BL5 Work Order History.pdf

PDF 856 KB Posted

Attached to
Full Maintenance Services for Houston, Beaumont, and Galveston, TX
Solicitation number
47PH0220R0017
Issued by

About this file

This solicitation notice outlines full maintenance service requirements for multiple federal facilities in Houston, Beaumont, and Galveston, Texas. Services include operation and maintenance, custodial work, and ground maintenance at buildings occupied by the U.S. Customs House, Bob Casey Courthouse, AllianceTower, La Branch Federal Building, Mickey Leland Federal Building and Parking Garage, and Galveston U.S. Courthouse/U.S. Post Office. Additional requirements cover operations and maintenance services at the FBI Office Building, FBI Guard House, and FBI Parking Garage in Houston as well as the Jack Brooks Federal Building in Beaumont. The solicitation number is 47PH0220R0011 and is reserved exclusively for Service-Disabled Veteran-Owned Small Businesses. The North American Industry Classification System code is 561210 for Facilities Support Services. The anticipated start date for the contract is May 1, 2021.

View the file

Other files

File Type Posted
Amendment 0004 47PH0220R0017 SF33.pdf PDF
Amendment 0004 Questions and Answers.pdf PDF
Amendment 0004 Figure B-3 Pricing of Services .xlsx XLSX spreadsheet
Amendment 0004 SF30.pdf PDF
Amendment 0003 Questions and Answers.pdf PDF
Amendment 0003 47PH0220R0017 SF33.pdf PDF
Amendment 0003 BL8 Leland Davits and Anchor Inspection Report.pdf PDF
Amendment 0003 BL7 Leland Design Guide.pdf PDF
Amendment 0003 Houston Galveston Beaumont OM_FM Spec Amend 0003 7 Jan 21.pdf PDF
47PH0220R0017 Amendment 0003.pdf PDF
Amendment 0003 BL5 Work Order History.xlsx XLSX spreadsheet
Amendment 0002 Houston Galveston Beaumont OM FM Spec 21 Dec 20.pdf PDF
Amendment 0002 BL5 Work Order History.xlsx XLSX spreadsheet
47PH0220R0017 Amendment 0002.pdf PDF
Amendment 0001 Attachment 4 Flag Policy.pdf PDF
Amendment 0001 Pre-Proposal Conference Houston Beaumont and Galveston.pptx PPTX presentation
Amendment 0001 Houston Galveston Beaumont OM_FM Spec 14 Dec 20 - Google Docs.pdf PDF
Amendment 0001 BL2 Inventory to Include Fire Alarm Devices.xlsx XLSX spreadsheet
47PH0220R0017 Amendment 0001 SF30.pdf PDF
Amendment 0001 Pre-Proposal Conference Questions and Answers.pdf PDF
Amendment 0001 Figure B-3 Pricing 5 YEAR- TOTAL_ESTIMATES.xlsx XLSX spreadsheet
BL2 Inventory to Include Fire Alarm Devices.pdf PDF
Exhibit M7 - Qualificaiton of Electrical Testing Technicians.pdf PDF
Exhibit M2 - Green Purchasing Report.pdf PDF
Figure L-3 Past Performance Questionnaire.pdf PDF
Exhibit C6 - Recycle Solid Water Trash Report.pdf PDF
Exhibit C2 Custodial Quality Assurance Surveillance Plan.pdf PDF
Exhibit C1 Building Information Sheet.pdf PDF
Attachment 1 Collective Bargaining Agreement for O_M personnel with Wage Determination.pdf PDF
Figure L-2 Management Plan Baseline.pdf PDF
Exhibit C8 - GSA Form 3638 Pest Control Work and Inspection Report.pdf PDF
Exhibit M4 - Bldg Op Plan Template.pdf PDF
Exhibit M10- PV Service Schedule V5.pdf PDF
Exhibit C4 - Building Exterior and Hardscape Plan.pdf PDF
Exhibit C7 - PBS Waste Audits.pdf PDF
47PH0220R0017 Solicitation and Specifications.pdf PDF
Exhibit M3 - Environmental Sustainable Products.pdf PDF
Figure B-1 for Union and Non Union Contracts.xlsx XLSX spreadsheet
BL6 PM Report.pdf PDF
BL3 Location General Information .pdf PDF
Exhibit C3 - Surveilence Form 1181-A.pdf PDF
Exhibit M9 Preventative Maintenance 2018 GSA OM Guide.pdf PDF
Exhibit M1 Quality Assurance Surveillance Plan.pdf PDF
Figure B-3 Pricing 5 YEAR- TOTAL_ESTIMATES.xlsx XLSX spreadsheet
Figure L-1 Management Plan Worksheet.xlsx XLSX spreadsheet
BL1- Houston_Galveston Fire Extinguisher Report.pdf PDF
Exhibit M8 - Misc Best Practices Shave Energy.pdf PDF
Exhibit M5 - Smart Buildings.pdf PDF
BL4 Roof Information.pdf PDF
Exhibit M6 Water Treatment.pdf PDF
Show 40 more

Latest 50 of 54 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4/20/20 2:43 PM 1 / 1

Houston 1 year of work orders Work Order Description Work Type

Work Sub- Type Status Asset Target Start

Dynamic Job Plan applied Site Location

19-42048222 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning

Tab.

WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 173735

19-42048223 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning

Tab.

WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 173736

19-51751306 827 RM, Replace carpet tile in the following cubes: 8W-21, 8W-23, 8W-15, 8W-19, 8W-25, 8W-12, 8W-09, 8W-27 (RONNIE/NOE/Email)

EXT 12/23/19

WR SERVCALL CLOSE 11/1/19 12:45:00 PM NO 07 60567

18-38237516 GYM, SHOWER SPRAY NOZZLE LEAKING

WHEN TURNED ON

WR SERVCALL CLOSE 1/4/19 2:15:00 PM NO 07 60567

19-42048751 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning

Tab.

WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 60567

19-43766613 BLDG, Mailroom door stop broken WR SERVCALL CLOSE 5/15/19 1:18:22 PM NO 07 60567

19-43766649 bldg, Mailroom processing door not closing properly (eMIALED)

WR SERVCALL CLOSE 5/15/19 1:15:00 PM NO 07 60567

19-51808172 BLDG., Source: P077KETX0701HSTN1 - LaBranch FB, Houston TX:Chillers /

ChwS_Temp_Alm Timestamp: 06-Nov-19 6:50:44 PM UTC State: Offnormal

Text: Chillers didn't bring temp below 60F in 15 mins (GSA/BAS) NC

WR SERVCALL CLOSE 11/6/19 1:45:00 PM NO 07 60648

19-42266326 BLDG, NiagaraNetwork P077KETX0701HSTN1 - LaBranch FB, Houston TX- - Ping Failed

CM EQFAIL CLOSE 4/7/19 2:30:00 AM NO 07 60648

19-44723696 bldg, NiagaraNetwork P077KETX0701HSTN1

- LaBranch FB, Houston TX - -Ping Failed

(BAS/GSA)

CM EQFAIL CLOSE 6/1/19 9:15:00 PM NO 07 60648

19-47599834 add NiagaraNetwork P077KETX0701HSTN1 - LaBranch FB, Houston TX - to equipment inventory

CM EQFAIL CLOSE 8/13/19 10:42:12 AM NO 07 60648

19-48867157 BLDG.,P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 / Tangent_Alarm

Timestamp: 02-Sep-19 1:01:14 PM UTC State: Offnormal Text: Tangent Down/

Fault (GSA/.BAS)

CM EQFAIL CLOSE 9/2/19 9:00:00 AM NO 07 60648

19-48866987 BLDG., Source: P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 /

Tangent_Alarm Timestamp: 01-Sep-19 8:54:02 PM UTC State: Offnormal

Text: Tangent Down/ Fault (GSA/BAS)

CM EQFAIL CLOSE 9/1/19 4:45:00 PM NO 07 60648

19-51746906 BLDG, P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 / Tangent_Alarm - -

Tangent Down/ Fault (GSA/BAS)

CM EQFAIL CLOSE 11/1/19 2:00:00 PM NO 07 60648

19-51746668 BLDG., P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 / Tangent_Alarm ;

Tangent Down/ Fault (GSA.BAS)

CM EQFAIL CLOSE 11/1/19 9:00:00 AM NO 07 60648

19-51770475 BLDG., P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 / Tangent_Alarm

Timestamp: 04-Nov-19 2:01:14 PM UTC State: Offnormal Text: Tangent Down/

Fault (GAS/BAS)

CM EQFAIL CLOSE 11/4/19 9:15:00 AM NO 07 60648

19-51770453 BLDG., P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 / Tangent_Alarm

Timestamp: 02-Nov-19 1:01:13 PM UTC State: Offnormal Text: Tangent Down/

Fault (GSA/BAS)

CM EQFAIL CLOSE 11/2/19 9:15:00 AM NO 07 60648

19-51803719 Source: P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 /

Tangent_Alarm Timestamp: 06-Nov-19 2:01:14 PM UTC State: Offnormal

Text: Tangent Down/ Fault (GSA/BAS)

NC

CM EQFAIL CLOSE 11/6/19 12:15:00 PM NO 07 60648

19-51803643 Source: P077KETX0701HSTN1 - LaBranch FB, Houston TX:io16_2 /

Tangent_Alarm Timestamp: 06-Nov-19 2:01:14 PM UTC State: Offnormal Text:

Tangent Down/ Fault (GSA/BAS) NC

CM EQFAIL CLOSE 11/6/19 9:15:00 AM NO 07 60648

18-38224414 TX0701- Electrical panel not labeled @ room

GSAI NORMAL CLOSE 1/3/19 9:34:23 AM NO 07 60648

18-38224445 TX0701- components missing from double door closing coordinator @ interior parking lot entrance extension 02-27-19

GSAI NORMAL CLOSE 1/3/19 9:41:25 AM NO 07 60648

19-39368649 TX0701- BAS-CHW DP=31.04 psi setpoint is

9.00 psi

GSAI NORMAL CLOSE 2/4/19 11:08:38 AM NO 07 60648

19-45630092 Someone replaced the tile in the conference room suite 1103 on May 20th as requested, however, the new tile is now brown. Please have someone fix the problem in the conference room ceiling.

