The contract opportunity is for the comprehensive rehabilitation of facilities on the Manitou Islands, to be managed by the National Park Service National Office. The Project Manual provides detailed technical specifications and requirements for the rehabilitation work, including specifications for various building systems, materials, and construction methods. It covers the scope of work, performance requirements, and quality control expectations. This appears to be a solicitation for construction services, with the anticipated contract award date and pricing terms not specified in this particular document.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SLEEPING BEAR DUNES NATIONAL LAKESHORE
COMPREHENSIVE FACILITY REHABILITATION
ON MANITOU ISLANDS
SLBE 318729
FINAL
CONSTRUCTION DOCUMENTS
PROJECT MANUAL
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
MAY 2024
ST
AT E OF MICH IGAN
L ICENS ED PROF ES S IONAL ENG
I N
EE
R
ZACHARY
MORRIS
License No.
6201310992
Michael Ostendorf
6201313818
5/10/2024 5/10/2024
Appendices
A. Asbestos Inspection, Lead Paint Testing, and PCB Bulk Product Testing Report (June 2023)
B. Asbestos Inspection, Lead Paint Testing, and PCB Bulk Product Testing Report (October 2023)
C. Limited Site Investigation
D. Manitou Island Rehabilitation – Test Pits – Subsurface Exploration Report
E. Manitou Island Rehabilitation – Chicago Road – Geotechnical Engineering Report
F. Superintendent’s Compendium
G. Existing Dock Drawings
Appendix A
Asbestos Inspection, Lead Paint Testing, and PCB Bulk
Product Testing Report (June 2023)
Facilities | Environmental | Geotechnical | Materials
Asbestos Inspection, Lead Paint Testing, and PCB Bulk Product Testing Report Project: Comprehensive Facility Rehabilitation on
Manitou Islands
North and South Manitou Islands
Glen Arbor Township, Michigan
June 14, 2023 | Project Number: N6237175
Prepared for:
VHB Inc.
351 McLaws Circle, Suite 3 Williamsburg, Virginia 23185-5797
12460 Plaza Drive Cleveland, Ohio 44130
P (216) 459-8378 F (216) 459-8954
Terracon.com
Facilities | Environmental | Geotechnical | Materials
June 14, 2023
VHB Inc.
351 McLaws Circle, Suite 3 Williamsburg, Virginia 23185-5797
Attn: Mr. Vikrant Desai P: (757) 279-2832 E: vdesai@vhb.com
Re: Asbestos Inspection, Lead Paint Testing, and PCB Bulk Product Testing Report Project: Comprehensive Facility Rehabilitation on Manitou Islands North and South Manitou Islands Glen Arbor Township, Michigan Terracon Project No. N6237175
Dear Mr. Desai:
Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report for the above-referenced project to VHB Inc. (Client). The purpose of this report is to present the results of an asbestos inspection, lead paint testing, and PCB bulk product testing scope of services which was conducted at the site on May 15, 16, and 17, 2023 prior to renovation activities regarding a rehabilitation project. The scope of services was limited to the planned rehabilitation project locations.
As a result of the completed scope of services, asbestos-containing materials, lead-containing paint, and PCB-containing bulk product materials were identified. Please see the attached report for further detail. The findings, results, recommendations, and conclusions presented in this report are based on conditions that existed at the time of the site visit.
Terracon appreciates the opportunity to provide this service to VHB, Inc. If you have any questions regarding this report, please contact the undersigned at (216) 459-8378.
Sincerely, Terracon Consultants, Inc.
Prepared By: Reviewed By:
Catherine Baney Joseph A. Tussey Department Manager Principal
Table Of Contents
INTRODUCTION
1.1 Asbestos Inspection
1.2 Lead PaintTesting
1.3 Polychlorinated Biphenyl (PCB) Bulk Product Testing
1.4 Reliance
PROJECT DESCRIPTION
Asbestos Inspection
3.1 Asbestos Visual Assessment
3.2 Asbestos Physical Assessment
3.3 Asbestos Sample Collection
3.4 Asbestos Sample Analysis
Lead Paint Testing
4.1 Lead Paint Visual Assessment
4.2 Lead Paint Physical Assessment
4.3 Lead Paint Sample Collection
4.4 Lead Paint Sample Analysis
PCB Bulk Product Testing
5.1 PCB Bulk Visual Assessment
5.2 PCB Bulk Sample Collection
5.3 PCB Bulk Sample Analysis
REGULATORY OVERVIEW
6.1 Asbestos Regulatory Overview
6.2 Lead Regulatory Overview
6.3 PCB Regulatory Overview
FINDINGS AND RECOMMENDATIONS
7.1 Asbestos Inspection Results
7.2 Lead Paint Testing Results
7.3 PCB Bulk Product Testing Results
7.4 Appendices
LIMITATIONS/GENERAL COMMENTS
APPENDIX A MATERIALS IDENTIFIED TO CONTAIN GREATER THAN 1% ASBESTOS
MATERIALS IDENTIFIED TO CONTAIN 1% ASBESTOS OR LESS
APPENDIX B B-1 –ASBESTOS INSPECTION SAMPLE & RESULTS SUMMARY
B-2 –PAINT SAMPLE & RESULTS SUMMARY
B-3 - PCB BULK PRODUCT SAMPLE & RESULTS SUMMARY
APPENDIX C C-1 – ASBESTOS ANALYTICAL LABORATORY REPORT & CHAIN-OF-CUSTODY
C-2 – LEAD PAINT ANALYTICAL LABORATORY REPORT & CHAIN-OF-CUSTODY
C-3 – PCB BULK PRODUCT ANALYTICAL LABORATORY REPORT & CHAIN-OF-CUSTODY
APPENDIX D LICENSES AND CERTIFICATIONS
APPENDIX E PHOTOGRAPHS
Facilities | Environmental | Geotechnical |Materials
ASBESTOS INSPECTION, LEAD PAINT TESTING,
AND PCB BULK PRODUCT TESTING REPORT
Project: Comprehensive Facility Rehabilitation on Manitou Islands North and South Manitou Islands Glen Arbor Township, Michigan
Terracon Project No. N6237175 June 14, 2023
INTRODUCTION
Terracon Consultants, Inc. (Terracon) conducted an asbestos inspection, lead paint testing, and PCB bulk product testing scope of services regarding the comprehensive facility rehibition on Manitou Islands project. The rehabilitation (i.e., renovation) project involves the exterior of 13 buildings located on South Manitou Island in Glen Arbor Township, Michigan and the exterior of nine (9) buildings on North Manitou Island in Glen Arbor Township, Michigan. The project also includes the interior (of two (2) of the nine (9) buildings located on North Manitou Island. The scope of services was conducted at the project site on May 15, 16, and 17, 2023, by Michigan Occupational Safety and Health Administration (MIOSHA) asbestos inspector Catherine Baney (#A54513).
