B08_Attach_15_Well_5A_Raw_Water_Test_Report.pdf
PDF 2 MB Posted
- Attached to
- GATE 225953 - Rehab Well No. 4 Sandy Hook NJ
- Solicitation number
- 140P2022R0044
About this file
This document contains a water test report and related federal contract opportunity. The water test report provides results of bacteriological and chemical testing of a raw water sample from Well 5A in Sandy Hook, New Jersey. Test results are provided for various regulated contaminants with concentrations reported along with their maximum contaminant level and detection limits. The related federal contract opportunity is solicitation number 140P2022R0044 for rehabilitation and replacement of Well 4 in Sandy Hook, New Jersey through the National Park Service Gateway National Recreation Area. The opportunity type is listed as a solicitation and no further details are provided on response dates, award dates, pricing or other procurement requirements.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
K Well 5A Raw Water Test
Report
Bacteriological and Chemical Testing
Garden State Laboratories, Inc.
Toll Free 800-273-8901
Fax 908-688-8966
Telephone 908-688-8900
Email: info@gslabs.com
Internet: www.gslabs.comMathew Klein, M.S., Founder (1916-1996)
Harvey Klein, M.S., Laboratory Director
Jordan B. Klein, B.A., Exec. Vice President
Sharon Ercoliani, B.A. Laboratory Manager
Main Lab 410 Hillside Avenue
NJDEP Lab Cert. #20044
Hillside, New Jersey 07205
Jersey Shore Lab 54 Main Street
NJDEP Lab Cert. #15037
Waretown, New Jersey 08758
Gateway NRA - Sandy HookFor:
Report Date:
26 Hudson Road
Laboratory Director:
Highlands, NJ 07732
03/14/2022
Robert GalanteAttention: GAT02Client Number:
03/02/2022Site:
Sample ID:
NFC - Potable
Field Blank
Collection Date/Time:
Lab Sample ID: 220302027-01
10:10
Analyte Method DF Sample Result MCL Rep. Limit MDL Lab Cert No.
Analysis
Date/Time Qualifiers
Matrix: Potable water Sample Type: Grab
PWTA PFCs EPA 537.1 1 cancelled IN598 03/09/22 20:38
03/02/2022Site:
Sample ID:
Raw-341 Randolph Rd.
Well 5A Spigot
Collection Date/Time:
Lab Sample ID: 220302027-02
10:10
Analyte Method DF Sample Result MCL Rep. Limit MDL Lab Cert No.
Analysis
Date/Time Qualifiers
Matrix: Potable water Sample Type: Grab
Gross Alpha
ECLS-R-GA
R8 1 3.06 pCi/L 03036 03/04/22 14:10
Iron, Total Recoverable EPA 200.7 1 8.20 mg/l 0.3 0.0500 0.0112 20044 03/10/22 10:21
Manganese, Total Recoverable
EPA 200.7 1 0.149 mg/l 0.05 0.00400 0.0008 20044 03/10/22 10:21
Arsenic, Total Recoverable EPA 200.8 1 < 0.00100 mg/l
0.005 0.00100 0.0005 20044 03/04/22 09:57
Lead, Total Recoverable EPA 200.8 1 < 0.00100 mg/l
0.015 0.00100 6E-05 20044 03/04/22 09:57
Mercury EPA 245.1 1 < 0.000200 mg/l
0.002 0.000200 7E-05 20044 03/10/22 13:32
1,2-Dibromoethane EPA 504.1 1 < 0.0100 µg/l 0.05 0.0100 0.0096 20044 03/04/22 20:03
1,2-Dibromo-3- Chloropropane
EPA 504.1 1 < 0.0100 µg/l 0.2 0.0100 0.0097 20044 03/04/22 20:03
1,2,3-Trichloropropane EPA 504.1 1 < 0.0100 µg/l 0.03 0.0100 0.0081 20044 03/04/22 20:03
Dichlorodifluoromethane EPA 524.2 1 < 0.500 µg/l 0.500 0.34 20044 03/03/22 11:39
Chloromethane EPA 524.2 1 < 0.500 µg/l 0.500 0.4 20044 03/03/22 11:39
Vinyl Chloride EPA 524.2 1 < 0.500 µg/l 2 0.500 0.4 20044 03/03/22 11:39
03/02/2022Site:
Sample ID:
Raw-341 Randolph Rd.
