Drawing Vol 1-4 Structural 614-700-SF-20231011.pdf
PDF 11 MB Posted
- Attached to
- Y1DA--614-22-700 EHRM Infrastructure Upgrades Construction Memphis TN Federal contract opportunity
- Solicitation number
- 36C77624B0013_1
About this file
This document is a set of drawings for structural elements related to a federal contract opportunity.
The associated contract opportunity is for EHRM (Electronic Health Record Modernization) infrastructure upgrades construction at the Memphis, TN VA Medical Center. The solicitation number is 36C77624B0013_1, and the opportunity type is a solicitation issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The description indicates this is for EHRM infrastructure upgrades construction at the Memphis, TN VAMC. No other details about the specific products, services, response dates, award dates, pricing terms, set asides, incumbents, or other salient information are provided in the given materials.
View the file
Other files for this federal contract opportunity
Show all 44
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BEAM LEGEND
W18X40 C=1"
CAMBERBEAM SIZE
20K20K
BEAM REACTION, TYP
(8) (8)(4)
QUANTITY OF SHEAR STUDS,
UNIFORMLY SPACED BETWEEN
ADJACENT FRAMING, TYP
(COMPOSITE CONSTRUCTION ONLY)
NOTES:
1) REACTION VALUE IS ASD (KIPS), UNO.
2) WHERE NO VALUE IS SHOWN, DESIGN CONNECTION FOR A MINIMUM REACTION OF 10 KIPS.
3) SPACE STUDS PER TYPICAL SHEAR STUD PLACEMENT DETAIL. MINIMUM NUMBER OF STUDS
PER GENERAL NOTES.
4) "M" IN PLACE OF BEAM SHAPE INDICATES W10X12 WITH MINIMUM CONNECTION.
5) HSS IN PLACE OF SHAPE INDICATES HSS10X4X5/16, UNO.
6) BEAMS ARE PRIMARY MEMBERS FOR FIREPROOFING UNLESS NOTED AS SECONDARY.
7) POSITIVE CAMBER UPWARDS, NEGATIVE CAMBER DOWNWARDS. CAMBER SHOWN
ON CANTILEVERS IS AT END OF CANTILEVER.
TYPE A
1. GROUT SOLID ALL CELLS CONTAINING REINFORCEMENT AND BELOW GRADE.
2. PROVIDE MATCHING HOOKED DOWELS INTO FOUNDATION FOR ALL VERTICAL REINFORCEMENT.
3. PROVIDE VERT. BAR AT ALL CORNERS, INTERSECTIONS, AND ENDS OF WALL. BAR SIZE TO MATCH TYP. VERT.
REINFORCEMENT.
4. PROVIDE VERT. BARS AT JAMBS OF ALL OPENINGS.
FOR OPENINGS W/ WIDTH < 3'-4" PROVIDE VERT. BARS AT FIRST TWO CORES AT EACH JAMB.
FOR OPENINGS W/ WIDTH > 3'-4" < 8'-0" PROVIDE VERT. BARS AT FIRST THREE CORES AT EACH JAMB.
BAR SIZE TO MATCH TYP. VERT. REINFORCEMENT.
5. PROVIDE VERT. BAR AT FIRST CORE ON EACH SIDE OF CONTROL JOINTS. BAR SIZE AND SPACING TO MATCH TYP.
VERT. REINFORCEMENT.
6. PROVIDE HORIZONTAL BOND BEAM W/ 1-#5 CONT. BELOW ALL WINDOW AND DOOR OPENINGS. EXTEND 2'-0" PAST
OPENING.
7. SPLICE ALL REINFORCEMENT PER TABLE THIS SHEET.
NOTES:
REINFORCEMENTCMU SIZE REMARKSMARK TYPE
CMU WALL SCHEDULE
#6 @ 16" OCAMW10 10"
1/
D 1/
D
D
BAR SIZE VERTICAL BARS HORIZONTAL BARS
#3 1'-10" 2'-4" 1'-10"
#4 2'-5" 3'-1" 2'-5"
#5 3'-0" 3'-11" 3'-0"
#6 3'-7" 4'-8" 3'-7"
#7 5'-3" 6'-9" 5'-3"
#8 6'-0" 7'-9" 6'-0"
#9 6'-9" 8'-9" 6'-9"
NOTES:
1. HORIZONTAL "BOTTOM" BARS ARE BARS 12" OR LESS FROM THE BOTTOM OF A
FOOTING, SLAB, OR OTHER CONCRETE MEMBER
2. ALL REINFORCING BARS ARE TO BE SPLICED WITH A CLASS B LAP SPLICE, U.N.O.
HORIZONTAL BOTTOM BARS
CONCRETE CONSTRUCTION
CLASS B LAP SPLICE LENGTHS
B1A-6 B1A-7
B1A-G
B1A-G.5
B1A-6 B1A-7
B1A-G
B1A-G.5
B
C
B7-12
B7-R
D
B7-12
B7-R
FLOOR LOAD SCHEDULE
A
B
TYP FLOOR 5 NOTE 1
ROOF 5
- 100 (NR) 0
C TYP FLOOR 5 150 (NR)
MARK
DEAD LOAD
(PSF)
DESCRIPTION
SDL
OCCUPANCY/USE
POINT LOAD
(LBS)
DESCRIPTION LIVE LOAD
(PSF)
SNOW LOAD (PSF)
SDL LL SL
NOTE 1
NOTE 1
NOTES:
1. SDL INDICATES SUPERIMPOSED DEAD LOAD AND IS DL IN ADDITION TO THE SELF WEIGHT OF THE PRIMARY STRUCTURAL SYSTEM.
2. (NR) INDICATES NON-REDUCIBLE LIVE LOAD.
D ROOF 5 20NOTE 1 -- --
35 BALANCED
MISCELLANEOUS SYMBOLS
NORTH ARROW
GRIDLINES
EARTH
SECTION NUMBER
SHEET NUMBER
S101
S101
CALLOUT NUMBER
SHEET NUMBER
A
ELEVATION REFERENCE
LIMIT OF EXTENT
CONTINUOUS EXTENT
F ## COLUMN FOOTING NOTATION
GB ## GRADE BEAM NOTATION
P ## PIER NOTATION
B ## CONCRETE BEAM NOTATION
PC ## PILE CAP NOTATION
WF ## WALL FOOTING NOTATION
SHEAR WALL NOTATIONSW ##
BW ## BEARING WALL NOTATION
GRAVEL
Name
Elevation
TF ## TRENCH FOOTING NOTATION
FLOOR DRAIN
FD
N
22 GA. 2" COMPOSITE DECK W/
3 1/4" LW CONCRETE AND WWF
6X6-W1.4XW1.4
DIRECTION OF SPAN
CONCRETE WASH
20 GA. 1 1/2" ROOF DECK
DIRECTION OF SPAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.S T
R U
C T
.2
.r v t
/1 /2
:4
:3
P
M
SI001
STRUCTURAL ABBREVIATIONS,
SYMBOLS, AND SCHEDULES
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 MAV ADK
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
STRUCTURAL ABBREVIATIONS
JST JOIST
JT JOINT
KB KNEE BRACE
KIP, K 1,000 POUNDS
KO KNOCK-OUT
KSI KIPS PER SQUARE INCH
L ANGLE OR LENGTH
LAB LABRATORY
LB POUND
LF LINEAL FOOT
LIN LINEAL, LINEAR
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONGIT LONGITUDINAL
LP LOW POINT
LSLT LONG SLOTTED HOLE
LTWT LIGHT WEIGHT
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL/ ELECTRICAL/ PLUMBING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MULT MULTIPLE
N/A NOT APPLICABLE
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVERFLOW DRAIN
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPPHD OPPOSITE HAND
ORIG ORIGINAL
OVS OVERSIZED HOLE
P PIER
PC PIER CAP OR PRECAST
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PREFAB PREFABRICATED
PREL PRELIMINARY
PREP PREPARATION, PREPARE
PROJ PROJECTION
PS PRESTRESSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT POST-TENSIONED
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT, REINFORCE
REQD REQUIRED
RO ROUGH OPENING
SCH SCHEDULE
SECT SECTION
SF SQUARE FEET
SHT SHEET
SIM SIMILAR
SL SLOPE
SL-DN SLOPE DOWN
SL-UP SLOPE UP
SOG SLAB-ON-GRADE
SP SHEET PILING
SPA SPACES, SPACE
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSLT SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
T/ TOP OF
T/GB TOP OF GRADE BEAM
TBS MECHANICAL TENSION BUTT SPLICE
TEMP TEMPERATURE
TF TRENCH FOOTING
THRU THROUGH
TRANS TRANSVERSE
TYP TYPICAL
UL UNDERWRITERS' LABORATORY INC.
