USED BY NEW FIBER PULLS. FIBER IN TRS THAT WILL NOT RELOCATE IS TO REMAIN AS EXISTING. B SIDE FIBER TO NEW TR LOCATIONS MAY REUSE PREVIOUS FIBER PATHS TO THE NEW TR ROOM. ADDITIONAL CONDUIT

MAY BE NEEDED TO GET THE FIBER TO THE NEW TR.

(TELECOMMUNICATIONS DEMOLITION NOTES APPLY TO ALL TELECOMMUNICATIONS

DEMOLITION PLANS AND ALL TELECOMMUNICATIONS DEMOLITION WORK)

TELECOMMUNICATIONS DEMOLITION GENERAL NOTES:

PHASING SEQUENCE LISTED BELOW IS FOR INFORMATION ONLY. CONTRACTOR SHALL BE

RESPONSIBLE FOR DEVELOPING PROJECT SCHEDULE AND PHASING AND SHALL INCLUDE WORK

REQUIRED TO ACCOMMODATE PHASING. SUBMIT PHASING PLAN TO OWNER FOR REVIEW AND

APPROVAL AND COORDINATE WITH OWNER PRIOR TO BEGINNING CONSTRUCTION.

A. SITE FIBER TO BUILDINGS: CONSTRUCT REDUNDANT SITE FIBER LOOP FROM MAIN COMPUTER

ROOM TO ALL BUILDINGS. MAINTAIN EXISTING FIBER PATHWAYS FROM THE EXISTING MAIN

COMPUTER ROOM AS CURRENTLY CONSTRUCTED FOR THE B SIDE FIBER.

B. NEW TELECOMMUNICATIONS ROOMS AND RESUPPORTED EXISTING TELECOMMUNICATIONS

ROOMS: CONSTRUCT NEW TELECOMMUNICATIONS ROOMS TO BE OPERATIONAL. RESUPPORT

EXISTING TELECOMMUNICATIONS ROOMS TO REMAIN WITH NEW RACKS AND BACKBONE CABLING.

PROVIDE NEW A/B POWER PANELS AND GROUNDING IN NEW AND EXISTING TO REMAIN ROOMS.

POWER ALL TELECOMMUNICATIONS ROOM LOADS FROM THE NEW PANELS. ROUTE NEW PRIMARY

AND REDUNDANT FIBER TO NEW TELECOMMUNICATIONS ROOMS AND EXISTING TO REMAIN

TELECOMMUNICATIONS ROOMS, FROM THE MAIN COMPUTER ROOM. UPON ACTIVATION OF THESE

NEW AND RESUPPORTED ROOMS, BOTH THE NEW AND EXISTING DISTRIBUTION NETWORKS WILL

BE SIMULTANEOUSLY ACTIVE TO ALLOW FOR RE-CABLING THE PROGRESSIVE TRANSITION FROM

THE EXISTING NETWORK TO THE NEW NETWORK FOR EACH AREA OUTLET INDIVIDUALLY.

C. EXISTING TELECOMMUNICATIONS ROOMS: MAINTAIN THE EXISTING TELECOMMUNICATIONS ROOMS

AND EXISTING BACKBONE CABLING UNTIL THE AREA OUTLETS BEING SERVED BY EACH

RESPECTIVE TELECOMMUNICATIONS ROOM HAS BEEN TRANSITIONED TO THE NEW

TELECOMMUNICATIONS ROOM.

D. RE-CABLING: FOR NEW TELECOMMUNICATIONS ROOMS, PROVIDE NEW CABLES FROM THE

EXISTING AREA OUTLETS TO THE NEW RACKS. REMOVE EXISTING CATEGORY 5E OR LOWER

CABLING AFTER NEW CABLES HAVE BEEN PULLED TO THE OUTLETS TO MAINTAIN OPERATIONAL

CAPABILITY OF THE SPACES TO THE GREATEST EXTENT POSSIBLE.

E. EXISTING CABLE REMOVAL: AFTER NEW CABLING HAS BEEN INSTALLED AND ACTIVATED, REMOVE EXISTING BACKBONE CABLING AND EXISTING AREA OUTLET CABLING FROM TELECOMMUNICATIONS

ROOMS BEING ABANDONED. REMOVE UNUSED CABLING IN PREVIOUSLY ABANDONED

TELECOMMUNICATIONS ROOMS.

F. INTERBUILDING BACKBONE: REPLACE THE EXISTING INTERBUILDING BACKBONE CABLING WITH

NEW BACKBONE CABLING. REUSE THE EXISTING BACKBONE PATHWAYS FOR NEW BACKBONE

CABLE INSTALLATION. SIDE A FIBER ROUTE SHALL UTILIZE EXISTING PATHWAYS. EXISTING FIBER UTILIZING EXISTING PATHWAYS SHALL NOT BE REMOVED UNTIL NEW FIBER ROUTE B IS COMPLETE

AND NEW TELECOMMUNICATIONS ROOMS ARE ONLINE AND FUNCTIONING.

G. EXISTING TELECOMMUNICATIONS PROVIDER: REMOVE THE TELECOMMUNICATIONS PROVIDER

CABLING TO THE EXISTING ENTRANCE FACILITY ROOM AND SUBSEQUENT EXISTING BACKBONE

CABLING FROM THERE TO THE EXISTING MAIN COMPUTER ROOMS. COORDINATE WITH THE VA AND

REMOVE/RELOCATE ANY REMAINING ITEMS FROM THE EXISTING MAIN COMPUTER ROOM.

DEMOLISH THE EXISTING MAIN COMPUTER ROOM.

H. SERVER MIGRATION: WITH BOTH THE EXISTING AND NEW DISTRIBUTION NETWORKS BEING

SIMULTANEOUSLY ACTIVE THROUGHOUT THE PROGRESSION OF RE-CABLINGS AND OUTLET

TRANSITIONS, MIGRATION OF SERVERS FROM THE EXISTING SERVER ROOM TO THE NEW MAIN

COMPUTER ROOM SHALL OCCUR BETWEEN THE TIME THAT THE NEW NETWORK IS ACTIVE (AND

READY TO ACCEPT NEW CABLES), BUT BEFORE THE OLD NETWORK IS DEACTIVATED AND

REMOVED. AT ALL TIMES, TWO (2) CORE SWITCHES NEED TO BE ACTIVE TO MAINTAIN UTILIZATION

OF EXISTING SERVER ROOM AND NEW SERVER ROOM TO ACCOMMODATE PHASING OF SYSTEMS

FROM OLD ROOM TO NEW ROOM.

I. NETWORK ELECTRONICS COORDINATION: CONSIDERING THE ABOVE PHASING, COORDINATION

WILL BE REQUIRED BETWEEN THE VA AND CABLING CONTRACTOR IN ORDER TO PROPERLY

SEQUENCE THE ACQUISITION, CONFIGURATION, AND ACTIVATION OF NETWORK ELECTRONICS IN COORDINATION WITH THE ACTIVATION OF EACH NEW NETWORK DISTRIBUTION POINT, ACTIVATION OF EACH RE-CABLED OUTLET, AND THE SUBSEQUENT DEACTIVATION OF BOTH EXISTING OUTLET

CABLES AND EXISTING NETWORK DISTRIBUTION POINTS.