We understand that our scope of services was requested due to the planned renovations of the specified exterior and interior areas of the selected buildings (noted above, and below in Section 2.0).
Asbestos inspections are required prior to renovation or demolition activities to satisfy requirements of the United States Environmental Protection Agency (USEPA) 40 Code of Federal Regulations (CFR) Part 61, Subpart M, the National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation and state of Michigan asbestos regulations. For lead paint, contractors need to take appropriate precautions to comply with the Occupational Safety and Health Administration (OSHA) lead in construction regulation (29 CFR 1962.62) when disturbing paints with lead. For PCB bulk product materials, the Code of Federal Regulations (CFR) at 40 CFR 761, the Toxic Substances Control Act (TSCA) is applicable for material handling and disposal.
Please note that the scope of services was specific and limited to the project-specified building exteriors and included the interior of two (2) buildings, which Terracon understood are being planned for rehabilitation activities (i.e., renovation).
1.1 Asbestos Inspection
Homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented with respect to accessible building components pertaining to the rehabilitation project scope. Although a reasonable effort was made to identify readily accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids, or in other concealed areas. Additional suspect materials may also exist in areas of buildings which were outside the scope of this inspection (e.g., areas not included in the rehabilitation scope). Bulk samples from suspect ACM within rehabilitation project areas were collected in general accordance with the sampling protocols outlined in USEPA 40 Code of Federal Regulations (CFR) Part 763, Subpart E – 763.86, known as the Asbestos Hazard Emergency Response Act (AHERA). Samples were delivered to an accredited laboratory for polarized light microscopy (PLM) analysis to determine asbestos content. When
Asbestos Inspection, PCB Bulk Product Testing, and Lead Paint Testing Report Project: Comprehensive Facility Rehabilitation on Manitou Islands | Glen Arbor Township, MI June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 2 applicable, the additional point count method (400 points) was utilized to accurately quantify samples identified by PLM analysis to contain low percentages of asbestos.
1.2 Lead Paint Testing
Paint chip/scraping samples were collected from accessible, representative, dominant-type painted components from accessible areas of the subject structures and locations included in the rehabilitation project. Sampling locations were chosen randomly to be representative of the homogeneous painted project areas. Although reasonable effort was made to inspect the substrate of the unique painting combinations, additional suspect but un-tested paint could be located at the site due to undetected changes in the paints or variations in lead concentrations in unique paint combinations, and in areas not included in the rehabilitation project scope. Collected paint chip/scraping samples were delivered to an accredited laboratory for lead content analysis by flame atomic absorption spectrophotometry
(FAAS).
1.3 Polychlorinated Biphenyl (PCB) Bulk Product Testing
The sampling scope of work was limited to readily accessible caulking, glazing and epoxy-type materials, if present, throughout the rehabilitation areas. Additional suspect materials may also exist in areas of buildings which were outside the scope of this inspection (e.g., areas not included in the rehabilitation scope). Sample collection was performed using a clean utility knife to remove caulking, glazing and epoxy-type materials from designated surfaces. Collected material samples were placed in sealable containers, labeled with unique sample numbers, and submitted under chain of custody for analysis by U.S. Environmental Protection Agency (USEPA) method SW8082.
1.4 Reliance
This report is for the exclusive use of VHB (Client) for the project being discussed. Reliance by any other party on this report is prohibited without the written authorization of Terracon and the Client.
Reliance on this report by the Client and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal, this report, and the Agreement between Terracon and the Client. The limitation of liability defined in the Agreement is the aggregate limit of Terracon’s liability to the Client.
PROJECT DESCRIPTION
The rehabilitation project involves the following 11 structures and exterior/interior areas as noted located on North Manitou Island:
Hans Halseth House QTRS (exterior rehabilitation only) o Single-story structure on a concrete block foundation, with a pitched wooden shingled roof and painted exterior wood siding.
Additionally, an adjacent shed is on concrete pad with a sloped wooden shingled roof and painted exterior wood siding.
Howard Foote Cottage (exterior rehabilitation only)
June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 3 o Single-story structure on a concrete block foundation, with a pitched asphalt shingled roof and painted exterior wood siding.
Newhall Cottage (exterior rehabilitation only) o Single-story structure on a concrete block foundation, with a pitched asphalt shingled roof and painted exterior wood siding.
Additionally, an adjacent shed structure constructed on concrete slab with a pitched asphalt shingled roof and painted exterior wood siding.
Riggs Cottage (exterior rehabilitation only) o Single-story structure on a concrete block foundation, with a pitched asphalt shingled roof, and painted exterior wood siding.