GSAI NORMAL CLOSE 6/19/19 10:17:28 AM NO 07 60648

19-39173014 BUILDING, ORDER HOSE FOR

EXTRACTOR MACHINE Extension

02/13/2019

OMI INITIAL CLOSE 1/24/19 9:15:00 AM NO 07 60648

19-40390083 BLDG, NiagaraBLDG, Network P077KETX0701HSTN1 - LaBranch FB, Houston TX-Ping Failed

WR SERVCALL CLOSE 2/14/19 7:15:00 AM NO 07 60648

19-40727785 BLDG, P077KETX0701HSTN1 - LaBranch FB, Houston TX:Boiler / HwS_Temp_Alm -

Boiler didn't bring temp above 90F in 60 mins

WR SERVCALL CLOSE 3/4/19 12:30:00 PM NO 07 60648

19-42048822 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning

Tab.

WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 60648

19-50492875 SOUTH PEDESTRIAN ELEVATOR, NOT

WORKING (RONALD 9801)

WR SERVCALL CLOSE 10/8/19 7:15:00 AM NO 07 61252

19-51747073 BLDG, P07QMETX0019BMT1 - Beaumont TX:Points / Twr2IsoAlarm - - Tower Faulted!!

(GSA/BAS)

CM EQFAIL CLOSE 11/1/19 2:00:00 PM NO 07 61252

19-51746691 BLDG,P07QMETX0019BMT1 - Beaumont TX:Points / Twr1IsoAlarm -Tower Faulted!!

(GSA/BAS)

CM EQFAIL CLOSE 11/1/19 3:30:00 AM NO 07 61252

19-39023895 3FL probation hallway near roof access door stained tiles, check for leaks, replace tiles

GSAI NORMAL CLOSE 1/16/19 7:59:21 AM NO 07 61252

19-39026725 Roof Cooling Tower heavy build up noted on the bottoms of the fill tiles, water was clear, no scale or build up noted inside tower

EXTENSION 02/01/19

GSAI NORMAL CLOSE 1/16/19 8:22:21 AM NO 07 61252

19-39025275 Chiller #1 Alarm panel showed several alarms "Returned CHWT is lower than cooling SP

Fault";

GSAI NORMAL CLOSE 1/16/19 8:10:43 AM NO 07 61252

19-39025182 3FL in front of door 301 probation hallway fan louder than expected, check for need maintenance and operational issues

GSAI NORMAL CLOSE 1/16/19 8:09:55 AM NO 07 61252

19-39024771 3FL roof access hallway behind door 301 stained tiles, check for leaks, replace tiles

GSAI NORMAL CLOSE 1/16/19 8:06:41 AM NO 07 61252

19-41862350 TX0019- Contact electrical utility- electrical entry well flooded. Has sump pump which looks to be inoperable

GSAI NORMAL CLOSE 3/18/19 4:20:03 PM NO 07 61252

19-42110648 TX0019- Review NCMMS equipment inventory. Use BAS naming convention to correct asset descriptions EXTENSION 8/9/19

GSAI NORMAL CLOSE 3/30/19 12:16:21 PM NO 07 61252

19-42110652 TX0019- Yellow Tag- FAILED MAIN DRAIN-

PIPING PVC: DRAIN CAN NOT ACCEPT

FULL FLOW EXTENSION 10/5/19 HOU-174

WAITING ON QUOTES

GSAI NORMAL CLOSE 3/30/19 12:33:07 PM NO 07 61252

19-42110649 TX0019- Verify all backflow preventers are on NCMMS inventory

GSAI NORMAL CLOSE 3/30/19 12:18:52 PM NO 07 61252

19-42171191 remove RR from plenum discharge and re-route

GSAI NORMAL CLOSE 4/2/19 7:49:36 AM NO 07 61252

19-42172817 north pedestrian gate into back parking lot (broadwayside) doesn't secure/close without pulling it

GSAI NORMAL CLOSE 4/2/19 9:12:43 AM NO 07 61252

19-42171249 four lobby lights out EXTENSION 6/15/19 GSAI NORMAL CLOSE 4/2/19 8:18:25 AM NO 07 61252

19-42171228 lights stored improperly in Judge Heartfield's IT Closet

GSAI NORMAL CLOSE 4/2/19 8:10:51 AM NO 07 61252

19-42171201 provide quote back lot parking signs/cards brown cards with white letters, laminated

EXTENSION 8/9/19

GSAI NORMAL CLOSE 4/2/19 7:59:13 AM NO 07 61252

19-42241832 1FL Giblin Jury Room Water Fountain Non Operational - REPEAT ITEM

GSAI NORMAL CLOSE 4/4/19 5:45:03 PM NO 07 61252

19-42241842 1FL Jury Room Wall paper peeling at double door

GSAI NORMAL CLOSE 4/4/19 5:51:20 PM NO 07 61252

19-42241835 1FL Jury Assembly Room Cut Ceiling Tile At Side Counter

GSAI NORMAL CLOSE 4/4/19 5:48:04 PM NO 07 61252

19-42241834 1FL Jury Room Entrance Door Interior Emergency Exit Light failed test

GSAI NORMAL CLOSE 4/4/19 5:47:08 PM NO 07 61252

19-42232043 sticky greasy substance running down walls in sallyport from equipment, check for leaks, clean area and equipment

GSAI NORMAL CLOSE 4/3/19 4:30:19 PM NO 07 61252

19-42280980 bldg, have the fire alarm at Jack Brooks put into test starting immediately 2:30p until we are able to complete installation of the mag locks on the stairwell doors approximately 6 p.m. tonight (eMAIL)

GSAI SAFETY CLOSE 4/9/19 4:00:00 PM NO 07 61252

19-42241844 1FL Bankruptcy Judge's RR Fan Not Operating GSAI NORMAL CLOSE 4/4/19 5:53:10 PM NO 07 61252

19-42241847 1FL Judge Giblins swinging door from gallery into pit making noise when in use

GSAI NORMAL CLOSE 4/4/19 5:56:19 PM NO 07 61252

19-43204518 BLDG, rePlace electrical conductivity mats in front of equipment at TX0019ZZ using govt furnished matls (LEENETTE GSAI)

GSAI SAFETY CLOSE 4/22/19 7:45:39 AM NO 07 61252

19-44494571 replace worn toiilet seats in men's public rr 1FL by freight elevator

GSAI NORMAL CLOSE 5/23/19 12:54:54 PM NO 07 61252

19-44494618 1FL men's RR by freight elevator has rust on urinal panel

GSAI NORMAL CLOSE 5/23/19 1:11:32 PM NO 07 61252

19-44416850 USMS 1st Floor high humidity, stuff througout GSAI NORMAL CLOSE 5/21/19 4:19:11 PM NO 07 61252

19-43820757 outside water faucets do not work

EXTENSION 9/13/19

GSAI NORMAL CLOSE 5/17/19 10:00:00 AM NO 07 61252

19-44861057 BLDG., do some small touch ups of painting in a couple areas to be field verified by Mona Doyle, Clerk of the Courts - EMAIL -GSAI

GSAI NORMAL CLOSE 6/11/19 10:30:00 AM NO 07 61252

19-44862432 BLDG, small hole in a wall from a desk that was pushed over happened apparently during work on the HVAC system the other night while the workers were working overnight

WW please field verify location, patch and paint the hole (EMAIL-GSAI)

GSAI NORMAL CLOSE 6/11/19 10:30:00 AM NO 07 61252

19-45569576 BLDG, purchase sheeting and install as quickly as possibly GSAI-LEENNETTE

GSAI NORMAL CLOSE 6/17/19 8:30:00 AM NO 07 61252

19-47006292 TX0019- BAS VAV 6 not maintaining space setpoint

GSAI NORMAL CLOSE 7/17/19 8:21:53 AM NO 07 61252

19-50307912 at least 3 backflow preventers missing from NCMMS Inventory

GSAI NORMAL CLOSE 9/26/19 6:40:04 AM NO 07 61252

19-53128394 3FL Probation Supervisor Adam Graves stained tiles - replace tiles and check for leaks

GSAI NORMAL CLOSE 12/5/19 8:46:26 AM NO 07 61252

19-54241923 Basement USMS Men's RR SHowerhead leaks from connection

GSAI NORMAL CLOSE 12/19/19 4:05:26 PM NO 07 61252

18-38219489 COURTS, LIGHTS NOT WORKING

(ANDREW (PA)

