This solicitation notice outlines full maintenance service requirements for multiple federal facilities in Houston, Beaumont, and Galveston, Texas. Services include operation and maintenance, custodial work, and ground maintenance at buildings occupied by the U.S. Customs House, Bob Casey Courthouse, AllianceTower, La Branch Federal Building, Mickey Leland Federal Building and Parking Garage, and Galveston U.S. Courthouse/U.S. Post Office. Additional requirements cover operations and maintenance services at the FBI Office Building, FBI Guard House, and FBI Parking Garage in Houston as well as the Jack Brooks Federal Building in Beaumont. The solicitation number is 47PH0220R0011 and is reserved exclusively for Service-Disabled Veteran-Owned Small Businesses. The North American Industry Classification System code is 561210 for Facilities Support Services. The anticipated start date for the contract is May 1, 2021.
View the file
Other files
Show 40 more
Latest 50 of 54 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4/20/20 2:43 PM 1 / 1
Houston 1 year of work orders Work Order Description Work Type
Work Sub- Type Status Asset Target Start
Dynamic Job Plan applied Site Location
19-42048222 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning
Tab.
WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 173735
19-42048223 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning
Tab.
WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 173736
19-51751306 827 RM, Replace carpet tile in the following cubes: 8W-21, 8W-23, 8W-15, 8W-19, 8W-25, 8W-12, 8W-09, 8W-27 (RONNIE/NOE/Email)
EXT 12/23/19
WR SERVCALL CLOSE 11/1/19 12:45:00 PM NO 07 60567
18-38237516 GYM, SHOWER SPRAY NOZZLE LEAKING
WHEN TURNED ON
WR SERVCALL CLOSE 1/4/19 2:15:00 PM NO 07 60567
19-42048751 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning
Tab.
WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 60567
19-43766613 BLDG, Mailroom door stop broken WR SERVCALL CLOSE 5/15/19 1:18:22 PM NO 07 60567
19-43766649 bldg, Mailroom processing door not closing properly (eMIALED)
WR SERVCALL CLOSE 5/15/19 1:15:00 PM NO 07 60567
19-51808172 BLDG., Source: P077KETX0701HSTN1 - LaBranch FB, Houston TX:Chillers /
ChwS_Temp_Alm Timestamp: 06-Nov-19 6:50:44 PM UTC State: Offnormal
Text: Chillers didn't bring temp below 60F in 15 mins (GSA/BAS) NC
WR SERVCALL CLOSE 11/6/19 1:45:00 PM NO 07 60648
19-42266326 BLDG, NiagaraNetwork P077KETX0701HSTN1 - LaBranch FB, Houston TX- - Ping Failed
CM EQFAIL CLOSE 4/7/19 2:30:00 AM NO 07 60648
19-44723696 bldg, NiagaraNetwork P077KETX0701HSTN1
- LaBranch FB, Houston TX - -Ping Failed
(BAS/GSA)
CM EQFAIL CLOSE 6/1/19 9:15:00 PM NO 07 60648
19-47599834 add NiagaraNetwork P077KETX0701HSTN1 - LaBranch FB, Houston TX - to equipment inventory
CM EQFAIL CLOSE 8/13/19 10:42:12 AM NO 07 60648
19-48867157 BLDG.,P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 / Tangent_Alarm
Timestamp: 02-Sep-19 1:01:14 PM UTC State: Offnormal Text: Tangent Down/
Fault (GSA/.BAS)
CM EQFAIL CLOSE 9/2/19 9:00:00 AM NO 07 60648
19-48866987 BLDG., Source: P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 /
Tangent_Alarm Timestamp: 01-Sep-19 8:54:02 PM UTC State: Offnormal
Text: Tangent Down/ Fault (GSA/BAS)
CM EQFAIL CLOSE 9/1/19 4:45:00 PM NO 07 60648
19-51746906 BLDG, P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 / Tangent_Alarm - -
Tangent Down/ Fault (GSA/BAS)
CM EQFAIL CLOSE 11/1/19 2:00:00 PM NO 07 60648
19-51746668 BLDG., P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 / Tangent_Alarm ;
Tangent Down/ Fault (GSA.BAS)
CM EQFAIL CLOSE 11/1/19 9:00:00 AM NO 07 60648
19-51770475 BLDG., P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 / Tangent_Alarm
Timestamp: 04-Nov-19 2:01:14 PM UTC State: Offnormal Text: Tangent Down/
Fault (GAS/BAS)
CM EQFAIL CLOSE 11/4/19 9:15:00 AM NO 07 60648
19-51770453 BLDG., P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 / Tangent_Alarm
Timestamp: 02-Nov-19 1:01:13 PM UTC State: Offnormal Text: Tangent Down/
Fault (GSA/BAS)
CM EQFAIL CLOSE 11/2/19 9:15:00 AM NO 07 60648
19-51803719 Source: P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 /
Tangent_Alarm Timestamp: 06-Nov-19 2:01:14 PM UTC State: Offnormal
Text: Tangent Down/ Fault (GSA/BAS)
NC
CM EQFAIL CLOSE 11/6/19 12:15:00 PM NO 07 60648
19-51803643 Source: P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 /
Tangent_Alarm Timestamp: 06-Nov-19 2:01:14 PM UTC State: Offnormal Text:
Tangent Down/ Fault (GSA/BAS) NC
CM EQFAIL CLOSE 11/6/19 9:15:00 AM NO 07 60648
18-38224414 TX0701- Electrical panel not labeled @ room
GSAI NORMAL CLOSE 1/3/19 9:34:23 AM NO 07 60648
18-38224445 TX0701- components missing from double door closing coordinator @ interior parking lot entrance extension 02-27-19
GSAI NORMAL CLOSE 1/3/19 9:41:25 AM NO 07 60648
19-39368649 TX0701- BAS-CHW DP=31.04 psi setpoint is
9.00 psi
GSAI NORMAL CLOSE 2/4/19 11:08:38 AM NO 07 60648
19-45630092 Someone replaced the tile in the conference room suite 1103 on May 20th as requested, however, the new tile is now brown. Please have someone fix the problem in the conference room ceiling.
GSAI NORMAL CLOSE 6/19/19 10:17:28 AM NO 07 60648
19-39173014 BUILDING, ORDER HOSE FOR
EXTRACTOR MACHINE Extension
02/13/2019
OMI INITIAL CLOSE 1/24/19 9:15:00 AM NO 07 60648
19-40390083 BLDG, NiagaraBLDG, Network P077KETX0701HSTN1 - LaBranch FB, Houston TX-Ping Failed
WR SERVCALL CLOSE 2/14/19 7:15:00 AM NO 07 60648
19-40727785 BLDG, P077KETX0701HSTN1 - LaBranch FB, Houston TX:Boiler / HwS_Temp_Alm -
Boiler didn't bring temp above 90F in 60 mins
WR SERVCALL CLOSE 3/4/19 12:30:00 PM NO 07 60648
19-42048822 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning
Tab.
WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 60648
19-50492875 SOUTH PEDESTRIAN ELEVATOR, NOT
WORKING (RONALD 9801)
WR SERVCALL CLOSE 10/8/19 7:15:00 AM NO 07 61252
19-51747073 BLDG, P07QMETX0019BMT1 - Beaumont TX:Points / Twr2IsoAlarm - - Tower Faulted!!
(GSA/BAS)
CM EQFAIL CLOSE 11/1/19 2:00:00 PM NO 07 61252
19-51746691 BLDG,P07QMETX0019BMT1 - Beaumont TX:Points / Twr1IsoAlarm -Tower Faulted!!