Riggs Generator Building (exterior rehabilitation only) o Single-story structure on a concrete block foundation, with a pitched asphalt shingled roof and painted exterior wood siding.
Riggs Shed (exterior rehabilitation only) o Single-story structure on a concrete block foundation, with a wood-shingled roof and wood siding.
Trude Cottage (interior and exterior rehabilitation) o Single-story structure on a concrete block foundation, with a pitched asphalt shingled roof and painted exterior wood siding. The interior is finished with wood panel walls and wood floors. A water heating tank was observed with no heating or cooling systems.
USLSS Dwelling QTRS (exterior rehabilitation only) o Two-story structure with full basement on a concrete floor with masonry foundation walls, a pitched wooden shingled roof, and painted exteriors.
USLSS Lifeboat Station (exterior rehabilitation only) o Two-story structure constructed on concrete blocks, a pitched wooden shingled roof, and painted exteriors.
Village Barn (interior and exterior rehabilitation) o One-story split-level structure, concrete floors, masonry foundation walls, wood interior and exterior finishes with a sloped metal roof. No observed heating or cooling systems.
Generator Building (exterior rehabilitation only) o Single-story concrete block and masonry stone building constructed slab-on-grade with a sloped newly installed asphalt shingled roof.
The rehabilitation project involves the exterior of the following 13 buildings on South Manitou Island:
June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 4
Beck Theodore Farmhouse (exterior rehabilitation only) o Two-story structure on a concrete block foundation, pitched asphalt shingled roof and painted exteriors.
Beck Theodore Shed (exterior rehabilitation only) o Single-story wooden shed structure with a pitched asphalt shingled roof and painted exteriors.
Benth Johnson/Kelderhouse QTRS (exterior rehabilitation only) o Two-story slab-on-grade structure with a rear porch, pitched wood shingled roof, and painted exteriors.
Hutzler, George C & Mary Ann House (exterior rehabilitation only) o Two-story slab-on-grade structure with a rear porch, pitched wood shingled roof, and painted exteriors.
Hutzler, George C & Mary Ann Barn (exterior rehabilitation only) o One-story slab-on-grade structure with wood exteriors not painted.
Hutzler, George C & Mary Shed (exterior rehabilitation only) o One-story slab-on-grade structure with wood exteriors not painted.
Hutzler, George I & Selma QTRS (exterior rehabilitation only) o Two-story slab-on-grade structure with a rear porch, pitched wood shingled roof, and painted exteriors.
Hutzler, George J & Margaretha Pig Barn (exterior rehabilitation only) o Two-story slab-on-grade structure with a rear porch, pitched asphalt shingled roof, and painted exteriors. The adjacent barn is a wood shingled roof and wood siding (not painted).
Johnsom, Benth House QTRS (exterior rehabilitation only) o Single-story slab-on-grade structure with a front porch, pitched wooden shingled roof, and painted exteriors.
Keeler, Ory & Betty House QTRS (exterior rehabilitation only) o Two-story slab on grade structure, with a pitched wooden shingled roof with painted exterior.
Maintenance Shop (exterior rehabilitation only) o One-story slab on grade structure, with a pitched asphalt shingled roof and painted exteriors.
Tobin, John & Lottie House QTRS (exterior rehabilitation only)
June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 5 o Two-story slab-on-grade with a front porch, pitched wooden shingled roof and painted exteriors.
USLSS Dwellings QTRS (exterior rehabilitation only) o Two-story with an attic and full basement, and a wooden shingled roof and painted exteriors.
ASBESTOS INSPECTION FIELD ACTIVITIES
The project-specific asbestos inspection was conducted at the site on May 15, 16, and 17, 2023 by MIOSHA-certified Asbestos Inspector Catherine E. Baney (#A54513). A copy of her asbestos inspector credential is attached in Appendix D. The asbestos inspection was conducted in general accordance with the sample collection protocols established in USEPA 40 CFR Part 763, Subpart E, Section 763.86, AHERA. A summary of the asbestos inspection activities is provided below.
3.1 Asbestos Visual Assessment
Inspection activities began with visual observations of accessible exterior areas of the 13 project buildings on South Manitou Island, and the nine (9) project buildings on North Manitou Island which included the exterior areas of all nine (9) and also the interior areas of two (2) of the nine (9) project buildings on North Manitou Island to identify homogeneous areas of suspect ACMs. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application. Building materials identified as concrete, glass, wood, masonry, metal, or rubber were not considered suspect ACM.
3.2 Asbestos Physical Assessment
A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material that can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
3.3 Asbestos Sample Collection
Based on the results of the visual observation, bulk samples from suspect ACM were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker. The selection of sample locations and frequency of sampling was based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.
With respect to the project-specific scope, Terracon collected a total of 93 bulk samples from 31 homogeneous areas of suspect ACM. A summary table of samples collected with analytical results is included in Appendix B.
June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 6
3.4 Asbestos Sample Analysis
Bulk samples were submitted under chain-of-custody to International Asbestos Testing Laboratories (IATL) of Mount Laurel, New Jersey for analysis by PLM with dispersion staining techniques per USEPA Method for Determination of Asbestos in Bulk Building Materials (600/R-93/116). The percentage of asbestos, where applicable, was determined by microscopic visual estimation using PLM analysis. The additional point count method (400 points) was utilized to accurately quantify samples identified by PLM analysis to contain low percentages of asbestos. IATL is accredited for PLM analysis under the National Voluntary Laboratory Accreditation Program (NVLAP), accreditation number 101165-0. The laboratory analytical report and sample chain-of-custody are included in Appendix C.
LEAD PAINT TESTING ACTIVITIES
Terracon representative Catherine E. Baney collected paint chip/scraping samples at the project site on May 15, 16, and 17, 2023. A summary of the lead paint testing activities is provided below.
