Amendment 0003 BL7 Leland Design Guide.pdf

PDF 2 MB Posted

Attached to
Full Maintenance Services for Houston, Beaumont, and Galveston, TX
Solicitation number
47PH0220R0017
Issued by

About this file

This solicitation notice seeks full maintenance services for federal facilities in Houston, Beaumont, and Galveston, Texas. The services include operation and maintenance, custodial work, and grounds maintenance at eight buildings totaling over 1.7 million rentable square feet. The facilities support services contract has a start date of May 1, 2021. The North American Industry Classification System code is 561210 for facilities support services, and the small business size standard is $41.5 million. The acquisition is reserved 100% for Service-Disabled Veteran-Owned Small Businesses.

View the file

Other files

File Type Posted
Amendment 0004 47PH0220R0017 SF33.pdf PDF
Amendment 0004 Questions and Answers.pdf PDF
Amendment 0004 Figure B-3 Pricing of Services .xlsx XLSX spreadsheet
Amendment 0004 SF30.pdf PDF
Amendment 0003 Questions and Answers.pdf PDF
Amendment 0003 47PH0220R0017 SF33.pdf PDF
Amendment 0003 BL8 Leland Davits and Anchor Inspection Report.pdf PDF
Amendment 0003 Houston Galveston Beaumont OM_FM Spec Amend 0003 7 Jan 21.pdf PDF
47PH0220R0017 Amendment 0003.pdf PDF
Amendment 0003 BL5 Work Order History.xlsx XLSX spreadsheet
Amendment 0002 Houston Galveston Beaumont OM FM Spec 21 Dec 20.pdf PDF
Amendment 0002 BL5 Work Order History.xlsx XLSX spreadsheet
47PH0220R0017 Amendment 0002.pdf PDF
Amendment 0001 Attachment 4 Flag Policy.pdf PDF
Amendment 0001 Pre-Proposal Conference Houston Beaumont and Galveston.pptx PPTX presentation
Amendment 0001 Houston Galveston Beaumont OM_FM Spec 14 Dec 20 - Google Docs.pdf PDF
Amendment 0001 BL2 Inventory to Include Fire Alarm Devices.xlsx XLSX spreadsheet
47PH0220R0017 Amendment 0001 SF30.pdf PDF
Amendment 0001 Pre-Proposal Conference Questions and Answers.pdf PDF
Amendment 0001 Figure B-3 Pricing 5 YEAR- TOTAL_ESTIMATES.xlsx XLSX spreadsheet
BL2 Inventory to Include Fire Alarm Devices.pdf PDF
Exhibit M7 - Qualificaiton of Electrical Testing Technicians.pdf PDF
Exhibit M2 - Green Purchasing Report.pdf PDF
Figure L-3 Past Performance Questionnaire.pdf PDF
Exhibit C6 - Recycle Solid Water Trash Report.pdf PDF
Exhibit C2 Custodial Quality Assurance Surveillance Plan.pdf PDF
Exhibit C1 Building Information Sheet.pdf PDF
Attachment 1 Collective Bargaining Agreement for O_M personnel with Wage Determination.pdf PDF
Figure L-2 Management Plan Baseline.pdf PDF
Exhibit C8 - GSA Form 3638 Pest Control Work and Inspection Report.pdf PDF
Exhibit M4 - Bldg Op Plan Template.pdf PDF
Exhibit M10- PV Service Schedule V5.pdf PDF
Exhibit C4 - Building Exterior and Hardscape Plan.pdf PDF
Exhibit C7 - PBS Waste Audits.pdf PDF
47PH0220R0017 Solicitation and Specifications.pdf PDF
Exhibit M3 - Environmental Sustainable Products.pdf PDF
BL5 Work Order History.pdf PDF
Figure B-1 for Union and Non Union Contracts.xlsx XLSX spreadsheet
BL6 PM Report.pdf PDF
BL3 Location General Information .pdf PDF
Exhibit C3 - Surveilence Form 1181-A.pdf PDF
Exhibit M9 Preventative Maintenance 2018 GSA OM Guide.pdf PDF
Exhibit M1 Quality Assurance Surveillance Plan.pdf PDF
Figure B-3 Pricing 5 YEAR- TOTAL_ESTIMATES.xlsx XLSX spreadsheet
Figure L-1 Management Plan Worksheet.xlsx XLSX spreadsheet
BL1- Houston_Galveston Fire Extinguisher Report.pdf PDF
Exhibit M8 - Misc Best Practices Shave Energy.pdf PDF
Exhibit M5 - Smart Buildings.pdf PDF
BL4 Roof Information.pdf PDF
Exhibit M6 Water Treatment.pdf PDF
Show 40 more

Latest 50 of 54 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G.T. Mickey Leland Federal Office Building Tenant Guidelines