(GSA/BAS)
CM EQFAIL CLOSE 11/1/19 3:30:00 AM NO 07 61252
19-39023895 3FL probation hallway near roof access door stained tiles, check for leaks, replace tiles
GSAI NORMAL CLOSE 1/16/19 7:59:21 AM NO 07 61252
19-39026725 Roof Cooling Tower heavy build up noted on the bottoms of the fill tiles, water was clear, no scale or build up noted inside tower
EXTENSION 02/01/19
GSAI NORMAL CLOSE 1/16/19 8:22:21 AM NO 07 61252
19-39025275 Chiller #1 Alarm panel showed several alarms "Returned CHWT is lower than cooling SP
Fault";
GSAI NORMAL CLOSE 1/16/19 8:10:43 AM NO 07 61252
19-39025182 3FL in front of door 301 probation hallway fan louder than expected, check for need maintenance and operational issues
GSAI NORMAL CLOSE 1/16/19 8:09:55 AM NO 07 61252
19-39024771 3FL roof access hallway behind door 301 stained tiles, check for leaks, replace tiles
GSAI NORMAL CLOSE 1/16/19 8:06:41 AM NO 07 61252
19-41862350 TX0019- Contact electrical utility- electrical entry well flooded. Has sump pump which looks to be inoperable
GSAI NORMAL CLOSE 3/18/19 4:20:03 PM NO 07 61252
19-42110648 TX0019- Review NCMMS equipment inventory. Use BAS naming convention to correct asset descriptions EXTENSION 8/9/19
GSAI NORMAL CLOSE 3/30/19 12:16:21 PM NO 07 61252
19-42110652 TX0019- Yellow Tag- FAILED MAIN DRAIN-
PIPING PVC: DRAIN CAN NOT ACCEPT
FULL FLOW EXTENSION 10/5/19 HOU-174
WAITING ON QUOTES
GSAI NORMAL CLOSE 3/30/19 12:33:07 PM NO 07 61252
19-42110649 TX0019- Verify all backflow preventers are on NCMMS inventory
GSAI NORMAL CLOSE 3/30/19 12:18:52 PM NO 07 61252
19-42171191 remove RR from plenum discharge and re-route
GSAI NORMAL CLOSE 4/2/19 7:49:36 AM NO 07 61252
19-42172817 north pedestrian gate into back parking lot (broadwayside) doesn't secure/close without pulling it
GSAI NORMAL CLOSE 4/2/19 9:12:43 AM NO 07 61252
19-42171249 four lobby lights out EXTENSION 6/15/19 GSAI NORMAL CLOSE 4/2/19 8:18:25 AM NO 07 61252
19-42171228 lights stored improperly in Judge Heartfield's IT Closet
GSAI NORMAL CLOSE 4/2/19 8:10:51 AM NO 07 61252
19-42171201 provide quote back lot parking signs/cards brown cards with white letters, laminated
EXTENSION 8/9/19
GSAI NORMAL CLOSE 4/2/19 7:59:13 AM NO 07 61252
19-42241832 1FL Giblin Jury Room Water Fountain Non Operational - REPEAT ITEM
GSAI NORMAL CLOSE 4/4/19 5:45:03 PM NO 07 61252
19-42241842 1FL Jury Room Wall paper peeling at double door
GSAI NORMAL CLOSE 4/4/19 5:51:20 PM NO 07 61252
19-42241835 1FL Jury Assembly Room Cut Ceiling Tile At Side Counter
GSAI NORMAL CLOSE 4/4/19 5:48:04 PM NO 07 61252
19-42241834 1FL Jury Room Entrance Door Interior Emergency Exit Light failed test
GSAI NORMAL CLOSE 4/4/19 5:47:08 PM NO 07 61252
19-42232043 sticky greasy substance running down walls in sallyport from equipment, check for leaks, clean area and equipment
GSAI NORMAL CLOSE 4/3/19 4:30:19 PM NO 07 61252
19-42280980 bldg, have the fire alarm at Jack Brooks put into test starting immediately 2:30p until we are able to complete installation of the mag locks on the stairwell doors approximately 6 p.m. tonight (eMAIL)
GSAI SAFETY CLOSE 4/9/19 4:00:00 PM NO 07 61252
19-42241844 1FL Bankruptcy Judge's RR Fan Not Operating GSAI NORMAL CLOSE 4/4/19 5:53:10 PM NO 07 61252
19-42241847 1FL Judge Giblins swinging door from gallery into pit making noise when in use
GSAI NORMAL CLOSE 4/4/19 5:56:19 PM NO 07 61252
19-43204518 BLDG, rePlace electrical conductivity mats in front of equipment at TX0019ZZ using govt furnished matls (LEENETTE GSAI)
GSAI SAFETY CLOSE 4/22/19 7:45:39 AM NO 07 61252
19-44494571 replace worn toiilet seats in men's public rr 1FL by freight elevator
GSAI NORMAL CLOSE 5/23/19 12:54:54 PM NO 07 61252
19-44494618 1FL men's RR by freight elevator has rust on urinal panel
GSAI NORMAL CLOSE 5/23/19 1:11:32 PM NO 07 61252
19-44416850 USMS 1st Floor high humidity, stuff througout GSAI NORMAL CLOSE 5/21/19 4:19:11 PM NO 07 61252
19-43820757 outside water faucets do not work
EXTENSION 9/13/19
GSAI NORMAL CLOSE 5/17/19 10:00:00 AM NO 07 61252
19-44861057 BLDG., do some small touch ups of painting in a couple areas to be field verified by Mona Doyle, Clerk of the Courts - EMAIL -GSAI
GSAI NORMAL CLOSE 6/11/19 10:30:00 AM NO 07 61252
19-44862432 BLDG, small hole in a wall from a desk that was pushed over happened apparently during work on the HVAC system the other night while the workers were working overnight
WW please field verify location, patch and paint the hole (EMAIL-GSAI)
GSAI NORMAL CLOSE 6/11/19 10:30:00 AM NO 07 61252
19-45569576 BLDG, purchase sheeting and install as quickly as possibly GSAI-LEENNETTE
GSAI NORMAL CLOSE 6/17/19 8:30:00 AM NO 07 61252
19-47006292 TX0019- BAS VAV 6 not maintaining space setpoint
GSAI NORMAL CLOSE 7/17/19 8:21:53 AM NO 07 61252
19-50307912 at least 3 backflow preventers missing from NCMMS Inventory
GSAI NORMAL CLOSE 9/26/19 6:40:04 AM NO 07 61252
19-53128394 3FL Probation Supervisor Adam Graves stained tiles - replace tiles and check for leaks
GSAI NORMAL CLOSE 12/5/19 8:46:26 AM NO 07 61252
19-54241923 Basement USMS Men's RR SHowerhead leaks from connection
GSAI NORMAL CLOSE 12/19/19 4:05:26 PM NO 07 61252
18-38219489 COURTS, LIGHTS NOT WORKING
(ANDREW (PA)
OMI INITIAL CLOSE 1/2/19 2:00:00 PM NO 07 61252
19-49128878 RFQ to repair burn at pumps in basement UP NORMAL CLOSE 9/11/19 8:54:57 AM NO 07 61252
19-40387864 P07QMETX0019BMT1 - Beaumont TX:Boilers / HwS_Temp_Alm2 - Boiler didn't bring temp above 90F in 60 mins
WR SERVCALL CLOSE 2/13/19 7:15:00 AM NO 07 61252
19-40390751 BLDG, P07QMETX0019BMT1 - Beaumont TX:Boilers / HwS_Temp_Alm1- Boiler didn't bring temp above 90F in 60 mins
WR SERVCALL CLOSE 2/14/19 12:00:00 PM NO 07 61252
19-40759192 104 RM, SINK IN CLERKS OFFICE DRAINS
SLOW ( RONALD 7552)
WR SERVCALL CLOSE 3/6/19 9:30:00 AM NO 07 61252
19-40794059 BLDG, JUDGES ENTRANCE NORTH SIDE
NOT SECURING (LOCKED) (RONALD 7590)
WR SERVCALL CLOSE 3/8/19 3:15:00 PM NO 07 61252
19-43374883 STAIRWELL - BLDG, REPORT THAT
TENANT GET STUCK IN AREA -SEE Email
(Ronald, Andrew & Email 8100)
WR SERVCALL CLOSE 4/29/19 12:45:00 PM NO 07 61252
19-45630234 BLDG, Provide weekly update for hvac issues including temp and humidity readings (GSAI
LEENETTE
WR SERVCALL CLOSE 6/19/19 10:30:00 AM NO 07 61252
19-45583468 Judge Truncale’s clerks-a keyboard pullout that he would like removed-(EMAILO) 6/18/19
WR SERVCALL CLOSE 6/18/19 3:15:00 PM NO 07 61252