4.1 Lead Paint Visual Assessment
Terracon’s lead paint activities began with visual observations of accessible areas of the project specific structures and areas to identify unique combinations of dominant-type paints. A unique combination of paint consists of paint that is applied to a building material and has similar color, substrate, and component.
Paint that was applied to equipment, furniture, or other movable objects was not included in the lead paint testing scope.
4.2 Lead Paint Physical Assessment
A physical assessment of each unique combination of paint was conducted to assess the condition of the paint. Paint was visually assessed and assigned a condition of intact (good), fair, or poor (top-layer failure, multi-layer failure, and substrate failure).
4.3 Lead Paint Sample Collection
Based on the results of the visual assessment, randomly selected locations of unique dominant-type combinations of paint were sampled. Painted surfaces comprising equipment, furniture, or other movable objects were not sampled. Paint chip/scraping samples were collected using a clean straight-edge razor to remove paint from accessible, representative, dominant-type painted components for lead-in paint analysis.
With respect to the project-specific scope, Terracon collected a total of 36 paint chip/scraping samples from dominant-type paint coatings at various random project locations. A summary table of samples collected with analytical results is included in Appendix B.
4.4 Lead Paint Sample Analysis
Paint chip/scraping samples were submitted under chain-of-custody to IATL of Mount Laurel, New Jersey for analysis by FAAS per USEPA Method SW 846-7000B (ASTM D3335-85A). The laboratory reports the analytical result for each sample as a percent of lead by weight (% by weight) and lead
June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 7 parts per million (ppm). IATL is accredited for lead analysis by the EPA National Lead Laboratory Accreditation Program (NLLAP), and the American Industrial Hygiene Association – Laboratory Accreditation Programs, LLC (AIHA-LAP, LLC), accreditation number 100188. The laboratory analytical report and sample cchain of custodyare included in Appendix C.
PCB BULK PRODUCT TESTING ACTIVITIES
Terracon representative Catherine E. Baney collected PCB bulk product samples from the project site on May 15, 16, and 17, 2023. A summary of the PCB bulk testing activities is provided below.
5.1 PCB Bulk Visual Assessment
Terracon identified accessible caulking, glazing, and epoxy-type materials (suspect to contain PCBs) where present relative to the project areas for sampling and laboratory analysis.
5.2 PCB Bulk Sample Collection
Sample collection was performed using a clean utility knife to remove caulking, glazing and epoxy-type materials from designated surfaces. Collected material samples were placed in sealable containers, labeled with unique sample numbers, and submitted under chain of custody to EMSL Analytical, Inc. (EMSL) of Cinnaminson, New Jersey for analysis by U.S. Environmental Protection Agency (USEPA) method SW8082. EMSL is a certified laboratory under the National Environmental Laboratory Accreditation Program (NELAP).
With respect to the project-specific scope, Terracon collected a total of 22 bulk product samples (i.e., glazing and caulking materials) for analysis of PCB content. A summary table of samples collected with analytical results is included in Appendix B.
5.3 PCB Bulk Sample Analysis
Collected material samples were placed in sealable containers, labeled with unique sample numbers, and submitted under chain of custody to EMSL Analytical, Inc. (EMSL) of Cinnaminson, New Jersey for analysis by U.S. Environmental Protection Agency (USEPA) method SW8082. EMSL is a certified laboratory under the National Environmental Laboratory Accreditation Program (NELAP). The laboratory analytical report and sample chain of custody are included in Appendix C.
REGULATORY OVERVIEW
6.1 Asbestos Regulatory Overview
The federal asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACM is considered RACM.
The asbestos NESHAP regulation classifies ACM as either RACM, Category I non-friable ACM or Category II non-friable ACM. RACM includes all friable ACM, along with Category I and Category II
June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 8 non-friable ACM that has become friable, will be or has been subjected to sanding, grinding, cutting or abrading, or ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder during renovation or demolition activity. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, resilient floor covering mastics and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials other than Category I non-friable ACM that contain more than 1% asbestos. Category II non-friable ACM generally includes but is not limited to cementitious material such as: cement pipes, cement siding, cement panels, glazing, mortar and grouts.
In Michigan, the federal asbestos NESHAP regulation has been delegated to the Michigan Department of Environment, Great Lakes, and Energy (EGLE). Notifications for removal of certain types of ACM (>160 square feet and/or >260 linear feet in quantities) must be submitted to EGLE at least 10 business days prior to work commencement and prior to building demolitions. The EGLE should be contacted for discussion regarding specific instructions on completion of these forms. The EGLE contact information is as follows: NESHAP Asbestos Program, EGLE Air Quality Division, P.O. Box 30260, Lansing, Michigan 48909-7760; telephone (517) 284-6777.
In Michigan, asbestos regulations are also enforced by LEO/MIOSHA. The LEO/MIOSHA Asbestos Program is responsible for the enforcement of most Michigan asbestos regulations including the Asbestos Abatement Contractors Licensing Act (Act 135, P.A. 1986, as amended), the Asbestos Workers Accreditation Act (Act 440, P.A. 1988, as amended), the Michigan Occupational Safety and Health Act (Act 154, P.A. 1974, as amended), and for meeting the state of Michigan’s mandated responsibilities under the EPA AHERA regulation. The LEO/MIOSHA Asbestos Program has the following six major areas of responsibility: 1) approval of asbestos training courses, 2) accreditation of workers,
3) licensing of asbestos abatement contractors, 4) processing of asbestos abatement project notifications (requires project notification at least 10 days prior to any non-emergency abatement project exceeding 10 linear feet or 15 square feet or both of friable ACM), 5) compliance investigations, and 6) EPA AHERA management plan review. The LEO/MIOSHA Asbestos Program contact information is as follows: State of Michigan, MIOSHA-CSHD-Asbestos Program, P.O. Box 30671, Lansing, Michigan 48909; telephone: (517) 284-7680; email: asbestos@michigan.gov.