November 18, 2015 Project No. 02.7017.000

Prepared by Gensler 711 Louisiana Street Suite 300 Houston, TX 77002

PROPERTY OF UNITED STATES GOVERNMENT

COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE SPECIFICATIONS TO UNAUTHORIZED PERSONS IS

PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

Tenant Standards G.T. Mickey Leland Federal Office Building 2 11.18.2015

Tenant Standards G.T. Mickey Leland Federal Office Building 3

TABLE OF CONTENT

INTRODUCTION 7

BUILDING INFORMATION

Overview of ARRA Project

DIVISION 01 – GENERAL REQUIREMENTS SUBGROUP

Sustainable Design Requirements

Commissioning Requirements

Life Safety Review

DIVISION 03 – CONCRETE

Cast In Place Concrete

Precast Concrete

DIVISION 05 – METALS

Decorative Formed Metal

DIVISION 06 – WOOD, PLUMBING & COMPOSITES

Interior Architectural Woodwork

DIVISION 07 – THERMAL AND MOISTURE PROTECTION

Applied Fireproofing

Fire-Resistive Joint Systems

Joint Sealants

Tenant Standards G.T. Mickey Leland Federal Office Building 4

DIVISION 08 – OPENINGS

Hollow Metal Doors and Frames

Aluminum Door and Window Frames

Flush Wood Doors

Access Doors and Frames

Aluminum Entrances and Storefronts

All-Glass Entrances and Storefronts

Glazed Aluminum Curtain Walls-Cassette System

Door Hardware

Glazing

DIVISION 09 – FINISHES

Gypsum Board Partitions

Tiling

Acoustical Panel Ceilings

Stone Flooring

Stone Facing

Base and Accessories

Tile Carpeting

Interior Painting

DIVISION 10 – SPECIALTIES

Signage……………………………………………………………………………………………………………………….… 53

Toilet Compartments

Fire-Protection Specialties

DIVISION 12 – FURNISHINGS

Roller Window Shades

Stone Countertops

Tenant Standards G.T. Mickey Leland Federal Office Building 5

DIVISION 21 – FIRE SUPPRESSION

Fire Suppression System

DIVISION 22 – PLUMBING

Plumbing Overview

General Requirements

Miscellaneous Brass Trim

Plumbing Fixtures

DIVISION 23 – HEATING, VENTILATING AND AIR CONDITIONING

Mechanical Overview

Controls

DIVISION 26 – ELECTRICAL

Electrical Requirements

Lighting Fixtures

DIVISION 27 – COMMUNICATIONS

Communication Requirements

DIVISION 28 – ELECTRONIC SAFETY AND SECURITY

Building Security System

Fire Alarm

Tenant Standards G.T. Mickey Leland Federal Office Building 6

Tenant Standards G.T. Mickey Leland Federal Office Building 7

INTRODUCTION

This document has been compiled to provide guidelines for ongoing tenant interior renovations in the newly renovated Mickey Leland Building. All renovations in the public spaces and corridors need to be designed consistent with the corresponding standards in these guidelines. In the tenant leased spaces, the ceilings and MEP/F need to be designed to meet these guidelines. While an agency can use these guidelines for the rest of their finish-out, there is no requirement for the other scope within the individual agency space to follow these guidelines. An agency can utilize their own agency standards in keeping with the P100.

BUILDING INFORMATION

1. Building/Facility Name: G. T. "Mickey" Leland Federal Office Building

2. Building/Facility Number: TX0298

3. Building/Facility Address: 1919 Smith Street, Houston, Texas 77002

4. Property Manager: Dawn Han, GSA, Gulf Coast Region 07

Telephone: (832) 397 8496

Fax: (281) 228 – 5613

Mobile: (713) 476 - 1798

Email: dawn.han@gsa.gov

Involvement: Responsible for the administration, operation, and maintenance of the building.

Overview of ARRA Project

The project was funded under the American Recovery and Reinvestment Act (ARRA), under the High Performance Green Building (HPGB) criteria. The scope of work included:

An over cladding of the building exterior façade with a new state of the art curtainwall system;

o Upgrade of related structural supporting components, including the capacity to support window cleaning operations off of the roof;

o Upgrades to the lighting systems for daylighting features of the new exterior façade, and related new lighting controls;

o Installation of new ceiling systems provided;

Renovation and upgrade of all public area finishes;

Upgrade building interior for Architectural Barriers Act (ABA) compliance, including build-out of additional ABA restrooms;

Modernization of first floor lobby and the security check-point;

Relocation and renovation of the cafeteria on the first floor;

Replacement of the building air handling units (AHUs) and related air distribution system in the tenant areas;

A new Building Automations System (BAS), integrated with the lighting controls and security systems;

Replacement of the air-side energy recovery systems;

Upgrades to the adjacent parking garage, including structural, lighting, and ABA improvements;

Replacement of the existing breezeway from the parking garage to the building lobby;

mailto:dawn.han@gsa.gov

Tenant Standards G.T. Mickey Leland Federal Office Building 8

Installation of new elevator, and reconstruct existing stairway, for access from parking garage tunnel to the breezeway;

Reconstruction of the plaza area;

Upgrades to the perimeter security barriers;

Addition of solar renewable energy on the top of the parking garage;

Upgrades to the fire alarm system for P-100 and NFPA compliant;

Upgrades to the fire protection system to comply with NFPA codes;

Each floor of the building was vacated so a complete renovations could be accomplished, and included replacement of all carpeting throughout the in the tenant lease along with new paint on all wall;

Removal of all abandoned telecommunications cabling; and

Installation of a new security system for all card readers and security cameras.

General Requirements

Subgroup

DIVISION 01

Tenant Standards G.T. Mickey Leland Federal Office Building 10

Tenant Standards G.T. Mickey Leland Federal Office Building 11

Sustainable Design Requirements

The Mickey Leland Federal Building Renovations was a Modernization project, as further defined in the Facility Standards for the Public Buildings Service, Appendix A

(http://www.gsa.gov/P100). Newly modernized GSA-owned facilities are required to meet the lowest energy consumption level attainable without a resulting increase in life-cycle cost, with a goal of reducing the present value energy cost budget to at least 20 percent below the pre-renovations level. (See Executive Order 13423 and the interagency memorandum of understanding on Federal Leadership in High Performance and Sustainable

Buildings – 2006.) The optimization of energy use for the facility will be delivered through an integrated approach affecting building envelope, mechanical and electrical systems, and interior heat, light and power loads.

The Mickey Leland Federal Building is intended to be a model for sustainability in GSA

Region 7. The following summarizes the sustainable issues that were addressed during the

Project design and construction. It is the intent of these guidelines to create a framework by which the sustainable design can be maintained as renovations occur with tenant agency lease changes.

A. LEED

The Project is currently a Gold certification under LEED NC v2009 rating system.

B. High Performance & Sustainability Building

Moisture Control strategy

Construction IAQ, 72 hour flush out before tenant space occupied

Eliminate ozone depleting compounds for new equipment and/or new kitchen appliances

C. Energy Policy Act of 2005 (EPACT’05)

New HVAC equipment to be energy efficient

Purchase ENERGY STAR or Federal Energy Management Program (FEMP) equipment and appliances

D. Energy Independence & Security Act (EISA) 2007

Use cost effective lighting fixtures

ENERGY STAR Label appliances

Use advanced meters for measurement and verification

E. Life Cycle Costing

Building design energy conservation measures process mandated by law and defined in CFR, Title 10, Part 436, Subpart A: Program Rules of the Federal Energy

Management Program. Governs: Thermal envelope, passive solar features, fenestrations, HVAC, domestic hot water, building automation, lighting, occupant productivity, system maintenance, environmental impact and any other issue that impacts cost over time.

F. Federal Recycled Content Requirements

Provide building materials with recycled content such that postconsumer material and recovered material for EPA-designated products constitutes not less than 10 percent of the total cost of Project materials.

G. Regional Materials

Provide a minimum of 10 percent of building materials (by cost) that are regional materials.

Tenant Standards G.T. Mickey Leland Federal Office Building 12

H. Certified Wood

Provide a minimum of 50 percent (by cost) of wood-based materials that are produced from wood obtained from forests certified by an FSC-accredited certification body to comply with FSC STD-01-001, "FSC Principles and Criteria for

Forest Stewardship."