OMI INITIAL CLOSE 1/2/19 2:00:00 PM NO 07 61252

19-49128878 RFQ to repair burn at pumps in basement UP NORMAL CLOSE 9/11/19 8:54:57 AM NO 07 61252

19-40387864 P07QMETX0019BMT1 - Beaumont TX:Boilers / HwS_Temp_Alm2 - Boiler didn't bring temp above 90F in 60 mins

WR SERVCALL CLOSE 2/13/19 7:15:00 AM NO 07 61252

19-40390751 BLDG, P07QMETX0019BMT1 - Beaumont TX:Boilers / HwS_Temp_Alm1- Boiler didn't bring temp above 90F in 60 mins

WR SERVCALL CLOSE 2/14/19 12:00:00 PM NO 07 61252

19-40759192 104 RM, SINK IN CLERKS OFFICE DRAINS

SLOW ( RONALD 7552)

WR SERVCALL CLOSE 3/6/19 9:30:00 AM NO 07 61252

19-40794059 BLDG, JUDGES ENTRANCE NORTH SIDE

NOT SECURING (LOCKED) (RONALD 7590)

WR SERVCALL CLOSE 3/8/19 3:15:00 PM NO 07 61252

19-43374883 STAIRWELL - BLDG, REPORT THAT

TENANT GET STUCK IN AREA -SEE Email

(Ronald, Andrew & Email 8100)

WR SERVCALL CLOSE 4/29/19 12:45:00 PM NO 07 61252

19-45630234 BLDG, Provide weekly update for hvac issues including temp and humidity readings (GSAI

LEENETTE

WR SERVCALL CLOSE 6/19/19 10:30:00 AM NO 07 61252

19-45583468 Judge Truncale’s clerks-a keyboard pullout that he would like removed-(EMAILO) 6/18/19

WR SERVCALL CLOSE 6/18/19 3:15:00 PM NO 07 61252

19-47036818 BLDG, FIRE PANEL NOT COMMUNICATION

W/ DENVER MEGA CENTER (NATHAN)

WR SERVCALL CLOSE 7/23/19 8:30:00 AM NO 07 61256

18-38233526 BLDG, ESCORT WINDOW WASHERS

(NATHAN (PA)

CM CORRECT CLOSE 1/3/19 9:15:00 AM NO 07 61256

18-38233496 building, ESCORT AT & T TECH IN VARIOUS

AREA (NATHAN (PA)

CM CORRECT CLOSE 1/3/19 8:30:00 AM NO 07 61256

19-42266333 BLDG, NiagaraNetwork P077KETX0081GVTN1 - Galveston, TX- -Ping

Failed

CM EQFAIL CLOSE 4/7/19 2:30:00 AM NO 07 61256

19-42266353 BLDG, P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm- - Chillers didn't bring temp below 60F in 30 mins

CM EQFAIL CLOSE 4/7/19 4:15:00 AM NO 07 61256

19-42810087 P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - - Chillers didn't bring temp below 60F in 30 mins (gsa/ bas)

CM EQFAIL CLOSE 4/16/19 9:00:00 PM NO 07 61256

19-43290659 bldg, P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - -Chillers didn't bring temp below 60F in 30 mins (gsa/ bas)

CM EQFAIL CLOSE 4/22/19 10:00:00 AM NO 07 61256

19-39026559 Water testing logs shows inhibitor and conductivity out of range

GSAI NORMAL CLOSE 1/16/19 8:21:02 AM NO 07 61256

19-42110661 TX0081- IR testing overdue for breakers on main switchgear DPN Panel

GSAI NORMAL CLOSE 3/30/19 1:44:22 PM NO 07 61256

19-42110667 TX0081- NCMMS create assets for IR testing equipment that is missing from equipment inventory (attach uploader)

GSAI NORMAL CLOSE 3/30/19 1:59:03 PM NO 07 61256

19-42110666 TX0081- IR testing overdue for breakers on main switchgear TDPLV

GSAI NORMAL CLOSE 3/30/19 1:57:44 PM NO 07 61256

19-42110665 TX0081- IR testing overdue for breakers on main switchgear TEMG

GSAI NORMAL CLOSE 3/30/19 1:57:25 PM NO 07 61256

19-42110664 TX0081- IR testing overdue for breakers on main switchgear WCH-2

GSAI NORMAL CLOSE 3/30/19 1:57:01 PM NO 07 61256

19-43352361 TX0081- BAS Chiiler Lag point is overridden

OFF

GSAI NORMAL CLOSE 4/29/19 10:39:05 AM NO 07 61256

19-43453701 TX0081- BAS Tune cooling tower PID GSAI NORMAL CLOSE 5/1/19 8:55:12 AM NO 07 61256

19-47185248 TX0081- BAS Chiller sequence point overridden

GSAI NORMAL CLOSE 7/29/19 9:44:07 AM NO 07 61256

18-38254632 BLDG, NEED ESCORT FOR WINDOW

WASHERS (NATHAN (PA)

UH UTILMISC CLOSE 1/4/19 8:00:00 AM NO 07 61256

19-39315204 502 RM, MAKE 10 KEYS MARSHAL BACK

DOOR (Nathan 7097)

UH UTILMISC CLOSE 1/31/19 11:00:00 AM NO 07 61256

18-38237550 BLDG, TOO HOT IN COURTROOM

(NATHAN)

WR SERVCALL CLOSE 1/4/19 3:00:00 PM NO 07 61256

18-38237553 BLDG, PRISONER ELEV STUCK IN

BASEMENT AND ALARMS SOUNDING

(NATHAN)

WR SERVCALL CLOSE 1/4/19 3:00:00 PM NO 07 61256

19-38286925 BLDG, JUDGE EDISON COURTS, NEED

KEY MADE (NATHAN )

WR SERVCALL CLOSE 1/9/19 8:00:00 AM NO 07 61256

19-38286938 BLDG, NEED KEY MADE (NATHAN) WR SERVCALL CLOSE 1/9/19 8:00:00 AM NO 07 61256

19-39420684 3rd FLR RRM, LIGHT OUT IN CUSTODIAL

CLOSET (NATHAN )

WR SERVCALL CLOSE 2/6/19 6:00:00 PM NO 07 61256

19-40210602 P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm Chillers didn't bring temp below 60F in 30 mins

WR SERVCALL CLOSE 2/11/19 7:15:00 AM NO 07 61256

19-39420683 NiagaraNetwork P077KETX0081GVTN1 - Galveston, TX PING FAILED (GSA/BAS)

WR SERVCALL CLOSE 2/7/19 7:30:00 PM NO 07 61256

19-40388804 P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - Chillers didn't bring temp below 60F in 30 mins

WR SERVCALL CLOSE 2/13/19 12:30:00 PM NO 07 61256

19-40282898 P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm -Chillers didn't bring temp below 60F in 30 mins (GSA/BAS)

WR SERVCALL CLOSE 2/12/19 6:30:00 AM NO 07 61256

19-40658931 BLDG, ELECTRICAL OUTLET PUSHED

INTO WALL - NO POWER ACCESSIBILITY

(NATHAN)

WR SERVCALL CLOSE 2/28/19 7:30:00 AM NO 07 61256

19-40748591 BLDG, Hot Water Supply Temp Below 90°F After Being Enabled for 30 Minutes. - Chillers didn't bring temp below 60F in 30 mins

WR SERVCALL CLOSE 3/5/19 2:00:00 PM NO 07 61256

19-40797626 DOCK, MAKE KEY FOR REAR DOCK

ENTRANCE (EMAILED 7617)

WR SERVCALL CLOSE 3/12/19 7:15:00 AM NO 07 61256

19-41860573 BLDG., P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - - Chillers didn't bring temp below 60F in 30 mins

WR SERVCALL CLOSE 3/16/19 10:45:00 AM NO 07 61256

19-42133560 BLDG, P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - -Chillers didn't bring temp below 60F in 30 mins

WR SERVCALL CLOSE 3/29/19 9:00:00 PM NO 07 61256

19-42049266 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning

Tab.

WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 61256

19-43576786 bldg, P077KETX0081GVTN1 - Galveston, TX:Chillers / ChwS_Temp_Alm - -Chillers didn't bring temp below 60F in 30 mins

WR SERVCALL CLOSE 5/10/19 3:45:00 AM NO 07 61256

19-42049267 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning

Tab.

WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 61257

19-40748488 bldg, P077KETX0101HSTN1 - Customs House (Houston Texas):HWSupplyTempAlm -

Hot Water Supply Temp Below 90°F After Being Enabled for 30 Minutes.