The United States Occupational Safety and Health Administration (USOSHA) asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The USOSHA standard requires that employee exposure to airborne asbestos must not exceed 0.1 fibers per cubic centimeter of air (0.1 f/cc) as an eight-hour time-weighted average (TWA) and not exceed 1.0 fibers per cubic centimeter of air (1.0 f/cc) over a 30-minute period known as an excursion limit (EL). The TWA and EL are known as USOSHA’s asbestos permissible exposure limits (PELs). The USOSHA standard classifies construction and maintenance activities that could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work.
6.2 Lead Regulatory Overview
The U.S. Consumer Safety Product Commission (CSPC) sets the maximum level of lead allowed in consumer paints at 0.009% by weight or 90 ppm. State regulations, federal EPA regulations, and the US Department of Housing and Urban Development (HUD) guidelines define “lead-based paint” (LBP) as a paint or other surface coating which contains a lead concentration equal to or exceeding 0.5% by weight or 5,000 ppm (5,000 mg/kg); and any surface like a surface tested that has a lead concentration equal to or exceeding that level.
June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 9
By contrast, the mission of OSHA with respect to lead-containing paint is to protect workers during construction activities that could result in hazardous exposures. OSHA states that construction work (including renovation, maintenance, and demolition) performed on structures coated with paint that contains lead at concentrations lower than HUD and CPSC standards can still result in exposures that exceed the regulatory limits. For this reason, OSHA has not defined a lower threshold lead concentration for lead-containing paint, but states that paint with any measurable level of lead may pose a significant potential for overexposure.
OSHA regulation 29 CFR 1926.62 (Lead Exposure in Construction) specifies that employers are responsible for ensuring that their employees are not exposed to airborne lead concentrations exceeding the OSHA permissible exposure limit (PEL) of fifty micrograms per cubic meter or air (50 µg/m3) averaged over an 8-hour period, and to take appropriate precautions when exposures reach an Action Level of 30 µg/m3 averaged over an 8-hour period. The standard was written to require initial exposure monitoring or the use of historical or objective data to ensure that employee exposures do not exceed the Action Level. If certain construction activities are being performed (e.g., torch cutting, manual demolition, sanding, grinding, etc.), employers must assume their employees are overexposed to lead and must provide personal protective equipment – including respiratory protection – until an exposure assessment proves otherwise.
The presence of lead in demolition debris from non-residential buildings has the potential to impose limitations on where and how the debris may be disposed. The Resource Conservation and Recovery Act (RCRA) requires each waste generator to determine if the wastes are hazardous. This can be determined either through generator knowledge or by testing. Toxicity Characteristic Leaching Procedure (TCLP) testing is the preferred method for determining if wastes are hazardous.
6.3 PCB Regulatory Overview
Current PCB regulations can be found in the Code of Federal Regulations (CFR) at 40 CFR 761, the Toxic Substances Control Act (TSCA). Under TSCA, PCB-containing caulk/glazing is considered PCB bulk product waste if the concentration of PCBs in the caulk/glazing is greater than or equal to (>) 50 ppm (40 CFR § 761.3). Caulk with PCB concentrations > 50 ppm must be disposed of as PCB bulk product waste according to 40 CFR § 761.62.
PCB-containing caulk/glazing is considered PCB bulk product waste if the concentration of PCBs in the caulk is greater than or equal to ( ) 50 ppm (see, 40 CFR § 761.3). PCB bulk product waste includes waste derived from manufactured products containing PCBs in a non-liquid state where the concentration at the time of designation for disposal is > 50 ppm PCBs (see, 40 CFR §§ 761.3 & 761.62). Caulk/glazing with PCB concentrations > 50 ppm is not authorized for use and must be disposed of as PCB bulk product waste according to 40 CFR § 761.62. Additionally, the definition of PCB bulk product waste includes building materials that have been coated or serviced with PCBs. That is, masonry, wood, metals, and other building materials that are purposely coated with PCB-containing caulk/glazing are regulated as PCB bulk product waste if the caulk coating the building materials contains PCBs at concentrations > 50 ppm. If your abatement plan states that you intend to dispose of the PCB caulk/glazing and any contaminated building materials together and the PCB caulk/glazing becomes separated from the adjacent contaminated building materials during remediation, you may still dispose of all the materials as a PCB bulk product waste. EPA realizes that the PCB caulk/glazing may need to be separated during removal from adjacent contaminated building materials due to the presence of other hazardous materials or may accidentally be separated during the removal process.
June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 10
If the PCB caulk/glazing has been removed from the adjacent building materials and disposed of separately, any contaminated adjacent building materials are considered PCB remediation waste. Also, if PCBs have contaminated the adjacent soil, the soil is considered PCB remediation waste. PCB remediation waste is subject to the cleanup and disposal requirements according to 40 CFR § 761.61.
FINDINGS AND RECOMMENDATIONS
Please note that this scope of services was specific and limited to the exterior areas of all buildings identified by the Client for inclusion in the rehabilitation project. In addition to all exterior areas of the project specific buildings, the interior of the Trude Cottage and the Village Barn located on North Manitou Island are also included in the rehabilitation project, therefore these two (2) interior areas were also included in our scope of services.
7.1 Asbestos Inspection Results
One (1) accessible material was confirmed to contain greater than 1% asbestos by PLM and point count (400 points) analysis.
The gray window glazing on the exterior windows of the Riggs Cottage were determined to contain 1.4% chrysotile by point count asbestos. Approximately 12 square feet of glazing located on 11 windows: a Category II non-friable asbestos material in fair condition.