I. Adhesives, sealants, and sealant primers that are used on the inside of the weatherproofing system and applied on-site shall comply with South Coast Air

Quality Management District (SCAQMD) Rule 1168, effective date of July 1, 2005 and rule amendment date of January 7, 2005

1. Paints and coatings used inside of the weather-proofing system and applied on-site shall comply with the following criteria:

i. Architectural paints and coatings applied to interior walls and ceilings shall not exceed the volatile organic compound (VOC) content limits established in Green Seal Standard GS-11, Paints.

ii. Anti-corrosive and anti-rust paints applied to interior ferrous metal substrates shall not exceed the VOC content limit of 250 g/L established in Green Seal Standard GC-03, Anti-Corrosive Paints.

iii. Clear wood finishes, floor coatings, stains, primers, and shellacs applied to interior elements shall not exceed the VOC content limits established in South Coast Air Quality Management District (SCAQMD)

Rule 1113, Architectural Coatings, rules in effect on January 1, 2004.

2. Do not use composite wood or agrifiber products or adhesives that contain urea-formaldehyde resin.

J. Alternative Energy

A total of 185kW of new photovoltaic panels with structural support and associated electrical controls are installed over the garage. Power produced at the garage is routed to the main electrical Switchboard in the basement of the Mickey Leland

Building. Invertors for PV array are located on 5th floor level of garage.

Commissioning Requirements

As a part of the effort to maintain the sustainability of the Mickey Leland Building, renovations that impact building systems should be re-commissioned so that the original commissioning goals can be maintained. Where new work impacts the systems described below, the GSA Project Managers and design teams should address re-commissioning in their project scope

The following systems were commissioned as a part of the ARRA funded Project renovation:

A. Building Envelope

1. New curtain wall assemblies)

B. Plumbing Systems:

1. Domestic Hot Water Heaters

2. Plumbing Fixtures

i. Spot checks of pressure tests and flushing of piping systems

ii. Irrigation System

Tenant Standards G.T. Mickey Leland Federal Office Building 13

C. Mechanical Systems:

1. Chilled Water Energy Recovery Units

2. Large Chilled Water Air Handling Units

3. Small Chilled Water Air Handling Units

4. Chilled Water Fan Coil Units

5. Self-contained Direct Exchanged Fan Coil Units

6. VAV Terminal Units

7. Master Pressure Control Terminal Units with Heat

8. VAV Pressure Dependent Diffusers

9. Misc. Exhaust / Transfer Fans

10. Toilet Exhaust Fans

11. Garage Exhaust Fans

12. Stairwell Pressurization Fans

13. Miscellaneous tenant space. Supply Fans

14. Building Chilled Water Pumps

15. Building Hot Water Pumps

16. Spot Checks of Duct Testing

17. Systems Integration (Central Building Automation System)

D. Electrical System

1. Lighting Controls / Occupancy Sensors

2. Garage Emergency Generator

3. Fire Alarm/ Fire Life Safety Systems—New Alarm Panel

4. Conveyance Systems—Tunnel/ Breezeway Elevator

Life Safety Review

A life safety review is based on an assessment of the exiting capacity through the egress systems on any floors under construction and the capacity at the level of exit discharge. The following summary is provided to assist in life safety analyses, which should be done for future renovations in the building.

The Mickey Leland Modernization Project reviewed the existing conditions, based on the uses on each floor for each agency. Any required modification were incorporated into the renovation project The occupant loads are provided with corresponding, code-mandated number of exits and total exit width so the number of egressing occupants can safely arrive at the level of exit discharge and discharge through the exiting components. This analysis also reviewed the arrangement of the means of egress to ensure the travel distances, encroachments into exit width, and exposures to hazards are minimized. Since the existing partitions in the tenant agency spaces were to remain and travel distances, dead-end conditions, and egress widths will not be modified as a result of this work, the modernization project did not address any existing code violations resulting from previous work inside tenant space.

The design team did identify two upper floors of the Mickey Leland Build ng that posed the greatest challenge to the existing systems on lower floors. Those were Level 4 (Public

Processing) and Level 12 (Flexible Meeting Space). It was assumed that the highest occupant load for the building will re-side on one of these floors. The egress analysis evaluated the 4th Floor. In accordance with NFPA 101 Section 7.3.1.4, “Where an exit serves more than one story, only the occupant load of each story considered individually shall be used in computing the required capacity of the exit at that story, provided that the required egress capacity of the exit is not decreased in the direction of egress travel.”

Tenant Standards G.T. Mickey Leland Federal Office Building 14

Special consideration was given to the First Floor occupant load since there is convergence on this level. The final design resulted in code compliant exiting at the ground floor for the egress from above and the first floor. The occupant loads determined whether or not the correct number of exits is provided for a space and primarily focused on spaces approaching the threshold for spaces that require more than one means of egress. The secondary goal of the exiting study was to ensure that additional Assembly occupancies could be accommodated on upper floor stair systems and through the level of exit discharge systems accordingly.

The load calculation performed was based on the premise that the overall building (gross area) is a business occupancy and that there are a number of smaller occupancy groups

(net area) that contain occupancies with higher or lower occupant loads (public waiting areas, processing areas, and training rooms vs. storage rooms, mechanical areas, etc.). The occupant loads were calculated using the gross or net areas of rooms and combined work-spaces, and applying published occupant load densities found in NFPA 101 and the IBC.

Some com-mon densities for spaces found in the building are:

A. Offices: 100 sf/occupant

B. Transitioning Corridors (Concourse) 100 sf/occupant

C. Storage: 300 sf/occupant

D. Large Mechanical Areas: 500 sf/occupant

E. Break/Conference Rooms: 15 sf/occupant (net)

F. Concentrated Seating: 7 sf/occupant (net)

G. Standing Cue Areas: 18 in./occupant (net)

The gross area of a floor (roughly 15,350) is used as the starting point for calculating the occupant load of each floor. This calculation does include all spaces within the interior perimeter of the exterior walls of the building (per NFPA 101 Section 3.3.17.2.1). This calculation satisfies the required method for Group B occupancies (the majority of the floors). The Design Team then isolated areas of the floor plan that warranted calculation using the “net area” method in NFPA 101 Section 3.3.17.2.1 and applied the appropriate net occupant load factor from NFPA 101 Table 7.3.1.2. The Design Team also applied a “net area” calculation method to smaller storage rooms and incidental areas on the floor plan.

Occupant loads of dense seating and other assembly areas were based the configuration of the room only (no common areas), per the definitions of “net” area.

All area measurements were conservative in the fact that they included normally unoccupied areas such as intermediate columns, small floor openings, and irregular areas of the floor plan without subtraction. Using the gross area method for the majority of the floor plan also ensures the majority of common areas such as corridors and stairs would be accounted.

Break room occupant loads are added to the overall occupant load of the floor since they can be occupied by different groups of people who are external to the overall office population. Similarly, conference rooms apply the higher occupant load density since it is possible that outside visitors could add to the occupant loads of these rooms. In general, assembly rooms with occupant loads less than 50 persons were considered Group B occupancies and storage rooms less than 250 sf were considered incidental to the Group B.