(NOTES SHALL APPLY TO OVERALL PROJECT PHASING)

OVERALL PHASING NOTES:

1. REFER TO SPECIFICATIONS APPENDIX A-B FOR ADDITIONAL PHASING INFORMATION.

TECHNOLOGY PHASING NOTES:

1. ADDITIONAL CERNER DEVICES WILL BE INSTALLED PRIOR TO THIS PROJECT'S COMPLETION.

CONTRACTOR TO INCLUDE AN ALLOWANCE FOR 10 ADDITIONAL 2-PORTS CAT 6A INFORMATION

OUTLETS IN THEIR PROPOSAL FOR THIS SHEET. LOCATIONS OF DATA CABLES ARE YET TO BE

DETERMINED. COORDINATE THE EXACT LOCATION OF OUTLETS WITH THE VA PROJECT MANAGER.

CERNER NOTES:

LEGEND: (LOW VOLTAGE COORDINATION LEGEND)

CF: CONTRACTOR FURNISHED

CI: CONTRACTOR INSTALLED

GF: GOVERNMENT FURNISHED

GI: GOVERNMENT INSTALLED

REMARKS: (LOW VOLTAGE COORDINATION LEGEND)

1. PATCH PANELS SHALL BE CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED PER SPECIFICATION.

REFER TO TYPICAL COMMUNICATION TERMINATION DETAIL.

2. ACCESS CONTROL SYSTEM IS AN EXTENSION OF AN EXISTING AVIGILON SYSTEM. NEW DEVICES SHALL

FUNCTION AS AN EXTENSION OF THE EXISTING SYSTEM.

3. PUBLIC ADDRESS SYSTEM IS AN EXTENSION OF AN EXISTING [MANUFACTURER MODEL] SYSTEM. NEW

DEVICES SHALL FUNCTION AS AN EXTENSION OF THE EXISTING SYSTEM.

4. PROVIDE VIDEO SURVEILLANCE FOR TELECOMMUNICATIONS ROOM AS PART OF AN APC NETBOTZ 750

(OR EQUIVALENT) ROOM MONITOR SYSTEM.

5. TELEVISION SYSTEM TO BE RECABLED WHERE EXISTING CABLING IS CATEGORY 5E OR BELOW OR

WHERE EXISTING TELECOMMUNICATIONS ROOM IS BEING ABANDONED. NO NEW TELEVISION

EQUIPMENT IS ANTICIPATED IN THIS CONTRACT.

6. PROVIDE TEMPERATURE AND HUMIDITY MONITORING FOR TELECOMMUNICATIONS ROOM AS PART OF

AN APC NETBOTZ 750 (OR EQUIVALENT) ROOM MONITOR SYSTEM.

7. WIRELESS ACCESS POINTS TO BE RECABLED WHERE EXISTING CABLING IS CATEGORY 5E OR BELOW OR WHERE EXISTING TELECOMMUNICATIONS ROOM IS BEING ABANDONED. NO NEW WIRELESS ACCESS

POINTS ARE ANTICIPATED IN THIS CONTRACT.

GENERAL NOTES: (LOW VOLTAGE COORDINATION LEGEND)

A. REFER TO SYMBOL LEGENDS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.

B. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL EQUIPMENT SELECTION FOR ALL SYSTEMS.

C. COORDINATE ROUGH-IN REQUIREMENTS WITH OWNER FOR OWNER FURNISHED SYSTEMS.

D. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO ABOVE NEAREST ACCESSIBLE CEILING SPACE, UNLESS OTHERWISE INDICATED.

E. WHERE CABLING IS CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED, TERMINATE AND TEST ALL

CABLING PER SPECIFICATION.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22122

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project : 22.3101

35% SCHEMATIC DESIGN 10/31/2022

65% DESIGN DEVELOPMENT 05/03/2023

95% CONSTRUCTION DOCUMENTS 08/16/2023

100% FINAL BID DOCUMENTS 09/27/2023

100% FINAL STAMPED BID DOCUMENTS 10/11/2023

10/11/2023B

IM

/2

.3

V

A M e m p h is E

H R

M I n fr a s tr u c tu re /6

-7

.E T

R

.r v t

/8 /2

:2

:1

P

M

TN000

TELECOMMUNICATIONS SYMBOLS AND

ABBREVIATIONS

VA Memphis EHRM Infrastructure

MEMPHIS, TN

614-22-700

N/A

10/11/2023 NMT SSK

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

SECURITY SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

ACCESS CONTROL DEVICE GENERAL:

PROVIDE ACCESS CONTROL COMPONENTS AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH ACCESS CONTROLLED DEVICE TYPE AT DOORS INDICATED. REFER TO FLOOR PLANS FOR DEVICE DESIGNATION. PROVIDE ROUGH-INS PER ACCESS CONTROL ROUGH-IN DETAIL. DOOR ACCESS COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. COORDINATE REQUIRED CONDUITS TO DOOR FRAME AND WALL MOUNTED DEVICES WITH DOOR HARDWARE CONTRACTOR. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. PROVIDE 20A 120V BRANCH CIRCUIT TO DOOR CONTROLLERS LOCATED WITHIN ACCESS CONTROL CABINET IN ASSOCIATED TR. PROVIDE FINAL CONNECTION OF 120V BRANCH CIRCUIT TO ALL POWER SUPPLIES REQUIRED FOR EACH DOOR FUNCTION. REFER TO E-SERIES ELECTRICAL FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. PROVIDE ACCESS CONTROL CABLING FROM DOOR CONTROLLER TO COMPONENTS REQUIRED BY THE DOOR HARDWARE SPECIFICATION INCLUDING BUT NOT LIMITED TO CARD READER, DOOR POSITION SWITCH, ELECTRIC STRIKE, ELECTRIFIED HINGE, DOOR RELEASE PUSH BUTTON, MAGNETIC LOCK, AND REQUEST TO EXIT. PROVIDE DOOR POSITION SWITCH AND REQUEST TO EXIT AT EACH ACCESS CONTROLLED DOOR, UNLESS PROVIDED BY DOOR HARDWARE CONTRACTOR. CONTRACTOR SHALL TERMINATE ACCESS CONTROL CABLING TO DEVICES AT DOOR LOCATION AND PROVIDE A 7'-0" PIGTAIL WITHIN TR AT ACCESS CONTROL CABINET WITH APPROPRIATE DEVICE LABEL. COORDINATE ALL TERMINATION REQUIREMENTS AND EXACT LOCATION OF TERMINATIONS WITH OWNER'S ACCESS CONTROL MANAGER. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 281300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. WHERE DOOR IS ALSO SPECIFIED/SHOWN TO

UTILIZE

DOOR OPERATOR, PROVIDE INTERLOCK TO ALLOW AUTOMATIC DOOR OPENING FROM THE ACCESS CONTROL SYSTEM UPON SUCCESSFUL CARD READ. SUBMIT SHOP DRAWINGS FOR APPROVAL. PROVIDE FIRE ALARM SYSTEM CONNECTION FOR DOOR RELEASE UPON ALARM. INTEGRATE ACCESS CONTROL SYSTEM WITH DOOR OPERATORS, FIRE ALARM, WANDER PREVENTION, INTERCOM, AND DOOR HARDWARE. REFER TO ACCESS CONTROL AND ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR COORDINATION OF FEATURES, DEVICES, AND CONNECTIONS REQUIRED.