UNO UNLESS NOTED OTHERWISE
UT ULTRA-SONIC TEST
VERT VERTICAL
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WD WOOD
WF WALL FOOTING
WP WORK POINT
WWF WELDED WIRE FABRIC
STRUCTURAL ABBREVIATIONS
A/E ARCHITECT/ENGINEER
ACI AMERICAN CONCRETE INSTITUTE
ACP AUGER CAST PILE
ADDL ADDITIONAL
ADJ ADJACENT
AGGR AGGREGATE
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BAL BALANCE
BD BOARD
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOTT BOTTOM
BRG BEARING
BRKT BRACKET
BTWN BETWEEN
C STANDARD CHANNEL
CANT CANTILEVER
CC CENTER TO CENTER
CF COLD FORMED
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONTROL JOINT OR CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEARANCE, CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
CTRD CENTERED
CU FT CUBIC FEET
CU IN CUBIC INCH
CYD CUBIC YARD
CW CONCRETE WALL
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DN DOWN
DO DITTO
DP DRILLED PIER OR DEEP
DWG DRAWING
DWL DOWELS
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION
ELEC ELECTRICAL
ENCL ENCLOSURE
ENGR ENGINEER
EOD EDGE OF DECK
EOJ EDGE OF JOIST
EOS EDGE OF SLAB
EQ EQUAL
EQPT EQUIPMENT
ES EACH SIDE
EW EACH WAY
EX EXISTING
EXP EXPANSION
EXT EXTERIOR
FAB FROM ADJACENT BEAM
FD FLOOR DRAIN
FDN FOUNDATION
FIN FINISH
FLG FLANGE
FLR FLOOR
FS FOOTING STEP
FT FEET
FTG FOOTING
FTGD FOOTING DRAIN
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GRND GROUND
GT GIRDER TRUSS
HAS, HS HEADED ANCHOR STUD
HK HOOK
HORIZ HORIZONTAL
HP HIGH POINT
HS HOLLOW STRUCTURAL SECTION
HT HIP TRUSS
HVAC HEATING, VENTILATION, AIR CONDITIONING
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
J/BRG JOIST BEARING
DESIGN DATA
THE BUILDING STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2021 INTERNATIONAL BUILDING CODE AND ASCE 7-22.
SEE LOAD MAPS FOR FLOOR LOADING CRITERIA.
SNOW LOAD DESIGN DATA
1. GROUND SNOW LOAD (PG) = 35 PSF
2. LOW-SLOPE ROOF SNOW LOAD (PF) = 30 PSF
3. SNOW EXPOSURE FACTOR (CE) = 1.0
4. THERMAL FACTOR (CT) = 1.0
5. SNOW LOAD IMPORTANCE FACTOR (IS) = 1.5
WIND LOAD DESIGN DATA
FOR BUILDING 1A
1. BASIC WIND SPEED (3-SECOND GUST) = 120 MPH
2. WIND EXPOSURE = C
3. WIND DESIGN PRESSURE (P) = VARIES WITH HEIGHT AND LOCATION
FOR BUILDING 7C AND 7E
1. WIND LOAD = 5 PSF
EARTHQUAKE DESIGN DATA
1. SHORT PERIOD SPECTRAL RESPONSE (SS) = 1.30
2. 1-SECOND SPECTRAL RESPONSE (S1) = 0.35
3. SEISMIC IMPORTANCE FACTOR (IE) = 1.50
4. RISK CATEGORY = IV
5. SEISMIC DESIGN CATEGORY = D
6. SITE CLASSIFICATION = D
7. SHORT PERIOD SPECTRAL RESPONSE COEFFICIENT (SDS) = 0.74
8. 1-SECOND SPECTRAL RESPONSE COEFFICIENT (SD1) = 0.47
9. ANALYSIS PROCEDURE UTILIZED = EQUIVALENT LATERAL FORCE PROCEDURE
SCALE: 1/8" = 1'-0"SI001
4 BUILDING 1A LEVEL 3, 4, & 5 LOAD MAP
SCALE: 1/8" = 1'-0"SI001
5 BUILDING 1A ROOF LOAD MAP
SCALE: 1/4" = 1'-0"SI001
6 BUILDING 7C AND 7E LEVEL 1 AND 2 LOAD MAP
SCALE: 1/4" = 1'-0"SI001
7 BUILDING 7C AND 7E ROOF LOAD MAP
A
NN
N
N
0' 8' 16'4' 0' 8' 16'4'
0' 8' 16'4' 0' 8' 16'4'
Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.S T
R U
C T
.2
.r v t
/1 /2
:4
:3
P
M
SI002
STRUCTURAL GENERAL NOTES VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 MAV ADK
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION OF
NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS, TIEDOWNS, ETC.
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING
DRAWINGS AND SPECIFICATIONS.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT. IF A DISCREPANCY OCCURS BETWEEN THE NOTES AND THE FULL SPECIFICATIONS, THE MORE STRINGENT
REQUIREMENT SHALL APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN ON THE DRAWINGS, SHALL BE MADE WITHOUT
THE APPROVAL OF THE STRUCTURAL ENGINEER.
CONTRACTOR TO COORDINATE ALL EQUIPMENT, ROOF DRAINS, CHASES, AND OTHER ITEMS CONNECTED TO THE STRUCTURE BEFORE
FABRICATION BEGINS.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE ANY CONCRETEOTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION, AND NAME AND LOCATION OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. FIBER REINFORCEMENT DOSAGE (WHEN USED), PRODUCT NAME AND MANUFACTURER NAME.
9. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
10. DESIGN SLUMP RANGE.
11. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
12. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN ACCORDANCE WITH "STANDARD DEVIATION"
DETERMINATION OUTLINED IN ACI 318.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO FABRICATE, ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER. DRAWINGS
SUBMITTED WITHOUT CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
SUBMIT ELECTRONIC VERSIONS OF SHOP DRAWINGS. SUBMIT SHOP DRAWINGS IN PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE REINFORCEMENT
2. CONCRETE MASONRY REINFORCEMENT
3. STRUCTURAL STEEL (INCLUDING DESIGN CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE
WHERE THE PROJECT IS CONSTRUCTED FOR ALL CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWINGS)
4. STEEL DECK
5. PRECAST CONCRETE COMPONENTS (PRECAST LINTELS, ARCHITECTURAL PRECAST)
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
MANUFACTURER'S TRADE NAMES AND NUMBERS USED HEREIN ARE ONLY TO IDENTIFY COLORS, FINISHES, TEXTURES, AND PATTERNS AS A BASIS OF DESIGN. PRODUCTS OF AUTHORIZED EQUAL MANUFACTURER'S EQUIVALENT TO COLORS, FINISHES, TEXTURES, AND PATTERNS OF MANUFACTURERS LISTED THAT MEET REQUIREMENTS OF TECHNICAL SPECIFICATIONS IN EVERY RESPECT MAY BE ACCEPTABLE WITH SUBMITTAL OF A COMPLETED SUBSTITUTION REQUEST CONTAINING ALL PRODUCT DATA, TESTING AND ACTUAL
SAMPLES, AND UPON APPROVAL IN WRITING BY CONTRACTING OFFICER.