As stated earlier, larger assembly or storage rooms were deducted from the gross area and occupant loads for those spaces were calculated separately.

Corridors, where occupants may be waiting or circulating, are calculated based on the occupant load factor for the gross business occupancy. The application of a gross occupant load calculation, using 100 sf per occupant, would assign a considerable occupant load to

Tenant Standards G.T. Mickey Leland Federal Office Building 15 the main circulating corridors as well as the individual corridors in the workspaces. In all, this estimate will be conservative since it would assume concurrent occupancy of the corridor space and the actual work areas on every floor.

The occupant loads were determined by dividing the area by the load factor. Any fraction is rounded up to the next whole number for most occupancies. Since storage occupancies have a characteristically low occupant load, only fractions 0.5 or greater are rounded up.

The occupant loads are compared to the egress capacity of the space or the egress capacity of the stairs and corridors serving the space. Using NFPA 101 exit width requirements (NFPA

101 Section 7.3.3.1), The Design Team was able to calculate the exit capacity of each door and stair.

The Design Team assumed a 32-in. clear width for nominal 36-in. doors. The exiting capacity of a 32-in. door is 160 occupants using the NFPA width factor of 0.20 in. per occupant for level exits. Spaces with the minimum 2 doors (as provided at the entrances to stair enclosures on upper floors), will automatically provide capacity for 320 persons.

The exiting capacity of each stair is based on the overall tread width of the stair (44 in.), divided by a width factor of 0.3 in./occupant. The resulting stair capacity was 146 occupants per stair. Since this capacity was less than the capacity of the doors, it was selected as the governing value - 292 occupants per floor.

Regardless of the current configuration of the upper floors, the Design Team’s objective is to provide sufficient exiting width on the first floor to properly accommodate the number of occupants using the existing system on upper floors. The actual occupant load analysis was performed on upper floors to also demonstrate that the reconfiguration of the level of exit discharge was sufficient to accommodate the higher occupant loads of the upper floors and added occupant loads due to exit convergence (Basement/First Floor).

Tenant Standards G.T. Mickey Leland Federal Office Building 16

Facility Construction

DIVISION 03

Concrete

Tenant Standards G.T. Mickey Leland Federal Office Building 18

Tenant Standards G.T. Mickey Leland Federal Office Building 19

Cast In Place Concrete

The lower structure in the building below the second floor is primarily a cast in place concrete construction. The central core of the building is a slip formed cast in place concrete construction. As such it is critical to the overall structural integrity of the building in that it provides the shear structural strength for the building. Opening shall not be cut in this concrete without seeking permission from the GSA Region 7 technical staff.

Precast Concrete

Above the second floor, the predominate structure of the building outside of the central core is precast concrete members. The floor is constructed of pre-cast double tee members with a nominal 2” topping slab with welded wire mesh reinforcing. Locations of all floor cores shall be coordinated with the GSA Region 7 technical staff.

Tenant Standards G.T. Mickey Leland Federal Office Building 20

DIVISION 05

Metals

Tenant Standards G.T. Mickey Leland Federal Office Building 22

Tenant Standards G.T. Mickey Leland Federal Office Building 23

Decorative Formed Metal

Includes Sheet Metal, Miscellaneous Metal, Column Covers, Metal Base, and Trim.

A. General:

Provide sheet metal without pitting, seam marks, roller marks, stains, discolorations, or other imperfections where exposed to view on finished units.

B. Products Provided:

Stainless-Steel Sheet Finishes – No. 4

C. Sealants, Interior:

Nonsag, paintable, nonstaining, latex sealant complying with ASTM C 834; of type and grade required to seal joints in decorative formed metal; and as recommended in writing by decorative formed metal manufacturer. Sealants shall have a VOC content of not more than 250 g/L when calculated according to 40 CFR 59, Subpart

D (EPA Method 24).

Tenant Standards G.T. Mickey Leland Federal Office Building 24

DIVISION 06

Wood, Plumbing & Composites

Tenant Standards G.T. Mickey Leland Federal Office Building 26

Tenant Standards G.T. Mickey Leland Federal Office Building 27

Interior Architectural Woodwork

Where fire-retardant-treated materials are indicated, use materials complying with requirements that are acceptable to authorities having jurisdiction, and with fire-test-response characteristics specified.

When possible, consider using Certified Wood products and materials as “FSC Pure" or "FSC

Mixed Credit" according to FSC STD-01-001, "FSC Principles and Criteria for Forest

Stewardship," and FSC STD-40-004, "FSC Standard for Chain of Custody Certification.

VOC Limits for Installation Adhesives and Sealants: Use products that comply with the following limits for VOC content when calculated according to 40 CFR 59, Subpart D (EPA

Method 24):

Wood Glues: 30 g/L.

Multipurpose Construction Adhesives: 70 g/L.

Structural Wood Member Adhesive: 140 g/L.

Architectural Sealants: 250 g/L.

A. Products Installed:

WB-1 - 2 ½” Painted Wood Base

WB-2 - 4 ½” Painted Wood Base

Color is BM 1595, Rocky Coast

B. Plastic Paneling

Gelcoat-finished, glass-fiber reinforced plastic panels complying with ASTM D 5319.

C. Trim Accessories:

Manufacturer's standard one-piece vinyl extrusions designed to retain and cover edges of panels. Provide division bars, inside corners, outside corners, and caps as needed to conceal edges.

Adhesive shall have a VOC content of 50 g/L or less when calculated according to 40

CFR 59, Subpart D (EPA Method 24).

Sealant shall have a VOC content of 250 g/L or less when calculated according to 40

D. Products Provided:

Kemlite, 0.09 inch, smooth finish.

Tenant Standards G.T. Mickey Leland Federal Office Building 29

DIVISION 07

Thermal and Moisture

Protection

Tenant Standards G.T. Mickey Leland Federal Office Building 30

Tenant Standards G.T. Mickey Leland Federal Office Building 31

Applied Fireproofing

While the building is predominately a concrete structure, there are locations where structural steel is present. It was provided with 2 hour rated protection. Cementitious

Sprayed Fire-Resistive Material was be used on to repair existing conditions damaged during construction or when new steel was incorporated.

A. VOC Content:

Products shall comply with VOC content limits of authorities having jurisdiction and the following VOC limits when calculated according to 40 CFR 59, Subpart D (EPA

Method 24):

1. Flat, Nonflat Paints and Coatings: 50 g/L.

2. Primers, Sealers, and Undercoaters: 100 g/L.

3. Anticorrosive and Antirust Paints Applied to Ferrous Metals: 100 g/L.

B. Product Installed

CAFCO 300 by Isolatek

C. Penetration Firestopping

Where rated assemblies are penetrated, firestopping is required. Provide penetration firestopping that is produced and installed to resist spread of fire according to requirements indicated, resist passage of smoke and other gases, and maintain original fire-resistance rating of construction penetrated. Penetration firestopping systems shall be compatible with one another, with the substrates forming openings, and with penetrating items if any.

