Drawing Vol 1-9 Electrical 614-700-EP-20231011.pdf
PDF 5 MB Posted
- Attached to
- Y1DA--614-22-700 EHRM Infrastructure Upgrades Construction Memphis TN Federal contract opportunity
- Solicitation number
- 36C77624B0013_1
About this file
This document is a set of electrical drawings and specifications related to a federal contract opportunity for the EHRM Infrastructure Upgrades Construction project at the Memphis, Tennessee VA Medical Center.
The key details are:
- Solicitation Number: 36C77624B0013_1
- Project Title: Y1DA--614-22-700 EHRM Infrastructure Upgrades Construction Memphis TN
- Agency: Department of Veterans Affairs Technology Acquisition Center Austin
- The drawings provide detailed electrical plans, including demolition, new work, one-line diagrams, and equipment schedules for the overall construction project. The electrical scope includes power, lighting, fire alarm, low voltage systems, switchgear, transformers, generators, and other electrical components. Specific areas covered include electrical rooms, IT spaces, mechanical spaces, and general facility spaces across multiple building levels.
View the file
Other files for this federal contract opportunity
Show all 44
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CEILING
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WR
XFMR
ZSI
A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG
CONDUCTORS. RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL
UTILIZE #8 AWG CONDUCTORS.
B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED
THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS.
REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING
PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR
LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL
MASTER LABEL AND/OR LPI SYSTEM CERTIFICATE.
D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO
ADDITIONAL COST TO THE OWNER.
E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS
AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT
CONFIGURATIONS ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE
FOR PROVIDING ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE
COORDINATION GOALS AND PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND
ALL NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE
SAME INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.
H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6'
OR LESS ACROSS THE ENTIRE CIRCUIT LENGTH.
I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO
REMAIN CABLING.
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
LEGEND: (LOW VOLTAGE COORDINATION LEGEND)
CF: CONTRACTOR FURNISHED
CI: CONTRACTOR INSTALLED
GF: GOVERNMENT FURNISHED
GI: GOVERNMENT INSTALLED
REMARKS: (LOW VOLTAGE COORDINATION LEGEND)
1. FIRE ALARM SYSTEM IS AN EXTENSION OF AN EXISTING SYSTEM. NEW DEVICES SHALL FUNCTION AS AN EXTENSION OF THE EXISTING
SYSTEM.
GENERAL NOTES: (LOW VOLTAGE COORDINATION LEGEND)
A. REFER TO SYMBOL LEGENDS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
B. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL EQUIPMENT SELECTION FOR ALL SYSTEMS.
C. COORDINATE ROUGH-IN REQUIREMENTS WITH OWNER FOR OWNER FURNISHED SYSTEMS.
D. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO ABOVE NEAREST ACCESSIBLE CEILING SPACE, UNLESS OTHERWISE INDICATED.
E. WHERE CABLING IS CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED, TERMINATE AND TEST ALL CABLING PER SPECIFICATION.
FIRE ALARM CF / CI CF / CI CF / CI 1
LOW VOLTAGE COORDINATION LEGEND
SYSTEMS
ROUGH-INS &
PATHWAYS
CABLING &
TERMINATIONS
DEVICES &
EQUIPMENT REMARKS
Nathan M. Timm
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:1
:0
P
M
EE000
ELECTRICAL SYMBOLS AND ABBREVIATIONS VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
N/A
10/11/2023 NMT SSK
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL FIXTURE
SYMBOLS
PLAN SYMBOL NAME
POWER POLE
RECEPTACLE - DOUBLE DUPLEX
- CONV
RECEPTACLE - DOUBLE DUPLEX
- EMERGENCY (RED) - CONV
RECEPTACLE - DUPLEX - CONV
RECEPTACLE - DUPLEX - CONV -
GFCI
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - CONV
TOGGLE DISCONNECT SWITCH
ELECTRICAL FIXTURE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
ELECTRICAL GROUND BAR PROVIDE LENGTH AS REQUIRED TO ACCOMMODATE TERMINATIONS, MINIMUM 20" IN LENGTH. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
EMERGENCY POWER OFF
SWITCH
GENERAL:
PROVIDE EMERGENCY POWER OFF (EPO) SWITCH AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH TYPE, AT APPROXIMATE LOCATIONS INDICATED ON PLANS. REFER TO PLANS FOR EPO SWITCH DESIGNATION. MOUNT AT 48" AFF, UNLESS OTHERWISE INDICATED. PROVIDE ELECTRICAL COMPONENTS FOR A COMPLETE SYSTEM, INCLUDING ALL NECESSARY RELAYS, TRANSFORMERS, AND SHUNTING DEVICES. COORDINATE
BACK BOX AND CONDUIT REQUIREMENTS WITH MANUFACTURER.
TYPE ‘EPO’, EMERGENCY POWER OFF SWITCH:
PROVIDE STI (SAFETY TECHNOLOGY INTERNATIONAL, INC) MODEL SS2-231PO-EN FLUSH MOUNT EPO SWITCH AND PROTECTIVE COVER, OR PRIOR APPROVED EQUIVALENT. COORDINATE WITH FINAL EQUIPMENT SELECTION. DESIGN EPO SYSTEMS WITH THE FOLLOWING FUNCTIONALITY (OTHER OPTIONS TO PREVENT UNINTENTIONAL OPERATION
OF THE DISCONNECT CONTROLS MAY BE CONSIDERED):
• DEPRESSED TRIGGER TO PREVENT ACCIDENTAL DISCHARGE FROM CASUAL CONTACT.
• COVER THE TRIGGER TO DISSUADE TRIGGERING EXCEPT IN AN ACTUAL EMERGENCY SITUATION.
• INTEGRATE THE EPO FUNCTION TO COVER ALL REQUIRED DISCONNECTIONS IN ONE TRIGGER PER EXIT.
• INITIATING THE EPO TRIGGER ONCE BEGINS A DELAYED DISCONNECTION (15 OR 30 SECONDS). AN AUDIO, VISUAL, OR OTHER TYPE OF SIGNAL SHOULD BE PRESENT AT ALL EPO TRIGGERS TO SHOW THIS COUNTDOWN.