ACCESS CONTROL PANEL CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN LOCAL BRANCH PANEL (GENERATOR FEED WHEN BUILDING HAS GENERATOR BACKUP). REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS.

COORDINATE CONNECTION REQUIREMENTS WITH FINAL EQUIPMENT SELECTION AND PROVIDE NEMA 5-20

RECEPTACLE OR HARD-WIRED CONNECTION TO CABINET AS REQUIRED.

CREDENTIAL CARD READER GENERAL:

PROVIDE PROXIMITY CARD READER [AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CARD READER TYPE] AT APPROXIMATE LOCATION INDICATED. [REFER TO FLOOR PLANS FOR CARD READER DESIGNATION.] PROVIDE ROUGH-IN PER ACCESS CONTROL ROUGH-IN DETAIL. WHERE SHOWN MOUNTED ON DOOR/WINDOW SYSTEM MULLION, PROVIDE MULLION MOUNT CARD READER SURFACE MOUNTED ON MULLION.

CABLING SHALL BE ROUTED RECESSED WITHIN MULLION TO ACCESSIBLE CEILING SPACE. COORDINATE INSTALLATION WITH MULLION MANUFACTURER. CARD READERS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT LOCATION OF CARD READER WITH ARCHITECT, ARCHITECTURAL INTERIOR ELEVATIONS, AND OTHER DOOR COMPONENTS INCLUDING BUT NOT LIMITED TO PUSH PLATE ACTUATORS, REQUEST TO EXIT PUSH BUTTONS, INTERCOM STATIONS, NURSE CALL CANCEL STATIONS, INTRUSION DETECTION KEYPADS, WANDER PREVENTION KEYPADS, AND INFANT PROTECTION KEYPADS. REFER TO ACCESS

CONTROL SYMBOL LEGEND DESCRIPTION FOR CABLING AND ADDITIONAL REQUIREMENTS.

TYPE ‘KEYPAD’, COMBINATION KEYPAD PROXIMITY CARD READER:

PROVIDE COMBINATION KEYPAD PROXIMITY CARD READER PER SPECIFICATION.

INTRUSION DETECTION SYSTEM

- CONTROL PANEL

CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN LOCAL UPS BRANCH PANEL OF THE ASSOCIATED CONSTRUCTION PHASE. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. COORDINATE CONNECTION REQUIREMENTS WITH FINAL EQUIPMENT SELECTION AND PROVIDED NEMA 5-20 RECEPTACLE OR HARD-WIRED CONNECTION TO CONTROL PANEL AS REQUIRED. PROVIDE ONE (1) NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTIONS 280513 AND 281300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, ROUGH-INS, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT LOCATION OF KEYPAD WITH ENGINEER, ARCHITECT, AND ARCHITECTURAL INTERIOR ELEVATIONS.

INTRUSION DETECTION SYSTEM

- KEYPAD

PROVIDE KEYPAD FOR INTRUSION DETECTION SYSTEM AT APPROXIMATE LOCATION INDICATED ON FLOOR PLANS, MOUNTED AT 48" AFF. COORDINATE CABLING AND ROUGH-IN REQUIREMENTS WITH MANUFACTURER. PROVIDE CABLING TO INTRUSION DETECTION SYSTEM CONTROL PANEL PER MANUFACTURER INSTALLATION REQUIREMENTS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE CABLING PER SPECIFICATION SECTIONS 280513 AND 281300. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTIONS 280513 AND 281300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, ROUGH-INS, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT LOCATION OF KEYPAD WITH ENGINEER, ARCHITECT, AND

ARCHITECTURAL INTERIOR ELEVATIONS.

INTRUSION DETECTION SYSTEM

- MOTION SENSOR

PROVIDE MOTION SENSOR COVERAGE OF SPACE INDICATED FOR INTRUSION DETECTION SYSTEM. EXACT QUANTITIES AND LOCATIONS OF DEVICES SHALL BE DETERMINED BY MANUFACTURER REQUIREMENTS. MOUNT DEVICES IN ACCESSIBLE LOCATIONS. PROVIDE BACK BOX AND CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING AT LOCATIONS INDICATED WITHIN GYP CEILINGS OR WHERE EXPOSED WITHIN UNFINISHED AREAS. COORDINATE CABLING AND ROUGH-IN REQUIREMENTS WITH MANUFACTURER. PROVIDE CABLING TO INTRUSION DETECTION SYSTEM CONTROL PANEL PER MANUFACTURER INSTALLATION REQUIREMENTS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE CABLING PER SPECIFICATION SECTIONS 280513 AND 281300. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTIONS 280513 AND 281300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, ROUGH-INS, AND CABLING. SUBMIT

SHOP DRAWINGS FOR APPROVAL.

SECURITY SURVEILLANCE

CAMERA - CEILING

GENERAL;

PROVIDE CABLING FOR POWER OVER ETHERNET (POE) SECURITY SURVEILLANCE CAMERA (AXIS M3067-P) AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CAMERA TYPE AT LOCATIONS INDICATED.

REFER TO FLOOR PLANS FOR CAMERA INSTALLATION LOCATION. SECURITY SURVEILLANCE COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 282300. PROVIDE ONE (1) CATEGORY 6A NETWORK DATA CABLE FROM ASSOCIATED TELECOMMUNICATIONS ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS, COILED ABOVE FINISHED CEILING WITH 10' OF SLACK. FOR CEILING TILE INSTALLATIONS, TERMINATE THE CEILING END WITH A RJ-45 FEMALE CONNECTOR MOUNTED IN A SURFACE MOUNT BLOCK. PROVIDE A 3' PATCH CABLE TO CONNECT THE CAMERA TO THE FEMALE RJ-45 CONNECTOR. INSTALL CAMERA CENTERED IN CEILING TILE. FOR LOCATIONS INDICATED WITHIN GYP CEILINGS, PROVIDE A BACK BOX WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING. IN UNFINISHED AREAS, PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX. COORDINATE ROUGH-IN REQUIREMENTS, PENDANT MOUNTS, PROTECTIVE DOMES, AND OTHER REQUIRED ACCESSORIES FOR EXTERIOR CAMERA LOCATIONS WITH SELECTED MANUFACTURER. PROVIDE 20A 120V NORMAL BRANCH CIRCUIT TO CAMERA LOCATIONS AS REQUIRED BY SELECTED MANUFACTURER FOR HEATED ENCLOSURES, PAN-TILT-ZOOM FUNCTIONS, AND ACCESSORIES.

COORDINATE CABLING, POWER, AND ROUGH-IN REQUIREMENTS WITH SELECTED MANUFACTURER FOR CAMERA LOCATIONS WITH NETWORK DATA CABLE LENGTHS EXCEEDING 100 METERS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE NETWORK DATA CABLES AND JACKS PER SPECIFICATION SECTION 280513. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 282300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT

MOUNTING LOCATION WITH OWNER PRIOR TO INSTALLATION.