CM EQFAIL CLOSE 3/5/19 2:00:00 PM NO 07 61257

19-42266321 BLDG, NiagaraNetwork P077KETX0101HSTN3 - Customs House

(Houston Texas) - - Ping Failed

CM EQFAIL CLOSE 4/7/19 2:30:00 AM NO 07 61257

19-42266343 BLDG, NiagaraNetwork P077KETX0101HSTN2 - Customs House

(Houston Texas) Platform Connection- - Ping Failed

CM EQFAIL CLOSE 4/7/19 2:30:00 AM NO 07 61257

19-51770478 BLDG., P077KETX0101HSTN1 - Customs House (Houston Texas):Basement MBB_5

Has Lost Communications (GSA.BAS)

CM EQFAIL CLOSE 11/4/19 9:15:00 AM NO 07 61257

18-38256312 ELEVATOR #1, STUCK ON 3rd FLR DOORS

CLOSED #005953386 (ISISDOR 6852)

WR SERVCALL CLOSE 1/7/19 8:15:00 AM NO 07 61257

19-39479052 P077KETX0101HSTN1 - Customs House (Houston

Texas):P077KETX0101HSTN2:MB2_23 Room 260 Zone Temperature - is at 80.6 °F which is above the high limit of 80.0 °F!

WR SERVCALL CLOSE 2/8/19 3:00:00 PM NO 07 61257

19-39462422 P077KETX0101HSTN1 - Customs House (Houston Texas):HWSupplyTempAlm = Hot Water Supply Temp Below 90°F After Being

Enabled for 30 Minutes.(GSA/BAS)

WR SERVCALL CLOSE 2/8/19 8:00:00 AM NO 07 61257

19-40449044 BLDG, P077KETX0101HSTN1 - Customs House (Houston Texas):HWSupplyTempAlm-ot Water Supply Temp Below 90°F After Being Enabled for 30 Minutes. (REF #40427437)

WR SERVCALL CLOSE 2/20/19 7:00:00 AM NO 07 61257

19-40427437 BLDG, P077KETX0101HSTN1 - Customs House (Houston Texas):HWSupplyTempAlm-ot Water Supply Temp Below 90°F After Being Enabled for 30 Minutes.

WR SERVCALL CLOSE 2/20/19 7:15:00 AM NO 07 61257

19-54351134 5300 RM, BLACK STUFF COMING FROM A/

C VENTS (JIMMIE 677) NC

WR SERVCALL CLOSE 12/31/19 2:50:13 PM NO 07 61266

19-39168150 TX0211ZZ.EL-1 - Building Running Too Late CM GLINK CLOSE 1/23/19 7:54:51 AM NO 07 61266

19-39168154 TX0211ZZ.EL-1 - Maximum Demand During Unoccupancy

CM GLINK CLOSE 1/23/19 7:56:00 AM NO 07 61266

19-39168152 TX0211ZZ.EL-1 - Short Demand Peak CM GLINK CLOSE 1/23/19 7:55:22 AM NO 07 61266

19-39168151 TX0211ZZ.EL-1 - Building Starting Too Early CM GLINK CLOSE 1/23/19 7:55:03 AM NO 07 61266

19-40991720 TX0211ZZ.EL-1 - Building Starting Too Early CM GLINK CLOSE 3/13/19 1:53:11 PM NO 07 61266

19-40991730 TX0211ZZ.CW - Maximum Demand During Unoccupancy

CM GLINK CLOSE 3/13/19 1:54:27 PM NO 07 61266

19-40991725 TX0211ZZ.EL-1 - Short Demand Peak CM GLINK CLOSE 3/13/19 1:53:44 PM NO 07 61266

19-40991733 TX0211ZZ.DW-1 - Excessive Water Usage During Unoccupancy

CM GLINK CLOSE 3/13/19 1:54:39 PM NO 07 61266

19-42266322 BLDG, NiagaraNetwork P077KETX0211HSTN1 - Bob Casey CH, Houston TX- - Ping Failed

CM EQFAIL CLOSE 4/7/19 8:30:00 AM NO 07 61266

19-42635844 Source: P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /

HwS_Temp_Alm Timestamp: 14-Apr-19 3:09:00 AM CDT State: Offnormal Text: Boiler didn't bring temp above 90F in 60 mins-

(EMAIL) 4/15/19

CM EQFAIL CLOSE 4/15/19 1:30:00 PM NO 07 61266

19-43432266 TX0211ZZ.EL-1 - Short Demand Peak CM GLINK CLOSE 4/30/19 8:21:24 PM NO 07 61266

19-43432270 TX0211ZZ.EL-1 - Maximum Demand During Unoccupancy

CM GLINK CLOSE 4/30/19 8:22:15 PM NO 07 61266

19-43432268 TX0211ZZ.EL-1 - Building Running Too Late CM GLINK CLOSE 4/30/19 8:21:52 PM NO 07 61266

19-43432267 TX0211ZZ.EL-1 - Building Starting Too Early CM GLINK CLOSE 4/30/19 8:21:37 PM NO 07 61266

19-51770462 BLDG., P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /

HwS_Temp_Alm Timestamp: 02-Nov-19 1:07:03 PM UTC State: Offnormal

Text: Boiler didn't bring temp above 90F in 60 mins (BAS/GSA)

CM EQFAIL CLOSE 11/2/19 9:15:00 AM NO 07 61266

19-54275288 BLDG. Source: P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant / HwS_Temp_Alm Timestamp: 21-Dec-19

11:03:27 PM CST State: Offnormal Text: Boiler didn't bring temp above 90F in 60 mins (GSA/BAS) NC

CM EQFAIL CLOSE 12/21/19 12:15:00 PM NO 07 61266

19-54245583 BLDG., Source: P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant / HwS_Temp_Alm Timestamp: 19-Dec-19

8:21:00 PM CST State: Offnormal Text: Boiler didn't bring temp above 90F in 60 mins (bas/gsa) NC

CM EQFAIL CLOSE 12/19/19 9:30:00 PM NO 07 61266

18-38223334 Judge Bryan's Jury Room Restrooms - Both RR floors have very dark discolored grout, lack lustre, stains and streaks, build up along wall base and thresholds

GSAI NORMAL CLOSE 1/3/19 8:32:42 AM NO 07 61266

18-38224116 4FL 4616 Bankruptcy Hallway Secured Doors do not shut or secure without manual action

GSAI NORMAL CLOSE 1/3/19 8:50:31 AM NO 07 61266

18-38224111 1FL dining room entrance from jury lobby escutcheon missing

GSAI NORMAL CLOSE 1/3/19 8:48:41 AM NO 07 61266

18-38224106 1FL Jury Assembly Hallway missing escushion by men's public rr near exit door

GSAI NORMAL CLOSE 1/3/19 8:46:31 AM NO 07 61266

18-38224101 1FL 1315 RR lights out GSAI NORMAL CLOSE 1/3/19 8:45:21 AM NO 07 61266

18-38224098 8FL 8405 Men's Public RR lights out GSAI NORMAL CLOSE 1/3/19 8:44:10 AM NO 07 61266

18-38224073 1FL Jury Room Hallways lack lustre, streaks and variations in finish, streaks, scuff marks, stains and build up along wall base and thresholds

GSAI NORMAL CLOSE 1/3/19 8:42:48 AM NO 07 61266

18-38224006 7FL 7415 Women Public RR Lights out GSAI NORMAL CLOSE 1/3/19 8:41:16 AM NO 07 61266

19-38339209 Chiller #3 OVER AMPING - possible programming issues causing ALARMS and over amping

GSAI NORMAL CLOSE 1/11/19 4:05:29 PM NO 07 61266

18-38225093 12FL 12118 tile grout has marked difference in color between the edges of the walls and partition bases and the rest of the floor; much of it is very dark and stained

GSAI NORMAL CLOSE 1/3/19 11:08:27 AM NO 07 61266

18-38225091 12FL 12124 Men's RR lights out GSAI NORMAL CLOSE 1/3/19 11:07:37 AM NO 07 61266

18-38225085 12FL Hallway by 12628 missing escutcheon GSAI NORMAL CLOSE 1/3/19 11:06:29 AM NO 07 61266

18-38225081 12FL 12118 Womens RR Exhaust fan making loud noises, cycling on and off continuosly and quickly

GSAI NORMAL CLOSE 1/3/19 11:05:28 AM NO 07 61266

18-38225077 Judge Elrod Breakroom stainless surfaces are streaked, showing possible water spots and drips

GSAI NORMAL CLOSE 1/3/19 11:04:52 AM NO 07 61266

18-38225071 7FL 7104 USAO Visitor Lobby Carpet Stains GSAI NORMAL CLOSE 1/3/19 11:03:54 AM NO 07 61266

18-38225050 1FL Mail Room Floors show numerous heavy streaks, scuff marks and dark stains; not uniform in finish and lacks lustre, build up along walls and thresholds

GSAI NORMAL CLOSE 1/3/19 10:59:13 AM NO 07 61266

18-38225043 1FL Freight Elevator Lobby Floor Floors show streaks, scuff marks, and dark stains; floor not uniform in finish and lacks lustre , build up along wall and thresholds

GSAI NORMAL CLOSE 1/3/19 10:58:07 AM NO 07 61266

18-38225032 1FL Lobby Entry/Lobby between elevators/ mail room and Jury AssemblyFloors show streaks, scuff marks, and dark stains; floor not uniform in finish and lacks lustre , build up along wall and threshold

GSAI NORMAL CLOSE 1/3/19 10:56:00 AM NO 07 61266

18-38224130 fire panel trouble alarms, possible reimburseable service troubleshoot, provide estimate and justification to GSA immediately

GSAI NORMAL CLOSE 1/3/19 8:55:11 AM NO 07 61266

18-38224118 7FL Rm 7409 Men's Public RR lights out GSAI NORMAL CLOSE 1/3/19 8:51:13 AM NO 07 61266