19-47036818 BLDG, FIRE PANEL NOT COMMUNICATION
W/ DENVER MEGA CENTER (NATHAN)
WR SERVCALL CLOSE 7/23/19 8:30:00 AM NO 07 61256
18-38233526 BLDG, ESCORT WINDOW WASHERS
(NATHAN (PA)
CM CORRECT CLOSE 1/3/19 9:15:00 AM NO 07 61256
18-38233496 building, ESCORT AT & T TECH IN VARIOUS
AREA (NATHAN (PA)
CM CORRECT CLOSE 1/3/19 8:30:00 AM NO 07 61256
19-42266333 BLDG, NiagaraNetwork P077KETX0081GVTN1 - Galveston, TX- -Ping
Failed
CM EQFAIL CLOSE 4/7/19 2:30:00 AM NO 07 61256
19-42266353 BLDG, P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm- - Chillers didn't bring temp below 60F in 30 mins
CM EQFAIL CLOSE 4/7/19 4:15:00 AM NO 07 61256
19-42810087 P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - - Chillers didn't bring temp below 60F in 30 mins (gsa/ bas)
CM EQFAIL CLOSE 4/16/19 9:00:00 PM NO 07 61256
19-43290659 bldg, P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - -Chillers didn't bring temp below 60F in 30 mins (gsa/ bas)
CM EQFAIL CLOSE 4/22/19 10:00:00 AM NO 07 61256
19-39026559 Water testing logs shows inhibitor and conductivity out of range
GSAI NORMAL CLOSE 1/16/19 8:21:02 AM NO 07 61256
19-42110661 TX0081- IR testing overdue for breakers on main switchgear DPN Panel
GSAI NORMAL CLOSE 3/30/19 1:44:22 PM NO 07 61256
19-42110667 TX0081- NCMMS create assets for IR testing equipment that is missing from equipment inventory (attach uploader)
GSAI NORMAL CLOSE 3/30/19 1:59:03 PM NO 07 61256
19-42110666 TX0081- IR testing overdue for breakers on main switchgear TDPLV
GSAI NORMAL CLOSE 3/30/19 1:57:44 PM NO 07 61256
19-42110665 TX0081- IR testing overdue for breakers on main switchgear TEMG
GSAI NORMAL CLOSE 3/30/19 1:57:25 PM NO 07 61256
19-42110664 TX0081- IR testing overdue for breakers on main switchgear WCH-2
GSAI NORMAL CLOSE 3/30/19 1:57:01 PM NO 07 61256
19-43352361 TX0081- BAS Chiiler Lag point is overridden
OFF
GSAI NORMAL CLOSE 4/29/19 10:39:05 AM NO 07 61256
19-43453701 TX0081- BAS Tune cooling tower PID GSAI NORMAL CLOSE 5/1/19 8:55:12 AM NO 07 61256
19-47185248 TX0081- BAS Chiller sequence point overridden
GSAI NORMAL CLOSE 7/29/19 9:44:07 AM NO 07 61256
18-38254632 BLDG, NEED ESCORT FOR WINDOW
WASHERS (NATHAN (PA)
UH UTILMISC CLOSE 1/4/19 8:00:00 AM NO 07 61256
19-39315204 502 RM, MAKE 10 KEYS MARSHAL BACK
DOOR (Nathan 7097)
UH UTILMISC CLOSE 1/31/19 11:00:00 AM NO 07 61256
18-38237550 BLDG, TOO HOT IN COURTROOM
(NATHAN)
WR SERVCALL CLOSE 1/4/19 3:00:00 PM NO 07 61256
18-38237553 BLDG, PRISONER ELEV STUCK IN
BASEMENT AND ALARMS SOUNDING
(NATHAN)
WR SERVCALL CLOSE 1/4/19 3:00:00 PM NO 07 61256
19-38286925 BLDG, JUDGE EDISON COURTS, NEED
KEY MADE (NATHAN )
WR SERVCALL CLOSE 1/9/19 8:00:00 AM NO 07 61256
19-38286938 BLDG, NEED KEY MADE (NATHAN) WR SERVCALL CLOSE 1/9/19 8:00:00 AM NO 07 61256
19-39420684 3rd FLR RRM, LIGHT OUT IN CUSTODIAL
CLOSET (NATHAN )
WR SERVCALL CLOSE 2/6/19 6:00:00 PM NO 07 61256
19-40210602 P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm Chillers didn't bring temp below 60F in 30 mins
WR SERVCALL CLOSE 2/11/19 7:15:00 AM NO 07 61256
19-39420683 NiagaraNetwork P077KETX0081GVTN1 - Galveston, TX PING FAILED (GSA/BAS)
WR SERVCALL CLOSE 2/7/19 7:30:00 PM NO 07 61256
19-40388804 P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - Chillers didn't bring temp below 60F in 30 mins
WR SERVCALL CLOSE 2/13/19 12:30:00 PM NO 07 61256
19-40282898 P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm -Chillers didn't bring temp below 60F in 30 mins (GSA/BAS)
WR SERVCALL CLOSE 2/12/19 6:30:00 AM NO 07 61256
19-40658931 BLDG, ELECTRICAL OUTLET PUSHED
INTO WALL - NO POWER ACCESSIBILITY
(NATHAN)
WR SERVCALL CLOSE 2/28/19 7:30:00 AM NO 07 61256
19-40748591 BLDG, Hot Water Supply Temp Below 90°F After Being Enabled for 30 Minutes. - Chillers didn't bring temp below 60F in 30 mins
WR SERVCALL CLOSE 3/5/19 2:00:00 PM NO 07 61256
19-40797626 DOCK, MAKE KEY FOR REAR DOCK
ENTRANCE (EMAILED 7617)
WR SERVCALL CLOSE 3/12/19 7:15:00 AM NO 07 61256
19-41860573 BLDG., P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - - Chillers didn't bring temp below 60F in 30 mins
WR SERVCALL CLOSE 3/16/19 10:45:00 AM NO 07 61256
19-42133560 BLDG, P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - -Chillers didn't bring temp below 60F in 30 mins
WR SERVCALL CLOSE 3/29/19 9:00:00 PM NO 07 61256
19-42049266 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning
Tab.
WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 61256
19-43576786 bldg, P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - -Chillers didn't bring temp below 60F in 30 mins
WR SERVCALL CLOSE 5/10/19 3:45:00 AM NO 07 61256
19-42049267 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning
Tab.
WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 61257
19-40748488 bldg, P077KETX0101HSTN1 - Customs House (Houston Texas):HWSupplyTempAlm -
Hot Water Supply Temp Below 90°F After Being Enabled for 30 Minutes.
CM EQFAIL CLOSE 3/5/19 2:00:00 PM NO 07 61257
19-42266321 BLDG, NiagaraNetwork P077KETX0101HSTN3 - Customs House
(Houston Texas) - - Ping Failed
CM EQFAIL CLOSE 4/7/19 2:30:00 AM NO 07 61257
19-42266343 BLDG, NiagaraNetwork P077KETX0101HSTN2 - Customs House
(Houston Texas) Platform Connection- - Ping Failed
CM EQFAIL CLOSE 4/7/19 2:30:00 AM NO 07 61257
19-51770478 BLDG., P077KETX0101HSTN1 - Customs House (Houston Texas):Basement MBB_5
Has Lost Communications (GSA.BAS)
CM EQFAIL CLOSE 11/4/19 9:15:00 AM NO 07 61257
18-38256312 ELEVATOR #1, STUCK ON 3rd FLR DOORS
CLOSED #005953386 (ISISDOR 6852)
WR SERVCALL CLOSE 1/7/19 8:15:00 AM NO 07 61257
19-39479052 P077KETX0101HSTN1 - Customs House (Houston
Texas):P077KETX0101HSTN2:MB2_23 Room 260 Zone Temperature - is at 80.6 °F which is above the high limit of 80.0 °F!
WR SERVCALL CLOSE 2/8/19 3:00:00 PM NO 07 61257
19-39462422 P077KETX0101HSTN1 - Customs House (Houston Texas):HWSupplyTempAlm = Hot Water Supply Temp Below 90°F After Being
Enabled for 30 Minutes.(GSA/BAS)
WR SERVCALL CLOSE 2/8/19 8:00:00 AM NO 07 61257
19-40449044 BLDG, P077KETX0101HSTN1 - Customs House (Houston Texas):HWSupplyTempAlm-ot Water Supply Temp Below 90°F After Being Enabled for 30 Minutes. (REF #40427437)
WR SERVCALL CLOSE 2/20/19 7:00:00 AM NO 07 61257
19-40427437 BLDG, P077KETX0101HSTN1 - Customs House (Houston Texas):HWSupplyTempAlm-ot Water Supply Temp Below 90°F After Being Enabled for 30 Minutes.