TELECOMMUNICATIONS MISC SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

CABLE TRAY PROVIDE CABLE TRAY AT LOCATIONS INDICATED ON PLANS. REFER TO FLOOR PLANS FOR TYPE DESIGNATION.

COORDINATE MOUNTING WITH OTHER TRADES AND REQUIREMENTS IN SPECIFICATION.

TYPE 'WIDTH x DEPTH", WIRE BASKET CABLE TRAY:

PROVIDE CABLE TRAY IN DIMENSION INDICATED ON FLOOR PLANS.

TYPE 'WIDTH LADDER', LADDER CABLE TRAY:

PROVIDE CABLE TRAY IN DIMENSION INDICATED ON FLOOR PLANS.

DATA SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

COMMUNICATIONS OUTLET -

CEILING

PROVIDE ONE (1) CATEGORY 6A NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS. TERMINATE CABLE WITH RJ45 CONNECTOR IN FACEPLATE, CENTERED IN CEILING TILE. PROVIDE WITH 15' OF CABLE SLACK AT LOCATION INDICATED. PROVIDE ROUGH-IN PER COMMUNICATIONS OUTLET DETAIL AT LOCATIONS INDICATED WITHIN GYP CEILINGS. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. CABLE SHALL BE ROUTED WITHIN CABLE

TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS.

COMMUNICATIONS OUTLET -

WALL

GENERAL:

PROVIDE COMMUNICATIONS OUTLET AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH OUTLET TYPE. REFER TO PLANS FOR OUTLET DESIGNATION AND QUANTITIES OF NETWORK VOICE/DATA CABLES TO BE PROVIDED TO OUTLET FROM ASSOCIATED NEAREST TELECOMMUNICATION ROOM. EXISTING CONDITIONS FOR THE WORK AREA OUTLETS ARE SHOWN ON THE PLANS IN THE FORMAT #D#V#P. SEE THE LEGEND BELOW FOR DESCRIPTION. FOR NEW OUTLET LOCATIONS, PROVIDE ROUGH-IN PER COMMUNICATIONS OUTLET DETAIL. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 271200 INCLUDING, BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, JACKS, INSERTS, FACEPLATES, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL.

COORDINATE EXACT FINAL LOCATION WITH ARCHITECTURAL INTERIOR ELEVATIONS PRIOR TO

INSTALLATION. PROVIDE CABLING AS LISTED BELOW. OUTLETS WITH NO CABLING DESIGNATION SHALL BE EMPTY WITH A BLANK WALL PLATE. CABLING DESIGNATIONS ARE TYPICAL FOR ALL WALL, FLOOR, AND CEILING COMMUNICATIONS DEVICES. REFER TO SPECIFICATIONS FOR CABLING REQUIREMENTS FOR EACH

TYPE.

D = ACTIVE DATA OUTLETS

V = ACTIVE VOICE OUTLETS

P = TOTAL NUMBER OF OUTLETS (WIRES WITH JACKS)

TYPE ‘H’, HORIZONTAL:

PROVIDE COMMUNICATIONS OUTLET DESCRIBED ABOVE, MOUNTED HORIZONTALLY TO ACCOMMODATE

BUILDING CONSTRAINTS.

TYPE ‘W’, WALL PHONE:

PROVIDE ONE (1) NETWORK DATA CABLE, MOUNTED IN WALL PHONE MOUNTING BRACKET FACEPLATE, MOUNTED AT 48” AFF. COORDINATE MOUNTING LOCATION WITH OTHER TRADES AND FINAL EQUIPMENT

SELECTION.

TYPE ‘FF’, MODULAR FURNITURE FEED VOICE/DATA CONNECTION:

PROVIDE ONE (1) JUNCTION BOX WITH TWO GANG TRIM RING AND BLANK FACEPLATE WITH 1 1/2” GASKETED GROMMET AT APPROXIMATE LOCATION INDICATED. PROVIDE ONE (1) 1” CONDUIT TO ABOVE FINISHED CEILING TO NEAREST CORRIDOR CABLE TRAY PER COMMUNICATIONS OUTLET DETAIL. CABLING SHALL PASS THROUGH JUNCTION BOX AND ROUTE THROUGH MODULAR FURNITURE COMMUNICATIONS RACEWAY. CABLES SHALL TERMINATE TO DEVICES MOUNTED WITHIN MODULAR FURNITURE. COORDINATE CABLE LENGTHS WITH FIELD VERIFIED FINAL TERMINATION LOCATIONS. COORDINATE REQUIREMENTS WITH MODULAR FURNITURE MANUFACTURER. PROVIDE VOICE/DATA FURNITURE FEED ADJACENT TO POWER FURNITURE FEED PER PLANS. PROVIDE MAXIMUM 12” BETWEEN BACK BOXES. COORDINATE

EXACT MOUNTING LOCATION WITH ARCHITECT AND MODULAR FURNITURE FINAL LOCATION.

WIRELESS ACCESS POINT -

CEILING

OWNER PROVIDED WIRELESS ACCESS POINT AT APPROXIMATE LOCATION INDICATED. PROVIDE TWO (2) CATEGORY 6A NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS, COILED ABOVE FINISHED CEILING. TERMINATE CABLE WITH RJ45 CONNECTOR WITH COMMSCOPE CEILING CONNECTOR ASSEMBLY (OR PRIOR APPROVED EQUIVALENT). PROVIDE WITH 15' OF CABLE SLACK AT LOCATION INDICATED. PROVIDE ROUGH-IN PER COMMUNICATIONS OUTLET DETAIL AT LOCATIONS INDICATED WITHIN GYP CEILINGS. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS.

CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN

UNFINISHED AREAS. LOCATIONS SHOWN ARE PRELIMINARY. CONFIRM FINAL LOCATION WITH

OWNER PRIOR TO PULLING CABLE.

ELECTRICAL FIXTURE SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

ELECTRICAL GROUND BAR PROVIDE LENGTH AS REQUIRED TO ACCOMMODATE TERMINATIONS, MINIMUM 20" IN LENGTH. REFER TO

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

EMERGENCY POWER OFF

SWITCH

GENERAL:

PROVIDE EMERGENCY POWER OFF (EPO) SWITCH AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH TYPE, AT APPROXIMATE LOCATIONS INDICATED ON PLANS. REFER TO PLANS FOR EPO SWITCH DESIGNATION. MOUNT AT 48" AFF, UNLESS OTHERWISE INDICATED. PROVIDE ELECTRICAL COMPONENTS FOR A COMPLETE SYSTEM, INCLUDING ALL NECESSARY RELAYS, TRANSFORMERS, AND SHUNTING DEVICES. COORDINATE

BACK BOX AND CONDUIT REQUIREMENTS WITH MANUFACTURER.