• PRESSING AN ADJACENT ABORT TRIGGER RESETS THE SYSTEM, ABORTING THE COUNTDOWN AND
DISCONNECTION.
• INITIATING THE EPO TRIGGER AGAIN DURING THE COUNTDOWN (DOUBLE PRESSING) ABORTS THE COUNTDOWN
AND IMMEDIATELY EXECUTES THE FULL DESIGNED DISCONNECTION.
JUNCTION BOX - WALL GENERAL:
PROVIDE JUNCTION BOX AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH JUNCTION BOX TYPE. REFER TO PLANS FOR JUNCTION BOX DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE FINISHED CEILING WHERE NOT INDICATED OTHERWISE. WHERE SHOWN ADJACENT TO RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 12” BETWEEN BACK BOXES. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS
WITHIN CONDUIT TO SOURCE INDICATED ON FLOOR PLANS.
RECEPTACLE - NEMA PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA
DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:
•NEMA 15-20 & L15-20: 3-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER •NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER •NEMA 21-30 & L21-30: 4-#10, #10 GND IN 3/4" CONDUIT; 30A, 3 POLE CIRCUIT BREAKER
FIRE ALARM SYMBOLS
PLAN SYMBOL NAME
DETECTOR - SYSTEM
SMOKE - CEILING
FIRE ALARM SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
FIRE ALARM CONTROL PANEL -
SURFACE MOUNT
CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN ASSOCIATED LIFE SAFETY BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKER). REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION.
PROVIDE SYSTEM SMOKE DETECTOR AT CEILING WITHIN 5 FEET OF PANEL (UNLESS SHOWN WITH ROOM
DETECTION COVERAGE ON PLAN). PROVIDE TWO (2) VOICE CONNECTIONS TO FACP.
FIRE ALARM POWER
SUPPLY/AMPLIFIER
CIRCUIT FIRE ALARM POWER SUPPLY / AMPLIFIER PANEL TO 20A 120V BRANCH CIRCUIT IN ASSOCIATED LIFE SAFETY BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKER). REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION. COORDINATE EXACT QUANTITY AND LOCATIONS WITH MANUFACTURER SHOP
DRAWINGS.
MONITORING MODULE PROVIDE FIRE ALARM MONITORING MODULE CONNECTED TO FIRE ALARM SYSTEM. PROVIDE WITH SURFACE MOUNT CONDUIT AND BACKBOX WHERE ASSOCIATED EQUIPMENT IS EXPOSED OR INSTALLED IN UNFINISHED
AREA. CONCEAL ALL CONDUITS WITHIN WALLS OR ABOVE CEILING IN FINISHED AREAS.
SMOKE DAMPER OR FIRE/SMOKE
DAMPER
CIRCUIT FIRE AND FIRE/SMOKE DAMPERS PROVIDED BY MECHANICAL CONTRACTOR TO 20A 120V BRANCH CIRCUITS IN ASSOCIATED LIFE SAFETY BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKERS).
EACH BRANCH CIRCUIT SHALL SERVE A MAXIMUM OF 20 DAMPERS. PROVIDE INDIVIDUAL CIRCUITS FOR EACH AIR HANDLING UNIT ZONE. REFER TO MECHANICAL PLANS FOR ASSOCIATED ZONES. CONTROL EACH DAMPER INDIVIDUALLY WITH ADDRESSABLE CONTROL MODULES FROM FIRE ALARM SYSTEM. LABEL EACH RELAY WITH THE NAME OF THE AIR HANDLING UNIT SERVING THE SMOKE ZONE AND WITH THE WORDS "SMOKE DAMPER CONTROL".
PROVIDE SYSTEM DUCT SMOKE DETECTOR IN ACCESSIBLE LOCATION WITHIN 5 FEET OF THE DAMPER TO CONTROL DAMPER. DUCT DETECTOR MAY BE OMITTED WHERE THE DAMPER IS INSTALLED IN A CORRIDOR WALL OR CEILING AND IS CONTROLLED BY AN AREA SMOKE DETECTION SYSTEM INSTALLED IN THE CORRIDOR. PROVIDE REMOTE STATUS INDICATOR AND TEST STATION FOR DETECTOR AND COORDINATE ASSOCIATED MOUNTING
LOCATION WITH OWNER. REFER TO ELECTRICAL POWER FLOOR PLANS FOR DAMPER LOCATIONS.
LIGHTING DEVICE SYMBOLS
PLAN SYMBOL NAME
LIGHT SWITCH
SWITCH - VACANCY SENSOR
ELECTRICAL MISC SYMBOLS
PLAN SYMBOL NAME
BRANCH CIRCUIT CONCEALED IN
CEILING OR WALL
BRANCH CIRCUIT CONCEALED IN
FLOOR OR BELOW GRADE
CLEARANCE SPACE
CONDUIT BREAK
CONDUIT DOWN
CONDUIT STUB-OUT
CONDUIT UP
HOMERUN TO PANEL
G = GFCI CIRCUIT
(PART) = PARTIAL CIRCUIT
SWITCHED RECEPTACLE
LIGHTING FIXTURE
SYMBOLS
PLAN SYMBOL NAME
EMERGENCY HATCH
EXIT SIGN - CEILING
CHEVRONS AS SHOWN
INDUSTRIAL STRIP LIGHT
PENDANT - STREAMLINE
SPOT LIGHT
TROFFER - RECESSED
WALL MOUNT - STRIPLIGHT
ONE LINE SYMBOL
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
CONTINUATION
GENERATOR
GENERATOR CONNECTION BOX
GROUND BAR
GROUNDING ELECTRODE
KEY INTERLOCK
PANEL BOARD
SURGE PROTECTIVE DEVICE
SWITCHBOARD
SWITCHBOARD/SWITCHGEAR
TRANSFORMER
UPS PANEL
UTILITY METER
ELECTRICAL EQUIPMENT
SYMBOLS
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
DISTRIBUTION PANEL
ENCLOSED CIRCUIT BREAKER -
SURFACE
ENCLOSED DISCONNECT
SWITCH - FUSED
ENCLOSED DISCONNECT
SWITCH - NON-FUSED
GENERATOR
LOW VOLTAGE PANEL
PANELBOARD - SURFACE
SWITCHBOARD
TRANSFORMER - DRY TYPE
UPS CABINET
ONE LINE SYMBOL LEGEND
PLAN SYMBOL NAME Description
DIGITAL METER PROVIDE DIGITAL METER FOR MONITORING OF POWER
CONSUMPTION. PROVIDE DATA CONNECTION FOR
ELECTRICAL METERING SYSTEM. COORDINATE WITH
MANUFACTURER OF METERING DEVICES FOR EXACT
REQUIREMENTS
Revisions: Date:
STAMP