18-38233770 USMS Guard Shack on Smith Street ROOF

LEAKS

GSAI NORMAL CLOSE 1/4/19 12:08:53 PM NO 07 61266

18-38233775 Smith Street USMS Guard Shack Water in building, under mat, office needs custodial service - ple

GSAI NORMAL CLOSE 1/4/19 12:10:36 PM NO 07 61266

18-38225141 12FL 12124 Mens RR tile grout has marked difference in color between the edges of the walls and parition bases and the rest of the floor which is very dark and stained in appearance

GSAI NORMAL CLOSE 1/3/19 11:16:47 AM NO 07 61266

18-38225149 12FL Back Secured Tile aroudn MCH Rooms through to DOJ and Freight/Judicial Elevators numerous streaks, scuff marks and stains throughout, not uniform in appearance, lacks lustre, very heavy build up around elevators and DOJ/Vacant Suite entrances

GSAI NORMAL CLOSE 1/3/19 11:18:06 AM NO 07 61266

19-39019550 Smith Street Guard Shack shows lack of mopping, sweeping, vacuuming per contract

GSAI NORMAL CLOSE 1/16/19 7:24:31 AM NO 07 61266

19-39019711 Smith Street Guard Shack Windows streaked and grimy

GSAI NORMAL CLOSE 1/16/19 7:25:46 AM NO 07 61266

19-39377153 Basement Shop has Numerous red tag fire extinguishers stored on floor; in cabinets/ lockers, stacked on top of cabinets/lockers need to be removed

GSAI FIRE CLOSE 2/5/19 8:32:12 AM NO 07 61266

19-39377161 Basement Shop - Several boxes of used bulbs sitting on floor, on top of shop table dating back to August 2018 need to be removed

GSAI NORMAL CLOSE 2/5/19 8:34:57 AM NO 07 61266

19-39377157 Several boxes of used bulbs sitting on floor, on top of shop table dating back to August

2018 need to be removed

GSAI NORMAL CLOSE 2/5/19 8:33:23 AM NO 07 61266

19-39377171 Basement Shop - old equipment sitting on floors, tables

GSAI NORMAL CLOSE 2/5/19 8:39:04 AM NO 07 61266

19-39391442 1FL 1010 Vending Room has dark and rust colored stains on floor around vending machines

GSAI NORMAL CLOSE 2/5/19 11:24:29 AM NO 07 61266

19-39391438 3FL Rm3132 Women RR Lights Out GSAI NORMAL CLOSE 2/5/19 11:23:56 AM NO 07 61266

19-39391426 3FL #3132 Women RR sanitary receptacle plate missing, basket falls on the floor during each use

GSAI NORMAL CLOSE 2/5/19 11:21:22 AM NO 07 61266

19-39390704 Basement Shop Consolidate flammables per code and discard rusted, painted, lockers/ cabinets that do not latch , have holes and/or not secure

GSAI SAFETY CLOSE 2/5/19 10:42:55 AM NO 07 61266

19-39390694 B417 Hallway Door at Basement doorknob does not secure; is loose, and will not lock all time

GSAI NORMAL CLOSE 2/5/19 10:41:40 AM NO 07 61266

19-39390672 Hallway outside Mechanic Office at B520 missing outlet cover

GSAI NORMAL CLOSE 2/5/19 10:40:52 AM NO 07 61266

19-39377213 B401 Womens RR light out GSAI NORMAL CLOSE 2/5/19 8:50:21 AM NO 07 61266

19-39377212 Basement Shop - several pieces of old equipment, computers, dusty found flammable lockers/cabinets and old documents need to be discarded

GSAI NORMAL CLOSE 2/5/19 8:48:54 AM NO 07 61266

19-42231100 back lot pedestrian exit gate frame is loose at wall, possibly needs anchor bolt tighented or replaced?

GSAI NORMAL CLOSE 4/3/19 3:49:41 PM NO 07 61266

19-42171276 Chiller 3 LAPSE in BAS ALARM NOTIFICATIONS, Programming Problems

GSAI NORMAL CLOSE 4/2/19 8:26:29 AM NO 07 61266

19-42238252 troubleshoot fire system alarms going off right after midnight repeatedly

GSAI FIRE CLOSE 4/3/19 7:03:00 AM NO 07 61266

19-42241812 Room 5020 Womens RR Toilet coming off the wall, needs repaired or replaced

GSAI NORMAL CLOSE 4/4/19 5:29:31 PM NO 07 61266

19-43311103 annual tree assessment overdue GSAI NORMAL CLOSE 4/25/19 10:36:31 AM NO 07 61266

19-44494631 CSO Control Rm and Break Rm 1FL hot on weekends, check equipment and check HVAC scheduling for OTUs

GSAI NORMAL CLOSE 5/23/19 1:15:23 PM NO 07 61266

19-44530216 Remove and/or relocate one of the two ashcans sitting in that area ; should not need more than one at this location

GSAI NORMAL CLOSE 5/24/19 9:31:52 AM NO 07 61266

19-44530136 Check wall for lights out and lights falling/ fixture coming off wall ; a few fixtures observed to be loose, hanging off wall , some lights out

GSAI NORMAL CLOSE 5/24/19 9:31:24 AM NO 07 61266

19-44529582 exterior security lights out GSAI NORMAL CLOSE 5/24/19 9:27:40 AM NO 07 61266

19-44529492 Courtroom 11C several lights out GSAI NORMAL CLOSE 5/24/19 9:26:55 AM NO 07 61266

19-44494738 Rm 5218 leak appears to be by or at window in ralph carter's office

GSAI NORMAL CLOSE 5/23/19 1:44:44 PM NO 07 61266

19-44494636 sallyport exhaust fans possible down , check operation

GSAI NORMAL CLOSE 5/23/19 1:16:35 PM NO 07 61266

19-44649660 TX0211- Verify proper operation of hot deck/ cold damper on BC_TC0118

GSAI NORMAL CLOSE 5/30/19 11:53:47 AM NO 07 61266

19-44530385 front sidewalk Relocate/redistribute ashcans, they are all bunched together

GSAI NORMAL CLOSE 5/24/19 9:33:07 AM NO 07 61266

19-44531653 1FL RM1022 CSO SUPV DOOR ENTRANCE

THRESHOLD Threshold at door 1022 coming up, has two different strips on top of feach other, is a tripping hazard, needs to be removed and re-installed

GSAI NORMAL CLOSE 5/24/19 9:50:20 AM NO 07 61266

19-44531644 plants have brown spots and appear distressed especally from entrance bed

GSAI NORMAL CLOSE 5/24/19 9:48:02 AM NO 07 61266

19-44531640 Post Office back room has missing ceiling tiles GSAI NORMAL CLOSE 5/24/19 9:46:38 AM NO 07 61266

19-44531630 postal office back entrance area and work room heavy layer of dirt and dust on floors, walls and throughout

GSAI NORMAL CLOSE 5/24/19 9:45:04 AM NO 07 61266

19-44531584 interior entrance door seals/gaskets worn leaving gaps on bottoms and between doors

GSAI NORMAL CLOSE 5/24/19 9:43:26 AM NO 07 61266

19-44531489 Back Dock Postal Doors exterior entrance door seals/gaskets coming off, hanging from doors leaving gaps on bottoms and between doors

GSAI NORMAL CLOSE 5/24/19 9:42:06 AM NO 07 61266

19-44753926 TX0211- Properly stow and secure gas cylinders

GSAI NORMAL CLOSE 6/3/19 1:47:16 PM NO 07 61266

19-44657946 dry pipe failed inspection at back dock GSAI FIRE CLOSE 5/30/19 2:45:24 PM NO 07 61266

19-44662506 TX0211- Verify proper operation of hot deck/ cold damper on BC_TC0106

GSAI NORMAL CLOSE 5/30/19 4:43:17 PM NO 07 61266

19-44661090 TX0211- Verify proper operation of hot deck/ cold damper on BC_TC0115

GSAI NORMAL CLOSE 5/30/19 3:52:09 PM NO 07 61266

19-50292393 RFQ to replace USMS guard shack back dock GSAI NORMAL CLOSE 9/25/19 8:48:46 AM NO 07 61266

19-51429491 exterior security lights out GSAI NORMAL CLOSE 10/21/19 6:58:47 AM NO 07 61266

19-51429492 Rm 3413 Women Public RR by US Trustee Door handle broken

GSAI NORMAL CLOSE 10/21/19 6:59:47 AM NO 07 61266

19-52676915 several exterior security and building lights out all around perimeter of building and inside secured lot

GSAI NORMAL CLOSE 11/19/19 8:20:28 AM NO 07 61266

19-52677077 1FL Postal Women RR dispensers and other fixtures,finishes has heavy layer of dust

GSAI NORMAL CLOSE 11/19/19 9:02:17 AM NO 07 61266

19-52677071 1FL Postal Men's RR Entry door threshold has heavy build up of what appears to be dirt and debris

GSAI NORMAL CLOSE 11/19/19 9:00:19 AM NO 07 61266

19-52676982 1FL Postal Mens RR floor shows dark stains, streaks, drips spots and debris