Two (2) accessible materials were confirmed to contain less than 1% asbestos by PLM and point count (400 points) analysis.
The gray window glazing on the exterior window of the Hutzler, George J and Margaretha Pig Barn building was determined to contain 0.5% chrysotile by point count analysis.
Approximately 11 square feet of glazing on 10 windows, not regulated by NESHAP since contains 1% or less asbestos.
The gray window glaze on the exterior window of the USLSS Dwelling QTRS building was determined to contain 0.75% chrysotile by point count analysis. Approximately 48 square feet of glazing on 36 windows, not regulated by NESHAP since contains 1% or less asbestos.
If the identified ACM containing greater than 1% asbestos will be impacted by rehabilitation activities (i.e., renovation), it would need to be properly removed and disposed prior to renovation activities by a state-licensed asbestos abatement contractor in accordance with applicable federal, state, and local asbestos regulations. If the material will not be impacted by renovation activities, it is recommended to manage the material in place in good condition under an asbestos operations and maintenance (O&M) plan.
Materials containing 1% asbestos or less are not regulated by federal or state EPA NESHAP regulations; however, such materials are regulated under the OSHA Asbestos Construction Standard regulation (29 CFR 1926.1101). If these materials will be impacted by rehabilitation activities (i.e., renovation), it is recommended that they also be properly removed and disposed prior to renovation activities by a state-licensed asbestos abatement contractor in accordance with the OSHA asbestos regulation. If the materials will not be impacted by renovation activities, it is recommended to manage these materials in place in good condition under an asbestos operations and maintenance (O&M) plan.
June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 11
If additional suspect materials (other than those sampled during this project-specific inspection) are revealed/encountered during renovation activities, those material(s) must be assumed asbestos-containing and work should cease until the material(s) can be sampled by a state-certified asbestos inspector and analytical results refute the positive assumption.
7.2 Lead Paint Testing Results
Analytical results indicated that lead was detected above the analytical method’s reporting limit in 28 of the 36 samples collected and analyzed. See the table in Appendix B for a listing of painted building components tested and their analytical results. The results apply to all building components of the same testing combination (i.e., building, building component, substrate, and paint color).
Although a reasonable effort was made to inspect the substrate of the unique painting combinations, additional suspect but un-tested paint(s) could be present due to undetected changes in the paints or variations in lead concentrations in unique paint combinations.
Please note that un-tested paint(s), if any, should be assumed to contain lead above the analytical method’s reporting limit unless sampled and laboratory analysis can refute the positive assumption.
Additionally, please note the lead sampling scope of services was not a surface-by-surface investigation for compliance with EPA lead renovation repair and painting (RRP), or US Housing and Urban Development (HUD) regulations or guidelines. The aforementioned regulations pertain to residential housing and child-occupied (<6 years old) facilities.
7.3 PCB Bulk Product Testing Results
Three (3) of the 22 bulk product samples (i.e., glazing and caulking materials) collected during this project, were report by the laboratory to contain PCBs (utilizing EPA Method SW8082) at concentrations above the analytical method’s reporting limit. These correspond to the following materials:
Exterior gray window glazing at the Hutzler, George C & Mary Ann House on the South Manitou Island was determined to contain 0.52 mg/kg total PCB.
Exterior gray window caulk at the Hutzler, George C & Mary Ann House on the South Manitou Island was determined to contain 0.27 mg/kg total PCB.
Exterior gray window glazing at the USLSS Dwelling QTRS was determined to contain 0.35 mg/kg total PCB.
However, none of these three (3) bulk materials were detected at concentrations above 50 mg/kg and therefore would not require disposal under TSCA. See Appendix B for a sample and results summary table.
7.4 Appendices
Summary tables with the materials containing are included in Appendix A. Summary tables of asbestos, PCB, and paint samples collected with analytical results are included in Appendices B-1, B- 2, and B-3. The asbestos, lead, and PCB laboratory analytical reports and sampled chain-of-custody forms are included in AppendicesC-1, C-2, and C-3. Licenses and certifications are included in Appendix D. Photographs are included in Appendix E.
June 14, 2023 | Terracon Report No. N6237175
Facilities | Environmental | Geotechnical | Materials 12
LIMITATIONS/GENERAL COMMENTS
In addition to any limitations noted in the previous sections of this report, Terracon did not perform sampling which jeopardized the safety of the inspector(s) or required demolition or destructive activities such as knocking large holes in walls, the dismantling of equipment, or removing of protective coverings. Reasonable efforts to access suspect materials within known areas of restricted access (e.g., crawl spaces) were made; however, confined spaces or areas that may pose a health or safety risk to Terracon personnel were not sampled. Sampling did not include suspect materials which could not be safely reached with available ladders/man-lifts.
This scope of services was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our site visit. The information contained in this report is relevant to the date on which this inspection was performed and may not represent conditions later. This report has been prepared on behalf of and exclusively for use by VHB for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding reported quantities and any further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third parties supplying information that may have been used in the preparation of this report. No warranty, express or implied is made.
APPENDIX A
Project: Comprehensive Facility Rehabilitation on Manitou Island South and North Manitou Islands Glen Arbor Township, Michigan
MATERIALS IDENTIFIED TO CONTAIN GREATER THAN 1% ASBESTOS
(LISTED BY HOMOGENEOUS AREA)
HA Material Description Material Locations % and Type
Asbestos*
EPA NESHAP
Classification Condition Estimated
Quantities**
AG Gray exterior window glazing compound
Exterior windows of Riggs Cottage on North Manitou Island
1.4% chrysotile by Point Count (PC)
Category II Non-Friable Fair
11 windows ~12 square feet
The materials listed in this table have been sampled and determined by laboratory analysis to contain asbestos >1% (or assumed as noted above). When disturbed, various federal, state, and local asbestos regulations apply. Until removal is necessary, these materials should be maintained in good condition, monitored for damage over time, and repaired as necessary by appropriately trained personnel (recommend managing through implementation of an asbestos operations and maintenance [O&M] plan). Removal may be necessary before renovations and in most cases before demolition.