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
T
A T E O F T E NN E S S EE
D
D
D
D
D
D
D
D
OFFICE
COMM
LIMITS OF BLANKET DEMOLITION
OFFICE
AEG 15B
LIMITS OF BLANKET DEMOLITION
STORAGE
AEG 1B
FLOOR MACHINE
AEG 2
LIMITS OF BLANKET DEMOLITION
SHAFT
LIMITS OF BLANKET DEMOLITION
COMMON SPACE
AE100
LIMITS OF BLANKET DEMOLITION
ADMIN OFFICE
AW101D
LIMITS OF BLANKET DEMOLITION
LIMITS OF BLANKET DEMOLITION
EMR CK3
AC
E
E
STACKS
DD D
D
DDD
D 48"
D
D
DATA
C2-507
BULK STORAGE
C2-513-1
LIMITS OF
SELECTIVE
DEMOLITION
ELECTRICAL
C2-378
LIMITS OF BLANKET DEMOLITION
D E
FACP
E
E
E
E
E
E
E
E
E
D
D
COMM
LIMITS OF BLANKET DEMOLITION
2GE
E
2FH
E
2GH
E
FACP
E
2GL
E
2FL1
E
Xfrmr 2GT E
E
E
D
D
E
EEEE
E E
LIMITS OF SELECTIVE DEMOLITION
WAITING
BWG 1625
LIMITS OF BLANKET DEMOLITION
SHAFT
SHAFT
LIMITS OF BLANKET DEMOLITION
D D
D
D
AC
E
DD
D
D
D
D D
LIMITS OF BLANKET DEMOLITION
A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK. EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS). EXISTING ELECTRICAL SYSTEMS SERVING ADJACENT AREAS SHALL REMAIN UNLESS OTHERWISE INDICATED. RE- SUPPORT EXISTING CONDUITS AND CABLES THAT MUST REMAIN. REFER TO FLOORPLANS FOR INDICATION OF DEMOLITION
TYPE FOR EACH AREA:
a. BLANKET DEMOLITION AREAS:
• EXISTING ELECTRICAL SYSTEMS WITHIN LIMITS OF DEMOLITION SHALL BE REMOVED UNLESS OTHERWISE INDICATED.
b. SELECTIVE DEMOLITION AREAS:
• PROVIDE DEMOLITION FOR ITEMS AS SHOWN. EXISTING ELECTRICAL SYSTEMS WITHIN LIMITS OF DEMOLITION SHALL
REMAIN UNLESS OTHERWISE INDICATED
B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).
C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION. SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND
IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.
D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS
RESPONSIBLE FOR DISPOSAL.
E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT. REMOVE AND PATCH WHERE BOXES ARE NOT REUSED.
F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE
ARCHITECT.
G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES. MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION. INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT BECOME INACCESSIBLE DUE TO NEW WORK.
H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND LIGHTING AS REQUIRED TO
ALLOW THE WORK OF OTHER TRADES TO PROCEED.
I. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND FUNCTIONALITY.
J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION.
PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE ARCHITECTURAL SPECIFICATIONS FOR MEANS
AND METHODS.
K. THIS PROJECT WILL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS. SYSTEM SERVICES TO
AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE MAINTAINED AT ALL TIMES.
L. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO MATCH ADJACENT SURFACE.
M. ALL UNLABELED ELECTRICAL DEVICES [WITH CIRCUITRY OR DEVICES MODIFIED DURING CONSTRUCTION] [THAT EXIST IN ALL ROOMS WHERE THERE IS WORK WITHIN SCOPE] SHALL BE CIRCUIT TRACED AS NEEDED WITH A LABEL PROVIDED.
(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND
ALL ELECTRICAL DEMOLITION WORK)
ELECTRICAL DEMOLITION GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:0
A M
B01-ED400
ENLARGED PLANS - ELECTRICAL - DEMO VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/4" = 1'-0"B01-ED400
4 ENLARGED PLAN - ELECTRICAL DEMO - COMM 6007/OFFICE 6006
0 4' 8'2'
SCALE: 1/4" = 1'-0"B01-ED400
1 ENLARGED PLAN - ELECTRICAL DEMO - OFFICE AEG 15B
SCALE: 1/4" = 1'-0"B01-ED400
2 ENLARGED PLAN - ELECTRICAL DEMO - AEG 1B/AEG 2
SCALE: 1/4" = 1'-0"B01-ED400
3 ENLARGED PLAN - ELECTRICAL DEMO - SHAFT - NEW TR CWG 1
SCALE: 1/4" = 1'-0"B01-ED400
6 ENLARGED PLAN - ELECTRICAL DEMO - COMMON SPACE AE100
SCALE: 1/4" = 1'-0"B01-ED400
5 ENLARGED PLAN - ELECTRICAL DEMO - ADMIN OFFICE AW101D
SCALE: 1/4" = 1'-0"B01-ED400
8 ENLARGED PLAN - ELECTRICAL DEMO - NEW TR C2-373
SCALE: 1/4" = 1'-0"B01-ED400
9 ENLARGED PLAN - ELECTRICAL DEMO - DATA C2-507
SCALE: 1/4" = 1'-0"B01-ED400
7 ENLARGED PLAN - ELECTRICAL DEMO - ELEC. C2-378
SCALE: 1/4" = 1'-0"B01-ED400
13 ENLARGED PLAN - ELECTRICAL DEMO - COMM 6206
SCALE: 1/4" = 1'-0"B01-ED400
10 ENLARGED PLAN - ELECTRICAL DEMO - ROOM AE200/P5-728
SCALE: 1/4" = 1'-0"B01-ED400
11 ENLARGED PLAN - ELECTRICAL DEMO - WAITING BWG 1625
SCALE: 1/4" = 1'-0"B01-ED400
12 ENLARGED PLAN - ELECTRICAL DEMO - SHAFT - NEW CW002
SCALE: 1/4" = 1'-0"B01-ED400
14 ENLARGED PLAN - ELECTRICAL DEMO - SHAFT - NEW TR CW003
SCALE: 1/4" = 1'-0"B01-ED400
15 ENLARGED PLAN - ELECTRICAL DEMO - SHAFT - NEW TR CW463
SHEET NOTES:
1. LIMITS OF TOTAL ELECTRICAL DEMOLITION WITHIN BOUND OF THIS ROOM. DEMOLISH ALL ELECTRICAL RECEPTACLES, DEVICES, AND LIGHTING APPLIANCES.