D. Penetrations in Fire-Resistance-Rated Walls:

Provide penetration firestopping with ratings determined per ASTM E 814 or UL

1479, based on testing at a positive pressure differential of 0.01-inch wg (2.49 Pa).

E. Penetrations in Horizontal Assemblies:

Provide penetration firestopping with ratings determined per ASTM E 814 or UL

1479, based on testing at a positive pressure differential of 0.01-inch wg (2.49 Pa).

F. Penetrations in Smoke Barriers:

Provide penetration firestopping with ratings determined per UL 1479.

G. W-Rating:

Provide penetration firestopping showing no evidence of water leakage when tested according to UL 1479.

H. Exposed Penetration Firestopping:

Provide products with flame-spread and smoke-developed indexes of less than 25 and 450, respectively, as determined per ASTM E 84.

I. VOC Content: Penetration firestopping sealants and sealant primers shall comply with the following limits for VOC content when calculated according to 40 CFR 59, Subpart D (EPA Method 24):

1. Sealants: 250 g/L.

2. Sealant Primers for Nonporous Substrates: 250 g/L.

3. Sealant Primers for Porous Substrates: 775 g/L.

J. Product Installed:

Hilti Firestop Systems

Tenant Standards G.T. Mickey Leland Federal Office Building 32

Fire-Resistive Joint Systems

A. Joints in or between Fire-Resistance-Rated Construction:

Provide fire-resistive joint systems with ratings determined per ASTM E 1966 or UL

2079.

B. Joints at Exterior Curtain-Wall/Floor Intersections:

Provide fire-resistive joint systems with rating determined by ASTM E 119 based on testing at a positive pressure differential of 0.01-inch wg (2.49 Pa) or ASTM E 2307.

C. Joints in Smoke Barriers:

Provide fire-resistive joint systems with ratings determined per UL 2079.

D. Exposed Fire-Resistive Joint Systems:

Provide products with flame-spread and smoke-developed indexes of less than 25 and 450, respectively, as determined per ASTM E 84.

E. VOC Content:

Fire-resistive joint system sealants shall comply with the following limits for VOC content when calculated according to 40 CFR 59, Sub-part D (EPA Method 24):

1. Architectural Sealants: 250 g/L.

2. Sealant Primers for Nonporous Substrates: 250 g/L.

3. Sealant Primers for Porous Substrates: 775 g/L.

Joint Sealants

Provide joint sealants, backings, and other related materials that are compatible with one another and with joint substrates under conditions of service and application, as stated by sealant manufacturer's published data, and as substantiated by the manufacturer for each application through testing.

A. VOC Content of Interior Sealants:

Provide sealants and sealant primers for use inside the weather-proofing system that comply with the following limits for VOC content when calculated according to 40 CFR

59, Subpart D (EPA Method 24):

1. Architectural Sealants: Not more than 250 g/L.

2. Nonmembrane Roof Sealants: 300 g/L.

3. Single-Ply Roof Membrane Sealants: 450 g/L.

4. Sealant Primers for Nonporous Substrates: Not more than 250 g/L.

5. Sealant Primers for Porous Substrates: Not more than 775 g/L.

B. Latex Sealant:

Non-elastomeric, one part, non-sag, paintable latex sealant that is recommended for exposed applications on the interior. Complying with ASTM C 834, Type OP (opaque sealants).

C. Products Installed: BASF Sonolastic SL2.

DIVISION 08

Openings

Tenant Standards G.T. Mickey Leland Federal Office Building 34

Tenant Standards G.T. Mickey Leland Federal Office Building 35

Hollow Metal Doors and Frames

A. Recycled Content of Steel Products:

1. Provide products with an average recycled content of steel products so post-consumer recycled content plus one-half of pre-consumer recycled content is not less than 20 percent.

2. Provide flush-design doors, 1-3/4 inches (44 mm) thick, of seamless hollow construction, unless otherwise indicated. Construct doors with sheets joined at their vertical edges by continuous welding the full height of the door, with no visible seams on their faces or vertical edges, and all welds ground and finished flush.

3. Fabricate steel door frames, formed to profiles indicated, with full 5/8 inch

(16 mm) stops, and of the following minimum thicknesses.

4. For interior use, form frames from cold- rolled steel sheet of the following thicknesses:

i. Openings up to, and including 48 inches (1200 mm) Wide: 0.053 inch

(1.3 mm).

ii. Openings More Than 48 inches (1200 mm) Wide: 0.067 inch (1.7 mm).

5. Provide frames either saw mitered and full (continuously) welded, or machine mitered and full welded, on back side at frame corners and stops with edges straight and true. Grind welds smooth and flush on exposed surfaces.

B. Product Installed:

Door Components, L.P.

Aluminum Door and Window Frames

Much of the work did and will involve reusing existing aluminum frames and top track. The intent of new material is to match existing material that is being reused.

A. Aluminum Framing:

ASTM B 221 (ASTM B 221M), Alloy 6063-T5 or alloy and temper required to suit structural and finish requirements, not less than 0.062 inch (1.6 mm) thick.

B. High-Performance Organic Finish:

Two-coat fluoropolymer finish complying with AAMA 2604 and containing not less than 70 percent PVDF resin by weight in color coat. Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturers' written instructions. Match existing finishes, which do vary somewhat by floor

C. Product Installed:

Versatrac Interior Frames 400 R Series, with adjustable depth throat frames and 1

½” wide face trim

Flush Wood Doors

Much of the work did and will involve reusing existing solid core wood doors. Some are wood veneer. Others are plastic laminate clad. The intent of new material is to match existing material that is being reused.

A. Particleboard Cores: ANSI A208.1, Grade LD-1 or Grade LD-2, made with binder containing no urea-formaldehyde resin.

Tenant Standards G.T. Mickey Leland Federal Office Building 36

B. Hardboard-Faced Door Construction for Opaque Finish:

AWI Section 1300, PC-5 CE.

C. Plastic Laminate for Interior tenant Doors: Nevamar Golden Ash WM8110T Textured

D. Certified Wood:

Flush wood doors shall be certified as "FSC Pure" or "FSC Mixed Credit" according to

FSC STD-01-001, "FSC Principles and Criteria for Forest Stewardship," and to FSC

STD-40-004, "FSC Standard for Chain of Custody Certification

E. Low-Emitting Materials:

Provide doors made with adhesives and composite wood products that do not contain urea formaldehyde.