Well 5A Spigot
Collection Date/Time:
Lab Sample ID: 220302027-02
10:10
Analyte Method DF Sample Result MCL Rep. Limit MDL Lab Cert No.
Analysis
Date/Time Qualifiers
Matrix: Potable water Sample Type: Grab
Bromomethane EPA 524.2 1 < 0.500 µg/l 0.500 0.28 20044 03/03/22 11:39
Chloroethane EPA 524.2 1 < 0.500 µg/l 0.500 0.376 20044 03/03/22 11:39
Trichlorofluoromethane EPA 524.2 1 < 0.500 µg/l 0.500 0.132 20044 03/03/22 11:39
1,1-Dichloroethylene EPA 524.2 1 < 0.500 µg/l 2 0.500 0.199 20044 03/03/22 11:39
Methylene Chloride EPA 524.2 1 < 0.500 µg/l 3 0.500 0.406 20044 03/03/22 11:39
Methyl tert-Butyl Ether EPA 524.2 1 < 0.500 µg/l 70 0.500 0.172 20044 03/03/22 11:39 t-1,2-Dichloroethylene EPA 524.2 1 < 0.500 µg/l 100 0.500 0.18 20044 03/03/22 11:39
Isopropyl ether EPA 524.2 1 < 0.500 µg/l 0.500 0.117 20044 03/03/22 11:39
1,1-Dichloroethane EPA 524.2 1 < 0.500 µg/l 50 0.500 0.153 20044 03/03/22 11:39
2,2-Dichloropropane EPA 524.2 1 < 0.500 µg/l 0.500 0.17 20044 03/03/22 11:39 cis-1,2-Dichloroethylene EPA 524.2 1 < 0.500 µg/l 70 0.500 0.182 20044 03/03/22 11:39
Chloroform EPA 524.2 1 < 0.500 µg/l 80 0.500 0.238 20044 03/03/22 11:39
Bromochloromethane EPA 524.2 1 < 0.500 µg/l 0.500 0.21 20044 03/03/22 11:39
1,1,1-Trichloroethane EPA 524.2 1 < 0.500 µg/l 30 0.500 0.16 20044 03/03/22 11:39
1,1-Dichloropropylene EPA 524.2 1 < 0.500 µg/l 0.500 0.22 20044 03/03/22 11:39
Carbon tetrachloride EPA 524.2 1 < 0.500 µg/l 2 0.500 0.19 20044 03/03/22 11:39
Benzene EPA 524.2 1 < 0.500 µg/l 1 0.500 0.145 20044 03/03/22 11:39
1,2-Dichloroethane EPA 524.2 1 < 0.500 µg/l 2 0.500 0.172 20044 03/03/22 11:39
Trichloroethylene EPA 524.2 1 < 0.500 µg/l 1 0.500 0.181 20044 03/03/22 11:39
1,2-Dichloropropane EPA 524.2 1 < 0.500 µg/l 5 0.500 0.11 20044 03/03/22 11:39
Bromodichloromethane EPA 524.2 1 < 0.500 µg/l 80 0.500 0.175 20044 03/03/22 11:39
Dibromomethane EPA 524.2 1 < 0.500 µg/l 0.500 0.163 20044 03/03/22 11:39 cis-1,3-Dichloropropylene EPA 524.2 1 < 0.500 µg/l 0.500 0.132 20044 03/03/22 11:39
Toluene EPA 524.2 1 < 0.500 µg/l 1000 0.500 0.258 20044 03/03/22 11:39 trans-1,3-Dichlropropylene EPA 524.2 1 < 0.500 µg/l 0.500 0.187 20044 03/03/22 11:39
1,1,2-Trichloroethane EPA 524.2 1 < 0.500 µg/l 3 0.500 0.119 20044 03/03/22 11:39
1,3-Dichloropropane EPA 524.2 1 < 0.500 µg/l 0.500 0.161 20044 03/03/22 11:39
Tetrachloroethylene EPA 524.2 1 < 0.500 µg/l 1 0.500 0.15 20044 03/03/22 11:39
Dibromochloromethane EPA 524.2 1 < 0.500 µg/l 80 0.500 0.194 20044 03/03/22 11:39
Chlorobenzene EPA 524.2 1 < 0.500 µg/l 50 0.500 0.14 20044 03/03/22 11:39
Ethylbenzene EPA 524.2 1 < 0.500 µg/l 700 0.500 0.301 20044 03/03/22 11:39
1,1,1,2-Tetrachloroethane EPA 524.2 1 < 0.500 µg/l 0.500 0.16 20044 03/03/22 11:39 m,p-Xylenes EPA 524.2 1 < 0.500 µg/l 1000 0.500 0.32 20044 03/03/22 11:39
03/02/2022Site:
Sample ID:
Raw-341 Randolph Rd.