WR SERVCALL CLOSE 2/20/19 7:15:00 AM NO 07 61257
19-54351134 5300 RM, BLACK STUFF COMING FROM A/
C VENTS (JIMMIE 677) NC
WR SERVCALL CLOSE 12/31/19 2:50:13 PM NO 07 61266
19-39168150 TX0211ZZ.EL-1 - Building Running Too Late CM GLINK CLOSE 1/23/19 7:54:51 AM NO 07 61266
19-39168154 TX0211ZZ.EL-1 - Maximum Demand During Unoccupancy
CM GLINK CLOSE 1/23/19 7:56:00 AM NO 07 61266
19-39168152 TX0211ZZ.EL-1 - Short Demand Peak CM GLINK CLOSE 1/23/19 7:55:22 AM NO 07 61266
19-39168151 TX0211ZZ.EL-1 - Building Starting Too Early CM GLINK CLOSE 1/23/19 7:55:03 AM NO 07 61266
19-40991720 TX0211ZZ.EL-1 - Building Starting Too Early CM GLINK CLOSE 3/13/19 1:53:11 PM NO 07 61266
19-40991730 TX0211ZZ.CW - Maximum Demand During Unoccupancy
CM GLINK CLOSE 3/13/19 1:54:27 PM NO 07 61266
19-40991725 TX0211ZZ.EL-1 - Short Demand Peak CM GLINK CLOSE 3/13/19 1:53:44 PM NO 07 61266
19-40991733 TX0211ZZ.DW-1 - Excessive Water Usage During Unoccupancy
CM GLINK CLOSE 3/13/19 1:54:39 PM NO 07 61266
19-42266322 BLDG, NiagaraNetwork P077KETX0211HSTN1 - Bob Casey CH, Houston TX- - Ping Failed
CM EQFAIL CLOSE 4/7/19 8:30:00 AM NO 07 61266
19-42635844 Source: P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /
HwS_Temp_Alm Timestamp: 14-Apr-19 3:09:00 AM CDT State: Offnormal Text: Boiler didn't bring temp above 90F in 60 mins-
(EMAIL) 4/15/19
CM EQFAIL CLOSE 4/15/19 1:30:00 PM NO 07 61266
19-43432266 TX0211ZZ.EL-1 - Short Demand Peak CM GLINK CLOSE 4/30/19 8:21:24 PM NO 07 61266
19-43432270 TX0211ZZ.EL-1 - Maximum Demand During Unoccupancy
CM GLINK CLOSE 4/30/19 8:22:15 PM NO 07 61266
19-43432268 TX0211ZZ.EL-1 - Building Running Too Late CM GLINK CLOSE 4/30/19 8:21:52 PM NO 07 61266
19-43432267 TX0211ZZ.EL-1 - Building Starting Too Early CM GLINK CLOSE 4/30/19 8:21:37 PM NO 07 61266
19-51770462 BLDG., P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /
HwS_Temp_Alm Timestamp: 02-Nov-19 1:07:03 PM UTC State: Offnormal
Text: Boiler didn't bring temp above 90F in 60 mins (BAS/GSA)
CM EQFAIL CLOSE 11/2/19 9:15:00 AM NO 07 61266
19-54275288 BLDG. Source: P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant / HwS_Temp_Alm Timestamp: 21-Dec-19
11:03:27 PM CST State: Offnormal Text: Boiler didn't bring temp above 90F in 60 mins (GSA/BAS) NC
CM EQFAIL CLOSE 12/21/19 12:15:00 PM NO 07 61266
19-54245583 BLDG., Source: P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant / HwS_Temp_Alm Timestamp: 19-Dec-19
8:21:00 PM CST State: Offnormal Text: Boiler didn't bring temp above 90F in 60 mins (bas/gsa) NC
CM EQFAIL CLOSE 12/19/19 9:30:00 PM NO 07 61266
18-38223334 Judge Bryan's Jury Room Restrooms - Both RR floors have very dark discolored grout, lack lustre, stains and streaks, build up along wall base and thresholds
GSAI NORMAL CLOSE 1/3/19 8:32:42 AM NO 07 61266
18-38224116 4FL 4616 Bankruptcy Hallway Secured Doors do not shut or secure without manual action
GSAI NORMAL CLOSE 1/3/19 8:50:31 AM NO 07 61266
18-38224111 1FL dining room entrance from jury lobby escutcheon missing
GSAI NORMAL CLOSE 1/3/19 8:48:41 AM NO 07 61266
18-38224106 1FL Jury Assembly Hallway missing escushion by men's public rr near exit door
GSAI NORMAL CLOSE 1/3/19 8:46:31 AM NO 07 61266
18-38224101 1FL 1315 RR lights out GSAI NORMAL CLOSE 1/3/19 8:45:21 AM NO 07 61266
18-38224098 8FL 8405 Men's Public RR lights out GSAI NORMAL CLOSE 1/3/19 8:44:10 AM NO 07 61266
18-38224073 1FL Jury Room Hallways lack lustre, streaks and variations in finish, streaks, scuff marks, stains and build up along wall base and thresholds
GSAI NORMAL CLOSE 1/3/19 8:42:48 AM NO 07 61266
18-38224006 7FL 7415 Women Public RR Lights out GSAI NORMAL CLOSE 1/3/19 8:41:16 AM NO 07 61266
19-38339209 Chiller #3 OVER AMPING - possible programming issues causing ALARMS and over amping
GSAI NORMAL CLOSE 1/11/19 4:05:29 PM NO 07 61266
18-38225093 12FL 12118 tile grout has marked difference in color between the edges of the walls and partition bases and the rest of the floor; much of it is very dark and stained
GSAI NORMAL CLOSE 1/3/19 11:08:27 AM NO 07 61266
18-38225091 12FL 12124 Men's RR lights out GSAI NORMAL CLOSE 1/3/19 11:07:37 AM NO 07 61266
18-38225085 12FL Hallway by 12628 missing escutcheon GSAI NORMAL CLOSE 1/3/19 11:06:29 AM NO 07 61266
18-38225081 12FL 12118 Womens RR Exhaust fan making loud noises, cycling on and off continuosly and quickly
GSAI NORMAL CLOSE 1/3/19 11:05:28 AM NO 07 61266
18-38225077 Judge Elrod Breakroom stainless surfaces are streaked, showing possible water spots and drips
GSAI NORMAL CLOSE 1/3/19 11:04:52 AM NO 07 61266
18-38225071 7FL 7104 USAO Visitor Lobby Carpet Stains GSAI NORMAL CLOSE 1/3/19 11:03:54 AM NO 07 61266
18-38225050 1FL Mail Room Floors show numerous heavy streaks, scuff marks and dark stains; not uniform in finish and lacks lustre, build up along walls and thresholds
GSAI NORMAL CLOSE 1/3/19 10:59:13 AM NO 07 61266
18-38225043 1FL Freight Elevator Lobby Floor Floors show streaks, scuff marks, and dark stains; floor not uniform in finish and lacks lustre , build up along wall and thresholds
GSAI NORMAL CLOSE 1/3/19 10:58:07 AM NO 07 61266
18-38225032 1FL Lobby Entry/Lobby between elevators/ mail room and Jury AssemblyFloors show streaks, scuff marks, and dark stains; floor not uniform in finish and lacks lustre , build up along wall and threshold
GSAI NORMAL CLOSE 1/3/19 10:56:00 AM NO 07 61266
18-38224130 fire panel trouble alarms, possible reimburseable service troubleshoot, provide estimate and justification to GSA immediately
GSAI NORMAL CLOSE 1/3/19 8:55:11 AM NO 07 61266
18-38224118 7FL Rm 7409 Men's Public RR lights out GSAI NORMAL CLOSE 1/3/19 8:51:13 AM NO 07 61266
18-38233770 USMS Guard Shack on Smith Street ROOF
LEAKS
GSAI NORMAL CLOSE 1/4/19 12:08:53 PM NO 07 61266
18-38233775 Smith Street USMS Guard Shack Water in building, under mat, office needs custodial service - ple
GSAI NORMAL CLOSE 1/4/19 12:10:36 PM NO 07 61266
18-38225141 12FL 12124 Mens RR tile grout has marked difference in color between the edges of the walls and parition bases and the rest of the floor which is very dark and stained in appearance
GSAI NORMAL CLOSE 1/3/19 11:16:47 AM NO 07 61266
18-38225149 12FL Back Secured Tile aroudn MCH Rooms through to DOJ and Freight/Judicial Elevators numerous streaks, scuff marks and stains throughout, not uniform in appearance, lacks lustre, very heavy build up around elevators and DOJ/Vacant Suite entrances
GSAI NORMAL CLOSE 1/3/19 11:18:06 AM NO 07 61266
19-39019550 Smith Street Guard Shack shows lack of mopping, sweeping, vacuuming per contract
GSAI NORMAL CLOSE 1/16/19 7:24:31 AM NO 07 61266
19-39019711 Smith Street Guard Shack Windows streaked and grimy
GSAI NORMAL CLOSE 1/16/19 7:25:46 AM NO 07 61266
19-39377153 Basement Shop has Numerous red tag fire extinguishers stored on floor; in cabinets/ lockers, stacked on top of cabinets/lockers need to be removed
GSAI FIRE CLOSE 2/5/19 8:32:12 AM NO 07 61266
19-39377161 Basement Shop - Several boxes of used bulbs sitting on floor, on top of shop table dating back to August 2018 need to be removed
GSAI NORMAL CLOSE 2/5/19 8:34:57 AM NO 07 61266
19-39377157 Several boxes of used bulbs sitting on floor, on top of shop table dating back to August
2018 need to be removed
GSAI NORMAL CLOSE 2/5/19 8:33:23 AM NO 07 61266
19-39377171 Basement Shop - old equipment sitting on floors, tables
GSAI NORMAL CLOSE 2/5/19 8:39:04 AM NO 07 61266
19-39391442 1FL 1010 Vending Room has dark and rust colored stains on floor around vending machines
GSAI NORMAL CLOSE 2/5/19 11:24:29 AM NO 07 61266
19-39391438 3FL Rm3132 Women RR Lights Out GSAI NORMAL CLOSE 2/5/19 11:23:56 AM NO 07 61266
19-39391426 3FL #3132 Women RR sanitary receptacle plate missing, basket falls on the floor during each use
GSAI NORMAL CLOSE 2/5/19 11:21:22 AM NO 07 61266
19-39390704 Basement Shop Consolidate flammables per code and discard rusted, painted, lockers/ cabinets that do not latch , have holes and/or not secure
GSAI SAFETY CLOSE 2/5/19 10:42:55 AM NO 07 61266
19-39390694 B417 Hallway Door at Basement doorknob does not secure; is loose, and will not lock all time
GSAI NORMAL CLOSE 2/5/19 10:41:40 AM NO 07 61266
19-39390672 Hallway outside Mechanic Office at B520 missing outlet cover
GSAI NORMAL CLOSE 2/5/19 10:40:52 AM NO 07 61266
19-39377213 B401 Womens RR light out GSAI NORMAL CLOSE 2/5/19 8:50:21 AM NO 07 61266
19-39377212 Basement Shop - several pieces of old equipment, computers, dusty found flammable lockers/cabinets and old documents need to be discarded
GSAI NORMAL CLOSE 2/5/19 8:48:54 AM NO 07 61266
19-42231100 back lot pedestrian exit gate frame is loose at wall, possibly needs anchor bolt tighented or replaced?