MATERIALS IDENTIFIED TO CONTAIN 1% ASBESTOS OR LESS
(LISTED BY HOMOGENEOUS AREA)
HA Material Description Material Locations % and Type Asbestos* Condition Estimated Quantities**
H Gray exterior window glazing compound
South Manitou Island Hutzler George J, and Margaretha
Pig Barn 0.5% Chrysotile by PC Fair
10 windows ~11 square feet
R Gray Exterior window glazing compound
South Manitou Island USLSS Dwelling QTRS 0.75% chrysotile by PC Fair
36 windows ~48 square feet Materials containing 1% asbestos or less are not regulated by EPA NESHAP; however, the OSHA personal exposure limits (0.1 f/cc of air as an eight-hour time-weighted average or 1.0 f/cc of air over 30 minutes) for asbestos apply when materials containing 1% asbestos or less are disturbed. A table listing the materials that contain 1% asbestos or less is provided above to enable the renovation contractor to make appropriate decisions concerning compliance issues with applicable federal and state OSHA regulations.
See Appendix B for a summary table of samples collected with analytical results. See Appendix C for detailed analytical results and chain of custody.
*% & Type Asbestos = This column contains both the analytical result of the sample with the highest concentration of asbestos detected in the samples that make up the HA and the types of asbestos identified.
**Estimated quantities are based on a cursory field evaluation and actual quantities may vary significantly, especially if asbestos-containing materials are present in hidden and/or inaccessible areas not evaluated as part of this inspection. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding reported quantities and any further investigation or remediation deemed necessary.
APPENDIX B-1
Project: Comprehensive Facility Rehabilitation on Manitou Island South and North Manitou Islands Glen Arbor Township, Michigan
LIMITED ASBESTOS INSPECTION SAMPLE & RESULTS SUMMARY
HA Sample Number Material Description HA Locations Sample
Location Lab Result
(% and Type Asbestos)
SOUTH MANITOU ISLAND PROJECT BUILDINGS
A
A-01
Asphalt Roof Shingles Beck Theodore
Farmhouse (lodge)
Front of house Black shingle – ND None
Detected (ND) Adhesive - ND
A-02 Middle house Black shingle – ND Adhesive - ND
A-03 Back of house Black shingle – ND Adhesive - ND
B
B-04
Asphalt Roof Shingles Beck Theodore Shed
Front of shed Black shingle – ND Adhesive - ND
B-05 Middle shed Black shingle – ND Adhesive - ND
B-06 Back of shed Black shingle – ND Adhesive - ND
C
C-07
Gray door caulk Beck Theodore
Farmhouse (lodge)
Front porch door ND
C-08 Back porch door ND
C-09 Front porch door ND
D
D-10
Gray window glazing compound
Hutzler, George C & Mary Ann
House
Window left of boarded door ND
D-11 Front of house first floor window
ND
D-12 Barn facing first floor window
ND
E
E-13
Gray window caulking compound
Hutzler, George C & Mary Ann
House
Front entrance door ND
E-14 Front entrance door ND
E-15 Rear entrance door ND
F
F-16
Gray window glazing compound
Hutzler, George I & Selma
QTRS, QMIS
Porch entrance window ND
F-17 Bump out window ND
F-18 Kitchen window ND
G
G-19
Gray window caulking compound
Hutzler, George J and
Margaretha Pig Barn
First floor window front entrance
ND
G-20 First floor window rear porch
ND
G-21 First floor single window ND
LIMITED ASBESTOS INSPECTION SAMPLE & RESULTS SUMMARY –
Continued
Facilities | Environmental | Geotechnical | Materials
HA Sample Number Material Description HA Locations Sample
Location Lab Result
(% and Type Asbestos)
H
H-22
Gray window glazing compound
Hutzler, George J and Margaretha
Pig Barn
First floor window front entrance
0.5% chrysotile by Point Count (PC)
H-23 Rear porch left window 0.25% chrysotile by PC
H-24 Rear porch middle window
ND
I
I-25 Gray door – glazing compound on window inserts
Hutzler, George J and
Margaretha Pig Barn
Front entrance door ND
I-26 Front entrance door ND
I-27 Rear entrance door ND
J
J-28
Gray door caulk
Hutzler, George J and
Margaretha Pig Barn
Front entrance door ND
J-29 Front entrance door ND
J-30 Rear entrance door ND
K
K-31
Asphalt exterior siding
Hutzler, George J and
Margaretha Pig Barn
Porch ND
K-32 Porch ND
K-33 Shed ND
L
L-34
Gray window glazing compound
Johnsom,Benth House QTRS, QMIS
Front porch window right ND
L-35 Front porch window left ND
L-36 Bump out window ND
M
M-37
Gray door caulk Johnsom,Benth House QTRS, QMIS
Left front door ND
M-38 Right front door ND
M-39 Left front door ND
N
N-40
Roof shingles Maintenance Shop
Roof ND
N-41 Roof ND
N-42 Roof ND
O
O-43
Gray window caulking compound
Maintenance Shop
Overhead door left ND
O-44 Overhead door middle ND
O-45 Left front window ND
P
P-46
Gray window caulking compound
Tobin, John & Lottie House
QTRS, QMIS
Front porch window ND
