Dead Leg Criteria Checklist.pdf

PDF 19 MB Posted

Attached to
Z1DA--667-18-119, Upgrade Water Distribution System, Main Hospital
Solicitation number
36C25622R0067
Issued by

About this file

This solicitation posting is for the upgrade of the water distribution system at the main hospital for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16. The solicitation number is 36C25622R0067 and is for project 667-19-101. Interested parties are sought to provide upgrades to the existing water distribution system at the main hospital to improve water delivery and quality of service. The deadline to respond is not specified in the document provided. Details on pricing, terms, set asides or incumbent contractors are not included.

View the file

Other files

File Type Posted
36C25622R0067 0003.pdf PDF
RFIs 36C25622R0067 sheet 1 - OBVA Answered.docx DOCX document
RFIs 36C25622R0067 sheet 2 - OBVA Answered.docx DOCX document
36C25622R0067 0002.pdf PDF
S04 Construction Site Visit 667-18-119.pdf PDF
Water Distrib - Resubmission - Plumbing New Work Dwgs 2.pdf PDF
36C25622R0067 0001.pdf PDF
Water Distrib - Resubmission - Asbestos Dwgs.pdf PDF
Water Distrib - Resubmission - Plumbing New Work Dwgs 4.pdf PDF
Water Distrib - Resubmission - Plumbing Dwgs 2.pdf PDF
Water Distrib - Resubmission - Plumbing New Work Dwgs 3.pdf PDF
Water Distrib - Resubmission - Plumbing As-Built Riser Diagram Dwgs.pdf PDF
Water Distrib - Resubmission - Plumbing New Work Dwgs 1.pdf PDF
Water Distrib - Resubmission - Plumbing Dwgs 3.pdf PDF
Water Distrib - Resubmission - Plumbing Dwgs 1.pdf PDF
Water Distribution ICRA FINAL.pdf PDF
Water Distrib - Resubmission - ICRA Dwgs 2.pdf PDF
WD - LA20220031 MOD 3 DATED 6-24-2022.txt TXT text file
36C25622R0067 EXHIBIT B R1.docx DOCX document
36C25622R0067 EXHIBIT E R1.docx DOCX document
Water Distrib - Resubmission - Civil Dwgs.pdf PDF
VHA Supplemental Contract Requirements for Ensuring Adequate COVID-19 Safety Protocols for Federal Contractors.docx DOCX document
36C25622R0067 EXHIBIT C R1.docx DOCX document
36C25622R0067 EXHIBIT D R1.docx DOCX document
Water Distrib - Resubmission - General Dwgs.pdf PDF
Water Distrib - Resubmission - Electrical Dwgs.pdf PDF
Water Distribution System Class I Precautions FINAL.pdf PDF
P09 Rev 7-1-22 667-18-111 Combinded Specifications.pdf PDF
P09 Construction REVISED SOW - 667-18-119.doc DOC document
36C25622R0067 EXHIBIT A R1.docx DOCX document
Water Distribution Class III Precaution FINAL.pdf PDF
Water Distribution System Preliminary Class 11 FINAL.pdf PDF
Water Distrib - Resubmission - ICRA Dwgs 1.pdf PDF
Cross Connection Sheets.pdf PDF
36C25622R0067 EXHIBIT F R1.docx DOCX document
36C25622R0067 Solicitation.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Overton Brooks VAMC Upgrade Water Distribution System

To Improve Legionella Prevention, Cooling Towers & Storage Tanks

1-SUB-4-001-A

Sub-Basement

Center of room

N/A

Cu

8"

1"

CW

A

Plug

None

Ball

N/A

Class I

1/PL-105

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

7881-7883

©Northeast Infrastructure, LLC 2021

Cooling Towers & Storage Tanks

1-SUB-4-002-A

Sub-Basement

Center of room

N/A

Cu

18"

3"

CW

A

Closed Valve

None

Gate

N/A

Class I

1/PL-105

03/20/2019

Picture of Dead Leg

7884-78877

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Cooling Towers & Storage Tanks

1-SUB-4-003-A

Sub-Basement

Center of room

N/A

Cu

8"

3/4"

CW

A

Plug

None

Ball

N/A

Class I

1/PL-105

03/20/2019

Picture of Dead Leg

7888-90

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-004-A

Sub-Basement

Center of room

N/A

Cu

21"

3/4"

CW

A

Closed Valve

None

Gate

N/A

Class I

1/PL-106

03/20/2019

Picture of Dead Leg

7891-7894

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-005-A

Sub-Basement

Center of room

N/A

Cu

54"

4"