GSAI NORMAL CLOSE 4/3/19 3:49:41 PM NO 07 61266
19-42171276 Chiller 3 LAPSE in BAS ALARM NOTIFICATIONS, Programming Problems
GSAI NORMAL CLOSE 4/2/19 8:26:29 AM NO 07 61266
19-42238252 troubleshoot fire system alarms going off right after midnight repeatedly
GSAI FIRE CLOSE 4/3/19 7:03:00 AM NO 07 61266
19-42241812 Room 5020 Womens RR Toilet coming off the wall, needs repaired or replaced
GSAI NORMAL CLOSE 4/4/19 5:29:31 PM NO 07 61266
19-43311103 annual tree assessment overdue GSAI NORMAL CLOSE 4/25/19 10:36:31 AM NO 07 61266
19-44494631 CSO Control Rm and Break Rm 1FL hot on weekends, check equipment and check HVAC scheduling for OTUs
GSAI NORMAL CLOSE 5/23/19 1:15:23 PM NO 07 61266
19-44530216 Remove and/or relocate one of the two ashcans sitting in that area ; should not need more than one at this location
GSAI NORMAL CLOSE 5/24/19 9:31:52 AM NO 07 61266
19-44530136 Check wall for lights out and lights falling/ fixture coming off wall ; a few fixtures observed to be loose, hanging off wall , some lights out
GSAI NORMAL CLOSE 5/24/19 9:31:24 AM NO 07 61266
19-44529582 exterior security lights out GSAI NORMAL CLOSE 5/24/19 9:27:40 AM NO 07 61266
19-44529492 Courtroom 11C several lights out GSAI NORMAL CLOSE 5/24/19 9:26:55 AM NO 07 61266
19-44494738 Rm 5218 leak appears to be by or at window in ralph carter's office
GSAI NORMAL CLOSE 5/23/19 1:44:44 PM NO 07 61266
19-44494636 sallyport exhaust fans possible down , check operation
GSAI NORMAL CLOSE 5/23/19 1:16:35 PM NO 07 61266
19-44649660 TX0211- Verify proper operation of hot deck/ cold damper on BC_TC0118
GSAI NORMAL CLOSE 5/30/19 11:53:47 AM NO 07 61266
19-44530385 front sidewalk Relocate/redistribute ashcans, they are all bunched together
GSAI NORMAL CLOSE 5/24/19 9:33:07 AM NO 07 61266
19-44531653 1FL RM1022 CSO SUPV DOOR ENTRANCE
THRESHOLD Threshold at door 1022 coming up, has two different strips on top of feach other, is a tripping hazard, needs to be removed and re-installed
GSAI NORMAL CLOSE 5/24/19 9:50:20 AM NO 07 61266
19-44531644 plants have brown spots and appear distressed especally from entrance bed
GSAI NORMAL CLOSE 5/24/19 9:48:02 AM NO 07 61266
19-44531640 Post Office back room has missing ceiling tiles GSAI NORMAL CLOSE 5/24/19 9:46:38 AM NO 07 61266
19-44531630 postal office back entrance area and work room heavy layer of dirt and dust on floors, walls and throughout
GSAI NORMAL CLOSE 5/24/19 9:45:04 AM NO 07 61266
19-44531584 interior entrance door seals/gaskets worn leaving gaps on bottoms and between doors
GSAI NORMAL CLOSE 5/24/19 9:43:26 AM NO 07 61266
19-44531489 Back Dock Postal Doors exterior entrance door seals/gaskets coming off, hanging from doors leaving gaps on bottoms and between doors
GSAI NORMAL CLOSE 5/24/19 9:42:06 AM NO 07 61266
19-44753926 TX0211- Properly stow and secure gas cylinders
GSAI NORMAL CLOSE 6/3/19 1:47:16 PM NO 07 61266
19-44657946 dry pipe failed inspection at back dock GSAI FIRE CLOSE 5/30/19 2:45:24 PM NO 07 61266
19-44662506 TX0211- Verify proper operation of hot deck/ cold damper on BC_TC0106
GSAI NORMAL CLOSE 5/30/19 4:43:17 PM NO 07 61266
19-44661090 TX0211- Verify proper operation of hot deck/ cold damper on BC_TC0115
GSAI NORMAL CLOSE 5/30/19 3:52:09 PM NO 07 61266
19-50292393 RFQ to replace USMS guard shack back dock GSAI NORMAL CLOSE 9/25/19 8:48:46 AM NO 07 61266
19-51429491 exterior security lights out GSAI NORMAL CLOSE 10/21/19 6:58:47 AM NO 07 61266
19-51429492 Rm 3413 Women Public RR by US Trustee Door handle broken
GSAI NORMAL CLOSE 10/21/19 6:59:47 AM NO 07 61266
19-52676915 several exterior security and building lights out all around perimeter of building and inside secured lot
GSAI NORMAL CLOSE 11/19/19 8:20:28 AM NO 07 61266
19-52677077 1FL Postal Women RR dispensers and other fixtures,finishes has heavy layer of dust
GSAI NORMAL CLOSE 11/19/19 9:02:17 AM NO 07 61266
19-52677071 1FL Postal Men's RR Entry door threshold has heavy build up of what appears to be dirt and debris
GSAI NORMAL CLOSE 11/19/19 9:00:19 AM NO 07 61266
19-52676982 1FL Postal Mens RR floor shows dark stains, streaks, drips spots and debris
GSAI NORMAL CLOSE 11/19/19 8:40:08 AM NO 07 61266
19-52676978 1FL Postal Men Employee RR entry door does not close all the way
GSAI NORMAL CLOSE 11/19/19 8:39:02 AM NO 07 61266
19-52783621 Grand Jury Womens RR Rm 3000B sink has hair, and other items in it, some build up around faucets
GSAI NORMAL CLOSE 11/20/19 4:14:09 PM NO 07 61266
19-52706821 2FL Probation Copy Room 2118 floor has scuff marks, streaks and stains, not uniform in appearance
GSAI NORMAL CLOSE 11/19/19 10:06:52 AM NO 07 61266
19-52706352 2FL Probation Copy Room 2118 - room inside copy room has HEAVILY STAINED tiles in Room 2118A, replace tiles and confirm no leaks
GSAI NORMAL CLOSE 11/19/19 10:05:48 AM NO 07 61266
19-52705789 2FL Womens RR Door 2134 entrance door does not close and secure
GSAI NORMAL CLOSE 11/19/19 10:04:33 AM NO 07 61266
19-52705418 2FL Hallway by doors 2529 and 2519 escutcheon missing
GSAI NORMAL CLOSE 11/19/19 10:03:46 AM NO 07 61266
19-52704823 2FL Rm 2019 Main break room floors heavily scuffed, build up of dirt and debris, heavy build up along wall base, floors not uniform in appearance
GSAI NORMAL CLOSE 11/19/19 10:02:39 AM NO 07 61266
19-52704375 2FL Rm 2102 Conf Rm replace stained tiles and check for leaks
GSAI NORMAL CLOSE 11/19/19 10:01:46 AM NO 07 61266
19-52677116 1FL Postal Storage Room 1212A sprinkler has debris hanging from it and escutcheon is missing
GSAI NORMAL CLOSE 11/19/19 9:09:14 AM NO 07 61266
19-52677107 1FL Postal Lobby Customer Service Stations have build up of dust, debris and dirt on floors and around work areas, especially heavy on the floor mats and at counter
GSAI NORMAL CLOSE 11/19/19 9:07:51 AM NO 07 61266
19-52677099 1FL Postal Lobby Floor has streaks, stains, spots and dirt/debris, not uniform in color or appearance
GSAI NORMAL CLOSE 11/19/19 9:06:12 AM NO 07 61266
19-52677092 1FL Postal Womens RR Sink has streaks and stains especially in basin around bottom
GSAI NORMAL CLOSE 11/19/19 9:05:04 AM NO 07 61266
19-52677082 1FL Womens Employee RR floor has build up of spots, stains, debris and floor has dingy color throughout
GSAI NORMAL CLOSE 11/19/19 9:03:33 AM NO 07 61266
19-52783653 3FL Grand Jury Courtroom Emergency Exit Light Blinking
GSAI NORMAL CLOSE 11/20/19 4:22:35 PM NO 07 61266
19-52783651 3FL Grand Jury Courtroom replace stained tile at emergency exit sign and check for leaks
GSAI NORMAL CLOSE 11/20/19 4:21:48 PM NO 07 61266