SUBMIT ELECTRONIC VERSIONS OF PRODUCT DATA IN PDF FORMAT TO THE STRUCTURAL ENGINEER AND COR FOR REVIEW.
1. FIBER REINFORCEMENT FOR CONCRETE
2. CONCRETE REINFORCEMENT
3. DIAMOND PLATE DOWELS FOR SLABS ON GRADE
4. CONCRETE CURING COMPOUND
5. CONCRETE JOINT SEALANT
6. WATER STOPS
7. MASONRY JOINT REINFORCEMENT
8. EXPANSION ANCHORS
9. ADHESIVE ANCHORS
10. NON-SHRINK GROUT
11. COLD FORMED METAL STUDS (EXTERIOR ONLY)
FOUNDATIONS
FOUNDATIONS HAVE BEEN DESIGNED BASED ON ASSUMED ALLOWABLE CAPACITIES OF 1500 PSF. CONTRACTOR SHALL ENGAGE A LICENSED GEOTECHNICAL ENGINEER TO REVIEW THE SOIL CONDITIONS AT THE SITE AS NECESSARY TO CONFIRM THE ALLOWABLE CAPACITIES PRIOR TO PLACEMENT OF THE FOUNDATIONS. CONFIRMATION OF THE ACCEPTABILITY OF THE SOILS SHALL BE REPORTED
IN WRITING TO THE STRUCTURAL ENGINEER.
IF ACTUAL ALLOWABLE CAPACITIES ARE FOUND TO BE LESS THAN THE ASSUMED VALUES, THE CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL NOT PROCEED WITH FOUNDATION CONSTRUCTION WITHOUT REVIEW BY THE
STRUCTURAL ENGINEER.
THE CONTRACTOR MAY PROPOSE AN ALTERNATE EQUIVALENT DRIVEN PILE SYSTEM FOR REVIEW AND APPROVAL BY THE ENGINEER OF RECORD. NO DRIVEN PILE SYSTEM OTHER THAN THOSE SPECIFIED SHALL BE USED WITHOUT REVIEW AND APPROVAL BY THE
ENGINEER OF RECORD.
FOUNDATIONS AND SOILS RELATED WORK SHALL BE INSPECTED BY A LICENSED GEOTECHNICAL ENGINEER. WRITTEN FIELD REPORTS
SHALL BE FORWARDED TO THE STRUCTURAL ENGINEER AS SOON AS THEY BECOME AVAILABLE.
FOUNDATION CONDITIONS NOTED DURING CONSTRUCTION, WHICH DIFFER FROM THOSE DESCRIBED IN THE GEOTECHNICAL REPORT, SHALL BE REPORTED TO THE STRUCTURAL ENGINEER AND GEOTECHNICAL ENGINEER BEFORE FURTHER CONSTRUCTION IS
ATTEMPTED.
EXCAVATIONS FOR SPREAD FOOTINGS, COMBINED FOOTINGS, CONTINUOUS FOOTINGS AND MAT FOUNDATIONS SHALL BE CLEANED AND HAND TAMPED TO UNIFORM SURFACE AND SHALL BE PROTECTED AND MAINTAINED UNIFORM UNTIL CONCRETE IS PLACED.
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE (ACI 318) AND COMMENTARY (ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301). READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94. IN CASE OF A
DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I, UNO.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F. THE RATIO OF THE AMOUNT (BY WEIGHT) OF FLY ASH TO TOTAL
CEMENTITIOUS MATERIALS IN THE MIX SHALL NOT EXCEED 25 PERCENT.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE
WITH OTHER ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN 0.1 PERCENT CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF CONCRETE SHALL BE PERFORMED IN
ACCORDANCE WITH THE LATEST EDITION OF ACI 306R, COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF CONCRETE SHALL BE PERFORMED IN
ACCORDANCE WITH THE LATEST EDITION OF ACI 305R, HOT WEATHER CONCRETING.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON THE DRAWINGS SHALL BE SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL BE USED IN THE FOLLOWING AREAS AND SHALL
HAVE THE PROPERTIES AS SHOWN BELOW:
FOUNDATIONS
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD. (USE TYPE II SULFATE RESISTANT CEMENT)
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 1/2 INCHES
7. AIR CONTENT: N/A
SLABS ON GRADE
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD. (USE TYPE II SULFATE RESISTANT CEMENT)
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: 6% +/- 1%
8. HIGH RANGE WATER REDUCING ADMIXTURE AND FIBER REINFORCING REQUIRED
SLABS ON STEEL DECK
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: N/A
CONCRETE SLABS ON GRADE
SLABS ON GRADE SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE LATEST EDITION OF THE GUIDE FOR CONCRETE FLOOR AND
SLAB CONSTRUCTION (ACI 302.1R).
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX. DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO ASTM C309, UNLESS NOTED OTHERWISE. ALL SCUFFS OR ABRASIONS TO THE CURING MEMBRANE SHALL BE RECOATED DAILY. OTHER CURING METHODS MAY BE USED WITH APPROVAL BY THE STRUCTURAL ENGINEER.
SLABS ON GRADE SHALL BE PLACED TO ACHIEVE THE FOLLOWING MINIMUM TOLERANCES:
OVERALL VALUES: FF = 25
LOCAL VALUES: FF = 20
THE MINIMUM LOCAL AREA SHALL BE ANY BAY DEFINED BY COLUMN LINES.
UNLESS SHOWN OR NOTED OTHERWISE, PROVIDE CONTROL OR CONSTRUCTION JOINTS IN SLABS-ON-GRADE AT A MAXIMUM SPACING OF 36 TIMES THE SLAB THICKNESS. PROVIDE JOINTS AT ALL COLUMN LOCATIONS. LOCATE JOINTS TO ELIMINATE RE-ENTRANT CORNERS AND TO CREATE SQUARE OR RECTANGULAR SECTIONS WITH MAXIMUM LONG SIDE TO SHORT SIDE RATIO OF 1.5 TO 1.
CONTROL JOINTS IN SLABS ON GRADE SHALL NOT RECEIVE JOINT FILLER MATERIAL UNLESS NOTED OTHERWISE.
CONCRETE SLABS ON METAL DECK
UNLESS INDICATED OTHERWISE ON THE DRAWINGS, CONCRETE SLABS ON METAL DECK SHALL BE PLACED AS REQUIRED TO MAINTAIN
A CONSTANT SLAB [THICKNESS].
CONTRACTOR SHALL ALLOW FOR THE DEFLECTION OF THE FLOOR ASSEMBLY DUE TO THE WET WEIGHT OF THE CONCRETE WHEN CALCULATING CONCRETE QUANTITIES AND SHALL INCLUDE THE COST OF ALL REQUIRED SLAB-ON-DECK CONCRETE IN THE BID PRICE.