TYPE ‘EPO’, EMERGENCY POWER OFF SWITCH:

PROVIDE STI (SAFETY TECHNOLOGY INTERNATIONAL, INC) MODEL SS2-231PO-EN FLUSH MOUNT EPO SWITCH AND PROTECTIVE COVER, OR PRIOR APPROVED EQUIVALENT. COORDINATE WITH FINAL EQUIPMENT SELECTION. DESIGN EPO SYSTEMS WITH THE FOLLOWING FUNCTIONALITY (OTHER OPTIONS TO PREVENT UNINTENTIONAL OPERATION

OF THE DISCONNECT CONTROLS MAY BE CONSIDERED):

• DEPRESSED TRIGGER TO PREVENT ACCIDENTAL DISCHARGE FROM CASUAL CONTACT.

• COVER THE TRIGGER TO DISSUADE TRIGGERING EXCEPT IN AN ACTUAL EMERGENCY SITUATION.

• INTEGRATE THE EPO FUNCTION TO COVER ALL REQUIRED DISCONNECTIONS IN ONE TRIGGER PER EXIT.

• INITIATING THE EPO TRIGGER ONCE BEGINS A DELAYED DISCONNECTION (15 OR 30 SECONDS). AN AUDIO, VISUAL, OR OTHER TYPE OF SIGNAL SHOULD BE PRESENT AT ALL EPO TRIGGERS TO SHOW THIS COUNTDOWN.

• PRESSING AN ADJACENT ABORT TRIGGER RESETS THE SYSTEM, ABORTING THE COUNTDOWN AND

DISCONNECTION.

• INITIATING THE EPO TRIGGER AGAIN DURING THE COUNTDOWN (DOUBLE PRESSING) ABORTS THE COUNTDOWN

AND IMMEDIATELY EXECUTES THE FULL DESIGNED DISCONNECTION.

JUNCTION BOX - WALL GENERAL:

PROVIDE JUNCTION BOX AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH JUNCTION BOX TYPE. REFER TO PLANS FOR JUNCTION BOX DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE FINISHED CEILING WHERE NOT INDICATED OTHERWISE. WHERE SHOWN ADJACENT TO RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 12” BETWEEN BACK BOXES. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS

WITHIN CONDUIT TO SOURCE INDICATED ON FLOOR PLANS.

RECEPTACLE - NEMA PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA

DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:

•NEMA 15-20 & L15-20: 3-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER •NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER •NEMA 21-30 & L21-30: 4-#10, #10 GND IN 3/4" CONDUIT; 30A, 3 POLE CIRCUIT BREAKER

LOW VOLTAGE COORDINATION LEGEND

SYSTEMS

ROUGH-INS &

PATHWAYS

CABLING &

TERMINATIONS

DEVICES &

EQUIPMENT REMARKS

ACCESS CONTROL CF / CI CF / CI CF / CI -

AUDIO / VIDEO INTERCOM CF / CI CF / CI CF / CI -

AUDIO / VISUAL CF / CI REMARK 2 OF / OI -

LIGHTING CONTROLS CF / CI OF / CI OF / CI -

NURSE CALL CF / CI CF / CI CF / CI -

PATIENT MONITORING/TELEMETRY CF / CI CF / CI OF / OI -

PUBLIC ADDRESS CF / CI CF / CI CF / CI -

SECURITY SURVEILLANCE (CCTV) CF / CI CF / CI OF / OI -

SOUND MASKING CF / CI CF / CI CF / CI -

TELEVISION (CATV) CF / CI CF / CI OF / OI -

TEMPERATURE MONITORING CF / CI OF / OI OF / OI -

VOICE / DATA CF / CI CF / CI OF / OI 1

WIRELESS ACCESS POINTS CF / CI CF / CI OF / OI 1

COMMUNICATION SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

4 POST COMMUNICATIONS RACK ROVIDE 7'-0" TALL 45U, 4 POST TELECOMMUNICATIONS CHANNEL RACK AT APPROXIMATE LOCATIONS INDICATED ON FLOOR PLANS. PROVIDE MIGHTY MO 20 CABLE MANAGEMENT RACK 30" DEPTH, WHITE FINISH MODEL NUMBER:

OR-MM2073038-W (OR PRIOR APPROVED EQUIVALENT) WITH VERTICAL CABLE MANAGEMENT OR-MM20VMD706 (OR PRIOR APPROVED EQUIVALENT). REFER TO FLOOR PLANS FOR DATA SWITCH ELECTRICAL SOURCE AND REQUIREMENTS. PROVIDE TELECOMMUNICATIONS RACK AND ALL ACCESSORIES PER SPECIFICATION SECTION 271100. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION, INCLUDING BUT NOT LIMITED TO: BRACKETS, MOUNTING FRAMES, HORIZONTAL AND VERTICAL WIRE MANAGEMENT, AND GROUNDING CONNECTIONS.

PROVIDE WITH RACK MOUNTED PDU:

APC AP8861 RPDU (OR PRIOR APPROVED EQUIVALENT); RACK PDU 2G, METERED; L21-20 PLUG; THREE PHASE;

120/208V INPUT; 20A; ZERO U, 5.7 KW, 208V, (36) C13 & (6) C19 & (2) 5-20 OUTLETS; A-SIDE BLACK, B-SIDE WHITE OR

OTHER DISTINCTIVE COLOR.

WHERE INDICATED ON PLANS PROVIDE:

EATON BLADE UPS ZC0517700110000 (OR PRIOR APPROVED EQUIVALENT), RACK-MOUNTED 5 KW, 6RU, 19" RACK-MOUNTABLE, 208V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH NEMA 20A L21-20P INPUT AND L21-20R

OUTPUT.

REFER TO VA OIT "INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES VERSION 3.1" FOR ALL COMPONENT REQUIREMENTS. COORDINATE EXACT FINAL LOCATION WITH OWNER'S IT REPRESENTATIVE PRIOR TO INSTALLATION. PROVIDE ALL POWER CONNECTIONS INDICATED ON FLOOR PLANS AT FINAL RACK LOCATION. REFER

TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

COMMUNICATIONS FIRE RATED

PATHWAY - FLOOR

PROVIDE STI FIRESTOP EZ-PATH COMMUNICATIONS FIRE RATED PATHWAY THROUGH FLOOR AT LOCATIONS INDICATED ON FLOORPLANS. COORDINATE MOUNTING LOCATION WITH STRUCTURE, EQUIPMENT WITHIN ROOM, ACCESS TO EQUIPMENT, WALLS BELOW ROOM, AND OTHER TRADES. INSTALL PER MANUFACTURERS RECOMMENDATIONS. REFER TO FLOOR PLANS FOR PATHWAY TYPE AND QUANTITIES. PROVIDE PATHWAY TYPES AS

INDICATED BELOW.

(F1) - FULL KIT CATALOG # EZDP144FKS2 (1-4"x4" PATHWAY) (F2) - FULL KIT CATALOG # EZDG444S2 (4-4"x4" PATHWAYS) (F3) - FLOOR GRID CATALOG # EZG844 AND ONE (1) PATHWAY MODULE CATALOG # EZD444MBS2 (4-4"x4" PATHWAYS & 4-4"x4" SPACES) (F4) - FULL KIT CATALOG # EZDG844S2 (8-4"x4" PATHWAYS)

COMMUNICATIONS FIRE RATED

PATHWAY – WALL

PROVIDE STI FIRESTOP EZ-PATH COMMUNICATIONS FIRE RATED PATHWAY AT LOCATIONS INDICATED ON FLOORPLANS. MOUNT PATHWAYS ABOVE ACCESSIBLE CEILING SPACES. COORDINATE MOUNTING HEIGHT WITH CABLE TRAY, TELECOMMUNICATION RACK HEIGHTS, CEILING, AND OTHER TRADES. INSTALL PER MANUFACTURERS RECOMMENDATIONS. COORDINATE REQUIRED WALL OPENING WITH STUD SPACING. REFER TO FLOOR PLANS FOR

PATHWAY TYPE AND QUANTITIES. PROVIDE PATHWAY TYPES AS INDICATED BELOW.