GSAI NORMAL CLOSE 11/19/19 8:40:08 AM NO 07 61266

19-52676978 1FL Postal Men Employee RR entry door does not close all the way

GSAI NORMAL CLOSE 11/19/19 8:39:02 AM NO 07 61266

19-52783621 Grand Jury Womens RR Rm 3000B sink has hair, and other items in it, some build up around faucets

GSAI NORMAL CLOSE 11/20/19 4:14:09 PM NO 07 61266

19-52706821 2FL Probation Copy Room 2118 floor has scuff marks, streaks and stains, not uniform in appearance

GSAI NORMAL CLOSE 11/19/19 10:06:52 AM NO 07 61266

19-52706352 2FL Probation Copy Room 2118 - room inside copy room has HEAVILY STAINED tiles in Room 2118A, replace tiles and confirm no leaks

GSAI NORMAL CLOSE 11/19/19 10:05:48 AM NO 07 61266

19-52705789 2FL Womens RR Door 2134 entrance door does not close and secure

GSAI NORMAL CLOSE 11/19/19 10:04:33 AM NO 07 61266

19-52705418 2FL Hallway by doors 2529 and 2519 escutcheon missing

GSAI NORMAL CLOSE 11/19/19 10:03:46 AM NO 07 61266

19-52704823 2FL Rm 2019 Main break room floors heavily scuffed, build up of dirt and debris, heavy build up along wall base, floors not uniform in appearance

GSAI NORMAL CLOSE 11/19/19 10:02:39 AM NO 07 61266

19-52704375 2FL Rm 2102 Conf Rm replace stained tiles and check for leaks

GSAI NORMAL CLOSE 11/19/19 10:01:46 AM NO 07 61266

19-52677116 1FL Postal Storage Room 1212A sprinkler has debris hanging from it and escutcheon is missing

GSAI NORMAL CLOSE 11/19/19 9:09:14 AM NO 07 61266

19-52677107 1FL Postal Lobby Customer Service Stations have build up of dust, debris and dirt on floors and around work areas, especially heavy on the floor mats and at counter

GSAI NORMAL CLOSE 11/19/19 9:07:51 AM NO 07 61266

19-52677099 1FL Postal Lobby Floor has streaks, stains, spots and dirt/debris, not uniform in color or appearance

GSAI NORMAL CLOSE 11/19/19 9:06:12 AM NO 07 61266

19-52677092 1FL Postal Womens RR Sink has streaks and stains especially in basin around bottom

GSAI NORMAL CLOSE 11/19/19 9:05:04 AM NO 07 61266

19-52677082 1FL Womens Employee RR floor has build up of spots, stains, debris and floor has dingy color throughout

GSAI NORMAL CLOSE 11/19/19 9:03:33 AM NO 07 61266

19-52783653 3FL Grand Jury Courtroom Emergency Exit Light Blinking

GSAI NORMAL CLOSE 11/20/19 4:22:35 PM NO 07 61266

19-52783651 3FL Grand Jury Courtroom replace stained tile at emergency exit sign and check for leaks

GSAI NORMAL CLOSE 11/20/19 4:21:48 PM NO 07 61266

19-52783646 3FL Grand Jury Mens RR 3009C replace stained tiles and check for leaks

GSAI NORMAL CLOSE 11/20/19 4:20:55 PM NO 07 61266

19-52783644 3FL Grand Jury Kitchenette at 3000c replace stained tiles and check for leaks

GSAI NORMAL CLOSE 11/20/19 4:20:03 PM NO 07 61266

19-52783639 3FL Grand Jury Kitchenette at 3000c escutcheon missing

GSAI NORMAL CLOSE 11/20/19 4:18:55 PM NO 07 61266

19-52783636 Grand Jury 3FL Women RR 3000B No Toilet Paper

GSAI NORMAL CLOSE 11/20/19 4:17:57 PM NO 07 61266

19-52783634 Grand Jury 3FL 3000B Women RR Toilet seat very loose

GSAI NORMAL CLOSE 11/20/19 4:17:00 PM NO 07 61266

19-52783656 3FL Grand Jury Room 3000E escutcheon missing

GSAI NORMAL CLOSE 11/20/19 4:23:37 PM NO 07 61266

19-52752340 Per BAS and onsite observation Boiler 2 in alarm when it comes on and pumps running when both boilers off

GSAI NORMAL CLOSE 11/19/19 11:34:50 AM NO 07 61266

19-52784141 3FL US Trustee Suite has Lights out throughout

GSAI NORMAL CLOSE 11/20/19 4:36:43 PM NO 07 61266

19-52783713 3FL Back Hallway by USMS hallway and Judge Ellisons Several Llights Out

GSAI NORMAL CLOSE 11/20/19 4:34:50 PM NO 07 61266

19-52783708 3FL Women RR Room 3232 by Ellisons Courtroom loose toilet seat

GSAI NORMAL CLOSE 11/20/19 4:34:02 PM NO 07 61266

19-52783706 3FL Women RR by Ellison's Courtroom Rm 3232 Lights Out

GSAI NORMAL CLOSE 11/20/19 4:33:19 PM NO 07 61266

19-52783700 3FL Mens RR Room 3636 by Judge Ellisons Courtroom has lights out

GSAI NORMAL CLOSE 11/20/19 4:32:00 PM NO 07 61266

19-52783693 3FL Hallway between men and women RR at 3007 B AND C replace stained tile and check for leaks

GSAI NORMAL CLOSE 11/20/19 4:30:54 PM NO 07 61266

19-52783687 3FL Grand Jury Kitchette by 3007C has drips, streaks on wall

GSAI NORMAL CLOSE 11/20/19 4:30:02 PM NO 07 61266

19-52783684 3FL Grand Jury Men RR 3007C Aluminum Streaked

GSAI NORMAL CLOSE 11/20/19 4:29:13 PM NO 07 61266

19-52783677 3FL Grand Jury Men's RR 3007C Exhaust Fan has heavy build up of dust and debris

GSAI NORMAL CLOSE 11/20/19 4:27:59 PM NO 07 61266

19-52783675 3FL Grand Jury Men RR 3007C replace stained tiles and check for leaks

GSAI NORMAL CLOSE 11/20/19 4:27:04 PM NO 07 61266

19-52783672 3FL Grand Jury Women RR 3007B aluminum dispensers streaked

GSAI NORMAL CLOSE 11/20/19 4:26:17 PM NO 07 61266

19-52783665 3FL Grand Jury 3007B Womens RR toilet seat very loose

GSAI NORMAL CLOSE 11/20/19 4:25:29 PM NO 07 61266

19-52783662 3FL Grand Jury Women RR 3007B replace stained tiles and check for leaks

GSAI NORMAL CLOSE 11/20/19 4:24:39 PM NO 07 61266

19-52909955 Court IT Liebert #1 No operating - went down over the weekend

GSAI NORMAL CLOSE 11/25/19 6:51:27 AM NO 07 61266

19-52784463 3FL US Trustee has dust accumulation on horizontal surfaces, and throughout suite

GSAI NORMAL CLOSE 11/20/19 4:38:03 PM NO 07 61266

19-52786081 1FL Women RR Room 1315 by jury assembly lights out

GSAI NORMAL CLOSE 11/20/19 4:44:56 PM NO 07 61266

19-52785718 1FL Mail Room Floors have streaks and stains throughout

GSAI NORMAL CLOSE 11/20/19 4:43:26 PM NO 07 61266

19-52785524 3FL US Trustee Break room has streaks, and scuff marks on floor , not uniform in appearance

GSAI NORMAL CLOSE 11/20/19 4:42:34 PM NO 07 61266

19-52785216 3FL US Trustee Entry Foyer has debris and dust on floor

GSAI NORMAL CLOSE 11/20/19 4:41:15 PM NO 07 61266

19-52784677 3FL US Trustee Suite has some debris and trash on floors throughout especially in corners of kitchen break area, open work areas and file room

GSAI NORMAL CLOSE 11/20/19 4:39:00 PM NO 07 61266

19-53127042 Entrapment Judges Elevator GSAI SAFETY CLOSE 12/4/19 2:51:08 PM NO 07 61266

19-53127171 Entrapment Judges Elevator 12-3-19 GSAI SAFETY CLOSE 12/4/19 2:56:57 PM NO 07 61266

19-53190211 1FL USMS Break Room & Locker ROom Floors have scuff marks and are not uniform in apeparance, cove base has heavy build up of dust and film

GSAI NORMAL CLOSE 12/11/19 8:28:21 AM NO 07 61266

19-53190618 Basement Custodial Storage Room has inoperable floor machine stored

GSAI NORMAL CLOSE 12/11/19 10:28:45 AM NO 07 61266

19-53190612 Basement Storage Room by judges gym - two live large cockroaches noted upon entry

GSAI NORMAL CLOSE 12/11/19 10:27:41 AM NO 07 61266

19-53190598 Basement Custodial Storage Room by judges gym has ants all down the hallway and in front of this room

GSAI NORMAL CLOSE 12/11/19 10:24:42 AM NO 07 61266

19-53190597 1FL Custodial Closet Room 1120 Custodial sink faucet has thick green build up

GSAI NORMAL CLOSE 12/11/19 10:23:50 AM NO 07 61266

19-53190593 1FL Custodial Closet Rm 1120 Chemcials in room and no MSDS sheets posted

