Amendment 0003 BL8 Leland Davits and Anchor Inspection Report.pdf

PDF 916 KB Posted

Attached to
Full Maintenance Services for Houston, Beaumont, and Galveston, TX
Solicitation number
47PH0220R0017
Issued by

About this file

This document includes a certificate of inspection for facade maintenance equipment at a federal building in Houston, Texas, as well as a solicitation notice for full maintenance services at multiple federal facilities in the region.

The certificate details the results of load testing and visual inspections performed on safety anchors, davit bases, and davit arms at the 1919 Smith building in Houston. Inspections found the equipment to be in good condition and compliant with federal regulations. The notice solicits proposals for full maintenance, operations, and groundskeeping services at seven federal buildings in Houston, Beaumont, and Galveston, Texas. Services include custodial work, repairs, and landscaping. The solicitation number is 47PH0220R0011 and it is reserved exclusively for service-disabled veteran-owned small businesses. The NAICS code is 561210 and the contract is expected to begin on May 1, 2021. The General Services Administration is the contracting agency.

View the file

Other files

File Type Posted
Amendment 0004 47PH0220R0017 SF33.pdf PDF
Amendment 0004 Questions and Answers.pdf PDF
Amendment 0004 Figure B-3 Pricing of Services .xlsx XLSX spreadsheet
Amendment 0004 SF30.pdf PDF
Amendment 0003 Questions and Answers.pdf PDF
Amendment 0003 47PH0220R0017 SF33.pdf PDF
Amendment 0003 BL7 Leland Design Guide.pdf PDF
Amendment 0003 Houston Galveston Beaumont OM_FM Spec Amend 0003 7 Jan 21.pdf PDF
47PH0220R0017 Amendment 0003.pdf PDF
Amendment 0003 BL5 Work Order History.xlsx XLSX spreadsheet
Amendment 0002 Houston Galveston Beaumont OM FM Spec 21 Dec 20.pdf PDF
Amendment 0002 BL5 Work Order History.xlsx XLSX spreadsheet
47PH0220R0017 Amendment 0002.pdf PDF
Amendment 0001 Attachment 4 Flag Policy.pdf PDF
Amendment 0001 Pre-Proposal Conference Houston Beaumont and Galveston.pptx PPTX presentation
Amendment 0001 Houston Galveston Beaumont OM_FM Spec 14 Dec 20 - Google Docs.pdf PDF
Amendment 0001 BL2 Inventory to Include Fire Alarm Devices.xlsx XLSX spreadsheet
47PH0220R0017 Amendment 0001 SF30.pdf PDF
Amendment 0001 Pre-Proposal Conference Questions and Answers.pdf PDF
Amendment 0001 Figure B-3 Pricing 5 YEAR- TOTAL_ESTIMATES.xlsx XLSX spreadsheet
BL2 Inventory to Include Fire Alarm Devices.pdf PDF
Exhibit M7 - Qualificaiton of Electrical Testing Technicians.pdf PDF
Exhibit M2 - Green Purchasing Report.pdf PDF
Figure L-3 Past Performance Questionnaire.pdf PDF
Exhibit C6 - Recycle Solid Water Trash Report.pdf PDF
Exhibit C2 Custodial Quality Assurance Surveillance Plan.pdf PDF
Exhibit C1 Building Information Sheet.pdf PDF
Attachment 1 Collective Bargaining Agreement for O_M personnel with Wage Determination.pdf PDF
Figure L-2 Management Plan Baseline.pdf PDF
Exhibit C8 - GSA Form 3638 Pest Control Work and Inspection Report.pdf PDF
Exhibit M4 - Bldg Op Plan Template.pdf PDF
Exhibit M10- PV Service Schedule V5.pdf PDF
Exhibit C4 - Building Exterior and Hardscape Plan.pdf PDF
Exhibit C7 - PBS Waste Audits.pdf PDF
47PH0220R0017 Solicitation and Specifications.pdf PDF
Exhibit M3 - Environmental Sustainable Products.pdf PDF
BL5 Work Order History.pdf PDF
Figure B-1 for Union and Non Union Contracts.xlsx XLSX spreadsheet
BL6 PM Report.pdf PDF
BL3 Location General Information .pdf PDF
Exhibit C3 - Surveilence Form 1181-A.pdf PDF
Exhibit M9 Preventative Maintenance 2018 GSA OM Guide.pdf PDF
Exhibit M1 Quality Assurance Surveillance Plan.pdf PDF
Figure B-3 Pricing 5 YEAR- TOTAL_ESTIMATES.xlsx XLSX spreadsheet
Figure L-1 Management Plan Worksheet.xlsx XLSX spreadsheet
BL1- Houston_Galveston Fire Extinguisher Report.pdf PDF
Exhibit M8 - Misc Best Practices Shave Energy.pdf PDF
Exhibit M5 - Smart Buildings.pdf PDF
BL4 Roof Information.pdf PDF
Exhibit M6 Water Treatment.pdf PDF
Show 40 more