(A1) - FULL KIT CATALOG # EZDP133CWK (1-3"x3" PATHWAY) (A2) - FULL KIT CATALOG # EZDP233GK (2-3"x3" PATHWAYS) (A3) - FULL KIT CATALOG # EZDP333GK (3-3"x3" PATHWAYS) (A4) - FULL KIT CATALOG # EZDP433GK (4-3"x3" PATHWAYS) (A7) - FULL KIT CATALOG # EZDP733GK (7-3"x3" PATHWAYS) (A8) - TWO (2) FULL KIT CATALOG # EZDP433GK (8-3"x3" PATHWAYS) (STACKED) (B1) - FULL KIT CATALOG # EZD22 (1-2"x2" PATHWAY) (C1) - FULL KIT CATALOG # EZDP44S2 (1-4"x4" PATHWAY) (C2) - TWO (2) MODULE CATALOG # EZD44S2 & ONE (1) EZP544W (2-4"x4" PATHWAYS) (C3) - THREE (3) CATALOG # EZD44S2 & ONE (1) EZP544W (3-4"x4" PATHWAYS) (C4) - FOUR (4) CATALOG # EZD44S2 & ONE (1) EZP544W (4-4"x4" PATHWAYS) (REQUIRES 16" STUD SPACING) (C5) - FIVE (5) CATALOG # EZD44S2 & ONE (1) EZP544W (5-4"x4" PATHWAYS) (REQUIRES 24" STUD SPACING)

PROVIDE STI FIRESTOP EZ-PATH CABLE SPILLWAY AT LOCATIONS INDICATED ON FLOORPLANS WITH SUBSCRIPT 'S'.

PROVIDE ONE (1) SPILLWAY PER SLEEVE. REFER TO FLOORPLANS FOR SPILLWAY TYPE AND QUANTITIES.

(A#S) - CATALOG NO. RCM33

(C#S) - CATALOG NO. EZRCM44S

PROVIDE STI FIRESTOP EZ-PATH EXTENSION MODULES AT LOCATIONS INDICATED ON PLANS WITH SUBSCRIPT 'E'.

PROVIDE ONE (1) EXTENSION MODULE PER SLEEVE. WHERE PATHWAY IS INDICATED WITH SUBSCRIPT 'EE', PROVIDE ONE (1) EXTENSION MODULES ON EACH END. REFER TO FLOORPLANS FOR EXTENSION MODULE TYPE AND

QUANTITIES.

(A#E) - CATALOG NO. EZD33E

(C#E) - CATALOG NO. EZD44ES

PLYWOOD BACKBOARD PROVIDE 3/4" THICK X 4' WIDE X 8' HIGH A/C GRADE FIRE-RETARDANT TREATED PLYWOOD BACKBOARD AT APPROXIMATE LOCATION INDICATED. REFER TO FLOORPLANS FOR WIDTHS. CUT ADDITIONAL PLYWOOD TO FIT APPROXIMATE WIDTH INDICATED ON FLOORPLANS. MOUNT PLYWOOD VERTICALLY. BUTT ADJACENT SHEETS TIGHTLY, AND FORM SMOOTH GAP-FREE CORNERS AND JOINTS. PROVIDE WITH TWO (2) COATS OF WHITE PAINT ON ALL FACES AND EDGES. PROVIDE WITH LABEL ON EACH SHEET OF PLYWOOD WITH FIRE RATINGS, VISIBLE

AFTER PAINTING. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

WALL MOUNT COMMUNICATIONS

RACK

PROVIDE 48" TALL 26U WALL MOUNT TELECOMMUNICATIONS CABINET AT APPROXIMATE LOCATIONS INDICATED ON FLOOR PLANS. PROVIDE CUBE-IT WALL-MOUNT CABINET; GEN 3; 26U; #12-24 TAPPED RAILS; TEMPERED GLASS DOOR; GLACIER WHITE (OR PRIOR APPROVED EQUIVALENT). PROVIDE TWO (2) RACK MOUNTED POWER STRIPS WITH L5-20 INPUT AND 5-15 OUTPUT, 1RU AT EACH RACK; CHATSWORTH 12820-708 (OR PRIOR APPROVED EQUIVALENT). REFER TO FLOOR PLANS FOR DATA SWITCH ELECTRICAL SOURCE AND REQUIREMENTS. PROVIDE TELECOMMUNICATIONS RACK AND ALL ACCESSORIES PER SPECIFICATION SECTION 271200. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION, INCLUDING BUT NOT LIMITED TO: PLYWOOD BACKING, BRACKETS, MOUNTING FRAMES, HORIZONTAL AND VERTICAL WIRE MANAGEMENT, BRUSH KIT, FAN KIT, FRONT AND REAR RAIL

KIT, FAN FILTER KIT, SHELF (TWO PER CABINET), AND GROUNDING CONNECTIONS.

PROVIDE WITH CABINET MOUNTED UPS:

EATON UPS (OR PRIOR APPROVED EQUIVALENT), 3 KW, 2RU, 19" RACK-MOUNTABLE, 208V UNINTERRUPTIBLE POWER

SUPPLY (UPS) WITH NEMA 20A L5-20P INPUT AND L5-20R OUTPUT.

REFER TO VA OIT "OIT DESIGN GUIDE FOR NATIONAL CEMETERY INSIDE PLANT TELECOMMUNICATIONS WALL-MOUNTED CABINET" FOR ALL COMPONENT REQUIREMENTS. COORDINATE EXACT FINAL LOCATION WITH OWNER'S IT REPRESENTATIVE PRIOR TO INSTALLATION. PROVIDE ALL POWER CONNECTIONS INDICATED ON FLOOR PLANS AT FINAL RACK LOCATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

Revisions: Date:

MAIN POINT OF ENTRY #2

FOUND DURING SURVEY.

BUILDING 5

ROOM 5102

NEW ENTRANCE ROOM #1

AND TR. FOR AT&T

SERVICE.

BUILDING 1A

ENTRANCE ROOM 1 AND

ROOM F101

MAIN COMPUTER

ROOM. BUILDING

1A ROOM E-107.

NEW ENTRANCE ROOM #2

AND TR. FOR CENTRYLINK

SERVICE.

BUILDING 1A

ENTRANCE ROOM 2 AND

ROOM G-107

BUILDING 6.

EXISTING

ENTRANCE ROOM FOR

AT&T AND CENTRYLINK.

CURRENT CORE

SWITCH LOCATION.

MAIN POINT OF

ENTRY FROM

BUILDING 6.