Well 5A Spigot
Collection Date/Time:
Lab Sample ID: 220302027-02
10:10
Analyte Method DF Sample Result MCL Rep. Limit MDL Lab Cert No.
Analysis
Date/Time Qualifiers
Matrix: Potable water Sample Type: Grab o-Xylene EPA 524.2 1 < 0.500 µg/l 1000 0.500 0.167 20044 03/03/22 11:39
Total Xylenes EPA 524.2 1 < 0.500 µg/l 1000 0.500 0.487 20044 03/03/22 11:39
Styrene EPA 524.2 1 < 0.500 µg/l 100 0.500 0.096 20044 03/03/22 11:39
Isopropyl Benzene EPA 524.2 1 < 0.500 µg/l 0.500 0.077 20044 03/03/22 11:39
Bromoform EPA 524.2 1 < 0.500 µg/l 80 0.500 0.231 20044 03/03/22 11:39
1,1,2,2-Tetrachloroethane EPA 524.2 1 < 0.500 µg/l 1 0.500 0.109 20044 03/03/22 11:39 n-Propyl benzene EPA 524.2 1 < 0.500 µg/l 0.500 0.11 20044 03/03/22 11:39
Bromobenzene EPA 524.2 1 < 0.500 µg/l 0.500 0.121 20044 03/03/22 11:39
1,3,5-Trimethylbenzene EPA 524.2 1 < 0.500 µg/l 0.500 0.171 20044 03/03/22 11:39
2-Chlorotoluene EPA 524.2 1 < 0.500 µg/l 0.500 0.113 20044 03/03/22 11:39
4-Chlorotoluene EPA 524.2 1 < 0.500 µg/l 0.500 0.194 20044 03/03/22 11:39 tert-Butylbenzene EPA 524.2 1 < 0.500 µg/l 0.500 0.179 20044 03/03/22 11:39
1,2,4-Trimethylbenzene EPA 524.2 1 < 0.500 µg/l 0.500 0.172 20044 03/03/22 11:39 sec-Butylbenzene EPA 524.2 1 < 0.500 µg/l 0.500 0.12 20044 03/03/22 11:39 p-Isopropyltoluene EPA 524.2 1 < 0.500 µg/l 0.500 0.092 20044 03/03/22 11:39
1,3-Dichlorobenzene EPA 524.2 1 < 0.500 µg/l 600 0.500 0.1 20044 03/03/22 11:39
1,4-Dichlorobenzene EPA 524.2 1 < 0.500 µg/l 75 0.500 0.137 20044 03/03/22 11:39 n-Butylbenzene EPA 524.2 1 < 0.500 µg/l 0.500 0.163 20044 03/03/22 11:39
1,2-Dichlorobenzene EPA 524.2 1 < 0.500 µg/l 600 0.500 0.165 20044 03/03/22 11:39
1,2,4-Trichlorobenzene EPA 524.2 1 < 0.500 µg/l 9 0.500 0.21 20044 03/03/22 11:39
Hexachlorobutadiene EPA 524.2 1 < 0.500 µg/l 0.500 0.149 20044 03/03/22 11:39
Naphthalene EPA 524.2 1 < 0.500 µg/l 300 0.500 0.5 20044 03/03/22 11:39
1,2,3-Trichlorobenzene EPA 524.2 1 < 0.500 µg/l 0.500 0.214 20044 03/03/22 11:39 tert-Butyl alcohol EPA 524.2 1 < 10.0 µg/l 10.0 2.392 20044 03/03/22 11:39
PWTA PFCs EPA 537.1 1 see attached IN598 03/09/22 20:38
Nitrate/Nitrite Lachat 10- 107-04-1-A
1 < 0.0500 mg/l 10 0.0500 0.02 20044 03/04/22 06:08 pH