2. CEILING MOUNTED DEVICES AND LIGHT FIXTURES IN THIS SPACE ARE EXISTING TO REMAIN. RETAIN EXISTING CIRCUITRY AND
PATHWAYS. REPOSITION FIXTURES AS NECESSARY TO EVENLY ILLUMINATE ROOM.
1 1
LIMITS OF BLANKET DEMOLITION
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
T
N
B01-EE400
B01-EE401
B01-EE401
B01-ED400
B01-EE400
B01-ED400
B01-EE400
B01-ED400
B01-ED400
B01-EE400
CU-CWG1.2
(ABOVE)
CU-CWG1.1
(BELOW)
1CU-CW160C
CU's SERVING TR's
IN BUILDING 1A
CU's SERVING TR's
IN BUILDING 1
GEN 3
E
GEN 4
E
GEN 2
E
GEN 1
E
PARALLELING GEAR
E
BLDG 5 GEN
E
WR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
AW
BW
CW CE
BE
AE
7C
7D 7E
7B
7A
GF
E D
J
5A
5BE
5BW 5BE5BW
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:1
A M
B01-EE100
GROUND LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 3/64" = 1'-0"B01-EE100
1 GROUND LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
N
0 32 6416
SHEET NOTES:
1. CONDENSING UNIT SERVES NEW ELECTRICAL ROOM CW160C IN BUILDING 1 BUILT AS PART OF THIS PROJECT.
PROVIDE POWER TO CONDENSING UNIT FROM MECHANICAL EQUIPMENT BRANCH PANEL SERVING AREA.
ANTICIPATED PANEL LOCATION IS WITHIN ELECTRICAL ROOM CW160C. CONTRACTOR SHALL FIELD VERIFY
PANEL EXACT LOCATION WITH CONCURRENT WORK IN SPACE.
2. EQUIPMENT MAINTENANCE RECEPTACLE:
POWER RECEPTACLE FROM NEW EQUIPMENT BRANCH POWER CIRCUIT FROM EXISTING EQUIPMENT BRANCH PANEL SERVING AREA. PROVIDE 20A/1 CIRCUIT BREAKER IN AVAILABLE SPACE. UTILIZE EXISTING SPARE 20A/1
CB WHERE AVAILABLE.
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B01-ED400
B01-EE400
B01-ED400
B01-EE400
B01-ED400
B01-ED400
B01-EE400
B01-EE400
B01-ED400
CU-AEG15B
1 WR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
AW
GF
E D
BW
CW CE
J
BE
AE
7D 7E
7B7C
7A
5A
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:2
A M
B01-EE101
FIRST LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 3/64" = 1'-0"B01-EE101
1 FIRST LEVEL FLOOR PLAN - ELECTRICAL - OVERALLN
0 32 6416
Revisions: Date:
SHEET NOTES:
1. EQUIPMENT MAINTENANCE RECEPTACLE:
POWER RECEPTACLE FROM NEW EQUIPMENT BRANCH POWER CIRCUIT FROM EXISTING EQUIPMENT BRANCH PANEL SERVING AREA. PROVIDE 20A/1 CIRCUIT BREAKER IN AVAILABLE SPACE. UTILIZE EXISTING SPARE 20A/1
CB WHERE AVAILABLE.
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B01-ED400
B01-EE400
B01-ED400
B01-ED400
B01-EE400
B01-EE400
B01-ED400
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
5A
AW AE
BW BE
CW CE
J
DE
F G
7C 7B
7A
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:3
A M
B01-EE102
SECOND LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
N
0 32 6416SCALE: 3/64" = 1'-0"B01-EE102
1 SECOND LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B01-ED400
B01-EE400
CU-G107.3
CU-G107.2
(BELOW)
CU-AW101D.2
(BELOW)
CU-BW002
(BELOW)
CU-AWG9
(ABOVE)
CU-AW101D.1
(ABOVE)
CU-G107.1
(ABOVE)
CU-AEG2 CU-AE100
(ABOVE)
CU-AE200
(BELOW)
CU-C2-373.1
(BELOW)
CU-C2-373.2
(ABOVE)
CU-6007.1 CU-6007.2
CU-C2-507.1 CU-C2-507.2
CU-6206.1 CU-6206.2
CU-CW002 CU-CW463
CU-CW003.1CU-CW003.2
WR
WR
WR
WR
WR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
BW
CW
DE
F G
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:3
A M
B01-EE103
THIRD LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
N
0 32 6416SCALE: 3/64" = 1'-0"B01-EE103
1 THIRD LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
Revisions: Date:
SHEET NOTES:
1. EQUIPMENT MAINTENANCE RECEPTACLE:
POWER RECEPTACLE FROM NEW EQUIPMENT BRANCH POWER CIRCUIT FROM EXISTING EQUIPMENT BRANCH PANEL SERVING AREA. PROVIDE 20A/1 CIRCUIT BREAKER IN AVAILABLE SPACE. UTILIZE EXISTING SPARE 20A/1
CB WHERE AVAILABLE.
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B01-ED400
B01-EE400
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
BW
CW
E
F G
D
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:4
A M
B01-EE104
FOURTH LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
N
0 32 6416SCALE: 3/64" = 1'-0"B01-EE104
1 FOURTH LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B01A-EE100
B01A-EE100
B01A-EE100
B01A-EE100
B01A-EE100
CU-DB1107A.1
(ABOVE)
CU-DB1107A.2
(BELOW)
CU-CW160C
CU-F101
(ABOVE)
CU-CWG1.2
(ABOVE)
CU-CWG1.1
(BELOW)
CU-CW160C
CU's SERVING TR's
IN BUILDING 1A
CU's SERVING TR's
IN BUILDING 1 WR
CU-F001
(BELOW)
WR
WR
R
S
ATS 11
ATS 7
ATS 2
ATS 1
ATS 8
ATS 10
ATS 6
ATS 3
SB-V1
CORRIDOR
CB1-19A
SW GEAR
FB1100
SB-V2
DP-A
ATS 5
SB-E2 SB-E1
METER UTILITY METER
ATS 4
I.T.