GSAI NORMAL CLOSE 12/11/19 10:22:57 AM NO 07 61266

19-53190587 1FL Custodial Closet Rm 1120 old dirty carpet roll on floor, old dirty rags on shelf

GSAI NORMAL CLOSE 12/11/19 10:22:04 AM NO 07 61266

19-53190572 1FL Women RR Rm1114 stall receptacle on floor - is one missing or is the one on floor need to be repaired - please fix and install correctly

GSAI NORMAL CLOSE 12/11/19 10:16:10 AM NO 07 61266

19-53190213 1FL Men RR Rm 1124 floor is dark, dull with scuff marks, stains and uneven in appearance

GSAI NORMAL CLOSE 12/11/19 8:28:59 AM NO 07 61266

19-53190725 Basement women's judicial locker/shower room faucet leaks when off

GSAI NORMAL CLOSE 12/11/19 10:52:06 AM NO 07 61266

19-53190817 2FL Large Breakroom #2019 floor has numerous scuff marks and stains throughout;

not uniform in apeparance and lacks lustre/ shine

GSAI NORMAL CLOSE 12/11/19 11:10:16 AM NO 07 61266

19-53190794 3FL Custodial Closet Rm 3409 chemicals on shelf and on cart with no MSDS

GSAI NORMAL CLOSE 12/11/19 11:05:25 AM NO 07 61266

19-53190783 3FL Custodial Closet Rm 3409 old out of service equipment stored

GSAI NORMAL CLOSE 12/11/19 11:04:16 AM NO 07 61266

19-53190755 Basement Court Employees Gym RM 3419 Ladies RR aluminum receptacles and containers have sticky light and dark stains, streaks

GSAI NORMAL CLOSE 12/11/19 10:58:54 AM NO 07 61266

19-53190743 Basement Courts employee gym restrooms have a dark orange film in bowls

GSAI NORMAL CLOSE 12/11/19 10:56:46 AM NO 07 61266

19-53190738 basement courts employee gym mat floor has dust, dirt and debris throughout

GSAI NORMAL CLOSE 12/11/19 10:55:27 AM NO 07 61266

19-53982893 Exterior building security canned lights out on Smith Street

GSAI NORMAL CLOSE 12/16/19 8:07:45 AM NO 07 61266

19-53983188 10FL Command Center has stained tiles -change tiles and check for leak

GSAI NORMAL CLOSE 12/16/19 9:58:15 AM NO 07 61266

19-53983181 10FL USMS Gym mirror streaked with dust and stains throughout

GSAI NORMAL CLOSE 12/16/19 9:57:00 AM NO 07 61266

19-53983169 10FL USMS MEn's Gym Shower Drips when off resulting in a large uneven patch of build up which is a SLIP/TRIPPING HAZARD

GSAI NORMAL CLOSE 12/16/19 9:54:21 AM NO 07 61266

19-53983158 10FL USMS Men's Gym SHower FLoor SLIP/ TRIPPING HAZARD - has very heavy build up of what appears to be mineral deposits and dirt and mildew

GSAI NORMAL CLOSE 12/16/19 9:52:02 AM NO 07 61266

19-53983144 10FL USMS GYm Air Freshener not mounted GSAI NORMAL CLOSE 12/16/19 9:48:37 AM NO 07 61266

19-53983140 10FL USMS Gym fire exntinguisher is sitting on floor

GSAI NORMAL CLOSE 12/16/19 9:47:48 AM NO 07 61266

19-53983120 B401 Basement Ladies RR Faucet leaking from base of unit

GSAI NORMAL CLOSE 12/16/19 9:38:56 AM NO 07 61266

19-53983106 10FL Gym mat floor stained, debris and sticky throughout

GSAI NORMAL CLOSE 12/16/19 9:33:10 AM NO 07 61266

19-53983098 10FL Hallways and lobbys have scuffs, scrapes, stains, lack lustre, not unifrom in appearance

GSAI NORMAL CLOSE 12/16/19 9:31:15 AM NO 07 61266

18-38219663 12th > 1st FLOOR, PERFORMED LIGHT

TOUR (VICTOR (PA)

OMI INITIAL CLOSE 1/2/19 9:00:00 AM NO 07 61266

19-39152544 Elevator 5, STUCK ON 2nd FLR W/ DOOR

OPEN #62995714 (ROBERT 6977)

UH UTILMISC CLOSE 1/22/19 8:45:00 AM NO 07 61266

19-40449048 ELEVATOR 3, NOT GOING TO CALLED

FLOOR tech called #63314144 (JIMMIE 7286)

UH UTILMISC CLOSE 2/20/19 6:30:00 PM NO 07 61266

19-39377224 B401 Women's RR cut off old locks, repair hinges for use misc hrs NTE 1 hour

UH UTILMISC CLOSE 2/5/19 8:54:12 AM NO 07 61266

19-43677656 ELEVATOR 4 & 5, NOT MOVING # 64235459

tech called (JIMMIE 8308)

UH UTILMISC CLOSE 5/14/19 3:00:00 PM NO 07 61266

19-43493896 ELEVATOR 3, STOPPING AT UNCALLED

FLOORS & MOVING SLOW TECH CALLED

#64109676 (ROBERT 8156)

UH UTILMISC CLOSE 5/2/19 10:30:00 AM NO 07 61266

19-40749238 ELEVATOR 5, NOT WORKING tech called #63400832 (Robert 7547)

UH UTILMISC CLOSE 3/5/19 1:00:00 PM NO 07 61266

19-42138281 ELEVATOR 5, DOOR CYCLING ON 12th FLR tech called #63753395 (ROBERT 7831)

UH UTILMISC CLOSE 4/1/19 8:45:00 AM NO 07 61266

19-42136449 ELEVATOR 8, STUCK ON 9 tech called

#63753395 (ROBERT 7830)

UH UTILMISC CLOSE 4/1/19 8:45:00 AM NO 07 61266

19-47715125 ELEVATOR 7, STUCK ON 7th FLR (tech called) # 65359261 (JIMMIE 9312)

UH UTILMISC CLOSE 8/14/19 3:45:00 PM NO 07 61266

19-43766579 4 ELEVATOR, LANDING HARD WHEN

STOPPING 64259467 (JIMMIE 8326)

UH UTILMISC CLOSE 5/15/19 1:00:00 PM NO 07 61266

19-44532093 ELEVATOR 4, HAD ENTRAPMENT BUT

TENANT WAS RELEASED (ROBERT 8414)

UH UTILMISC CLOSE 5/23/19 9:45:00 AM NO 07 61266

18-38256142 BLDG. Judge Weirline-RRM JUROR, SINK IN

MEN'S JUROR (ROBERT 6851)

WR SERVCALL CLOSE 1/7/19 7:30:00 AM NO 07 61266

19-39367477 P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr2_Alarm (gsa/bas

WR SERVCALL CLOSE 2/4/19 10:00:00 AM NO 07 61266

19-39460971 P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant / HwS_Temp_Alm info = Boiler didn't bring temp above 90F in 60 mins (GSA/BAS)

WR SERVCALL CLOSE 2/8/19 8:00:00 AM NO 07 61266

19-39402541 Operator 22 @ Firetron 281-452-6323 515 Rusk St. Houston TX 77002 Issue: Fire Alarm Went Off And The Fire Dept. Was Dispatched

Caller ID: 2814526323 (gsa/alarm)

WR SERVCALL CLOSE 2/6/19 7:30:00 AM NO 07 61266

19-40387867 P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant / HwS_Temp_Alm - Boiler didn't bring temp above 90F in 60 mins

WR SERVCALL CLOSE 2/13/19 7:15:00 AM NO 07 61266

19-40210698 Chillers didn't bring temp below 60F in 30 mins Tangent Down/ Fault (GSA/BAS)

WR SERVCALL CLOSE 2/11/19 7:15:00 AM NO 07 61266

19-40210824 P077KETX0211HSTN1 - Bob Casey CH, Houston

TX:CHWPumpVSD_FaultCHWPump3 Alarm Active!! (GSA/BAS)

WR SERVCALL CLOSE 2/11/19 7:15:00 AM NO 07 61266

19-40449967 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Utility / Tangent_Alarm-

Tangent Down/ Fault

WR SERVCALL CLOSE 2/21/19 8:00:00 AM NO 07 61266

19-40449320 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /

HwS_Temp_Alm-Boiler didn't bring temp above 90F in 60 mins

WR SERVCALL CLOSE 2/21/19 9:00:00 AM NO 07 61266

19-40413291 BLDG,NiagaraNetwork P077KETX0211HSTN1 - Bob Casey CH, Houston TX-Ping Failed

WR SERVCALL CLOSE 2/19/19 7:15:00 AM NO 07 61266

19-40413297 BLDG-P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /

HwS_Temp_Alm - Boiler didn't bring temp above 90F in 60 mins

WR SERVCALL CLOSE 2/19/19 7:15:00 AM NO 07 61266

19-40413294 BLDG-P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Utility / Tangent_Alarm-

Tangent Down/ Fault (GSA/BAS)

WR SERVCALL CLOSE 2/19/19 7:15:00 AM NO 07 61266

19-40704299 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /

HwS_Temp_Alm - Boiler didn't bring temp above 90F in 60 mins (GSA/BAS)