SM 4500 H+
B
1 6.59 SU 6.5-8.5 15037 03/02/22 10:15
Free Chlorine, Residual SM 4500Cl-
G 1 < 0.0500 mg/l 4 0.0500 0.02 15037 03/02/22 10:12
E. coli
SM 9223 B
Colilert
Absent per 100ml
Absent 1 15037 03/02/22 14:25
Total Coliform
SM 9223 B
Colilert 18
Absent per
100ml Absent 1.00 15037 03/02/22 14:25
DF=Dilution factor, <=less than, MCL=Maximum Contaminant Level, Rep. Limit=Reporting Limit and MDL=Method Detection Limit.
The liability of Garden State Laboratories, Inc. for services rendered shall in no event exceed the amount of the invoice.
When sample is collected by Garden State Labs, it is taken in accordance with the most current Field Sampling Plan GSL.FS.
Main Lab certified by NJDEP #20044-TNI, NY Dept. of Health #11550 and PADEP #68-03680.
ANALYTICAL REPORT
Eurofins Eaton South Bend 110 S Hill Street South Bend, IN 46617 Tel: (574)233-4777
Laboratory Job ID: 810-16621-1 Client Project/Site: 220302027-02,01
For:
Garden State Labs
410 HILLSIDE AVE
Hillside, New Jersey 07205
Attn: Sharon Ercoliani
Authorized for release by:
3/14/2022 10:07:29 AM
Anne Petersen, Project Manager (574)233-4777 anne.petersen@eurofinset.com
This report has been electronically signed and authorized by the signatory. Electronic signature is intended to be the legally binding equivalent of a traditionally handwritten signature.
Results relate only to the items tested and the sample(s) as received by the laboratory.
https://secure.testamericainc.com/TotalAccess/login.aspx http://www.testamericainc.com/services-we-offer/ask-the-expert http://www.eurofinsus.com/Env mailto:anne.petersen@eurofinset.com
Table of Contents
Client: Garden State Labs Project/Site: 220302027-02,01
Laboratory Job ID: 810-16621-1
Eurofins Eaton South Bend
3/14/2022
Cover Page
Table of Contents
Definitions/Glossary
Detection Summary
Client Sample Results
Surrogate Summary
QC Sample Results
QC Association Summary
Lab Chronicle
Certification Summary
Method Summary
Sample Summary
Chain of Custody
Receipt Checklists
Definitions/Glossary Job ID: 810-16621-1Client: Garden State Labs
Project/Site: 220302027-02,01
Glossary
These commonly used abbreviations may or may not be present in this report.