CW

B

Spigot

None

Gate

N/A

Class I

1/PL-106

03/20/2019

Picture of Dead Leg

7895-7897

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-006-A

Sub-Basement

Center of room

N/A

Cu

11"

1 1/2"

HW

A

Cap

None

Ball

11"

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7898-7902

Cooling Towers & Storage Tanks

1-SUB-4-007-A

Sub-Basement

Center of room

N/A

Cu

20"

4"

HW

A

Cap

None

None

None

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7903-7910

Cooling Towers & Storage Tanks

1-SUB-4-008-A

Sub-Basement

Center of room

N/A

Cu

36"

6"

HW

A

Cap

None

Gate

6"

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7911-7913

Cooling Towers & Storage Tanks

1-SUB-4-009-A

Sub-Basement

Center of room

N/A

Cu

8"

1"

HW

A

Closed Valve

None

Ball

6"

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7926-7930

Cooling Towers & Storage Tanks

1-SUB-4-010-B

Sub-Basement

West Wall

N/A

Cu

276''

3/4"

HW

B

Spigot

None

Globe

108"

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Old Connection For Washing Machine

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7931-7935

Cooling Towers & Storage Tanks

1-SUB-4-011-B

Sub-Basement

West Wall

N/A

Cu

144''

3/4"

CW

B

Spigot

None

Globe

N/A

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Old Connection For Washing Machine

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7931-7935

Cooling Towers & Storage Tanks

1-SUB-4-012-A

Sub-Basement

Center of room

N/A

Cu

196"

4"

CW

A

Closed Valve

None

Ball

N/A

Class I

1/PL-106

03/21/2019

Picture of Dead Leg

8001-8002

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-013-A

Sub-Basement

Center of room

N/A

Cu

16"

1 1/4"

HWR

A

Cap

None

None

2"

Class I

1/PL-106

03/21/2019

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-016-A

Sub-Basement

Center of room

N/A

Cu

18"

2"

HWR

A

Cap

None

Ball

None

Class I

1/PL-106

03/21/2019

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-017-A

Sub-basement

Center of room

N/A

Cu

24"

1/2"

CW

A

Closed Valve

None

Ball

N/A

Class I

1/PL-101

03/21/2019

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-018-A

Sub-Basement

Center of room

N/A

Cu

168"

1"

HWR

A

Closed Valve

None

Gate

84"

Class I

1/PL-107

03/21/2019

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-019-A

Sub-Basement

Center of room

N/A

Cu

10"

1/2"

CW

A

Cap

None

None

N/A

Class I

1/PL-106

03/21/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

8012-14

Cooling Towers & Storage Tanks

1-SUB-4-020-A

Sub-Basement

East Wall

N/A

Cu

28"

1/2"

CW

A

Cap

None

None

N/A

Class I

2/PL-107

03/22/2019

Picture of Dead Leg

8015-8017

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-021-A

Sub-Basement

East Wall

N/A

Cu

120"

1/2"

HWR

A

Cap

None

None

120"

Class I

2/PL-107

03/22/2019

Picture of Dead Leg

8015-8017

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Tagged as HW instead of HWR

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-022-A

Sub-Basement

Center of room

N/A

Cu

302''

2"

CW

A

Cap

None

None

N/A

Class I

1/PL-101

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-023-A

Sub-Basement

Center of room

N/A

Cu

7''

3/4"

HW

A

Cap

None

None

7"

Class I

1/PL-101

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-024-B

Sub-Basement

Center of room

N/A

Cu

78''

1/2"

CW

B

Fixture

Eyewash

Ball

N/A

Class I

1/PL-101

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-025-A

Sub-Basement

Center of room

N/A

Cu

20''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-106

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-026-A

Sub-Basement

Center of room

N/A

Cu

20''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-106

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-027-B

Sub-Basement

East Wall

N/A

Cu

160''

1/2"

CW

B

Fixture

Eyewash

None

N/A

Class I

1/PL-105

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-028-B

Sub-Basement

Center of room

N/A

Cu

8"

3/4"

CW

B

Spigot

None

None

N/A

Class I

1/PL-106

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-029-A

Sub-Basement

Center of room

N/A

Cu

88''

1"

CW

A

Closed Valve

None

Ball

N/A

Class I

1/PL-101

04/08/2019Date of Inspection:

Picture of Dead Leg

Image Not Available

Pipe Function

Dead Leg Type

Termination

Fixture Served

Valve Type

Hot Non-Insulated

Location in ICRA

Drawing Number

Comments / Recommendations

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Location in Room

Wall Type

Piping Material

Pipe Length

Pipe Size

Cooling Towers & Storage Tanks

1-SUB-4-030-A

Sub-Basement

Center of room

N/A

Cu

26''