F. Product Installed:

VT Industries Architectural Wood Doors

Access Doors and Frames

A. Fire-Rated Access Doors and Frames:

Units complying with NFPA 80 that are identical to access door and frame assemblies tested for fire-test-response characteristics according to the following test method and that are listed and labeled by UL or another testing and inspecting agency acceptable to authorities having jurisdiction:

1. NFPA 252 or UL 10B for fire-rated access door assemblies installed vertically.

i. NFPA 288 for fire-rated access door assemblies installed horizontally

Flush Access Doors with Concealed Flanges or Fire-Rated, Flush Access Doors with

Concealed Flanges.

Aluminum Entrances and Storefronts

A. Aluminum:

Conform to the requirements published in AA "Aluminum Standards and Data," referenced ASTM standards.

B. Carbon Steel:

For carbon steel components required to join, reinforce or support the assembly of aluminum components provide carbon steel con-forming to ASTM A 36/A 36M for structural shapes, plates, and bars; ASTM A 1008/A 1008M for cold-rolled sheet and strip; or ASTM A 1011/A 1011M for hot-rolled sheet and strip.

C. Concealed Sealing Materials:

All sealing materials concealed within the entrances and storefronts shall be silicone, compatible with and adherent to each material it will be in contact with, as recommended by the manufacturer to fulfill performance requirements.

Provide sealants for use inside of the weatherproofing system that have a VOC content of

250 g/L or less when calculated according to 40 CFR 59, Sub-part D (EPA Method 24).

Tenant Standards G.T. Mickey Leland Federal Office Building 37

All-Glass Entrances and Storefronts

A. Glass GL-9:

ASTM C 1048, Kind FT (fully tempered), Condition A (uncoated surfaces), Type I

(transparent), tested for surface and edge compression per ASTM C 1048 and for impact strength per 16 CFR 1201 for Category II materials.

B. Aluminum Extrusions:

ASTM B 221 (ASTM B 221M), with strength and durability characteristics of not less than Alloy 6063-T5.

Glazed Aluminum Curtain Walls–Cassette System

The curtain wall system consists of thermally bro-ken cassette system aluminum mullions with a fluropolymer finish, and insulating glass with a high performance low emissivity coating set into the framing with structural silicon to provide a mullion-less appearance.

Exposed aluminum exterior surfaces are finished with Valspar Floropon Classic II 933X440

Bright Silver. Exposed interior aluminum surfaces are finished with Valspar Flurocryl Classic

II KJM0102 Bright Silver.

The new window system will consist of 1/4" glass – ½" airspace – 3/8" laminated glass. The laminated glass should consist of 3/16” plate – 0.060” thick interlayer – 3/16” plate. The interlayer should be a polyvinyl butyral material.

In instances where tenant improvements require new partitions to join the curtain wall, end of partitions should be capped with available attic stock of the custom partition closure extrusions fabricated for the ARRA building renovation. When this attic stock is depleted, floatable trim and adjustable partition closures should be provided. Building standard products for this application are to be Gordon Final Forms Series 911 trim and Gordon

Mullion Mate adjustable aluminum partition closures. The closure configuration appropriate for typical conditions in Leland Building will consist of 2 Mullion Mate 5 assemblies factory spliced back to back and designed to fill openings ranging from 9” to 13¾”. Closures should be powder coated with custom color to match curtain wall.

Door Hardware

Much of the work did and will involve reusing existing door hardware. An inventory of existing hard-ware using a hardware supplier such as Assa Abloy provides an opportunity to inventory existing hardware to be reused and identify hardware that can be reused and hardware which is damaged. New hardware should be proposed to coordinate with the existing hardware being reused. Lock cylinders should use a best keyway.

A. Door Hardware Schedule:

Prepared by or under the supervision of supplier, detailing fabrication and assembly of door hardware, as well as procedures and diagrams. Coordinate the final Door

Hardware Schedule with doors, frames, and related work to ensure proper size, thickness, hand, function, and finish of door hardware.

B. Products Installed:

1. Locket – Corbin Russwin ML2000

2. Trim Design – Corbin Russwin ML2000 and ML20900 ECL

3. Hinges – McKinney Five Knuckle

4. Astragals and Stiles – Pemko

5. Stops and Holders – Rixson

6. Stops, Flush Bolts, Strikes &Coordinators, Guards and Silencers – Rockwood

Tenant Standards G.T. Mickey Leland Federal Office Building 38

Glazing

A. Float Glass:

ASTM C 1036, Type I (transparent glass, flat), Quality q3 (glazing select); class as indicated in schedules at the end of Part 3

B. Fully Tempered Glass:

Provide glass complying with ASTM C1048 Kind FT and meeting the requirements of

ANSI Z97.1. Surface compression shall be equal to or greater than 10,000 psi (69

MPa). After tempering, heat soak 100 percent of all fabricated glass units to

European Union Standard EN14179 to eliminate inclusion related glass break-age.

Statistical heat soaking shall not be permitted.

Tenant Standards G.T. Mickey Leland Federal Office Building 39

DIVISION 09

Finishes

Tenant Standards G.T. Mickey Leland Federal Office Building 40

Tenant Standards G.T. Mickey Leland Federal Office Building 41

Gypsum Board Partitions

Existing partition typically are one layer of 5/8” gypsum board on 3 5/8” metal studs with

Aluminum framing top track (assumed to be a RACO type product).

A. Fire-Resistance-Rated Assemblies:

For fire-resistance-rated assemblies, provide materials and construction identical to those tested in assembly indicated according to ASTM E 119 by an independent testing agency.

B. STC-Rated Assemblies:

For STC-rated assemblies, provide materials and construction identical to those tested in assembly indicated according to ASTM E 90 and classified according to

ASTM E 413 by an independent testing agency.

C. Recycled Content:

Provide gypsum panel products with recycled content such that post-consumer re-cycled content plus one-half of pre-consumer recycled content constitutes a minimum of 40 percent by weight.

D. Regional Materials:

Gypsum panel products shall be manufactured within 500 miles (800 km) of Project site from materials that have been extracted, harvested, or recovered, as well as manufactured, within 500 miles (800 km) of Project site.

E. Gypsum Wallboard:

ASTM C 1396.

1. Regular Type: Typically 5/8” thick with long edges tapered.

2. Type X: Typically 5/8” thick with long edges tapered

F. Flexible Gypsum Board:

ASTM C 1396/C 1396M. Manufactured to bend to fit radii and to be more flexible than standard regular-type gypsum board of same thickness.

1. Thickness: 1/4 inch (6.4 mm).

2. Long Edges: Tapered.

G. Gypsum Ceiling Board:

ASTM C 1396/C 1396M.

1. Thickness: 1/2 inch (12.7 mm).

2. Long Edges: Tapered.

H. Glass-Mat, Water-Resistant Backing Board:

ASTM C 1178/C 1178M, with manufacturer's standard edges.

I. Water-Resistant Gypsum Backing Board:

ASTM C 1396/C 1396M, with manufacturer's standard edges.