¤ Listed under the "D" column to designate that the result is reported on a dry weight basis
Abbreviation
%R Percent Recovery
CFL Contains Free Liquid
CFU Colony Forming Unit
CNF Contains No Free Liquid
DER Duplicate Error Ratio (normalized absolute difference)
Dil Fac Dilution Factor
DL Detection Limit (DoD/DOE)
DL, RA, RE, IN Indicates a Dilution, Re-analysis, Re-extraction, or additional Initial metals/anion analysis of the sample
DLC Decision Level Concentration (Radiochemistry)
EDL Estimated Detection Limit (Dioxin)
LOD Limit of Detection (DoD/DOE)
LOQ Limit of Quantitation (DoD/DOE)
MCL EPA recommended "Maximum Contaminant Level"
MDA Minimum Detectable Activity (Radiochemistry)
MDC Minimum Detectable Concentration (Radiochemistry)
MDL Method Detection Limit
ML Minimum Level (Dioxin)
MPN Most Probable Number
MQL Method Quantitation Limit
NC Not Calculated
ND Not Detected at the reporting limit (or MDL or EDL if shown)
NEG Negative / Absent
POS Positive / Present
PQL Practical Quantitation Limit
PRES Presumptive
QC Quality Control
RER Relative Error Ratio (Radiochemistry)
RL Reporting Limit or Requested Limit (Radiochemistry)
RPD Relative Percent Difference, a measure of the relative difference between two points
TEF Toxicity Equivalent Factor (Dioxin)
TEQ Toxicity Equivalent Quotient (Dioxin)
TNTC Too Numerous To Count
Eurofins Eaton South Bend
Page 3 of 14 3/14/2022
Detection Summary
Project/Site: 220302027-02,01
Client Sample ID: 220302027-02 Lab Sample ID: 810-16621-1
No Detections.
Eurofins Eaton South Bend
This Detection Summary does not include radiochemical test results.
Page 4 of 14 3/14/2022
Client Sample Results
Project/Site: 220302027-02,01
Lab Sample ID: 810-16621-1Client Sample ID: 220302027-02 Matrix: Drinking WaterDate Collected: 03/02/22 10:10
Date Received: 03/03/22 13:30
Method: 537.1 - Perfluorinated Alkyl Acids (LC/MS)
RL MDL
Perfluorooctanesulfonic acid (PFOS) <1.9 1.9 ng/L 03/08/22 09:23 03/09/22 20:38 1
Analyte Dil FacAnalyzedPreparedUnit DResult Qualifier
1.9 ng/L 03/08/22 09:23 03/09/22 20:38 1Perfluorooctanoic acid (PFOA) <1.9
1.9 ng/L 03/08/22 09:23 03/09/22 20:38 1Perfluorononanoic acid (PFNA) <1.9
13C2 PFHxA 97 70 - 130 03/08/22 09:23 03/09/22 20:38 1
Surrogate Dil FacAnalyzedPreparedQualifier Limits%Recovery
13C2 PFDA 97 03/08/22 09:23 03/09/22 20:38 170 - 130
13C3 HFPO-DA 93 03/08/22 09:23 03/09/22 20:38 170 - 130
d5-NEtFOSAA 84 03/08/22 09:23 03/09/22 20:38 170 - 130
Eurofins Eaton South Bend
Page 5 of 14 3/14/2022
Surrogate Summary
Project/Site: 220302027-02,01
Method: 537.1 - Perfluorinated Alkyl Acids (LC/MS) Prep Type: Total/NAMatrix: Drinking Water
Lab Sample ID Client Sample ID (70-130) (70-130) (70-130) (70-130)
PFHxA PFDA HFPODA d5NEFOS
97 97 93 84810-16621-1
Percent Surrogate Recovery (Acceptance Limits)
220302027-02
97 94 95 93LLCS 810-14329/2-A Lab Control Sample
99 95 96 94MBL 810-14329/1-A Method Blank
Surrogate Legend
PFHxA = 13C2 PFHxA
PFDA = 13C2 PFDA