FB1116
LIMITS OF BLANKET DEMOLITION
B1A-A-G.2
B1A-B-G.2 B1A-A-G.2-1
B1A-B-G.2-1
B1A-A-G.2-3
B1A-B-G.2-3
L2 1-
L2 1-
L2 1-
L2 1-
I1
I1
B1A-B-G.2-17
B1A-A-G.2-17 a b a b
B1A-B-G.2-11,13,15
B1A-A-G.2-11,13,15
B1A-B-G.2-5,7,9
B1A-A-G.2-5,7,9
A C
-F
TR
F001
BREAK ROOM
DB1112
CLEAN LINEN
DB1007
LIMITS OF
ELECTRICAL
DEMOLITION
3 3
B1A-A-G.1B1A-B-G.1 a b
B1A-A-G.1-1,3,5 B1A-B-G.1-1,3,5
B1A-B-G.1-7,9,11
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20
B1A-B-G.1-19
B1A-A-G.1-23
B1A-A-G.1-21
B1A-A-G.1-25
B1A-B-G.1-21 B1A-B-G.1-23 B1A-B-G.1-25
C4EE
126"
I1b bI1
B1A-A-G.1-7,9,11
B1A-B-G.1-13,15,17 B1A-A-G.1-13,15,17
A C
-D B
A .1
A C
-D B
A .2
TR
DB1107A
BREAK RM-2
DB1112-2
CLEAN LINEN-2
DB1107-2
B1A-A-G.1-19
I1
I1 a a
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
AW
BW
CW CE
BE
AE
7C
7D 7E
7B
7A
GF
E D
J
5A
5BE
5BW 5BE5BW
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:3
A M
B01A-EE100
GROUND LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
1A
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
N
0 32 6416SCALE: 3/64" = 1'-0"B01A-EE100
1 B01A GROUND LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
SCALE: 1/4" = 1'-0"B01A-EE100
2 ENLARGED PLAN - ELECTRICAL - SWITCHGEAR - B1A - ROOM FB1100
SCALE: 1/4" = 1'-0"B01A-EE100
4 ENLARGED PLAN - ELECTRICAL DEMO - I.T. FB1116
SCALE: 1/4" = 1'-0"B01A-EE100
5 ENLARGED PLAN - ELECTRICAL - TR F001
SCALE: 1/4" = 1'-0"B01A-EE100
3 ENLARGED PLAN - ELECTRICAL DEMO - BREAKROOM DB1112/CLEAN LINEN DB1007
SCALE: 1/4" = 1'-0"B01A-EE100
6 ENLARGED PLAN - ELECTRICAL - TR DB1107A
0 4' 8'2'
SHEET NOTES:
1. CONDENSING UNIT SERVES ELECTRICAL ROOM CW160C BEING BUILT AS PART OF THIS PROJECT. PROVIDE
POWER TO CONDENSING UNIT FROM MECHANICAL EQUIPMENT BRANCH PANEL SERVING AREA. ANTICIPATED PANEL LOCATION IS WITHIN ELECTRICAL ROOM CW160C. CONTRACTOR SHALL FIELD VERIFY PANEL EXACT
LOCATION.
2. CIRCUIT NEW RECEPTACLE FROM EXISTING NORMAL BRANCH CIRCUIT SERVING ROOM.
3. CEILING MOUNTED DEVICES AND LIGHT FIXTURES IN THIS SPACE ARE EXISTING TO REMAIN. RETAIN EXISTING
CIRCUITRY AND PATHWAYS. REPOSITION FIXTURES AS NECESSARY TO EVENLY ILLUMINATE ROOM.
4. LIMITS OF TOTAL ELECTRICAL DEMOLITION WITHIN BOUND OF THIS ROOM. DEMOLISH ALL ELECTRICAL
RECEPTACLES, DEVICES, AND LIGHTING APPLIANCES.
5. EQUIPMENT MAINTENANCE RECEPTACLE:
POWER RECEPTACLE FROM NEW EQUIPMENT BRANCH POWER CIRCUIT FROM EXISTING EQUIPMENT BRANCH PANEL SERVING AREA. PROVIDE 20A/1 CIRCUIT BREAKER IN AVAILABLE SPACE. UTILIZE EXISTING SPARE 20A/1
CB WHERE AVAILABLE.
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
F
FS FS FS FS FS FS
FS
FS
FS
FSFSFSFSFS
FS
FS
FS
B01A-EE101
B01A-EE101
B01A-EE101
B01A-EE101
B01A-EE101
B01A-EE101
B01A-EE101
B01A-EE101
COMPUTER
E107
LIMITS OF TOTAL ELECTRICAL DEMOLITION
MCR OLD PANEL 1 MCR OLD PANEL 2
D D b a a
(MAINT. BYPASS A) MCR UPS AMCR UPS B (MAINT. BYPASS B)
MM
(TYP) 2
b
5 5
CRU-E107.1
CRU-E107.2
CLEAN AGENT
b b b a b b a b a bb b bb
MRC PANEL BMRC PANEL A
SERVER ROOM
E107
MRC PANEL
A-1,3,5
MRC PANEL
A-2,4,6
MRC PANEL
B-1,3,5
MRC PANEL
B-2,4,6
MRC PANEL A-7
(PART)
MRC PANEL A-7
(PART)
MRC PANEL B-7
(PART)
MRC PANEL B-7
(PART)
MRC PANEL B-9
(PART)
MRC PANEL B-9
(PART)
3 3
(TYP)2
(TYP) 2
(TYP)2
E
G1 G1
G1G1 G1
G1 G1
G1 G1
G1
G1
G1G1
G1G1
G1G1
G1G1
G1 a a a a
LS
LS
MRC PANEL B-11
(PART)MRC PANEL B-11
(PART)
MRC PANEL A-9
(PART)
MRC PANEL A-9
(PART)
MRC PANEL B-11
(PART)
EPO
MRC PANEL A-11
BATT
D182
HAC
D129
LIMITS OF ELECTRICAL DEMOLITION
UPS OLD-1
D
UPS OLD-2
D
T-B1A-DP-A
T-B1A-DP-B
B1A-DP-A.0
B1A-DP-B.0
T-B1A-A-1.2
(ABOVE)
T-B1A-A-1.1
(BELOW)
D S
T
-B 1A
-A -1
.1
D S
T
-B 1A
-A -1
.2
96" 48"
BATT
D182
EE800
B1A-DP-A
B1A-DP-B
I1I1
I1
B1A-DP-A-41
B1A-DP-B-41
I.T.