BUILDING 1

ROOM BEG-23A

2" C FOR AT&T NEW

CIRCUIT FROM

BASEMENT TO

ENTRANCE ROOM #1

CURRENT PUMP

ROOM AND CABLE

RISER, BUILDING 01

ROOM 6025.

EXISTING F1 EZ PATH

UP TO FIRST FLOOR

ROOM 6159

NEW 2" C

JUNCTION BOX

OUTSIDE OF

BUILDING 1

ROOM 6003

JUNCTION BOX EXISTING AT&T

ROUTE

MAIN POINT OF ENTRY #1.

EXISTING AT&T PATH. (2) 2" C AND

(1) 1" C.

EXISTING

JUNCTION BOX

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22122

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project : 22.3101

KEYPLAN N

AW

BW

CW CE

BE

AE

7C

7D 7E

7B

7A

GF

E D

J

5A

5BE

5BW 5BE5BW

35% SCHEMATIC DESIGN 10/31/2022

65% DESIGN DEVELOPMENT 05/03/2023

95% CONSTRUCTION DOCUMENTS 08/16/2023

100% FINAL BID DOCUMENTS 09/27/2023

100% FINAL STAMPED BID DOCUMENTS 10/11/2023

10/11/2023B

IM

/2

.3

V

A M e m p h is E

H R

M I n fr a s tr u c tu re /6

-7

.E T

R

.r v t

/8 /2

:2

:1

P

M

TN001

CAMPUS TELECOMMUNICATIONS PATHWAYS VA Memphis EHRM Infrastructure

MEMPHIS, TN

614-22-700

10/11/2023 NMT SSK

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

NO SCALETN001

1 CAMPUS TELECOMMUNICATIONS PATHWAYS

1,1A, 5, 6, 7, 9,10

GENERAL NOTES:

A. REFER TO SHEET TN000 TECHNOLOGY COVERSHEET FOR TECHNOLOGY SYMBOL LIST AND GENERAL

DEMOLITION NOTES FOR ADDITIONAL DEMOLITION SCOPE.

SHEET NOTES:

1. THE EXISTING ROUTE OF CENTRYLINK/LUMEN SERVICE ON THE VA CAMPUS IS UNKNOWN. LOCAL VA STAFF

TO COORDINATE WITH THE SERVICE PROVIDER FOR LOCATION OF EXISTING DUCT BANK. DUCT BANK FOR

ISP2 HAS BEEN REMOVED FROM THE SCOPE OF THIS EHRM PROJECT.

2. ONCE A FIBER ROUTE HAS BEEN ESTABLISHED FOR CENTRYLINK/LUMEN SERVICE ON THE VA CAMPUS, (1) 2" C WILL NEED TO BE INSTALLED TO TRANSFER THE FIBER FROM THE BUILDING POINT OF ENTRY TO

ENTRANCE ROOM #2 IN BUILDING 1A ROOM G-103.

DN

TR

F001

SW GEAR

FB1100

TR

DB1107A

TRANS VAULT

GB1101

SW GEAR

GB1105A

TRANS VAULT

GB1102

GENERATORS

GB1103

SWITCHGEAR

AWG15

TRANSFORMER

VAULT

TR

5146A

TR

E24-10

TR

AEG15B

TR

AWG 9

TR

CWG 1

COMM

CEG 52

TR

MECH

BC116

MECH

BD103 TR

BB153A

TR

BC111A

COMM

GB1110

PARALLELING GEAR

G E

N

G E

N

G E

N

G E

N

R E

G

E G

-4

LE

G

A T

S

ATS 4

B

LD

G

G E

N

DPX

GA ELECTRIC

CWG 47A

TR

AEG 2

NEW TELE

TELEPHONE

5130A

TELE

TELE

COMMUNICATION

BC102

TELE COMM

BC121

TELE COMM

BB131

TELE

COMM

BB100

COMM

EB1113A

TELE

COMMUNICATION

BE110A

ELEC

EB1113

CONF RM

E25-10

A1

A

A

A3

B1 ←

A1

A1 →A5 →

A

A12 →A

A

A12 →

A

A7 → A1

A26 → A

A

A26 →

A

A1 ←

A

B

A8 → B1 ← A1 → B1 ←

A7

A1

B

A6 →

A6 →

A3

A3 →

A3

B1 →

A1 →

A

B1

B1 →

A1 →

B1 → A1 →

A1 B1

A8 → B1 ←

A1 →

B

A26 → A

B

A

B1

A1 →

A6 →

B

B1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22122

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project : 22.3101

AW

BW

CW CE

BE

AE

7C

7D 7E

7B

7A

GF

E D

J

5A

5BE

5BW 5BE5BW

35% SCHEMATIC DESIGN 10/31/2022

65% DESIGN DEVELOPMENT 05/03/2023

95% CONSTRUCTION DOCUMENTS 08/16/2023

100% FINAL BID DOCUMENTS 09/27/2023

100% FINAL STAMPED BID DOCUMENTS 10/11/2023

10/11/2023B

IM

/2

.3

V

A M e m p h is E

H R

M I n fr a s tr u c tu re /6

-7

.E T

R

.r v t

/8 /2

:2

:2

P

M

TN002-00

GROUND LEVEL FLOOR PLAN - CAMPUS

OVERALL - INTRA-BUILDING FIBER ROUTING

DIAGRAM

VA Memphis EHRM Infrastructure

MEMPHIS, TN

614-22-700

10/11/2023 NMT SSK

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1" = 30'-0"TN002-00

1 GROUND LEVEL FLOOR PLAN - CAMPUS OVERALL - TELECOM

0 30' 60'15'

1,1A, 5, 6, 7, 9,10

SHEET NOTES:

1. F1 B SIDE DOWN FROM FIRST FLOOR (2 COUNT).

2. ROUTE NOTED F1 CABLING IN J-HOOKS AS SPECIFIED FROM THIS POINT TO TELECOM ROOM.

3. F1 A SIDE UP TO FIRST FLOOR (6 COUNT).

4. F1 B SIDE DOWN FROM FIRST FLOOR (1 COUNT).

5. EXISTING DUCTBANK TO SERVE AS PATHWAY FOR B SIDE FIBER BETWEEN BUILDINGS. REFER TO CIVIL

SHEETS FOR EXTERIOR DETAILS.

6. NEW DUCTBANK TO SERVE AS PATHWAY FOR A SIDE FIBER BETWEEN BUILDINGS. REFER TO CIVIL SHEETS

FOR EXTERIOR DETAILS.

7. ALL CABLE TRAY SHOWN IS EXISTING 12" X 4" LADDER TRAY. EXISTING CABLE TRAY TO BE RE-USED FOR

COPPER AND FIBER PATHS. CONTRACTOR TO PROVIDE A TEMPORARY SOLUTION FOR RE-USING EXISTING CABLE TRAY FOR NEW PATH WHILE MAINTAINING EXISTING CABLING DURING TRANSITION. OLD COPPER AND FIBER CABLES TO BE DEMOLISHED AFTER THE TRANSITION HAS BEEN CONFIRMED BY THE VA. IF ADDITIONAL LADDER TRAY IS NEEDED FOR THE PROJECT, IT SHOULD BE INSTALLED AT A MINIMUM SIZE OF 12" X 4".