HFPODA = 13C3 HFPO-DA
d5NEFOS = d5-NEtFOSAA
Eurofins Eaton South Bend
Page 6 of 14 3/14/2022
QC Sample Results
Project/Site: 220302027-02,01
Method: 537.1 - Perfluorinated Alkyl Acids (LC/MS)
Client Sample ID: Method BlankLab Sample ID: MBL 810-14329/1-A
Matrix: Drinking Water Prep Type: Total/NA
Analysis Batch: 14399 Prep Batch: 14329
RL MDL
Perfluorooctanesulfonic acid (PFOS) <0.40 2.0 ng/L 03/08/22 09:23 03/09/22 16:13 1
MBL MBL
Analyte Dil FacAnalyzedPreparedDUnitResult Qualifier
<0.40 2.0 ng/L 03/08/22 09:23 03/09/22 16:13 1Perfluorooctanoic acid (PFOA)
<0.50 2.0 ng/L 03/08/22 09:23 03/09/22 16:13 1Perfluorononanoic acid (PFNA)
13C2 PFHxA 99 70 - 130 03/09/22 16:13 1
MBL MBL
Surrogate
03/08/22 09:23
Dil FacPrepared AnalyzedQualifier Limits%Recovery
95 03/08/22 09:23 03/09/22 16:13 113C2 PFDA 70 - 130
96 03/08/22 09:23 03/09/22 16:13 113C3 HFPO-DA 70 - 130
94 03/08/22 09:23 03/09/22 16:13 1d5-NEtFOSAA 70 - 130
Client Sample ID: Lab Control SampleLab Sample ID: LLCS 810-14329/2-A
Matrix: Drinking Water Prep Type: Total/NA
Analysis Batch: 14399 Prep Batch: 14329
Perfluorooctanesulfonic acid
(PFOS)
1.95 2.00 ng/L 103 50 - 150
Analyte
LLCS LLCS
DUnitResult Qualifier %Rec
Spike
Added
%Rec.
Limits
Perfluorooctanoic acid (PFOA) 1.95 2.14 ng/L 109 50 - 150
Perfluorononanoic acid (PFNA) 1.95 2.02 ng/L 104 50 - 150
13C2 PFHxA 70 - 130
Surrogate
LLCS LLCS
Qualifier Limits%Recovery
9413C2 PFDA 70 - 130
9513C3 HFPO-DA 70 - 130
93d5-NEtFOSAA 70 - 130
Eurofins Eaton South Bend
Page 7 of 14 3/14/2022
QC Association Summary
Project/Site: 220302027-02,01
LCMS
Prep Batch: 14329
Lab Sample ID Client Sample ID Prep Type Matrix Method Prep Batch
Drinking Water 537.1 DW810-16621-1 220302027-02 Total/NA
Drinking Water 537.1 DWMBL 810-14329/1-A Method Blank Total/NA
Drinking Water 537.1 DWLLCS 810-14329/2-A Lab Control Sample Total/NA
Analysis Batch: 14399
Lab Sample ID Client Sample ID Prep Type Matrix Method Prep Batch
Drinking Water 537.1 14329810-16621-1 220302027-02 Total/NA
Drinking Water 537.1 14329MBL 810-14329/1-A Method Blank Total/NA
Drinking Water 537.1 14329LLCS 810-14329/2-A Lab Control Sample Total/NA
Eurofins Eaton South Bend
Page 8 of 14 3/14/2022
Lab Chronicle Client: Garden State Labs Job ID: 810-16621-1
Project/Site: 220302027-02,01
Client Sample ID: 220302027-02 Lab Sample ID: 810-16621-1 Matrix: Drinking WaterDate Collected: 03/02/22 10:10
Date Received: 03/03/22 13:30
Prep 537.1 DW 03/08/22 09:23 SS14329 EA SB
Type
Batch Batch
MethodPrep Type LabAnalystRun
Prepared or Analyzed
Batch
Number
Dilution
Factor
Total/NA
Analysis 537.1 1 14399 03/09/22 20:38 MH EA SBTotal/NA
Laboratory References:
EA SB = Eurofins Eaton South Bend, 110 S Hill Street, South Bend, IN 46617, TEL (574)233-4777
Eurofins Eaton South Bend
Page 9 of 14 3/14/2022
Accreditation/Certification Summary
Project/Site: 220302027-02,01
Laboratory: Eurofins Eaton South Bend The accreditations/certifications listed below are applicable to this report.