19-52783646 3FL Grand Jury Mens RR 3009C replace stained tiles and check for leaks
GSAI NORMAL CLOSE 11/20/19 4:20:55 PM NO 07 61266
19-52783644 3FL Grand Jury Kitchenette at 3000c replace stained tiles and check for leaks
GSAI NORMAL CLOSE 11/20/19 4:20:03 PM NO 07 61266
19-52783639 3FL Grand Jury Kitchenette at 3000c escutcheon missing
GSAI NORMAL CLOSE 11/20/19 4:18:55 PM NO 07 61266
19-52783636 Grand Jury 3FL Women RR 3000B No Toilet Paper
GSAI NORMAL CLOSE 11/20/19 4:17:57 PM NO 07 61266
19-52783634 Grand Jury 3FL 3000B Women RR Toilet seat very loose
GSAI NORMAL CLOSE 11/20/19 4:17:00 PM NO 07 61266
19-52783656 3FL Grand Jury Room 3000E escutcheon missing
GSAI NORMAL CLOSE 11/20/19 4:23:37 PM NO 07 61266
19-52752340 Per BAS and onsite observation Boiler 2 in alarm when it comes on and pumps running when both boilers off
GSAI NORMAL CLOSE 11/19/19 11:34:50 AM NO 07 61266
19-52784141 3FL US Trustee Suite has Lights out throughout
GSAI NORMAL CLOSE 11/20/19 4:36:43 PM NO 07 61266
19-52783713 3FL Back Hallway by USMS hallway and Judge Ellisons Several Llights Out
GSAI NORMAL CLOSE 11/20/19 4:34:50 PM NO 07 61266
19-52783708 3FL Women RR Room 3232 by Ellisons Courtroom loose toilet seat
GSAI NORMAL CLOSE 11/20/19 4:34:02 PM NO 07 61266
19-52783706 3FL Women RR by Ellison's Courtroom Rm 3232 Lights Out
GSAI NORMAL CLOSE 11/20/19 4:33:19 PM NO 07 61266
19-52783700 3FL Mens RR Room 3636 by Judge Ellisons Courtroom has lights out
GSAI NORMAL CLOSE 11/20/19 4:32:00 PM NO 07 61266
19-52783693 3FL Hallway between men and women RR at 3007 B AND C replace stained tile and check for leaks
GSAI NORMAL CLOSE 11/20/19 4:30:54 PM NO 07 61266
19-52783687 3FL Grand Jury Kitchette by 3007C has drips, streaks on wall
GSAI NORMAL CLOSE 11/20/19 4:30:02 PM NO 07 61266
19-52783684 3FL Grand Jury Men RR 3007C Aluminum Streaked
GSAI NORMAL CLOSE 11/20/19 4:29:13 PM NO 07 61266
19-52783677 3FL Grand Jury Men's RR 3007C Exhaust Fan has heavy build up of dust and debris
GSAI NORMAL CLOSE 11/20/19 4:27:59 PM NO 07 61266
19-52783675 3FL Grand Jury Men RR 3007C replace stained tiles and check for leaks
GSAI NORMAL CLOSE 11/20/19 4:27:04 PM NO 07 61266
19-52783672 3FL Grand Jury Women RR 3007B aluminum dispensers streaked
GSAI NORMAL CLOSE 11/20/19 4:26:17 PM NO 07 61266
19-52783665 3FL Grand Jury 3007B Womens RR toilet seat very loose
GSAI NORMAL CLOSE 11/20/19 4:25:29 PM NO 07 61266
19-52783662 3FL Grand Jury Women RR 3007B replace stained tiles and check for leaks
GSAI NORMAL CLOSE 11/20/19 4:24:39 PM NO 07 61266
19-52909955 Court IT Liebert #1 No operating - went down over the weekend
GSAI NORMAL CLOSE 11/25/19 6:51:27 AM NO 07 61266
19-52784463 3FL US Trustee has dust accumulation on horizontal surfaces, and throughout suite
GSAI NORMAL CLOSE 11/20/19 4:38:03 PM NO 07 61266
19-52786081 1FL Women RR Room 1315 by jury assembly lights out
GSAI NORMAL CLOSE 11/20/19 4:44:56 PM NO 07 61266
19-52785718 1FL Mail Room Floors have streaks and stains throughout
GSAI NORMAL CLOSE 11/20/19 4:43:26 PM NO 07 61266
19-52785524 3FL US Trustee Break room has streaks, and scuff marks on floor , not uniform in appearance
GSAI NORMAL CLOSE 11/20/19 4:42:34 PM NO 07 61266
19-52785216 3FL US Trustee Entry Foyer has debris and dust on floor
GSAI NORMAL CLOSE 11/20/19 4:41:15 PM NO 07 61266
19-52784677 3FL US Trustee Suite has some debris and trash on floors throughout especially in corners of kitchen break area, open work areas and file room
GSAI NORMAL CLOSE 11/20/19 4:39:00 PM NO 07 61266
19-53127042 Entrapment Judges Elevator GSAI SAFETY CLOSE 12/4/19 2:51:08 PM NO 07 61266
19-53127171 Entrapment Judges Elevator 12-3-19 GSAI SAFETY CLOSE 12/4/19 2:56:57 PM NO 07 61266
19-53190211 1FL USMS Break Room & Locker ROom Floors have scuff marks and are not uniform in apeparance, cove base has heavy build up of dust and film
GSAI NORMAL CLOSE 12/11/19 8:28:21 AM NO 07 61266
19-53190618 Basement Custodial Storage Room has inoperable floor machine stored
GSAI NORMAL CLOSE 12/11/19 10:28:45 AM NO 07 61266
19-53190612 Basement Storage Room by judges gym - two live large cockroaches noted upon entry
GSAI NORMAL CLOSE 12/11/19 10:27:41 AM NO 07 61266
19-53190598 Basement Custodial Storage Room by judges gym has ants all down the hallway and in front of this room
GSAI NORMAL CLOSE 12/11/19 10:24:42 AM NO 07 61266
19-53190597 1FL Custodial Closet Room 1120 Custodial sink faucet has thick green build up
GSAI NORMAL CLOSE 12/11/19 10:23:50 AM NO 07 61266
19-53190593 1FL Custodial Closet Rm 1120 Chemcials in room and no MSDS sheets posted
GSAI NORMAL CLOSE 12/11/19 10:22:57 AM NO 07 61266
19-53190587 1FL Custodial Closet Rm 1120 old dirty carpet roll on floor, old dirty rags on shelf
GSAI NORMAL CLOSE 12/11/19 10:22:04 AM NO 07 61266
19-53190572 1FL Women RR Rm1114 stall receptacle on floor - is one missing or is the one on floor need to be repaired - please fix and install correctly
GSAI NORMAL CLOSE 12/11/19 10:16:10 AM NO 07 61266
19-53190213 1FL Men RR Rm 1124 floor is dark, dull with scuff marks, stains and uneven in appearance
GSAI NORMAL CLOSE 12/11/19 8:28:59 AM NO 07 61266
19-53190725 Basement women's judicial locker/shower room faucet leaks when off
GSAI NORMAL CLOSE 12/11/19 10:52:06 AM NO 07 61266
19-53190817 2FL Large Breakroom #2019 floor has numerous scuff marks and stains throughout;
not uniform in apeparance and lacks lustre/ shine
GSAI NORMAL CLOSE 12/11/19 11:10:16 AM NO 07 61266
19-53190794 3FL Custodial Closet Rm 3409 chemicals on shelf and on cart with no MSDS
GSAI NORMAL CLOSE 12/11/19 11:05:25 AM NO 07 61266
19-53190783 3FL Custodial Closet Rm 3409 old out of service equipment stored
GSAI NORMAL CLOSE 12/11/19 11:04:16 AM NO 07 61266
19-53190755 Basement Court Employees Gym RM 3419 Ladies RR aluminum receptacles and containers have sticky light and dark stains, streaks
GSAI NORMAL CLOSE 12/11/19 10:58:54 AM NO 07 61266
19-53190743 Basement Courts employee gym restrooms have a dark orange film in bowls
GSAI NORMAL CLOSE 12/11/19 10:56:46 AM NO 07 61266
19-53190738 basement courts employee gym mat floor has dust, dirt and debris throughout
GSAI NORMAL CLOSE 12/11/19 10:55:27 AM NO 07 61266
19-53982893 Exterior building security canned lights out on Smith Street
GSAI NORMAL CLOSE 12/16/19 8:07:45 AM NO 07 61266
19-53983188 10FL Command Center has stained tiles -change tiles and check for leak
GSAI NORMAL CLOSE 12/16/19 9:58:15 AM NO 07 61266
19-53983181 10FL USMS Gym mirror streaked with dust and stains throughout
GSAI NORMAL CLOSE 12/16/19 9:57:00 AM NO 07 61266