F100A
LIMITS OF BLANKET DEMOLITION
B1A-A-1.2
B1A-B-1.2
B1A-A-1.2-3
B1A-A-1.2-1
B1A-B-1.2-3
L21-20
L21-20
L21-20
L21-20
I1
I1
B1A-B-1.2-17 a b a b B1A-B-1.2-11,13,15
B1A-A-1.2-11,13,15
B1A-B-1.2-5,7,9
B1A-A-1.2-5,7,9
A C
-F
TR
F101
B1A-A-1.2-17
I1
I1 b a
B1A-B-1.2-1
3 STACKS
E
FAPS
E E
E
E
AC
E
E
E E
PA
E
RED
E E
E
E
E
E
COMM
G107
LOUNGE
G103
LIMITS OF BLANKET DEMOLITION
E
E E
PA
E
RED
E E
E
E
E
E
B1A-B-1.1
(BELOW)
B1A-A-1.1
B1A-B-1.1-1
B1A-A-1.1-1
B1A-B-1.1-3B1A-A-1.1-3
B1A-A-1.1-7,9,11
B1A-B-1.1-7,9,11 B1A-A-1.1-13,15,17
L21-20
L21-20
L21-20
L21-20 a b
B1A-B-1.1-13,15,17
A C
-G
7.
A C
-G
7.
AC-G107.3
TR
G107
TR-1
G107-1
I1 I1
I1I1 a b b a
B1A-A-1.1-5
B1A-B-1.1-5
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
AW
GF
E D
BW
CW CE
J
BE
AE
7D 7E
7B7C
7A
5A
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:4
A M
B01A-EE101
FIRST LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
1A
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
N
0 32 6416
SCALE: 3/64" = 1'-0"B01A-EE101
1 B01A FIRST LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
SHEET NOTES:
SCALE: 1/4" = 1'-0"B01A-EE101
7 ENLARGED PLAN - ELECTRICAL DEMO - COMPUTER E107
SCALE: 1/4" = 1'-0"B01A-EE101
8 ENLARGED PLAN - ELECTRICAL - SERVER ROOM E107
SCALE: 1/4" = 1'-0"B01A-EE101
2 ENLARGED PLAN - ELECTRICAL DEMO - BATT D182/HAC D129
SCALE: 1/4" = 1'-0"B01A-EE101
3 ENLARGED PLAN - ELECTRICAL - UPS D182
SCALE: 1/4" = 1'-0"B01A-EE101
6 ENLARGED PLAN - ELECTRICAL DEMO - IT F100A
SCALE: 1/4" = 1'-0"B01A-EE101
9 ENLARGED PLAN - ELECTRICAL - TR F101
0 4' 8'2'
SCALE: 1/4" = 1'-0"B01A-EE101
4 ENLARGED PLAN - ELECTRICAL DEMO - LOUNGE G103/COMM G107
SCALE: 1/4" = 1'-0"B01A-EE101
5 ENLARGED PLAN - ELECTRICAL - TR G103
1. PROVIDE INTERCONNECTION BETWEEN CLEAN AGENT FIRE SUPRESSION
SYSTEM AND EXISTING FIRE ALARM SYSTEM.
2. PROVIDE ONE POWER BUSWAY TAP PER SERVER ROOM CABINET, MOUNTED
CENTER ABOVE CABINET AT 8' AFF. EACH BUSWAY TAP SHALL HAVE ONE 20A,
3-POLE CIRCUIT BREAKER WITH A L21-20R DROP CORD FOR EACH CABINET.
HIGH DENSITY CABINET TAPS SHALL HAVE DUAL 20A, 3-POLE CIRCUIT
BREAKERS EACH WITH A L21-20R DROP CORD.
3. HIGH DENSITY CABINET. PROVIDE WITH TWO L21-20R DROP CORDS FROM 'A'
SIDE AND 'B' SIDE POWER BUSWAYS (FOUR TOTAL).
4. 150A, 208Y/120V, 3-PHASE, 4 WIRE BUSWAY. FEEDER SHALL BE (4) #2/0, #6 GND
IN 2" CONDUIT. FEEDER FOR THIS BUSWAY AND ADJACENT BUSWAY SHALL BE
FED TO INDICATED PANEL ALONG A DIVERSE PATHWAY.
5. PROVIDE EATON 93PM 200-3 (N+1) OR EQUIVALENT 80 KW (80 KW + 50 KW
REDUNDANT MODULE) UPS WITH SIDECAR WRAPAROUND BYPASS CABINET,
AND MINIMUM 10 MINUTES OF BATTERY RUNTIME. PROVIDE AS 480V, 3-PHASE
INPUT AND 208Y/120V, 3-PHASE, 4 WIRE OUTPUT WITH K13 RATED
TRANSFORMER.
6. RETAIN EXISTING CIRCUIT FOR REUSE WITH NEW RECEPTACLES IN NEW
CONSTRUCTION. EXTEND EXISTING NORMAL POWER CIRCUIT TO POWER NEW
RECEPTACLES IN SAME ROOM.
7. EXTEND EXISTING LIFE SAFETY LIGHTING BRANCH CIRCUIT TO POWER NEW
LIFE SAFETY LIGHTS IN SPACE.
8. LIMITS OF TOTAL ELECTRICAL DEMOLITION WITHIN BOUND OF THIS ROOM.
DEMOLISH ALL ELECTRICAL RECEPTACLES, DEVICES, AND LIGHTING
APPLIANCES.