1"

HW

A

Closed Valve

None

Ball

None

Class I

1/PL-101

04/08/2019Date of Inspection:

Picture of Dead Leg

Image Not Available

Pipe Function

Dead Leg Type

Termination

Fixture Served

Valve Type

Hot Non-Insulated

Location in ICRA

Drawing Number

Comments / Recommendations

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Location in Room

Wall Type

Piping Material

Pipe Length

Pipe Size

Cooling Towers & Storage Tanks

1-SUB-CS-001-B

Sub-Basement

Crawlspace

Center of room

N/A

Cu

7''

3/4"

CW

B

Spigot

None

Gate

N/A

Class I

1/PL-103

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-002-B

Sub-Basement

Crawlspace

Center of room

N/A

Cu

7''

3/4"

HW

B

Spigot

None

Gate

7"

Class I

1/PL-103

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-003-B

Sub-Basement

Crawlspace

Center of room

N/A

Cu

6"

1 1/4"

HWR

B

Spigot

None

Gate

6"

Class I

1/PL-103

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Comments / Recommendations

Pipe Size

Pipe Function

Dead Leg Type

Termination

Date of Inspection:

Location in Room

Wall Type

Piping Material

Pipe Length

Fixture Served

Valve Type

Hot Non-Insulated

Location in ICRA

Drawing Number

Picture of Dead Leg

Image Not Available

Cooling Towers & Storage Tanks

1-SUB-CS-004-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

135''

1 1/4"

CW

A

Closed Valve

None

Ball

N/A

Class I

1/PL-103

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Open Ended Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-005-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

174''

3/4"

HWR

A

Closed Valve

None

Ball

N/A

Class I

1/PL-103

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-006-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

718''

3/4"

HW

A

Closed Valve

None

Ball

718"

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Open Ended Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-007-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

717''

3/4"

CW

A

Closed Valve

None

None

N/A

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Open Ended Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-008-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

159''

3/4"

HW

A

Closed Valve

None

Ball

159"

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Open Ended Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-009-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

408''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Bent Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-010-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

384''

1/2"

HW

A

Cap

None

None

384"

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Bent Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-011-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

41''

1"

HWR

A

Cap

None

None

41"

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-012-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

54''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-013-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

54''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-014-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

54''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-015-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

54''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-016-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

24''

3/4"

HW

A

Closed Valve

None

Ball

24"

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-017-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

110''

3/4"

CW

A

Cap

None

None

N/A

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-018-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

13''

3/4"

CW

A

Cap

None

None

N/A

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-019-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

27''

3/4"

CW

A

Cap

None

None

N/A

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-020-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

129''

3/4"

CW

A

Cap

None

None

N/A

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-021-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

185''

1"

HW

A

Cap

None

Gate

185"

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-022-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

195''

1"

CW

A

Cap

None

Gate

N/A

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-023-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

402''

1"

HW

A

Cap

None

None

None

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-024-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

74''

1"

CW

A

Cap

None

Gate

N/A

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-025-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

4"

1/2"

HW

A

Cap

None

None

4"

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-026-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

4"

1/2"

CW

A

Cap

None

None

N/A

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-027-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

10''

3/4"

HW

A

Cap

None

Gate

10"

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-028-A

Sub-Basement

Crawlspace

East Wall

N/A

Cu

131''

3/4"

HW

A

Cap

None

Gate

131"

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-029-A

Sub-Basement

Crawlspace

East Wall

N/A

Cu

147''

3/4"

CW

A

Cap

None

Gate

N/A

Class I

1/PL-101

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-CS-030-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

111''

3/4"

HW

A

Closed Valve

None

Ball

111"

Class I

1/PL-101

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-CS-031-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

762''

1 1/2"

HW

A

Cap

None

None

None

Class I

1/PL-101

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-CS-032-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

159''

1/2"

CW

A

Cap

None

None

N/A

Class I

1/PL-101

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-CS-033-B

Sub-Basement

Crawlspace

North Wall

N/A

Cu

6"

3/4"

CW

B

Spigot

None

None

N/A

Class I

1/PL-102

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-CS-034-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

6"

3/4"

CW

A

Plug

None

None

N/A

Class I

1/PL-102

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-STAIRS-001-B

Sub-Basement

Stairs

East Wall

N/A

Cu

228''

3/4"

CW

B

Spigot

None

None

N/A

Class I

1/PL-105

02/27/2020

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-STAIRS-002-B

Sub-Basement

Stairs

East Wall

N/A

Cu

96''

3/4"

CW

B

Spigot

None

Gate

N/A

Class I

1/PL-106

02/27/2020

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap,…