19-53983169 10FL USMS MEn's Gym Shower Drips when off resulting in a large uneven patch of build up which is a SLIP/TRIPPING HAZARD
GSAI NORMAL CLOSE 12/16/19 9:54:21 AM NO 07 61266
19-53983158 10FL USMS Men's Gym SHower FLoor SLIP/ TRIPPING HAZARD - has very heavy build up of what appears to be mineral deposits and dirt and mildew
GSAI NORMAL CLOSE 12/16/19 9:52:02 AM NO 07 61266
19-53983144 10FL USMS GYm Air Freshener not mounted GSAI NORMAL CLOSE 12/16/19 9:48:37 AM NO 07 61266
19-53983140 10FL USMS Gym fire exntinguisher is sitting on floor
GSAI NORMAL CLOSE 12/16/19 9:47:48 AM NO 07 61266
19-53983120 B401 Basement Ladies RR Faucet leaking from base of unit
GSAI NORMAL CLOSE 12/16/19 9:38:56 AM NO 07 61266
19-53983106 10FL Gym mat floor stained, debris and sticky throughout
GSAI NORMAL CLOSE 12/16/19 9:33:10 AM NO 07 61266
19-53983098 10FL Hallways and lobbys have scuffs, scrapes, stains, lack lustre, not unifrom in appearance
GSAI NORMAL CLOSE 12/16/19 9:31:15 AM NO 07 61266
18-38219663 12th > 1st FLOOR, PERFORMED LIGHT
TOUR (VICTOR (PA)
OMI INITIAL CLOSE 1/2/19 9:00:00 AM NO 07 61266
19-39152544 Elevator 5, STUCK ON 2nd FLR W/ DOOR
OPEN #62995714 (ROBERT 6977)
UH UTILMISC CLOSE 1/22/19 8:45:00 AM NO 07 61266
19-40449048 ELEVATOR 3, NOT GOING TO CALLED
FLOOR tech called #63314144 (JIMMIE 7286)
UH UTILMISC CLOSE 2/20/19 6:30:00 PM NO 07 61266
19-39377224 B401 Women's RR cut off old locks, repair hinges for use misc hrs NTE 1 hour
UH UTILMISC CLOSE 2/5/19 8:54:12 AM NO 07 61266
19-43677656 ELEVATOR 4 & 5, NOT MOVING # 64235459
tech called (JIMMIE 8308)
UH UTILMISC CLOSE 5/14/19 3:00:00 PM NO 07 61266
19-43493896 ELEVATOR 3, STOPPING AT UNCALLED
FLOORS & MOVING SLOW TECH CALLED
#64109676 (ROBERT 8156)
UH UTILMISC CLOSE 5/2/19 10:30:00 AM NO 07 61266
19-40749238 ELEVATOR 5, NOT WORKING tech called #63400832 (Robert 7547)
UH UTILMISC CLOSE 3/5/19 1:00:00 PM NO 07 61266
19-42138281 ELEVATOR 5, DOOR CYCLING ON 12th FLR tech called #63753395 (ROBERT 7831)
UH UTILMISC CLOSE 4/1/19 8:45:00 AM NO 07 61266
19-42136449 ELEVATOR 8, STUCK ON 9 tech called
#63753395 (ROBERT 7830)
UH UTILMISC CLOSE 4/1/19 8:45:00 AM NO 07 61266
19-47715125 ELEVATOR 7, STUCK ON 7th FLR (tech called) # 65359261 (JIMMIE 9312)
UH UTILMISC CLOSE 8/14/19 3:45:00 PM NO 07 61266
19-43766579 4 ELEVATOR, LANDING HARD WHEN
STOPPING 64259467 (JIMMIE 8326)
UH UTILMISC CLOSE 5/15/19 1:00:00 PM NO 07 61266
19-44532093 ELEVATOR 4, HAD ENTRAPMENT BUT
TENANT WAS RELEASED (ROBERT 8414)
UH UTILMISC CLOSE 5/23/19 9:45:00 AM NO 07 61266
18-38256142 BLDG. Judge Weirline-RRM JUROR, SINK IN
MEN'S JUROR (ROBERT 6851)
WR SERVCALL CLOSE 1/7/19 7:30:00 AM NO 07 61266
19-39367477 P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr2_Alarm (gsa/bas
WR SERVCALL CLOSE 2/4/19 10:00:00 AM NO 07 61266
19-39460971 P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant / HwS_Temp_Alm info = Boiler didn't bring temp above 90F in 60 mins (GSA/BAS)
WR SERVCALL CLOSE 2/8/19 8:00:00 AM NO 07 61266
19-39402541 Operator 22 @ Firetron 281-452-6323 515 Rusk St. Houston TX 77002 Issue: Fire Alarm Went Off And The Fire Dept. Was Dispatched
Caller ID: 2814526323 (gsa/alarm)
WR SERVCALL CLOSE 2/6/19 7:30:00 AM NO 07 61266
19-40387867 P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant / HwS_Temp_Alm - Boiler didn't bring temp above 90F in 60 mins
WR SERVCALL CLOSE 2/13/19 7:15:00 AM NO 07 61266
19-40210698 Chillers didn't bring temp below 60F in 30 mins Tangent Down/ Fault (GSA/BAS)
WR SERVCALL CLOSE 2/11/19 7:15:00 AM NO 07 61266
19-40210824 P077KETX0211HSTN1 - Bob Casey CH, Houston
TX:CHWPumpVSD_FaultCHWPump3 Alarm Active!! (GSA/BAS)
WR SERVCALL CLOSE 2/11/19 7:15:00 AM NO 07 61266
19-40449967 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Utility / Tangent_Alarm-
Tangent Down/ Fault
WR SERVCALL CLOSE 2/21/19 8:00:00 AM NO 07 61266
19-40449320 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /
HwS_Temp_Alm-Boiler didn't bring temp above 90F in 60 mins
WR SERVCALL CLOSE 2/21/19 9:00:00 AM NO 07 61266
19-40413291 BLDG,NiagaraNetwork P077KETX0211HSTN1 - Bob Casey CH, Houston TX-Ping Failed
WR SERVCALL CLOSE 2/19/19 7:15:00 AM NO 07 61266
19-40413297 BLDG-P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /
HwS_Temp_Alm - Boiler didn't bring temp above 90F in 60 mins
WR SERVCALL CLOSE 2/19/19 7:15:00 AM NO 07 61266
19-40413294 BLDG-P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Utility / Tangent_Alarm-
Tangent Down/ Fault (GSA/BAS)
WR SERVCALL CLOSE 2/19/19 7:15:00 AM NO 07 61266
19-40704299 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /
HwS_Temp_Alm - Boiler didn't bring temp above 90F in 60 mins (GSA/BAS)
WR SERVCALL CLOSE 3/4/19 7:15:00 AM NO 07 61266
19-40672516 bldg, NiagaraNetwork P077KETX0211HSTN1
- Bob Casey CH, Houston TX - - Ping Failed
WR SERVCALL CLOSE 3/1/19 10:45:00 AM NO 07 61266
19-40672520 BLDG,P077KETX0298HSTN2 - Mickey Leland FB, Houston
TX:P077KETX0298HSTN1:AHU1_FanStatus is in Alarm
WR SERVCALL CLOSE 3/1/19 10:45:00 AM NO 07 61266
19-40992730 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -Hot
Water Supply Temp is below 90°F after being activated for 30 Minutes (GSA/BAS)
WR SERVCALL CLOSE 3/14/19 8:15:00 AM NO 07 61266
19-40797607 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -Hot
Water Supply Temp is below 90°F after being activated for 30 Minutes.(GSA/BAS)
WR SERVCALL CLOSE 3/12/19 7:15:00 AM NO 07 61266
19-40994766 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -Hot
Water Supply Temp is below 90°F after being activated for 30 Minutes. (GSA/BAS)
WR SERVCALL CLOSE 3/14/19 11:30:00 PM NO 07 61266
19-41876334 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -Hot Water
Supply Temp is below 90°F after being activated for 30 Minutes GSA/BAS
WR SERVCALL CLOSE 3/20/19 9:45:00 AM NO 07 61266
19-42009570 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chiller3_FaultCH3 - Alarm
Active!! (GSA/BAS)
WR SERVCALL CLOSE 3/23/19 11:15:00 AM NO 07 61266
19-42009582 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chiller1 / ChwS_Temp_Alm1
- - Chiller 1 Didn't bring temp below 60F in 30 mins (GSA/BAS)
WR SERVCALL CLOSE 3/23/19 11:30:00 AM NO 07 61266
19-42009580 BLDG,P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr1_Alarm - -Chiller 1
Down!! (GSA/BAS)
WR SERVCALL CLOSE 3/23/19 11:15:00 AM NO 07 61266
19-42023666 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr2_Alarm (gsa/bas)
WR SERVCALL CLOSE 3/25/19 10:00:00 PM NO 07 61266
19-42023670 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -is below 90°F after being activated for 30 Minutes.