GENERAL NOTES:

A. REFER TO SHEET TN000 TECHNOLOGY COVERSHEET FOR TECHNOLOGY SYMBOL LIST AND GENERAL

DEMOLITION NOTES FOR ADDITIONAL DEMOLITION SCOPE.

B. CONTRACTOR TO FIELD VERIFY CONDUIT RISER ROUTE WITH OWNER PRIOR TO INSTALLATION.

C. WHEN A-LEG AND B-LEG FIBERS ARE RUN IN THE SAME CORRIDOR, IN OPPOSITE DIRECTIONS, BOTH FIBER

MAY BE PLACED IN THE SAME CABLE TRAY. WHEN A-LEG AND B-LEG FIBERS ARE IN THE SAME CORRIDOR, AND RUN THE SAME DIRECTION FOR MORE THAN 40 FEET, MAINTAIN A MINIMUM OF 6' OF SEPARATION.

D. PROVIDE JUNCTION BOX WHEN CONNECTING NEW CONDUIT TO EXISTING CONDUIT INFRASTRUCTURE.

CONTRACTOR TO PROVIDE AS BUILT DRAWINGS INDICATING JUNCTION BOX LOCATIONS.

E. PROVIDE #3/0 COPPER IN 1" PVC CONDUIT FROM SECONDARY GROUND BAR IN EACH TR TO THE TELECOMMUNICATIONS MAIN GROUND BAR LOCATED IN THE MAIN SERVER ROOM (ROOM E-107). SEE

ASSOCIATED ENLARGED PLAN FOR EACH TR FOR GROUND BAR LOCATION.

AW101D

TR

TR-1

G107-1

SERVER ROOM

E107

STAFF / TECH

CLERICAL-2

E108-2

TR

F101

ELEC

E130

COMM

E131

TR

BC211A

TR

BB253A

MECH

1F115A

MECH

1F115 ELECTRICAL

1F127

IT

IF126

ELECTRICAL

CW197

TR

C2-507

M C

R U

P S

B

(M A

IN

T

. B Y

P A

S S

B

(M A

IN

T

. B Y

P A

S S

A

M C

R U

P S

A

TR

C2-373

TELECOM

AW175

TELECOM

CW104B

TEL CLOSET

C2-506

TELEPHONE

RECORDS

MR103A

EC

1C102

TELE

1C122

Room 1A132

Room C1-37-1

EC

1A101

TELECOM

T/C

ELEC

EC-2C

B3

B2 →B5 →

B

B

A2 ← B7 →

A1B3

A1 ← B15 →

A1

B1

A1 ← B15 →B16 →

B

B16 →B6 ←

B

A4

B2

A4 → B2 ←

B4

A28

A

A

B32 →

B22 ←

B10 →

B10 → B4 →

A2 → B6 ←

A1 B1

A1

A1 ← B1 →

B2 B1

B4 → B3 →

B

A2 ← B7 → B6 →

B1

B6 → B3 →

B3

B3

3 4 5

7 8

A

B

B32 →

A1 →

A

B

A

A

→ A1 →

B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22122

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project : 22.3101

AW

GF

E D

BW

CW CE

J

BE

AE

7D 7E

7B7C

7A

5A

35% SCHEMATIC DESIGN 10/31/2022

65% DESIGN DEVELOPMENT 05/03/2023

95% CONSTRUCTION DOCUMENTS 08/16/2023

100% FINAL BID DOCUMENTS 09/27/2023

100% FINAL STAMPED BID DOCUMENTS 10/11/2023

10/11/2023B

IM

/2

.3

V

A M e m p h is E

H R

M I n fr a s tr u c tu re /6

-7

.E T

R

.r v t

/8 /2

:2

:4

P

M

TN003-01

FIRST LEVEL FLOOR PLAN - CAMPUS OVERALL

- INTRA-BUILDING FIBER ROUTING DIAGRAM

VA Memphis EHRM Infrastructure

MEMPHIS, TN

614-22-700

10/11/2023 NMT SSK

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1" = 30'-0"TN003-01

1 FIRST LEVEL FLOOR PLAN - CAMPUS OVERALL - INTRA-BUILDING FIBER ROUTING DIAGRAM

1,1A, 5, 6, 7, 9,10

1. F1 B SIDE DOWN TO GROUND FLOOR (1 COUNT).

2. F1 B SIDE UP TO SECOND FLOOR (1 COUNT).

3. F1 A SIDE UP TO SECOND FLOOR (4 COUNT).

4. F1 B SIDE DOWN TO GROUND FLOOR (3 COUNT).

5. F1 B SIDE UP TO SECOND FLOOR (3 COUNT).

6. F1 B SIDE DOWN TO GROUND FLOOR (2 COUNT).

7. TWO (2) F1 A SIDE DOWN TO GROUND FLOOR (27 COUNT).

8. F1 B SIDE DOWN TO GROUND FLOOR (1 COUNT).

9. ROUTE NOTED F1 CABLING IN J-HOOKS AS SPECIFIED FROM THIS POINT TO TELECOM ROOM.

10. ALL CABLE TRAY SHOWN IS EXISTING 12" X 4" LADDER TRAY. EXISTING CABLE TRAY TO BE RE-

USED FOR COPPER AND FIBER PATHS. CONTRACTOR TO PROVIDE A TEMPORARY SOLUTION

FOR RE-USING EXISTING CABLE TRAY FOR NEW PATH WHILE MAINTAINING EXISTING CABLING

DURING TRANSITION. OLD COPPER AND FIBER CABLES TO BE DEMOLISHED AFTER THE

TRANSITION HAS BEEN CONFIRMED BY THE VA. IF ADDITIONAL LADDER TRAY IS NEEDED FOR

THE PROJECT, IT SHOULD BE INSTALLED AT A MINIMUM SIZE OF 12" X 4".

SHEET NOTES:

GENERAL NOTES:

A. REFER TO SHEET TN000 TECHNOLOGY COVERSHEET FOR TECHNOLOGY SYMBOL LIST AND GENERAL

DEMOLITION NOTES FOR ADDITIONAL DEMOLITION SCOPE.

B. CONTRACTOR TO FIELD VERIFY CONDUIT RISER ROUTE WITH OWNER PRIOR TO INSTALLATION.

C. WHEN A-LEG AND B-LEG FIBERS ARE RUN IN THE SAME CORRIDOR, IN OPPOSITE DIRECTIONS, BOTH FIBER

MAY BE PLACED IN THE SAME CABLE TRAY. WHEN A-LEG AND B-LEG FIBERS ARE IN THE SAME CORRIDOR, AND RUN THE SAME DIRECTION FOR MORE THAN 40 FEET, MAINTAIN A MINIMUM OF 6' OF SEPARATION.

D. PROVIDE JUNCTION BOX WHEN CONNECTING NEW CONDUIT TO EXISTING CONDUIT INFRASTRUCTURE.

CONTRACTOR TO PROVIDE AS BUILT DRAWINGS INDICATING JUNCTION BOX LOCATIONS.

E. PROVIDE #3/0 COPPER IN 1" PVC CONDUIT FROM SECONDARY GROUND BAR IN EACH TR TO THE…