PRIOR TO PLACEMENT OF CONCRETE SLABS ON METAL DECK, THE CONTRACTOR SHALL CAREFULLY REVIEW THE ELEVATIONS OF THE STRUCTURAL STEEL FRAMING, INCLUDING CAMBERED MEMBERS, FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF ANY DISCREPANCIES (SUCH AS IMPROPER CAMBER, IMPROPER STEEL ELEVATIONS, ETC.) IMMEDIATELY AND SHALL NOT BEGIN CONCRETE PLACEMENT WITHOUT PRIOR REVIEW BY THE STRUCTURAL
ENGINEER.
ACTUAL CONCRETE SLAB THICKNESS SHALL NOT BE LESS THAN THE INDICATED NOMINAL THICKNESS AT ANY LOCATION. IF ANY CONDITION IS DISCOVERED THAT WOULD PREVENT PLACEMENT OF CONCRETE TO THE NOMINAL THICKNESS; CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL NOT PROCEED WITH CONCRETE PLACEMENT WITHOUT PRIOR REVIEW
BY THE STRUCTURAL ENGINEER.
SLABS ON METAL DECK SHALL RECEIVE A SMOOTH TROWEL FINISH, AND BE PLACED TO ACHIEVE THE FOLLOWING MINIMUM
TOLERANCES:
OVERALL VALUES: FF = 25
LOCAL VALUES: FF = 20
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX. DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO ASTM C309. ALL SCUFFS OR ABRASIONS TO THE CURING MEMBRANE SHALL BE RECOATED DAILY. OTHER
CURING METHODS MAY BE USED WITH APPROVAL BY THE STRUCTURAL ENGINEER.
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000
PSI.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE LATEST EDITION OF THE FOLLOWING STANDARDS:
ACI 301, ACI 315, ACI 318 AND ACI DETAILING MANUAL (SP66).
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE THE FOLLOWING MINIMUM CONCRETE COVER
OVER REINFORCEMENT AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3 INCHES
#6 BARS AND LARGER EXPOSED TO EARTH OR WEATHER: 2 INCHES
#5 BARS AND SMALLER EXPOSED TO EARTH OR WEATHER: 1-1/2 INCHES
BEAM AND COLUMN TIES, STIRRUPS AND SPIRALS: 1-1/2 INCHES
ELEVATED SLAB BARS NOT EXPOSED TO EARTH OR WEATHER: 3/4 INCH
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR
APPROVED BY THE STRUCTURAL ENGINEER.
WHERE LAP SPLICE LENGTHS ARE NOT SHOWN OR NOTED, PROVIDE A CLASS "B" LAP.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE STANDARD HOOKS, UNLESS NOTED OTHERWISE.
PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS AT CORNERS OF ALL WALLS AND GRADE BEAMS. LAP
SPLICE CORNER BARS WITH STRAIGHT BARS.
UNLESS OTHERWISE SHOWN OR NOTED, PROVIDE 2-#5 BARS (ONE EACH FACE) AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE BARS PARALLEL TO THE SIDES OF THE OPENING AND EXTEND 24" BEYOND CORNERS.
WELDED WIRE FABRIC
WELDED WIRE FABRIC SHALL BE SMOOTH WIRE FABRIC CONFORMING TO ASTM A185. FABRIC SHALL BE SUPPLIED IN FLAT SHEETS AND
LAPPED A MINIMUM OF ONE SPACE PLUS 2 INCHES.
WELDED WIRE FABRIC SHALL BE PLACED AS FOLLOWS, UNLESS NOTED OTHERWISE:
SLABS ON GRADE: 2 INCHES DOWN FROM TOP OF SLAB.
SLABS ON METAL DECK: 3/4 INCH DOWN FROM TOP OF SLAB.
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31 FOR EACH DAY'S POUR AND FOR EACH 100 CUBIC YARDS. EACH SET SHALL INCLUDE ONE SPECIMEN TESTED AT 7 DAYS, 2 SPECIMENS TESTED AT 28 DAYS AND ONE SPECIMEN RETAINED IN RESERVE TO BE TESTED AT THE DIRECTION OF THE STRUCTURAL ENGINEER. SPARE CYLINDER MAY BE DISCARDED 90 DAYS AFTER CASTING
UNLESS
DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER. THIS SET OF TEST CYLINDERS SHALL BE PROTECTED AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES DURING THE COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN ADDITIONAL SET OF CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED. THESE CYLINDERS SHALL BE STORED IMMEDIATELY ADJACENT TO, AND CURED UNDER THE SAME CONDITIONS AS THE BUILDING CONCRETE. SPECIAL
CURING BOXES ARE NOT PERMITTED FOR THESE TEST CYLINDERS.
FORWARD COPIES OF TEST RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER, READY-MIX SUPPLIER AND CONTRACTOR WITHIN 24
HOURS AFTER TESTING.
MASONRY
CONCRETE MASONRY HAS BEEN DESIGNED IN ACCORDANCE WITH THE LATEST EDITION OF THE BUILDING CODE REQUIREMENTS FOR
CONCRETE MASONRY STRUCTURES (ACI 530).
CONCRETE MASONRY SHALL CONSIST OF HOLLOW UNITS CONFORMING TO THE REQUIREMENTS OF ASTM C90, WITH A MINIMUM NET AREA COMPRESSIVE STRENGTH OF 1900 PSI. CONCRETE MASONRY ASSEMBLAGES SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH
(F'M) OF 2,000 PSI AT 28 DAYS.
MORTAR SHALL BE TYPE S PROPORTIONED IN ACCORDANCE WITH ASTM C270.
GROUT FOR REINFORCED MASONRY SHALL BE PROPORTIONED IN ACCORDANCE WITH ASTM C476. COARSE AND FINE AGGREGATES SHALL CONFORM TO ASTM C404. USE COARSE GROUT FOR ALL GROUTING EXCEPT HIGH-LIFT POURS DEFINED BY ACI 530, WHERE FINE
GROUT SHALL BE USED.
PROVIDE 9-GAUGE GALVANIZED STEEL WIRE JOINT REINFORCEMENT IN ALL MASONRY CONSTRUCTION. REINFORCEMENT SHALL BE CONTINUOUS AND BE LAPPED EIGHT INCHES AT SPLICES. CUT REINFORCEMENT AT ALL CONTROL AND EXPANSION JOINTS. SPACE REINFORCEMENT AT 8" ON CENTER FOR PARAPETS AND BELOW GROUND FLOOR ELEVATION. ELSEWHERE SPACE REINFORCEMENT AT
16 INCHES ON CENTER.
BEAMS AND LINTELS SHALL BEAR A MINIMUM OF 8 INCHES ONTO SUPPORTING MASONRY, UNLESS NOTED OTHERWISE. BEARING FOR ALL BEAMS, LINTELS, JOISTS, ETC. SHALL BE GROUTED SOLID A MINIMUM OF ONE COURSE (8 INCHES) BELOW BEARING ELEVATION, UNLESS NOTED OTHERWISE.
EXPANSION ANCHORS
EXPANSION ANCHORS SHALL BE CARBON STEEL ANCHORS AS MANUFACTURED BY HILTI FASTENING SYSTEMS OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER AND SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
EXPANSION ANCHORS SHALL NOT BE INSTALLED IN CONCRETE UNTIL IT HAS ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE
STRENGTH.