9. CEILING MOUNTED DEVICES AND LIGHT FIXTURES IN THIS SPACE ARE
EXISTING TO REMAIN. RETAIN EXISTING CIRCUITRY AND PATHWAYS.
REPOSITION FIXTURES AS NECESSARRY TO EVENLY ILLUMINATE ROOM.
10. EXTEND EXISTING CRITICAL LIGHTING BRANCH CIRCUIT TO POWER NEW
LIGHTS IN THIS SPACE.
11. SEE MECHANICAL PLANS FOR LOCATION OF CLEAN AGENT DISCHARGE
STROBES AND CLEAN INDICATING LIGHTS.
UPS PHASING PLAN: SEE PHASING NOTES ON SHEET 'B01A-E600 - ONE-LINE DIAGRAM'.
PHASING NOTES:
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B01A-EE102
B01A-EE102
LIMITS OF ELECTRICAL DEMOLITION
B1A-A-2.1
B1A-B-2.1 B1A-A-2.1-1
B1A-B-2.1-1 B1A-A-2.1-3 B1A-B-2.1-3
I1
I1 ab a b
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20
B1A-A-2.1-5,7,9
A C
-F
1.
B1A-B-2.1-17,19,21 B1A-A-2.1-17,19,21 B1A-B-2.1-11,13,15 B1A-A-2.1-11,13,15
B1A-B-2.1-5,7,9
A C
-F
1.
TR
F201
B1A-B-2.1-23,25,27 B1A-A-2.1-23,25,27 a bI1
I1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
5A
AW AE
BW BE
CW CE
J
DE
F G
7C 7B
7A
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:5
A M
B01A-EE102
SECOND LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
1A
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 3/64" = 1'-0"B01A-EE102
1 B01A SECOND LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
SCALE: 1/4" = 1'-0"B01A-EE102
2 ENLARGED PLAN - ELECTRICAL DEMO - COURTYARD BWG 1636
SCALE: 1/4" = 1'-0"B01A-EE102
3 ENLARGED PLAN - ELECTRICAL - TR F201
N
0 32 6416
0 4' 8'2'
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B01A-EE103
B01A-EE103
CU-G107.3
LIMITS OF ELECTRICAL DEMOLITION
B1A-A-3.1
B1A-B-3.1 B1A-A-3.1-1
B1A-B-3.1-1
B1A-A-3.1-3 B1A-B-3.1-3
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20 ab
B1A-B-3.1-5,7,9
B1A-A-3.1-5,7,9
B1A-A-3.1-11,13,15 B1A-B-3.1-11,13,15 B1A-A-3.1-17,19,21 B1A-B-3.1-17,19,21
B1A-A-3.1-23,25,27
B1A-B-3.1-23,25,27
A C
-F
1.
A C
-F
1.
TR
F301
I1I1
I1
I1 ba b a
B1A-B-3.1-29
B1A-A-3.1-29
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
BW
CW
DE
F G
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:0
A M
B01A-EE103
THIRD LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
1A
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
0 4' 8'2'
SCALE: 3/64" = 1'-0"B01A-EE103
1 B01A THIRD LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
N
0 32 6416
SCALE: 1/4" = 1'-0"B01A-EE103
2 ENLARGED PLAN - ELECTRICAL DEMO - COURTYARD C2-6DDD
SCALE: 1/4" = 1'-0"B01A-EE103
3 ENLARGED PLAN - ELECTRICAL - TR F301
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B01A-EE104
B01A-EE104
LIMITS OF ELECTRICAL DEMOLITION
B1A-A-4.1
B1A-B-4.1
B1A-A-4.1-3
B1A-B-4.1-3
B1A-B-4.1-1
B1A-A-4.1-1
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20 ab
B1A-A-4.1-17,19,21
B1A-B-4.1-11,13,15 B1A-A-4.1-11,13,15
B1A-A-4.1-5,7,9
A C
-F
1.
A C
-F
1.
TR
F401
I1I1
I1
I1 ba b a
B1A-B-4.1-23
B1A-A-4.1-23
B1A-B-4.1-17,19,21
B1A-B-4.1-5,7,9
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
BW
CW
E
F G
D
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:0
A M
B01A-EE104
FOURTH LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
1A
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 3/64" = 1'-0"B01A-EE104
1 B01A FOURTH LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
N
0 32 6416
SCALE: 1/4" = 1'-0"B01A-EE104
2 ENLARGED PLAN - ELECTRICAL DEMO - COURTYARD C4-4-575
SCALE: 1/4" = 1'-0"B01A-EE104
3 ENLARGED PLAN - ELECTRICAL - TR F401
0 4' 8'2'
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B01A-EE105
B01A-EE105
LIMITS OF ELECTRICAL DEMOLITION
B1A-A-5.1
B1A-B-5.1
B1A-B-5.1-1
B1A-A-5.1-3
B1A-B-5.1-3
B1A-A-5.1-1
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20 b a
C4 126"
A C
-F
1.
A C
-F
1.
TR
F501
I1I1
I1
I1 ba b a
B1A-B-5.1-23
B1A-A-5.1-23
B1A-A-5.1-17,19,21
B1A-B-5.1-11,13,15 B1A-A-5.1-11,13,15
B1A-A-5.1-5,7,9
B1A-B-5.1-17,19,21
B1A-B-5.1-5,7,9
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
F
E
G
D
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:1
A M
B01A-EE105
FIFTH LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
1A
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
0 4' 8'2'
SCALE: 3/64" = 1'-0"B01A-EE105
1 B01A FIFTH LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
N
0 32 6416
SCALE: 1/4" = 1'-0"B01A-EE105
2 ENLARGED PLAN - ELECTRICAL DEMO - COURTYARD F406-457
SCALE: 1/4" = 1'-0"B01A-EE105
3 ENLARGED PLAN - ELECTRICAL - TR F501
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
CU-F501.2 CU-F501.1
CU-F401.1CU-F401.2
CU-F301.2
CU-F201.2 CU-F201.1
CU-F301.1
ET-1
P-1 P-2
DC-E107.1
DC-E107.2
WR1
1 WR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
F
E
G
D
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:1
A M
B01A-EE106
SIXTH LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
1A
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/16" = 1'-0"B01A-EE106
1 B01A SIXTH LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
N
0 32 6416
Revisions: Date:
SHEET NOTES:
1. EQUIPMENT MAINTENANCE RECEPTACLE:
POWER RECEPTACLE FROM NEW EQUIPMENT BRANCH POWER CIRCUIT FROM EXISTING EQUIPMENT BRANCH PANEL SERVING AREA. PROVIDE 20A/1 CIRCUIT BREAKER IN AVAILABLE SPACE. UTILIZE EXISTING SPARE 20A/1
CB WHERE AVAILABLE.