Tiling

A. ANSI Ceramic Tile Standard:

Provide tile that complies with ANSI A137.1 for types, compositions, and other characteristics indicated

Tenant Standards G.T. Mickey Leland Federal Office Building 42

B. Static Coefficient of Friction:

For tile installed on walkway surfaces, provide products with the following values as determined by testing identical products per ASTM C 1028.

C. Water-Cleanable Epoxy Grout:

ANSI A118.3, with a VOC content of 65 g/L or less when calculated according to 40

CFR 59, Subpart D.

D. Sealants shall have a VOC content of 250 g/L or less when calculated according to 40

CFR 59, Sub-part D (EPA Method 24).

E. Products installed:

1. TL-1 -

Manufacturer: Daltile

Style/series: Urban Landscape

Color: Silver Lake

Size: 12”x24” Rectified

Grout: Laticrete – 78 sterling silver

Location: Typical Restroom floor

2. TL-2 -

Manufacturer: Daltile

Style/series: Ritten house square collection

Color: arctic white 0190

Finish: semi-gloss

Size: 3"x6"B

Base: cover: -a3361, bullnose-s-4369

Base corner: scr-l-3361, bullnose coner-scr-l-4369

Grout: Mapei - 93 warm gray

Location: Typical Restroom wall

3. TL-3 -

Manufacturer: Daltile

Style/series: quarry tile

Color: dawn 0q63

Size: 6" x 6"

Description: unglazed

Grout: Laticrete - 45 raven

Location: Flooring at all Kitchen Area

Acoustical Panel Ceilings

A. Acoustical Panel Standard:

Provide manufacturer's standard panels of configuration indicated that comply with

ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated.

B. Seismic Performance:

Acoustical ceiling shall with-stand the effects of earthquake motions determined according to ASCE/SEI 7.

C. Surface-Burning Characteristics:

Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

Tenant Standards G.T. Mickey Leland Federal Office Building 43

D. Products installed:

1. ACT-1

Manufacturer: USG

Style/series: Frost Clima Plus – beveled tegular

Color: white

Size: 2’ x 2’

Location: typical tenant spaces and corridors

Note: edge type fl - grid profile (g) Fineline 1/8" dxf

2. ACT-2

Manufacturer: USG

Style/series: sheetrock lay-in panels Clima Plus

Color: white

Size: 2’ x 2’ x ½”

Location: back of house

3. ACT-3

Manufacturer: USG

Style/series: Halcyon Clima Plus Logix panel

Color: white

Size: 6" x 1"

Location: typical elevator lobbies

Note: edge type fl - grid profile (d) Fineline 1/8" dxf

Stone Flooring

For stone flooring installed on walkway surfaces, provide finished installation with the following values as determined by testing identical installations and products per ASTM C

1028 – Level surfaces: Min of 0.6.

Stone for floors shall comply with requirements of FloorScore Standard.

Provide granite complying with ASTM C 615 and NBGQA's "Specifications for Architectural

Granite"

Products Installed:

1. ST-1

Manufacturer: Stone marketing international

Color: Afton White

Finish: flamed

Size: 2’-6” x 5’-0”

Description: granite

Location: ground level lobby

2. ST-2

Manufacturer: ColdSprings Granite

Color: Mesabi Black

Finish: flamed

Location: ground level lobby accent

Tenant Standards G.T. Mickey Leland Federal Office Building 44

Stone Facing

Provide limestone complying with ASTM C 568

A. Water-Cleanable Epoxy Adhesive:

ANSI A118.3, with a VOC content of 65 g/L or less when calculated according to 40

CFR 59, Subpart D (EPA Method 24).

B. Joint Sealants:

Manufacturer's standard sealants of characteristics indicated below and will not stain the stone they are applied to.

C. VOC Content:

250 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

D. Product Installed:

ST-3

Manufacturer: Vermont Structural Slate

Color: Sheffield Vein Cut

Finish: Honed

Description: limestone

Location: ground level lobby wall

Base and Accessories

A. FloorScore Compliance:

Stone for floors shall comply with requirements of FloorScore Standard

B. Adhesives:

Water-resistant type recommended by manufacturer to suit resilient products and substrate conditions indicated.

C. VOC Content:

Comply with the following limits when calculated according to 40 CFR 59, Subpart D

(EPA Method 24):

1. Cove Base Adhesives: Not more than 50 g/L.

2. Rubber Floor Adhesives: Not more than 60 g/L.

Installed products:

RB-1 manufacturer: Flexco

Color: 018 - baby breath

Description: 2 1/2" cove rubber base

Location: typical tenant space

RB-2 manufacturer: Johnsonite

Color: white

Description: 2 1/2" straight rubber base

Location: typical tenant corridor

RB-3 manufacturer: Roppe

Color: 161 snow

Description: 10" rubber stringer and wall base

Location: ground level

Tenant Standards G.T. Mickey Leland Federal Office Building 45

Resilient Tile Flooring

Prepare substrates according to manufacturer's written recommendations to ensure adhesion of resilient products.

Trowelable Leveling and Patching Compounds: Latex-modified, Portland cement based or blended hydraulic cement based formulation provided or approved by resilient product manufacturer for applications indicated.

Adhesives: Water-resistant type recommended by manufacturer to suit resilient products and substrate conditions indicated. Use adhesives that comply with the following limits for

VOC content when calculated according to 40 CFR 59, Subpart D (EPA Method 24) - VCT and Asphalt Tile Adhesives: Not more than 50 g/L.

FloorScore Compliance: Resilient tile flooring shall comply with FloorScore Standard

Products installed:

VT-1 manufacturer: Armstrong

Style/series: Safety Zone Excelon slip-retardant

Color: 57002 weathered alabaster

Location: back of house corridors level 1

VT-2 manufacturer: Armstrong

Color: 51941 polar white

Location: Public corridors level 1

VT-3 manufacturer: Armstrong

Style/series: Bio-based striations

Color: Warm grey T3608

Size: 12” x 24”

Location: Level 5

VT-4 manufacturer: Armstrong

Style/series: Bio-based striations

Color: Twilight T3603

Size: 12” x 24”

Location: Level 5

VT-5 manufacturer: Armstrong

Style/series: static dissipative tile

Color: 51951 armor grey

Size: 12" x 12"

Location: level 5

VT-6 manufacturer: Flexco

Color: French Grey with Black

Size: 12" x 12"

Location: Tunnel Elevator Cab Floor

Tenant Standards G.T. Mickey Leland Federal Office Building 46

VT-7 manufacturer: Armstrong

Style/series: imperial texture standard Excelon

Color: 5903 blue gray

Location: tenant spaces - per finish plans

Tile Carpeting

Emissions: Provide carpet tile that complies with testing and product requirements of CRI's

"Green Label Plus" program.