ADHESIVE ANCHORS
ADHESIVE ANCHORS SHALL BE HILTI "HIT HY200" FOR SOLID SUBSTRATE AND HILTI "HIT HY270" FOR HOLLOW SUBSTRATE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNLESS NOTED OTHERWISE ON PLANS. ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS BY INSTALLERS TRAINED BY THE MANUFACTURER'S
REPRESENTATIVE.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 BOLT DIAMETERS UNLESS NOTED OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED, NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING COMPOUNDS. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF
5,000 PSI IN 28 DAYS.
WATERSTOPS
SELF-EXPANDING STRIP WATER STOPS SHALL BE VOLCLAY WATERSTOP-RX 101 UNLESS NOTED OTHERWISE. INSTALL IN ACCORDANCE
WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.
PVC WATERSTOPS
PROVIDE FACTORY MADE WATERSTOP FABRICATIONS FOR ALL CHANGES OF DIRECTION, INTERSECTIONS, AND TRANSITIONS LEAVING
ONLY STRAIGHT BUTT JOINT SPLICES FOR THE FIELD.
PROVIDE HOG RINGS OR GROMMETS SPACED AT 12 INCHES ON CENTER ALONG LENGTH OF WATERSTOP.
PROVIDE TEFLON COATED THERMOSTATICALLY CONTROLLED WATERSTOP SPLICING IRONS FOR FIELD BUTT SPLICES.
FIELD BUTT SPLICES SHALL BE HEAT FUSED WELDED USING A TEFLON COATED THERMOSTATICALLY CONTROLLED WATERSTOP SPLICING IRON AT APPROXIMATELY 380 DEGREES F. FOLLOW APPROVED MANUFACTURER RECOMMENDATIONS.
LAPPING OF WATERSTOP, USE OF ADHESIVES, OR SOLVENTS SHALL NOT BE ALLOWED.
CENTER WATERSTOP IN JOINT AND SECURE WATERSTOP IN CORRECT POSITION USING HOG RINGS OR GROMMETS SPACED AT 12 INCHES ON CENTER ALONG THE LENGTH OF THE WATERSTOP AND WIRE TIE TO ADJACENT REINFORCING STEEL.
MASTIC COATING
MASTIC COATING FOR PROTECTION OF INDICATED ITEMS SHALL BE BITUMASTIC 50 COAL TAR MASTIC BY CARBOLINE OR EQUIVALENT SUBSTITUTE APPROVED BY THESTRUCTURAL ENGINEER. INSTALL AT LOCATIONS INDICATED ON DRAWINGS.
UNLESS NOTED OTHERWISE, APPLY MASTIC TO A COATING THICKNESS OF 18 MILS. PROVIDE FULL COVERAGE OVER ITEMS INDICATED
TO RECEIVE COATING.
STRUCTURAL STEEL
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST EDITION WITH AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES, LATEST EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992, 50 KSI.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE SHAPES SHALL CONFORM TO ASTM A36, UNLESS NOTED
OTHERWISE.
STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE C.
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED OTHERWISE.
STEEL STUDS SHALL CONFORM TO ASTM A108.
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, APPROVED BY THE RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION. BOLTED CONNECTIONS FOR STRUCTURAL STEEL MEMBERS SHALL BE MADE WITH 3/4" DIAMETER A325 BOLTS, UNLESS NOTED OTHERWISE.
BOLTED CONNECTIONS SHALL BE TIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED CONNECTIONS IN BRACE ELEMENTS
ARE TO BE FULLY PRETENSIONED WITH CLASS A FAYING SURFACES.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN WELDING SOCIETY'S STRUCTURAL WELDING
CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992 STEEL AS A BASE METAL SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES.
UNLESS OTHERWISE SHOWN OR NOTED ON THE DRAWINGS, OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD E70XX
ELECTRODES.
STRUCTURAL STEEL THAT RECEIVES FINISH PAINT SHALL BE SHOP-PRIMED WITH A RUST-INHIBITING PRIMER, UNLESS NOTED OTHERWISE ON THE DRAWINGS. CONTRACTOR SHALL VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT SYSTEM SPECIFIED BY THE
ARCHITECT. COORDINATE FINISH PAINTING REQUIREMENTS WITH THE ARCHITECT.
STRUCTURAL STEEL THAT IS NOT EXPOSED IN THE FINISHED CONSTRUCTION AND DOES NOT RECEIVE FINISH PAINT SHALL NOT BE
SHOP-PRIMED, UNLESS NOTED OTHERWISE ON THE DRAWINGS.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN CONFORMANCE WITH ASTM A123.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE BOLTED SLIP-CRITICAL CONNECTIONS.
3. SURFACES TO RECEIVE SHEAR STUD CONNECTIONS.
4. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN ARCHITECTURAL FINISH COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE. FOR PAINTED STEEL, USE A PRIMER EQUIVALENT TO THE SHOP PAINT. FOR GALVANIZED STEEL, USE
A ZINC-RICH COLD-GALVANIZING PAINT.
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD SPECIFICATION AND MANUAL OF STEEL CONSTRUCTION. UNLESS NOTED OTHERWISE ON THE DRAWINGS, DESIGN BEAM CONNECTIONS NOT SHOWN, TO SUPPORT A MINIMUM OF A 10 KIP SHEAR REACTION. PROVIDE NO LESS THAN 2 BOLTS IN ANY SINGLE LINE OF BOLTS, UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
PROVIDE L4X4X1/4 FRAMED OPENINGS FOR ALL ROOF PENETRATIONS 12 INCHES OR LARGER ALONG ANY SIDE, UNLESS LARGER FRAMING IS INDICATED. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR PENETRATIONS. COORDINATE FRAMED OPENING SIZES
AND LOCATIONS WITH THE MECHANICAL AND PLUMBING CONTRACTORS.
GALVANIZE ALL EXPOSED STEEL.
STEEL ROOF DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE STEEL DECK INSTITUTE'S SPECIFICATIONS AND
CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL ROOF DECK ACCESSORIES, INCLUDING CLOSURES, SUPPLEMENTARY FRAMING, AND SUMP
PANS, WHETHER OR NOT SUCH ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN ROOF DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS. PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
ROOF DECK SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION.
PROVIDE STEEL ROOF DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
STEEL FLOOR DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE STEEL DECK INSTITUTE'S SPECIFICATIONS AND
CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL FLOOR DECK ACCESSORIES, SUCH AS EDGE FORMS, CLOSURES, FILLERS AND POUR STOPS FOR A COMPLETE INSTALLATION, WHETHER OR NOT SUCH ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN FLOOR DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS. PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
STEEL FLOOR DECK IS INTENDED TO BE INSTALLED IN AN UNSHORED CONDITION UNLESS NOTED OTHERWISE. DECK SUPPLIER SHALL REVIEW ALL SPAN CONDITIONS AND CONFIRM THAT THE SUPPLIED PRODUCT IS SUFFICIENT TO SAFELY SUPPORT THE WET WEIGHT OF
CONCRETE AND ASSOCIATED CONSTRUCTION LIVE LOADS WITHOUT THE NEED FOR SHORING.
FLOOR DECK UNITS SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION.
PROVIDE INTERIOR STEEL FLOOR DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
PROVIDE FLOOR DECK SUPPORTING EXTERIOR SLABS WITH A GALVANIZED FINISH IN ACCORDANCE WITH ASTM A924 G90.
RENOVATION (EXISTING CONDITIONS)
INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE DRAWINGS WAS TAKEN FROM DRAWINGS THAT WERE PREPARED FOR THE WAR DEPARTMENT, ENTITLED SEISMIC MODERNIZATION - PHASE ONE, DATED JUNE 23, 1995, AND 120 BED S.C.I UNIT, DATED 4-1-83.
WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS PERFORMED IN ACCORDANCE WITH THE ABOVE INDICATED ORIGINAL DRAWINGS INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES, MATERIALS, DETAILS, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO
NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS.
WHERE NEW WORK IS TO BE FITTED TO OLD WORK, THE CONTRACTOR SHALL CHECK ALL DIMENSIONS AND CONDITIONS IN THE FIELD, AND REPORT ANY ERRORS OR DISCREPANCIES TO THE STRUCTURAL ENGINEER PRIOR TO THE FABRICATION AND ERECTION OF ANY
NEW MEMBERS.
EXISTING MATERIALS TO BE REMOVED AND REINSTALLED AS PART OF THE PROJECT, THAT BECOME DAMAGED, SHALL BE REPLACED
WITH NEW MATERIAL OF EQUAL QUALITY AND APPEARANCE, AT THE CONTRACTORS EXPENSE.
ALL WORK SHALL BE PREFORMED WITHOUT DAMAGE TO ADJACENT RETAINED WORK. ADJACENT EXISTING CONSTRUCTION SHALL BE
PROTECTED FROM DUST, DIRT, AND DEBRIS ACCUMULATION AT ALL TIMES.
B1A-M
B1A-L B1A-K.9
B1A-K.1 B1A-K
B1A-J.9
B1A-J.1 B1A-J
B1A-H.9
B1A-H.2 B1A-H
B1A-G.9
B1A-H.3
B1A-G3
B1A-G2 B1A-G
B1A-F
B1A-E
B1A-E.8
B1A-E.9
B1A-D.9
B1A-E.2
B1A-D B1A-C.9
B1A-D.2
B1A-C B1A-B.9
B1A-C.2
B1A-A
B1A-B B1A-B.2
B1A-1B1A-1.1 B1A-2 B1A-3 B1A-4 B1A-4.8 B1A-5B1A-5.1 B1A-6 B1A-7 B1A-7.9B1A-8 B1A-9 B1A-9.5 B1A-10 B1A-11 B1A-12B1A-11.5
M
L
K
J
H
G
N
P P1P2
P4 P5
Q
R
S
T
B1A-6B1A-7
B1A-G
B1A-G.5
B1A-H
B1A-F
B1A-5 B1A-8
SF103
SF103
SF103
LEVEL 2 FRAMING PLAN
LEVEL 3-5 FRAMING PLAN
LEVEL 6 FRAMING PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
AW
BW
CW CE
BE
AE
7C
7D 7E
7B
7A
GF
E D
J
5A
5BE
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
5BW
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.S T
R U
C T
.2
.r v t
/1 /2
:4
:2
P
M
B01A-SF100
BUILDING 1A OVERALL FLOOR
PLAN
VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
1A
10/11/2023 MAV ADK
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/16" = 1'-0"B01A-SF100
1 BUILDING 1A OVERALL PLAN
0' 20' 40' 80'
N
B7-5
B7-6
B7-7 B7-8 B7-9 B7-10 B7-11 B7-12 B7-13 B7-14B7-15 B7-16 B7-17B7-18 B7-19 B7-20 B7-21 B7-22 B7-23 B7-24
B7-A
B7-C
B7-D
B7-E B7-F
B7-G
B7-I
B7-K
B7-M
B7-P B7-Q
B7-R
B7-S
B7-X
B7-Y
B7-V
B7-AA
B7-CC
B7-DD
B7-EE
B7-FF
B7-25 B7-26 B7-27
B7 -N
B7 -L
B7 -J
B7 -H
B7 -E.1
B7 -C.1
B7 - 27.1 B7 - 27.9B7 - 28 B7 - 28.8B7 - 29 B7 - 29.9B7 - 30
B7-12
B7-R
B7-19
B7-Q
SF103
SF103
SF103
FOUNDATION PLAN
LEVEL 1 AND 2 FRAMING PLAN
LEVEL 3 FRAMING PLAN
SF103
SF103
SF103
FOUNDATION PLAN
LEVEL 1 AND 2 FRAMING PLAN
LEVEL 3 FRAMING PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
AW
BW
CW CE
BE
AE
7C
7D 7E
7B
7A
GF
E D
J
5A
5BE
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
5BW
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.S T
R U
C T
.2
.r v t
/1 /2
:4
:2
P
M
B07-SF101
BUILDING 7 OVERALL FLOOR PLAN VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 MAV ADK
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/16" = 1'-0"B07-SF101
1 BUILDING 7 OVERALL PLAN
N
0' 20' 40' 80'
B7-1
B7-2 B7-3 B7-4
B7-Q
B7-R
B7-U
B1A-M
B1A-L B1A-K.9
B1A-K.1 B1A-K
B1A-J.9
B1A-J.1 B1A-J
B1A-H.9
B1A-H.2 B1A-H
B1A-G.9
B1A-H.3
B1A-G3
B1A-G2 B1A-G
B1A-F
B1A-E
B1A-E.8
B1A-E.9
B1A-D.9
B1A-E.2
B1A-D B1A-C.9
B1A-D.2
B1A-C B1A-B.9
B1A-C.2
B1A-A
B1A-B B1A-B.2
B1A-9.5 B1A-10 B1A-11 B1A-12B1A-11.5
M
L
K
J
H
G
F
N
P P1P2
P4 P5
Q
R
S
T
U
U.7
V
18.818.417.517.116.215.915.31514.914
17 18 19
13121110
14.113.112.811.911.110.69.89.2 9.79.3
8.37.97.16. 25 .84.94.13.62.71.91.30.70.3
G
P
P5
SF104
SF104
SF104
LEVEL 2 FRAMING PLAN
LEVEL 1 FRAMING PLAN
GROUND LEVEL, LEVEL 1 AND 2 FRAMING PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
AW
BW
CW CE
BE
AE
7C
7D 7E
7B
7A
GF
E D
J
5A
5BE
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
5BW
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.S T
R U
C T
.2
.r v t
/1 /2
:4
:2
P
M
B01-SF102
BUILDING 1 OVERALL FLOOR PLAN VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
10/11/2023 MAV ADK
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/16" = 1'-0"B01-SF102
1 BUILDING 1 OVERALL PLAN
0' 20' 40' 80'
N
B1A-6 B1A-7
B1A-G
B1A-G.5
B1A-H
B1A-F
B1A-5 B1A-8
NEW W10X26 COLUMN
EXISTING BEAMS, TYP
25' - 7" 10' - 0" 25' - 7"
61' - 2"
/2
/2
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING 3 1/4" CONCRETE ON 2" METAL DECK NOT SHOWN FOR CLARITY.
3. EXISTING LEVEL 2 FINISH ELEVATION IS ASSUMED 277.67'
SF502
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
EX. W18X106
EX. W18X106
EX. W12X19
SF502
Sim
B1A-6 B1A-7
B1A-G
SF502
B1A-G.5
/2
W16X31
W
X
W
X
W
X
SF502
B1A-H
B1A-F
B1A-5 B1A-8
25' - 7" 10' - 0" 25' - 7"
EXISTING COLUMN, TYP
EXISTING SLAB
SF502
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING LEVEL 3 FINISH ELEVATION IS ASSUMED 291.33'. LEVEL 4 = 305.83', AND LEVEL 5 = 320.33' .