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
DN
B05-EE100
B05-EE100
B05-EE100
BLDG 5 GEN
E
WORKSMEN
COMP OFFICE
WHEEL CHAIR
5146A
LIMITS OF ELECTRICAL DEMOLITION
B5-A-G
(BELOW)B5-B-G
I1
I1
48"
48"
48" 48"
48"
48"
48" 48"
B5-B-G-27
B5-A-G-27
B5-A-G-29 (PART)
L21-20
B5-A-G-25
B5-B-G-29
B5-A-G-1,3,5 B5-B-G-1,3,5
B5-A-G-7,9,11
A C
-5
6.
A C
-5
6.
TR
5146A
WORKSMEN
COMP OFFICE
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20
L21-20 b a
B5-B-G-7,9,11 B5-A-G-13,15,17
B5-B-G-19,21,23 B5-A-G-19,21,23 B5-B-G-13,15,17 b a a b
I1
I1
B5-B-G-25 (PART)
B5-A-G-29 (PART)
B5-B-G-25 (PART)
T-B5-DP-B
(BELOW)
T-B5-DP-A
(ABOVE)
B5-DP-B
B5-DP-A
DPX-A
E
MCC-1
E
MCC-X1
E
DPC
E
ATS 3
E
ATS 1
E
ATS 2
E
MSB
E
MECH EQUP
EE800
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
AW
BW
CW CE
BE
AE
7C
7D 7E
7B
7A
GF
E D
J
5A
5BE
5BW 5BE5BW
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:3
A M
B05-EE100
GROUND LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
N
0 32 6416
SCALE: 3/64" = 1'-0"B05-EE100
1 GROUND LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
SCALE: 1/4" = 1'-0"B05-EE100
2 ENLARGED PLAN - ELECTRICAL DEMO - ROOMS 5146A AND 5147
SCALE: 1/4" = 1'-0"B05-EE100
3 ENLARGED PLAN - ELECTRICAL - TR 5146A
SCALE: 1/4" = 1'-0"B05-EE100
4 ENLARGED PLAN - ELECTRICAL - SWITCHGEAR - B5 - MECHANICAL EQUIPMENT 5165
SHEET NOTES:
1. CEILING MOUNTED DEVICES AND LIGHT FIXTURES IN THIS SPACE ARE EXISTING TO
REMAIN. RETAIN EXISTING CIRCUITRY AND PATHWAYS. REPOSITION FIXTURES AS
NECESSARRY TO EVENLY ILLUMINATE ROOM.
2. RETAIN EXISTING CIRCUIT FOR REUSE WITH NEW RECEPTACLES IN NEW
CONSTRUCTION. EXTEND EXISTING NORMAL POWER CIRCUIT TO POWER NEW
RECEPTACLES IN SAME ROOM.
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B05-EE101
B05-EE101
CU-AEG15B
WR3
LIMITS OF BLANKET DEMOLITION
B5-B-1
B5-A-1
B5-B-1-3
B5-A-1-1
B5-B-1-1
B5-A-1-3 L2 1-
L2 1-
I1
I1
B5-B-1-11
B5-A-1-11 a b a b B5-B-1-5,7,9
B5-A-1-5,7,9
A C
-5
TR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
KEYPLAN N
AW
GF
E D
BW
CW CE
J
BE
AE
7D 7E
7B7C
7A
5A
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.E T
R
.r v t
/1 /2
:3
:4
A M
B05-EE101
FIRST LEVEL FLOOR PLAN - ELECTRICAL -
OVERALL
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 NMT MOJ
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 3/64" = 1'-0"B05-EE101
1 B05 FIRST LEVEL FLOOR PLAN - ELECTRICAL - OVERALL
SCALE: 1/4" = 1'-0"B05-EE101
2 ENLARGED PLAN - ELECTRICAL DEMO - OFFICE 5242
SCALE: 1/4" = 1'-0"B05-EE101
3 ENLARGED PLAN - ELECTRICAL - TR 5242N
0 32 6416
0 4' 8'2'
SHEET NOTES:
1. LIMITS OF TOTAL ELECTRICAL DEMOLITION WITHIN BOUND OF THIS ROOM. DEMOLISH ALL
ELECTRICAL RECEPTACLES, DEVICES, AND LIGHTING APPLIANCES.
2. SERVES ROOM AEG15B IN BUILDING 1. REFER TO SHEET B01 - EE101 FOR MORE INFORMATION.
3. EQUIPMENT MAINTENANCE RECEPTACLE:
POWER RECEPTACLE FROM NEW EQUIPMENT BRANCH POWER CIRCUIT FROM EXISTING
EQUIPMENT BRANCH PANEL SERVING AREA. PROVIDE 20A/1 CIRCUIT BREAKER IN AVAILABLE
SPACE. UTILIZE EXISTING SPARE 20A/1 CB WHERE AVAILABLE.
Revisions: Date:
R E
G
IS
T E R E D E N G IN E
E R
N 2
O.
0 0 1 1 8
AGRICULTURE
C E O
M M E R C
TRACY J. HAUSER
10/11/2023
S
B05-EE102
B05-EE102
CU-5242
CU-201ACU-5146A.1
CU-5146A.2
WR
ROOF LEVEL ABOVE 1
WAITING
BWG 1641
LIMITS OF BLANKET DEMOLITION
B5-A-2
B5-B-2
B5-A-2-3B5-B-2-3
B5-A-2-1
B5-B-2-1
L21-20
L21-20
I1
I1
B5-B-2-11
B5-A-2-11 b a a bB5-A-2-5,7,9
B5-B-2-5,7,9
AC-201A
TR
5201A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321…
This is the start of the file's text. The full file is on GovTribe.