Authority Program Identification Number Expiration Date
New Jersey NELAP IN598 06-30-22
Eurofins Eaton South Bend
Page 10 of 14 3/14/2022
Method Summary
Project/Site: 220302027-02,01
Method Method Description LaboratoryProtocol
EPA537.1 Perfluorinated Alkyl Acids (LC/MS) EA SB
EPA537.1 DW Extraction of Perfluorinated Alkyl Acids EA SB
Protocol References:
EPA = US Environmental Protection Agency
Laboratory References:
EA SB = Eurofins Eaton South Bend, 110 S Hill Street, South Bend, IN 46617, TEL (574)233-4777
Eurofins Eaton South Bend
Page 11 of 14 3/14/2022
Sample Summary
Project/Site: 220302027-02,01
Lab Sample ID Client Sample ID Matrix Collected Received
810-16621-1 220302027-02 Drinking Water 03/02/22 10:10 03/03/22 13:30
Eurofins Eaton South Bend Page 12 of 14 3/14/2022
Page 13 of 14 3/14/2022
Login Sample Receipt Checklist
Client: Garden State Labs Job Number: 810-16621-1
Login Number: 16621
Question Answer Comment
Creator: Pehling-Wright, Penny
List Source: Eurofins Eaton South Bend
List Number: 1
TrueThe cooler's custody seal, if present, is intact.
TrueSample custody seals, if present, are intact.
TrueSamples were received on ice.
TrueCooler Temperature is acceptable.
TrueCooler Temperature is recorded.
TrueCOC is present.
TrueCOC is filled out in ink and legible.
TrueCOC is filled out with all pertinent information.
TrueThere are no discrepancies between the containers received and the COC.
TrueSamples are received within Holding Time (excluding tests with immediate
HTs)
TrueSample containers have legible labels.
TrueContainers are not broken or leaking.
TrueSample collection date/times are provided.
TrueThere is sufficient vol. for all requested analyses, incl. any requested
MS/MSDs
TrueContainers requiring zero headspace have no headspace or bubble is
<6mm (1/4").
TrueSamples do not require splitting or compositing.
TrueContainer provided by EEA
Eurofins Eaton South Bend Page 14 of 14 3/14/2022
Reported Date: 3/6/2022 Current Rev R0
Final Comment
Attention:
Phone: 908-688-8900 Email:
The test results contained within this report meet the requirements of NELAP and/or the specific certification program that is applicable, unless otherwise noted.
NELAC Certification #: 03036
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL.
EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.
Danvas Omare Garden State Laboratories Inc 410 Hillside Avenue Hillside, NJ 07205 dparker@gslabs.com
The following analytical report covers the analysis performed on samples submitted to EMSL Analytical, Inc. on 03/03/2022 at 11:30.
The results are tabulated on the attached data pages for the following client designated project:
220302027-02
The reference number for these samples is EMSL Order #782201316. Please use this reference when calling about these samples.
If you have any questions, please do not hesitate to contact me at (800)220-3675.
782201316
GDST25
EMSL ANALYTICAL, INC.
200 Route 130 North cinnaminsonradonlab@emsl.com | http://www.EMSL.com Telephone: (800)220-3675 FAX: (856)786-0327
EMSL ORDER ID:
EMSL CUSTOMER ID:
Cinnaminson, NJ 08077
Dominic Gehret, Radiochemistry Laboratory Manager or other approved signatory
RDN_Generic_NonLimsReport_V4.4_Feb 20211 Page 1 of 3 mailto:dparker@gslabs.com mailto:cinnaminsonradonlab@emsl.com http://www.EMSL.com
EMSL Sample ID. Client Sample ID. Start Sampling Date Start Sampling Time
782201316-0001 220302027-02 3/2/2022 10:10 AM
Laboratory Report- Sample Summary
Danvas Omare Garden State Laboratories Inc 410 Hillside Avenue Hillside, NJ 07205
220302027-02
782201316
GDST25
908-688-8900 dparker@gslabs.com
03/02/2022 10:10 03/03/2022 11:30
EMSL ANALYTICAL, INC.