3. T/STEEL AS FOLLOWS, LEVEL 3 = 290.89', LEVEL 4= 305.39', LEVEL 5 = 319.89'
4. NEW SLAB TO MATCH THE THICKNESS AND FINISH LEVEL OF THE EXISTING SLAB.
SF502
1'
3 1/8" 3 1/8"
F V
1'
/2
NEW W10X26 COLUMN
NEW W10X26 COLUMN
EODEOD
E O
D
B1A-6 B1A-7
B1A-G
B1A-G.5 W16X31
W
X
W
X
W
X
/2
B1A-H
B1A-F
B1A-5 B1A-8
25' - 7" 10' - 0" 25' - 7"
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING LEVEL 6 FINISH ELEVATION IS ASSUMED 336.33'.
3. T/STEEL = 335.89'
4. NEW SLAB TO MATCH THE THICKNESS AND FINISH LEVEL OF THE EXISTING SLAB.
SF502
SIM
SF502
SIM
SF502
SF502
SIM
SIM
1'
F V
1'
/2 " 3 1/8"
3 1/8"
NEW W10X26 COLUMN
NEW W10X26 COLUMN
EOD
EOD
E O
D
B7-12
B7-R
11' - 10"
4" GAP
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING GROUND FLOOR FINISH ELEVATION IS ASSUMED 249'-0" AND PILE CAP ELEVATION IS
ASSUMED 240'-8".
3. EXISTING STRUCTURAL CONCRETE JOISTS NOT SHOWN FOR CLARITY.
SF501
M W
SF502
MW10
M W
SF502
SIM
WALL FOOTING
1"
4" G
A P
SF502
B7-12
B7-R
11' - 10" 4"
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING LEVEL 1 FINISH ELEVATION IS ASSUMED 264'-0" AND LEVEL 2 ELEVATION IS ASSUMED 277'-8".
3. T/STEEL FOR LEVEL 1 = 263'-6 3/4", T/STEEL FOR LEVEL 2 = 277'-2 3/4".
W12X14
W12X14
(2
E Q
S P
A C
IN
G
W12X14
1'
EXISTING CMU WALL
M W
M W
MW10
SF501
SF501
SF502
SIM
SIM
SIM
1'
1"
4" G
A P
B7-12
B7-R
SF502
11' - 10"
11' - 10"
4" GAP
W12X14
W12X14
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING LEVEL 3 FINISH ELEVATION IS ASSUMED 291'-4".
3. T/STEEL = 291'-2 1/2" = T/WALL
(2
E Q
S P
A C
IN
G
M W
MW10
M W
1'
W12X14
SF501
SF501
SF502
SIM
SIM
1"
4" G
A P
1'
B7-19
B7-Q
4" GAP
11' - 10"
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING GROUND FLOOR FINISH ELEVATION IS ASSUMED 249'-0" AND TOP OF FOUNDATION
ELEVATION IS ASSUMED 240'-8".
3. EXISTING STRUCTURAL CONCRETE JOISTS NOT SHOWN FOR CLARITY.
1"
SF501
MW10
M W
M W
SF502
SF502
SIM
SIM
WALL FOOTING
4" G
A P
B7-19
B7-Q
W12X14
W12X14
SF502
4" GAP
11' - 10"
1"
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING LEVEL 1 FINISH ELEVATION IS ASSUMED 264'-0" AND LEVEL 2 FINISH ELEVATION IS ASSUMED
277'-8".
3. T/STEEL FOR LEVEL 1 = 263'-6 3/4", T/STEEL FOR LEVEL 2 = 277'-2 3/4".
(2
E Q
S P
A C
IN
G
1'
W12X14
MW10
M W
M W
SF501
SF502
SF501
4" G
A P
1'
B7-19
B7-Q
SF502
W12X14
W12X14
11' - 10"
1"
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING LEVEL 3 FINISH ELEVATION IS ASSUMED 291'-4".
3. T/STEEL = 291'-2 1/2" = T/WALL
4" GAP
(2
E Q
S P
A C
IN
G
1'
W12X14
M W
MW10
M W
SF502
SF501
SIM
SF501
SIM
SIM
4" G
A P
1'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.S T
R U
C T
.2
.r v t
/1 /2
:4
:2
P
M
SF103
ENLARGED PLANS VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
VARIES
10/11/2023 MAV ADK
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"SF103
1 BUILDING 1A LEVEL 2 FRAMING PLAN
SCALE: 1/8" = 1'-0"SF103
2 BUILDING 1A LEVEL 3, 4, & 5 FRAMING PLAN
SCALE: 1/8" = 1'-0"SF103
3 BUILDING 1A LEVEL 6 (ROOF) FRAMING PLAN
SCALE: 1/4" = 1'-0"SF103
4 BUILDING 7C FOUNDATION PLAN
SCALE: 1/4" = 1'-0"SF103
5 BUILDING 7C LEVEL 1 AND 2 FRAMING PLAN
SCALE: 1/4" = 1'-0"SF103
6 BUILDING 7C LEVEL 3 (ROOF) FRAMING PLAN
SCALE: 1/4" = 1'-0"SF103
7 BUILDING 7E FOUNDATION PLAN
SCALE: 1/4" = 1'-0"SF103
8 BUILDING 7E LEVEL 1 AND 2 FRAMING PLAN
SCALE: 1/4" = 1'-0"SF103
9 BUILDING 7E LEVEL 3 (ROOF) FRAMING PLAN
NNN
NNN
NNN
0' 4' 8' 12'2' 0' 4' 8' 12'2' 0' 4' 8' 12'2'
0' 4' 8' 12'2'0' 4' 8' 12'2'0' 4' 8' 12'2'
0' 4' 8' 12'2' 0' 4' 8' 12'2' 0' 4' 8' 12'2'
EXISTING WALL
SIM
SIM
SIM
G
EXISTING WALL
8'
/4
8' - 10"
9'
SF501
1'
1'
E Q
E Q
W12X19
W12X19
W12X19
SF502
M W
SF502
FV
F V
SF501
SIM
SIM
P4
P5
SF502
5'
4' - 0 3/4"7' - 0"
SF502
Sim
FV
F V
FV
SF502
SF502
SF502
Sim
Sim
COORDINATE DEMO OF EXISTING
WALL WITH ARCH DEMO PLANS
P4
P5
SF502
7' - 0" 4' - 0 3/4"
COORDINATE DEMO OF EXISTING
WALL WITH ARCH DEMO PLANS
SF502
SIM
5'
FV
F V
FV
SF502
SF502
SIM
SIM
SF502 SIM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22122
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 22.3101
35% SCHEMATIC DESIGN 10/31/2022
65% DESIGN DEVELOPMENT 05/03/2023
95% CONSTRUCTION DOCUMENTS 08/16/2023
100% FINAL BID DOCUMENTS 09/27/2023
100% FINAL STAMPED BID DOCUMENTS 10/11/2023
B
IM
/2
.3
V
A M e m p h is E
H R
M I n fr a s tr u c tu re /6
-7
.S T
R U
C T
.2
.r v t
/1 /2
:4
:3
P
M
SF104
ENLARGED PLANS VA Memphis EHRM Infrastructure
MEMPHIS, TN
614-22-700
VARIES
10/11/2023
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/4" = 1'-0"SF104
1 ELEVATOR GROUND LEVEL, LEVEL 2 AND 3 FRAMING PLAN
SCALE: 1/2" = 1'-0"SF104
2 BUILDING 1 LEVEL 1 FRAMING PLAN
SCALE: 1/2" = 1'-0"SF104
3 BUILDING 1 LEVEL 2 FRAMING PLAN
N
N N
0' 4' 8' 12'2'
0' 4' 8' 12'2' 0' 4' 8' 12'2'
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING LEVEL 1 FINISH ELEVATION IS ASSUMED 264'-0" .
