Amendment 0003 BL8 Leland Davits and Anchor Inspection Report.pdf
PDF 916 KB Posted
- Solicitation number
- 47PH0220R0017
About this file
This document includes a certificate of inspection for facade maintenance equipment at a federal building in Houston, Texas, as well as a solicitation notice for full maintenance services at multiple federal facilities in the region.
The certificate details the results of load testing and visual inspections performed on safety anchors, davit bases, and davit arms at the 1919 Smith building in Houston. Inspections found the equipment to be in good condition and compliant with federal regulations. The notice solicits proposals for full maintenance, operations, and groundskeeping services at seven federal buildings in Houston, Beaumont, and Galveston, Texas. Services include custodial work, repairs, and landscaping. The solicitation number is 47PH0220R0011 and it is reserved exclusively for service-disabled veteran-owned small businesses. The NAICS code is 561210 and the contract is expected to begin on May 1, 2021. The General Services Administration is the contracting agency.
View the file
Other files
Show 40 more
Latest 50 of 54 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CERTIFICATE OF REGULATION COMPLIANCE
FAÇADE MAINTENANCE DAVITS, DAVIT BASES AND SAFETY ANCHORS
Prepared for Pegasus Support Services LLC.
1919 Smith Houston, TX 77002
Visual Certificate Expiration Date: June 26, 2019
Physical Certificate Expiration Date: June 26, 2023
Job # 15604
CLIENT
Pegasus Support Services LLC 100 Stoneforest Dr., Suite 100
Woodstock, GA 30189
SCOPE
This certificate is for the load test and Visual Inspection for
Roof Level 24 -o (24) safety anchor Tiebacks.
o (14) Davit Bases.
o (2) Davit Arms
TEST PROCEDURE
Physical test
A 2500-pound force was exerted on each safety anchor June 26, 2018. This pull was made at a position that simulated the forces that would likely be exerted on the safety anchors in normal operation.
Inspection of Anchors
This year the anchors were visually inspected for signs of potential defects. Due to the corrosive nature of our local environment McCrory Engineering, Inc. requires a Physical load test be performed every fifth year with annual visual inspection between each load teat interval.
Inspection of Parapet
The parapet wall is 7' high which is above the legal height does not require to be tied off personnel while working on the roof. Personnel working near some of the Davit Bases needs to wear a Harness because there is no parapet.
Basis for Test
The tests were conducted to conform with the procedures in the Federal Register Rules and Regulations designated “Part II, the Department of Labor, OSHA, 29 CFR Part 1910 – Amended, Section 1910.66, (Powered Platforms for Building Maintenance)”, 29 CFR Part 1926 – Subpart L (“Scaffolds”) and ANSI International Window Cleaning Association I-14.1-2001.
TEST RESULTS
All Most of the Tiebacks were found free of Physical Defect, deflection and Corrosion.
All Davit Arms and Bases were found free of physical defect and corrosion.
NOTE: Most of the wall mounted Tiebacks were found with Minor corrosion.
McCrory Engineering recommends to services these tiebacks. Use a Metal Brush and clean the surface and apply some Anticorrosion or Galvanized coating.
CERTIFICATION
I HEREBY CERTIFY that a physical assessment was made of the façade maintenance components installed on the roof level of the
1919 Smith, located in Houston, TX
Findings show that the equipment does meet the requirements of Federal Regulation 29 CFR 1910.66, 29 CFR Part 1926 and ANSI International Window Cleaning Association I-14.1-2001.
I CERTIFY that I am a registered Professional Engineer in the State of Texas.
Staff Assistants used in the testing are full-time employees of McCrory Engineering working under the direct supervision of this Professional Engineer.
I FURTHER CERTIFY that the findings and conclusions contained in this report have been, to the best of my knowledge, correctly and completely stated without bias, and are based upon my observations and my experience. No responsibility is assumed for events that occur after the submission of this report and no warranty, either expressed or implied, is made.
CERTIFIED THIS 26TH DAY OF JUNE, 2018
E. Don McCrory, Jr., P. E.
Registration No. 36647
Texas Registered Engineering Firm F-3951
Typical Beam mounted Safety Anchor Tiebacks
Typical Wall Mounted Tiebacks (Showing minor corrosion)
Typical Davit Arm
Typical Davit Base
Load Testing the Davit Arm with a Tieback
Load Testing the Arm for ~1500 Pounds