WR SERVCALL CLOSE 3/4/19 7:15:00 AM NO 07 61266

19-40672516 bldg, NiagaraNetwork P077KETX0211HSTN1

- Bob Casey CH, Houston TX - - Ping Failed

WR SERVCALL CLOSE 3/1/19 10:45:00 AM NO 07 61266

19-40672520 BLDG,P077KETX0298HSTN2 - Mickey Leland FB, Houston

TX:P077KETX0298HSTN1:AHU1_FanStatus is in Alarm

WR SERVCALL CLOSE 3/1/19 10:45:00 AM NO 07 61266

19-40992730 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -Hot

Water Supply Temp is below 90°F after being activated for 30 Minutes (GSA/BAS)

WR SERVCALL CLOSE 3/14/19 8:15:00 AM NO 07 61266

19-40797607 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -Hot

Water Supply Temp is below 90°F after being activated for 30 Minutes.(GSA/BAS)

WR SERVCALL CLOSE 3/12/19 7:15:00 AM NO 07 61266

19-40994766 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -Hot

Water Supply Temp is below 90°F after being activated for 30 Minutes. (GSA/BAS)

WR SERVCALL CLOSE 3/14/19 11:30:00 PM NO 07 61266

19-41876334 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -Hot Water

Supply Temp is below 90°F after being activated for 30 Minutes GSA/BAS

WR SERVCALL CLOSE 3/20/19 9:45:00 AM NO 07 61266

19-42009570 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chiller3_FaultCH3 - Alarm

Active!! (GSA/BAS)

WR SERVCALL CLOSE 3/23/19 11:15:00 AM NO 07 61266

19-42009582 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chiller1 / ChwS_Temp_Alm1

- - Chiller 1 Didn't bring temp below 60F in 30 mins (GSA/BAS)

WR SERVCALL CLOSE 3/23/19 11:30:00 AM NO 07 61266

19-42009580 BLDG,P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr1_Alarm - -Chiller 1

Down!! (GSA/BAS)

WR SERVCALL CLOSE 3/23/19 11:15:00 AM NO 07 61266

19-42023666 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr2_Alarm (gsa/bas)

WR SERVCALL CLOSE 3/25/19 10:00:00 PM NO 07 61266

19-42023670 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -is below 90°F after being activated for 30 Minutes.

WR SERVCALL CLOSE 3/26/19 6:00:00 AM NO 07 61266

19-42023664 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr1_Alarm- - Chiller 1 Down!!

(gsa/bas)

WR SERVCALL CLOSE 3/25/19 10:30:00 PM NO 07 61266

19-42133731 BLDGM, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr1_Alarm - -Chiller 1

Down!!

WR SERVCALL CLOSE 3/29/19 11:30:00 PM NO 07 61266

19-42009594 BLDG,P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chiller1 /

ChwS_Temp_Alm1- - Chiller 1 Didn't bring temp below 60F in 30 mins (GSA/BAS)

WR SERVCALL CLOSE 3/24/19 5:00:00 PM NO 07 61266

19-42009589 BLDG,P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr2_Alarm- - Chiller 2

Down!! (GSA/BAS)

WR SERVCALL CLOSE 3/24/19 4:30:00 PM NO 07 61266

19-42009587 BLDG,P077KETX0211HSTN1 - Bob Casey CH, Houston

TX:CWPumpVSD_FaultCWPump3 - - Alarm Active!! (GSA/BAS)

WR SERVCALL CLOSE 3/24/19 3:45:00 PM NO 07 61266

19-42009576 BLDG, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Chlr2_Alarm - -Chiller 2

Down!! (GSA/BAS)

WR SERVCALL CLOSE 3/23/19 11:45:00 AM NO 07 61266

19-42050214 1ST & 8TH FL-LIGHT OUT REPLACE IN

BOTH ELEVATOR LOBBIES-(

WR SERVCALL CLOSE 3/27/19 10:45:00 AM NO 07 61266

19-42036427 bldg, P077KETX0211HSTN1 - Bob Casey CH, Houston TX:HW_SupplyTemp - -Hot Water

Supply Temp is below 90°F after being activated for 30 Minutes.(gsa/bas)

WR SERVCALL CLOSE 3/27/19 12:45:00 AM NO 07 61266

19-42049275 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning

Tab.

WR SERVCALL CLOSE 4/1/19 8:00:00 AM NO 07 61266

19-43571599 BLDG, condenser pump # leaking from seals (ROBERT EmaIled) EXTENSION 07/02/19

WR SERVCALL CLOSE 5/8/19 2:00:00 PM NO 07 61266

19-44767611 ELEVATOR 5, LOCKED ON 1st FLR-NEED

SPILL / BROKEN GLASS CLEANED UP

(CARMEN 8523)

WR SERVCALL CLOSE 6/4/19 9:45:00 AM NO 07 61266

19-44819673 DOCK/SALLY-PORT, FANS NOT WORKING

**very stuffy (ROBERT 8586)

WR SERVCALL CLOSE 6/10/19 11:00:00 AM NO 07 61266

19-47182622 OUTSIDE-BACK GATE, NEED MESS

CLEANED UP (you will need HOT water & gloves) see marshal for more info (CARMEN 9104)

WR SERVCALL CLOSE 7/29/19 8:30:00 AM NO 07 61266

19-47560384 ELEVATOR 7, STUCK ON 1st FLR tech called #65323599 (JIMMIE 9271)

WR SERVCALL CLOSE 8/12/19 8:30:00 AM NO 07 61266

19-48727221 7125 RM, DOOR NOT SECURING CLOSED

(alarm sounding) (ROBERT 9431)

WR SERVCALL CLOSE 8/28/19 9:00:00 AM NO 07 61266

19-48793835 ELEVATOR 3, STOPPING AT EACH FLOOR

& DOOR NOT OPENING #65553391 (JIMMIE

9450)

WR SERVCALL CLOSE 8/30/19 11:30:00 AM NO 07 61266

19-48793410 ELEVATOR 1, PLEASE CHECK-STUCK ON

1st FLR # 65553391 (JIMMIE 9449)

WR SERVCALL CLOSE 8/30/19 11:30:00 AM NO 07 61266

19-50307859 ELEVATOR 7, STUCK ON 1st FLR W/ DOOR

PARTIALLY OPEN # 65858542 (VICTOR

9679)

WR SERVCALL CLOSE 9/25/19 12:45:00 PM NO 07 61266

19-51379621 FREIGHT ELEVATOR, NOT GOING TO SET

FLOOR AND LIGHT NOT LITE (JIMMIE 9891)

WR SERVCALL CLOSE 10/16/19 5:00:00 PM NO 07 61266

19-52760260 Source: P077KETX0211HSTN1 - Bob Casey CH, Houston TX:Boiler_Plant /

HwS_Temp_Alm Timestamp: 17-Nov-19 10:10:11 AM UTC State: Offnormal

Text: Boiler didn't bring temp above 90F in 60 mins (GSA/BAS) NC

WR SERVCALL CLOSE 11/17/19 5:30:00 AM NO 07 61266

19-52910295 10204 RRM, TOILET OVERFLOW (VICTOR

341) NC

WR SERVCALL CLOSE 11/25/19 9:15:00 AM NO 07 61266

19-53985269 ELEVATOR 2, ENTRAPMENT >> RELEASED

#67377523 (GUSTAVO 535) NC

WR SERVCALL CLOSE 12/16/19 7:45:00 AM NO 07 61275

19-42266337 BLDG, NiagaraNetwork P077KETX0297HSTN1 - Alliance Tower, Houston TX- - Ping Failed

CM EQFAIL CLOSE 4/7/19 2:30:00 AM NO 07 61275

19-47307307 Entrance Awning Water Leak at front building entrance EXTENSION 10/18/19

GSAI NORMAL CLOSE 7/30/19 4:34:49 PM NO 07 61275

19-42140915 ELEVATOR 4, STUCK IN BSMT DOOR

CLOSED tech called #006150920 (LEON

7835)

UH UTILMISC CLOSE 4/1/19 10:00:00 AM NO 07 61275

19-45646489 ELEVATOR 2, MAKING NOISE WHILE

MOVING #6331388 (GUSTAVO 8717)

UH UTILMISC CLOSE 6/20/19 8:45:00 AM NO 07 61275

19-46191180 ELEVATOR 4, STUCK IN BASEMENT

#006372628 (LEON 8873)

UH UTILMISC CLOSE 7/9/19 8:00:00 AM NO 07 61275

19-39366807 P077KETX0297HSTN1 - Alliance Tower, Houston TX:Chiller2 / ChwS_Temp_Alm2

(GSA/BAS)

WR SERVCALL CLOSE 2/4/19 8:15:00 AM NO 07 61275

19-40227650 NiagaraNetwork P077KETX0297HSTN1 - Alliance Tower, Houston TX - Ping Failed

(GSA/BAS)

WR SERVCALL CLOSE 2/12/19 7:15:00 AM NO 07 61275

19-40283718 P077KETX0297HSTN1 - Alliance Tower, Houston TX:Chiller3 / ChwS_Temp_Alm3 - Chiller 3 Didn't bring temp below 60F in 30 mins

WR SERVCALL CLOSE 2/12/19 8:45:00 AM NO…