Latest 50 of 54 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CERTIFICATE OF REGULATION COMPLIANCE

FAÇADE MAINTENANCE DAVITS, DAVIT BASES AND SAFETY ANCHORS

Prepared for Pegasus Support Services LLC.

1919 Smith Houston, TX 77002

Visual Certificate Expiration Date: June 26, 2019

Physical Certificate Expiration Date: June 26, 2023

Job # 15604

CLIENT

Pegasus Support Services LLC 100 Stoneforest Dr., Suite 100

Woodstock, GA 30189

SCOPE

This certificate is for the load test and Visual Inspection for

Roof Level 24 -o (24) safety anchor Tiebacks.

o (14) Davit Bases.

o (2) Davit Arms

TEST PROCEDURE

Physical test

A 2500-pound force was exerted on each safety anchor June 26, 2018. This pull was made at a position that simulated the forces that would likely be exerted on the safety anchors in normal operation.

Inspection of Anchors

This year the anchors were visually inspected for signs of potential defects. Due to the corrosive nature of our local environment McCrory Engineering, Inc. requires a Physical load test be performed every fifth year with annual visual inspection between each load teat interval.

Inspection of Parapet

The parapet wall is 7' high which is above the legal height does not require to be tied off personnel while working on the roof. Personnel working near some of the Davit Bases needs to wear a Harness because there is no parapet.

Basis for Test

The tests were conducted to conform with the procedures in the Federal Register Rules and Regulations designated “Part II, the Department of Labor, OSHA, 29 CFR Part 1910 – Amended, Section 1910.66, (Powered Platforms for Building Maintenance)”, 29 CFR Part 1926 – Subpart L (“Scaffolds”) and ANSI International Window Cleaning Association I-14.1-2001.

TEST RESULTS

All Most of the Tiebacks were found free of Physical Defect, deflection and Corrosion.

All Davit Arms and Bases were found free of physical defect and corrosion.

NOTE: Most of the wall mounted Tiebacks were found with Minor corrosion.

McCrory Engineering recommends to services these tiebacks. Use a Metal Brush and clean the surface and apply some Anticorrosion or Galvanized coating.

CERTIFICATION

I HEREBY CERTIFY that a physical assessment was made of the façade maintenance components installed on the roof level of the

1919 Smith, located in Houston, TX

Findings show that the equipment does meet the requirements of Federal Regulation 29 CFR 1910.66, 29 CFR Part 1926 and ANSI International Window Cleaning Association I-14.1-2001.

I CERTIFY that I am a registered Professional Engineer in the State of Texas.

Staff Assistants used in the testing are full-time employees of McCrory Engineering working under the direct supervision of this Professional Engineer.

I FURTHER CERTIFY that the findings and conclusions contained in this report have been, to the best of my knowledge, correctly and completely stated without bias, and are based upon my observations and my experience. No responsibility is assumed for events that occur after the submission of this report and no warranty, either expressed or implied, is made.

CERTIFIED THIS 26TH DAY OF JUNE, 2018

E. Don McCrory, Jr., P. E.

Registration No. 36647

Texas Registered Engineering Firm F-3951

Typical Beam mounted Safety Anchor Tiebacks

Typical Wall Mounted Tiebacks (Showing minor corrosion)

Typical Davit Arm

Typical Davit Base

Load Testing the Davit Arm with a Tieback

Load Testing the Arm for ~1500 Pounds