3. T/STEEL = 263' - 6 3/4"
4. SDL = 10 PSF, LL = 100 PSF
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING LEVEL 2 FINISH ELEVATION IS ASSUMED 277'-8" .
3. T/STEEL = 277' - 2 3/4"
4. SDL = 10 PSF, LL = 100 PSF
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS RELATED TO THE EXISTING STRUCTURE.
2. EXISTING GROUND LEVEL FINISH ELEVATION IS ASSUMED 249'-0" LEVEL 2 FINISH ELEVATION IS
ASSUMED 277'-8" AND LEVEL 3 FINISH ELEVATION IS ASSUMED 291'-4".
3. T/STEEL FOR GROUND LEVEL = 248' - 6 3/4", FOR LEVEL 2 = 277' - 2 3/4", FOR LEVEL 3 = 290' - 10 3/4".
4. SDL = 10 PSF, LL = 100 PSF
VERTICAL REINF. CONTIN.
THRU BOND BEAM
CORES FILLED SOLID
WITH GROUT
SEE SCHED.
OPEN CORE CMU BOND BEAM
W/ WEB KNOCKOUTS OR CUT
FROM STANDARD UNITS
3 1/2"
NOTE: USE OPEN CORE
BOND BEAMS, TYPICAL
EXCEPT FOR LINTELS &
OTHER CONDITIONS WHERE
BOTTOM OF UNITS WILL BE
EXPOSED
VERTICAL REINF. CONTIN.
THRU BOND BEAM
CORES FILLED SOLID
WITH GROUT
SEE SCHED.
CMU BOND BEAM UNITS2 "
SCHEDULE
REINF.SIZE
6"
8"
10"
12"
(1) #5
(2) #5
(2) #5
(2) #5
MIN. 6" EMBEDMENT MIN. 36 DIA. LAP
STEP NEW FOOTING AS
REQUIRED TO PREVENT
UNDERMINING EX. FOOTING OR
BEARING ON PREVIOUS BACKFILL.
ROUGHEN EXISTING SURFACE
PRIOR TO NEW CONCRETE
PLACEMENT
#5 DOWELS IN SAME NO. AS FOOTING
REINF. EPOXY DOWEL TO EX.
FOOTING REF. SPECIFIC SECTIONS &
WALL FOOTING SCHEDULE
EX. FOUNDATION WALL &
FOOTING REF. PLAN FOR
APPROX. T/FTG. ELEV.
SEE PLAN
MASONRY WALL PER PLAN AND SCHEDULE
6' MIN.
5" M
IN
T/FOOTING
PER PLAN
NEW MASONRY WALL FOOTING
(9) #6 CONTINOUS
LONGITUDINAL BARS
#5 TRANSVERSE BARS @ 9" OC
MIN
1' - 0"
2' - 0"
ADDITIONAL #5 Z-BARS @ 9" OC
SEE PLAN & SECTIONS FOR VERTICAL
REINFORCING SIZE & SPACING. LAP
BARS 48 DIA. AT SPLICES
BLOCK CORES W/ REINF. STEEL
TO BE FILLED WITH GROUT THE
FULL HEIGHT OF WALL
LADDER-TYPE HORIZONTAL
JOINT REINF. @ 16" O.C.
VERTICALLY (DISCONTINUOUS
AT CONTROL JOINTS)
CMU SASH BLOCK W/ CRUCIFORM RUBBER
OR PVC CONTROL JOINT, SEE
SPECIFICATIONS. SEE ARCHITECTURAL
DRAWINGS FOR CONTROL JOINT LOCATIONS
CONCRETE
FOOTING
FULLY BED MORTAR JOINTS
AT STARTER COURSE OFF
FOOTINGS WHERE CELLS
ARE NOT GROUTED
REDUCE SPA. TO 8" BELOW
GRADE & AT PARAPETS
ELEVATION
PLAN
1'-6"1'-6"
LADDER-TYPE HORIZONTAL
JOINT REINF.
VERTICAL WALL REINF.
PER PLAN & SECTIONS
CMU SASH UNITS W/
CRUCIFORM CONTROL JOINT
INSERT, SEE SPECS.
BOND BEAM REINFORCING TO BE
CONTINUOUS THRU CONTROL JOINT
(COAT W/ MASTIC FOR BOND BREAK)
NOTE:
1. BOND BEAM REINFORCEMENT
SHALL NOT BE LAPPED WITHIN
8'-0" OF CONTROL JOINT.
2. HORIZ. JOINT REINFORCEMENT TO BE
DISCONTINUOUS AT CONTROL JOINTS.
CORNER BARS TO MATCH
NO. & SIZE OF CONTIN.
BOND BEAM REINFORCING
CMU BOND BEAM -
THICKNESS VARIES
CONTINUOUS REINFORCING
CONTINUOUS REINFORCING
PROVIDE PRE-FABRICATED "L'S" AND "T'S" AT
CORNERS OF HORIZONTAL JOINT REINF.
CORNER BARS TO MATCH
NO. & SIZE OF CONTIN.
BOND BEAM REINFORCING
CMU BOND BEAM -
THICKNESS VARIES
NOT AT CONTROL JOINT AT CONTROL JOINT
JAMB BAR - FULL HT.
BOND BEAM LINTEL
PER PLAN & SCHEDULE
MASONRY OPENING
PER ARCH. PLANS
8" MIN.
BEARING
OFFSET & LAP JAMB
BAR 48 DIA. AT
CONTROL JT.
2 LAYERS OF FLASHING
AT BEARING
MASONRY OPENING
PER ARCH. PLANS
8" MIN.
BEARING
CMU CONTROL JOINT-SEE
ARCH. DWGS. FOR LOC'N.
COAT THIS PORTION OF
BARS w/ GREASE TO
PREVENT BOND
3. MECHANICALLY FASTEN SIDELAPS @ 36" O.C. MAX. w/ #10 TEK SCREWS.
1. 2", 22 GA. GALVANIZED COMPOSITE STEEL FLOOR DECK.
4. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. WELD DECK TO SUPPORTING STRUCTURE USING 3/4" DIAMETER WELDS.
NOTE:
36" COVER
5. SIDELAPS MAY BE NESTING, OR INTERLOCKING AT CONTRACTOR'S OPTION.
36/4 PATTERN w/ SIDELAP
FASTENERS @ 36" O.C. MAX.
S
LA
B 't
' V A
R
IE
S
R E
F.
P
LA
N S
S
C H
E D
U
LE
36" COVER
36/7 PATTERN W/ SIDELAP
FASTENERS @ 18" O.C. MAX.
36/4 PATTERN W/ SIDELAP
FASTENERS @ 18" O.C. MAX.
TYPICAL U.N.O.
HIGH ROOFS ABOVE +25'-0"
NOTE:
1. 1 1/2", 20 GA. GALVANIZED WIDE RIB STEEL ROOF DECK. CLEAN, TREAT AND PRIME.
2. USE #10 TEK SCREW SIDELAP FASTENERS, U.N.O.
3. MECHANICAL FASTENERS SHALL BE USED IN LIEU OF WELDS.
4. USE THE FOLLOWING HILTI POWER ACTUATED FASTENERS:
X-HSN 24 FOR OPEN-WEB STEEL JOISTS & STRUCTURAL STEEL 1/8" ≤ 't' ≤ 3/8" X-ENP-19 L15 FOR HEAVY OPEN-WEB STEEL JOISTS & STRUCTURAL STEEL 't' ≥ 1/4"
S-SLC 01 M HWH SIDELAP FASTENERS
ACCEPTABLE ALTERNATE: PNEUTEK AIR/SAFE…
This is the start of the file's text. The full file is on GovTribe.