200 Route 130 North cinnaminsonradonlab@emsl.com | http://www.EMSL.com Telephone: (800)220-3675 FAX: (856)786-0327
Attention:
Project Name:
Phone:
Email:
Collected:
Received:
EMSL ORDER ID:
EMSL CUSTOMER ID:
Customer PO:
EMSL Project ID:
Cinnaminson, NJ 08077
Analyzed:
Reported: 3/6/2022
See Results
Initial Report
Dominic Gehret, Radiochemistry Laboratory Manager
If "Preliminary Report" is displayed in the signature box; this indicates that there are samples that have not yet been analyzed, that are in a preliminary state, or that analysis is in progress but not completed at the time of report issue.
Report Date Report Revision Revision Comments 3/6/2022 R0 or other approved signatory
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody.
Samples are within quality control criteria and met method specifications unless otherwise noted.
RDN_Generic_NonLimsReport_V4.4_Feb 20211 Page 2 of 3 mailto:dparker@gslabs.com mailto:cinnaminsonradonlab@emsl.com http://www.EMSL.com
Test Parameter Units Result Uncertainty
SDWA
DL
Start Count Date/ Time
End Count Date/ Time Analyst Status Count Method Comment
NJ Rapid Gross Alpha pCi/L 3.06 1.90 1.90 03/04/2022
14:10 03/04/2022
05:10
KS /
JAW First Count
ECLS-R-
GA Rev.8
Sample Specific Comments
(1)= Analyte was analyzed for, but not detected above the SDWA DL
(2)= Analyte was analyzed for, but not detected above the MDA
Additional Comments
Sample Identification: 220302027-02 Lab Sample #: 782201316-0001 Date/Time Collected: 3/2/2022 10:10 AM
* The uncertainty reported is an expanded uncertainty of 1.96-sigma.
* For NJ Rapid Gross Alpha, the uncertainty reported is an expanded uncertainty of 1.65-sigma.
* The SDWA detection limit is defined in 40 CFR 141.25(c) as equal to the analyte concentration which can be counted with a precision of plus or minus 100% at the 95% confidencelevel (1.96σ where σ is the standard deviation of the net counting rate of the sample).
* For drinking water, the regulatory limit for gross alpha is 15 pCi/L with an SDWA DL of 3 pCi/L..
* For drinking water, the regulatory limit for combined radium-226 and radium-228 is 5 pCi/L with each having an SDWA DL of 1 pCi/L.
* If gross alpha result from the 36 – 48 hour count exceeds 5pCi/L, the plancheted sample is recounted between 20 – 28 hours after the midpoint of the initial count.
Analytical Report
Danvas Omare Garden State Laboratories Inc 410 Hillside Avenue Hillside, NJ 07205
220302027-02
782201316
GDST25
908-688-8900 dparker@gslabs.com
03/02/2022 10:10 03/03/2022 11:30
EMSL ANALYTICAL, INC.
200 Route 130 North cinnaminsonradonlab@emsl.com | http://www.EMSL.com Telephone: (800)220-3675 FAX: (856)786-0327
Attention:
Project Name:
Phone:
Email:
Collected:
Received:
EMSL ORDER ID:
EMSL CUSTOMER ID:
Customer PO:
EMSL Project ID:
Cinnaminson, NJ 08077
Analyzed:
Reported: 3/6/2022
See Results
Initial Report
Dominic Gehret, Radiochemistry Laboratory Manager
If "Preliminary Report" is displayed in the signature box; this indicates that there are samples that have not yet been analyzed, that are in a preliminary state, or that analysis is in progress but not completed at the time of report issue.
Report Date Report Revision Revision Comments 3/6/2022 R0 or other approved signatory
RDN_Generic_NonLimsReport_V4.4_Feb 20211 Page 3 of 3 mailto:dparker@gslabs.com mailto:cinnaminsonradonlab@emsl.com http://www.EMSL.com
| GATE 225953 - DB RFP PART 5 - ATTACHMENTS |
| Attachment K - Well 5A Raw Water Test Report |
File details come from the government source that posted it. Updated .