Trowelable Leveling and Patching Compounds: Latex-modified, hydraulic-cement-based formulation provided by or recommended by carpet tile manufacturer

Adhesives: Water-resistant, mildew-resistant, nonstaining type to suit products and subfloor conditions indicated, that complies with flammability requirements for installed carpet tile and that is recommended by carpet tile manufacturer.

VOC Content: Provide adhesives with VOC content not more than 50 g/L when calculated according to 40 CFR 59, Subpart D (EPA method 24).

CPT-1 Manufacturer: J&J Invision

Style/series: mache trace (7609) modular

Color: 452 paste

Installation: ashlar

CPT-2 manufacturer: J&J Invision

Style/series: mache trace special #961-449313-004-01

Location: floors 2, 10 (conference rooms) and all corridors

CPT-3 manufacturer: J&J Invision

Style/series: mache trace special #961-449313-004-01

Location: tunnel

CPT-4 manufacturer: J&J Invision

Color: 438 litho

Location: floors 2,4,6,7,8,11,15,23

CPT-5 manufacturer: J&J Invision

Style/series: mache trace special #961-449313-004-07

Location: floors 3, 9 , 12, 16, 17, 18, 19, 20, 22

CPT-6 manufacturer: Shaw

Style/series: stereo # 59250

Color: 50100 surf w/ ecoworx

Location: Floor 4 (IRS customer service)

Tenant Standards G.T. Mickey Leland Federal Office Building 47

CPT-7 manufacturer: J&J Invision

Style/series: mache trace (7609) modular

Color: 443 sketch

Location: floors 4, 8, 10, 11, 14, 15, 16, 21, 22

CPT-8 manufacturer: J&J Invision

Color: 453 stencil

Location: floors 8, 9, 10, 11

CPT-9 manufacturer: J&J Invision

Style/series: tumbled stone (7955) modular

Color: 326 agate

Description: carpet tile

Location: Floor 23 (IRS)

CPT-10 manufacturer: J&J Invision

Style/series: mache trace special-963-454892-001-03

Description: carpet tile

Location: level 4, level 5, level 8

Interior Painting

Interior Gypsum Board Primer: Factory-formulated latex-based primer for interior application

Interior Ferrous-Metal Primer: Factory-formulated quick-drying rust-inhibitive metal primer

Interior Zinc Coated Metal Primer: Factory formulated galvanized metal primer

Interior Metal – Galvanized Metal Primer

Latex, Interior, Institutional Low Odor/VOC, Flat (Gloss Level 1)

Interior Flat Latex-Emulsion Size: Factory-formulated flat latex-based interior paint.

Latex, Interior, Institutional Low Odor/VOC, (Gloss Level 3)

Latex, Interior, Institutional Low Odor/VOC, Semi-Gloss (Gloss Level 5)

Tenant Standards G.T. Mickey Leland Federal Office Building 48

P-1 manufacturer: Benjamin Moore

Color: oc-131 white down

Finish: egg shell

P-2 manufacturer: Benjamin Moore

Color: oc-67 ice mist

Finish: egg shell

Location: typical corridors, common areas

P-3 manufacturer: Benjamin Moore

Finish: flat

Location: gyp. Bd. Ceiling

P-4 manufacturer: PPG

Color: 530-1 silver feather

Finish: semi-gloss

Location: typ. Restroom

P-5 manufacturer: Benjamin Moore

Location: janitor's closet

P-6 manufacturer: Sherwin Williams

Color: sw6242 bracing blue

Location: level 23 accent wall

P-7 manufacturer: Sherwin Williams

Color: sw6516 down pour

P-8 manufacturer: Sherwin Williams

Color: sw6528 cosmos

P-9 manufacturer: Sherwin Williams

Color: sw6914 rice paddy

P-10 manufacturer: Sherwin Williams

Color: sw6601 tanager

Tenant Standards G.T. Mickey Leland Federal Office Building 49

P-11manufacturer: Sherwin Williams

Color: sw6130 mannered gold

P-12 manufacturer: Sherwin Williams

Color: sw6507 resolute blue

P-13 manufacturer: Sherwin Williams

Color: sw6307 fine wine

P-14 manufacturer: Sherwin Williams

Color: sw6510 loyal blue

P-15 manufacturer: Sherwin Williams

Color: sw6866 heartthrob red

Location: level 5 accent wall

P-16 manufacturer: Sherwin Williams

Color: sw7063 - nebulous white

Location: garage stairwell walls

P-17 manufacturer: Sherwin Williams

Color: sw7067 - cityscape

Location: garage steel stairs, doors & railings

Aluminum Closure Piece

Closure piece between demising wall and mullion: Gordon Mullion Mate (3-5)

Tenant Standards G.T. Mickey Leland Federal Office Building 50

DIVISION 10

Specialties

Tenant Standards G.T. Mickey Leland Federal Office Building 52

Tenant Standards G.T. Mickey Leland Federal Office Building 53

Interior Signage

Tenant Standards G.T. Mickey Leland Federal Office Building 54

Tenant Standards G.T. Mickey Leland Federal Office Building 55

Tenant Standards G.T. Mickey Leland Federal Office Building 56

Tenant Standards G.T. Mickey Leland Federal Office Building 57

Tenant Standards G.T. Mickey Leland Federal Office Building 58

Tenant Standards G.T. Mickey Leland Federal Office Building 59

Toilet Compartments

Stainless-Steel Finish: No. 4 bright, directional polish on exposed faces. Protect exposed surfaces from damage by application of strippable, temporary protective covering before shipment.

Product Installed: Accurate Stainless Steel Ceiling Hung Partitions

Toilet, Bath, and Laundry Accessories

Products Installed: American Specialties, Inc.

Dual Toilet Paper Holder. Model # 0697-GAL

Partition Mounted Toilet Paper Dispenser with Sanitary Disposal. Model # 04813

Surface Mounted Sanitary Napkin Disposal. Model #0852

Semi-recessed Roll Paper Towel Dispenser. Model # 04523-6

Recessed Automatic Roll Paper Towel Dispenser and Waste Receptacle. Model # 046924A

Stainless Steel Free Standing Waste Receptacle. Model # 0810/0811

Lavatory Mounted Soap Dispenser. Model # 0332

Wall Mounted Automatic Foam Soap Dispenser. Model # 20365

Surface Mounted Seat Cover Dispenser. Model #0477-SM

1-1/2” DIA Grab Bar Series with Snap-on Flange Covers. Model #3800

Interlock Stainless Steel Framed Mirror. Model #0600

Fire-Protection Specialties

Product Installed: Activar Fire Protection Cabinets with vertical duo panel with pull and Saf-

T-Lok. Provide Red vertical FE Letters.

Tenant Standards G.T.