WR SERVCALL CLOSE 3/26/19 6:00:00 AM NO 07 61266
19-42023664 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr1_Alarm- - Chiller 1 Down!!
(gsa/bas)
WR SERVCALL CLOSE 3/25/19 10:30:00 PM NO 07 61266
19-42133731 BLDGM, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr1_Alarm - -Chiller 1
Down!!
WR SERVCALL CLOSE 3/29/19 11:30:00 PM NO 07 61266
19-42009594 BLDG,P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chiller1 /
ChwS_Temp_Alm1- - Chiller 1 Didn't bring temp below 60F in 30 mins (GSA/BAS)
WR SERVCALL CLOSE 3/24/19 5:00:00 PM NO 07 61266
19-42009589 BLDG,P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr2_Alarm- - Chiller 2
Down!! (GSA/BAS)
WR SERVCALL CLOSE 3/24/19 4:30:00 PM NO 07 61266
19-42009587 BLDG,P077KETX0211HSTN1 - Bob Casey CH, Houston
TX:CWPumpVSD_FaultCWPump3 - - Alarm Active!! (GSA/BAS)
WR SERVCALL CLOSE 3/24/19 3:45:00 PM NO 07 61266
19-42009576 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr2_Alarm - -Chiller 2
Down!! (GSA/BAS)
WR SERVCALL CLOSE 3/23/19 11:45:00 AM NO 07 61266
19-42050214 1ST & 8TH FL-LIGHT OUT REPLACE IN
BOTH ELEVATOR LOBBIES-(
WR SERVCALL CLOSE 3/27/19 10:45:00 AM NO 07 61266
19-42036427 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -Hot Water
Supply Temp is below 90°F after being activated for 30 Minutes.(gsa/bas)
WR SERVCALL CLOSE 3/27/19 12:45:00 AM NO 07 61266
19-42049275 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning
Tab.
WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 61266
19-43571599 BLDG, condenser pump # leaking from seals (ROBERT EmaIled) EXTENSION 07/02/19
WR SERVCALL CLOSE 5/8/19 2:00:00 PM NO 07 61266
19-44767611 ELEVATOR 5, LOCKED ON 1st FLR-NEED
SPILL / BROKEN GLASS CLEANED UP
(CARMEN 8523)
WR SERVCALL CLOSE 6/4/19 9:45:00 AM NO 07 61266
19-44819673 DOCK/SALLY-PORT, FANS NOT WORKING
**very stuffy (ROBERT 8586)
WR SERVCALL CLOSE 6/10/19 11:00:00 AM NO 07 61266
19-47182622 OUTSIDE-BACK GATE, NEED MESS
CLEANED UP (you will need HOT water & gloves) see marshal for more info (CARMEN 9104)
WR SERVCALL CLOSE 7/29/19 8:30:00 AM NO 07 61266
19-47560384 ELEVATOR 7, STUCK ON 1st FLR tech called #65323599 (JIMMIE 9271)
WR SERVCALL CLOSE 8/12/19 8:30:00 AM NO 07 61266
19-48727221 7125 RM, DOOR NOT SECURING CLOSED
(alarm sounding) (ROBERT 9431)
WR SERVCALL CLOSE 8/28/19 9:00:00 AM NO 07 61266
19-48793835 ELEVATOR 3, STOPPING AT EACH FLOOR
& DOOR NOT OPENING #65553391 (JIMMIE
9450)
WR SERVCALL CLOSE 8/30/19 11:30:00 AM NO 07 61266
19-48793410 ELEVATOR 1, PLEASE CHECK-STUCK ON
1st FLR # 65553391 (JIMMIE 9449)
WR SERVCALL CLOSE 8/30/19 11:30:00 AM NO 07 61266
19-50307859 ELEVATOR 7, STUCK ON 1st FLR W/ DOOR
PARTIALLY OPEN # 65858542 (VICTOR
9679)
WR SERVCALL CLOSE 9/25/19 12:45:00 PM NO 07 61266
19-51379621 FREIGHT ELEVATOR, NOT GOING TO SET
FLOOR AND LIGHT NOT LITE (JIMMIE 9891)
WR SERVCALL CLOSE 10/16/19 5:00:00 PM NO 07 61266
19-52760260 Source: P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /
HwS_Temp_Alm Timestamp: 17-Nov-19 10:10:11 AM UTC State: Offnormal
Text: Boiler didn't bring temp above 90F in 60 mins (GSA/BAS) NC
WR SERVCALL CLOSE 11/17/19 5:30:00 AM NO 07 61266
19-52910295 10204 RRM, TOILET OVERFLOW (VICTOR
341) NC
WR SERVCALL CLOSE 11/25/19 9:15:00 AM NO 07 61266
19-53985269 ELEVATOR 2, ENTRAPMENT >> RELEASED
#67377523 (GUSTAVO 535) NC
WR SERVCALL CLOSE 12/16/19 7:45:00 AM NO 07 61275
19-42266337 BLDG, NiagaraNetwork P077KETX0297HSTN1 - Alliance Tower, Houston TX- - Ping Failed
CM EQFAIL CLOSE 4/7/19 2:30:00 AM NO 07 61275
19-47307307 Entrance Awning Water Leak at front building entrance EXTENSION 10/18/19
GSAI NORMAL CLOSE 7/30/19 4:34:49 PM NO 07 61275
19-42140915 ELEVATOR 4, STUCK IN BSMT DOOR
CLOSED tech called #006150920 (LEON
7835)
UH UTILMISC CLOSE 4/1/19 10:00:00 AM NO 07 61275
19-45646489 ELEVATOR 2, MAKING NOISE WHILE
MOVING #6331388 (GUSTAVO 8717)
UH UTILMISC CLOSE 6/20/19 8:45:00 AM NO 07 61275
19-46191180 ELEVATOR 4, STUCK IN BASEMENT
#006372628 (LEON 8873)
UH UTILMISC CLOSE 7/9/19 8:00:00 AM NO 07 61275
19-39366807 P077KETX0297HSTN1 - Alliance Tower, Houston TX:Chiller2 / ChwS_Temp_Alm2
(GSA/BAS)
WR SERVCALL CLOSE 2/4/19 8:15:00 AM NO 07 61275
19-40227650 NiagaraNetwork P077KETX0297HSTN1 - Alliance Tower, Houston TX - Ping Failed
(GSA/BAS)
WR SERVCALL CLOSE 2/12/19 7:15:00 AM NO 07 61275
19-40283718 P077KETX0297HSTN1 - Alliance Tower, Houston TX:Chiller3 / ChwS_Temp_Alm3 - Chiller 3 Didn't bring temp below 60F in 30 mins
WR SERVCALL CLOSE 2/12/19 8:45:00 AM NO…