P-47 Back porch window ND
P-48 First floor window ND
Q
Q-49
Gray door caulk Tobin, John & Lottie House
QTRS, QMIS
Front door ND
Q-50 Front door ND
Q-51 Front door ND
R R-52 Gray window glazing compound
USLSS
Dwellings
QTRS, SMIS
Window south bump out
ND
Facilities | Environmental | Geotechnical | Materials
HA Sample Number Material Description HA Locations Sample
Location Lab Result
(% and Type Asbestos)
R-53
Window behind radio tower west facing
0.75% Chrysotile by PC
R-54 North porch window ND
NORTH MANITOU ISLAND PROJECT BUILDINGS
AA
AA-55
Gray window glazing compound
Hans Halseth House QRTS
QMIS
First floor porch north window
ND
AA-56
First floor porch south window
ND
AA-57
First floor southeast window
ND
AB
AB-58
Asphalt Roof Shingles Howard Foote Cottage
Roof ND
AB-59 Roof ND
AB-60 Roof ND
AC
AC-61
Gray window glazing compound
Howard Foote Cottage
Window left of porch door ND
AC-62 Window right of porch door ND
AC-63
Window next to boarded window first floor
ND
AD
AD-64
Gray window glazing compound
Newhall Cottage
Front porch window ND
AD-65
Rear of house northeast window
ND
AD-66
Rear of house northwest window
ND
AE
AE-67
Asphalt Roof Shingles Newhall Cottage
Roof ND
AE-68 Roof ND
AE-69 Roof ND
AF
AF-70
Asphalt Roof Shingles Riggs Cottage
Roof ND
AF-71 Roof ND
AF-72 Roof ND
AG
AF-73
Gray window glazing compound Riggs Cottage
Window north of front door 1.4% Chrysotile by PC
AF-74
Window south of front door 1.2% Chrysotile by PC
AF-75
Window south of back door
1.4% Chrysotile by PC
AH
AH-76
Asphalt Roof Shingles Riggs Generator Building
Roof ND
AH-77 Roof ND
AH-78 Roof ND
Facilities | Environmental | Geotechnical | Materials
HA Sample Number Material Description HA Locations Sample
Location Lab Result
(% and Type Asbestos)
AI
AI-79
Gray window glazing compound Trude Cottage
Interior windows ND
AI-80 Interior windows ND
AI-81 Interior windows ND
AJ
AJ-82
Asphalt Roof Shingles Trude Cottage
Roof Shingle – ND Tar - ND
AJ-83 Roof Shingle – ND Tar - ND
AJ-84 Roof Shingle – ND Tar - ND
AK
AK-85
Gray window glazing compound
USLSS Lifeboat Station QTRS
QMIS
Southwest window ND
AK-86 West facing window ND
AK-87 Southeast facing window ND
AL
AL-88
Gray window glazing compound
USLSS Dwelling
QTRS QMIS
East facing porch middle window
ND
AL-89
East facing porch north window
ND
AL-90 West facing south window ND
AM
AM-91
Gray window glazing compound Village Barn
Lower-level window – sliding barn door west side
ND
AM-92
Lower level – window southeast
ND
AM-93
Lower-level window northeast
APPENDIX B-2
Project: Comprehensive Facility Rehabilitation on Manitou Island South and North Manitou Islands
Glen Arbor Township, Michigan Project:
LIMITED PAINT SAMPLE & RESULTS SUMMARY
Sample Number Component Color Substrate Sample Location Condition
Lab Result (% lead and lead in mg/kg)
South Manitou Island Project Buildings
LP-01
Window and building trim
Green Wood Beck Theodore
Farmhouse (lodge) Window trim
Fair 0.038%
LP-02 Exterior siding White Wood
Beck Theodore Farmhouse (lodge)
Building exterior Good 1.5%
15,000
LP-03 Exterior siding White Wood Beck Theodore Shed
Building exterior Good 0.052%
LP-04
Window and building trim
Green Wood Beck Theodore Shed Building corner trim Good 0.099%
LP-05 Porch and steps Blue Wood
Benth Johnson/Kelderhouse
QTRS QMIS
Front porch
Good 3.2% 32,000
LP-06 Trim Green Wood
Benth Johnson/Kelderhouse
QTRS QMIS
First floor window
Good 0.0050%
LP-07 Siding White Wood
Benth Johnson/Kelderhouse
QTRS QMIS
Building exterior
Good 0.0060%
LP-08 Siding White Wood Hutzler, George C &
Mary Ann House Building exterior
Good 0.027%
LP-09 Siding White Wood Hutzler, George I & Selma QTRS, QMIS Building exterior
Good 0.044%
LP-10 Trim Green Wood Hutzler, George I & Selma QTRS, QMIS First floor window
Good 0.11% 1,100
LP-11 Siding White Wood Hutzler, George J & Margaretha Pig Barn
Exterior siding Good 0.48%
4,800
LP-12 Porch and steps Blue Wood
Johnson, Benth House
QTRS QMIS
Front porch
Good <0.00052%
LP-13 Trim Green Wood Johnson, Benth
House QTRS QMIS First floor window
Good 0.0071%
LP-14 Siding White Wood Johnson, Benth
House QTRS QMIS Building Exterior
Good 1.0% 10,000
Sample Number Component Color Substrate Sample Location Condition
Lab Result (% lead and lead in mg/kg)
South Manitou Island Project Buildings
LP-15 Trim Green Wood Keeler, Ory & Betty House QTRS, QMIS Frist floor window
Good <0.0071% <71
LP-16 Siding White Wood Keeler, Ory & Betty House QTRS, QMIS Building exterior
Good 0.35%
LP-17 Siding Beige Wood Maintenance Shop Good <0.0055% <55
LP-18 Trim Green Wood Tobin, John & Lottie House QTRS QMIS First floor window
Good <0.0046% <46
LP-19 Siding Yellow Wood Tobin, John & Lottie House QTRS QMIS Building exterior
Good 6.1% 61,000
LP-20 Wall White…