B08_Attach_11_Hazardous_Materials_Survey.pdf
PDF 3 MB Posted
- Attached to
- GATE 225953 - Rehab Well No. 4 Sandy Hook NJ
- Solicitation number
- 140P2022R0044
About this file
This document summarizes the results of a hazardous materials survey conducted at Sandy Hook Well #4 located in Highlands, New Jersey. The survey identified lead-containing paints at the site that will require abatement in accordance with applicable regulations. Asbestos-containing materials were not identified. However, well pumps and motors at the site potentially contain hazardous constituents such as PCBs, mercury, and lubricating oils that would require proper handling as hazardous waste in accordance with federal, state, and local regulations.
The related federal contract opportunity is to rehabilitate and replace Well #4 at Sandy Hook in the Gateway National Recreation Area in New Jersey. The solicitation number is 140P2022R0044 and is being conducted by the National Park Service to complete this work in accordance with all applicable regulations and standards.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G
Hazardous Materials Survey
– Well #4
Sandy Hook Well #4 341 Randolph Drive
Highlands, New Jersey September 9, 2021
Terracon Project No. J6215069
Prepared for:
VHB Inc.
Williamsburg, Virginia
Prepared by:
Terracon Consultants, Inc.
South Plainfield, New Jersey
Terracon Consultants, Inc. 4081 Hadley Road, Unit B, South Pla inf ie ld, New Jersey 07080 P (908) 546-6161 F (908) 546-6160 terracon.com
September 9, 2021
VHB Inc.
351 McLaws Cir., Suite 3 Williamsburg, Virginia 23185
Attn: Mr. Vikrant Desai P: (757) 279-2832 E: vdesai@vhb.com
Re: Hazardous Materials Survey Sandy Hook Well #4 341 Randolph Drive Highlands, New Jersey Terracon Project No. J6215069
Dear Mr. Desai:
Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report for the above-referenced site to VHB Inc. The purpose of this report is to present the results of a hazardous material survey which was performed at the site on August 9, 2021. This survey was conducted in general accordance with Task Order #140P2021F0100, dated June 28, 2021. We understand that this survey was requested due to planned replacement of Well #4 in the Sandy Hook National Recreation Area.
As a result of the asbestos survey and limited lead paint testing, paints containing lead were identified at the site. No asbestos-containing materials were identified. Well pumps/motors were observed at the site which may contain hazardous constituents such lubricating oils that could potentially contain PCBs and mercury seals. Please refer to the report for further details.
Terracon appreciates the opportunity to provide this service to VHB Inc. If you have any questions regarding this report, please contact the undersigned at (908) 546-6161.
Sincerely, Terracon Consultants, Inc.
Megan E Cruz FOR: Joseph A. Tussey Senior Staff Scientist Authorized Project Reviewer mailto:vdesai@vhb.com
TABLE OF CONTENTS
1.0 INTRODUCTION
1.1 Project Objective
1.2 Reliance
2.0 BUILDING DESCRIPTION
3.0 FIELD ACTIVITIES
3.1 Asbestos Sampling
3.1.1 Asbestos Visual Assessment
3.1.2 Asbestos Physical Assessment
3.1.3 Asbestos Sample Collection
3.2 Limited Lead Paint Sampling
3.3 Hazardous Materials Observations
4.0 REGULATORY OVERVIEW
4.1 Asbestos
4.2 Lead Paint
5.0 FINDINGS AND RECOMMENDATIONS
5.1 Asbestos
5.2 Lead Paint
5.3 Hazardous Material Items Observation Summary
6.0 LIMITATIONS/GENERAL COMMENTS
APPENDIX A SUMMARY OF ASBESTOS & LEAD PAINT SAMPLES AND ANALYTICAL RESULTS
APPENDIX B ASBESTOS & LEAD PAINT ANALYTICAL LABORATORY DATA
APPENDIX C LICENSES AND CERTIFICATIONS
APPENDIX D PHOTOGRAPHS
Reliable ■ Responsive ■ Resourceful 1
HAZARDOUS MATERIALS SURVEY
Sandy Hook Well #4
341 Randolph Drive, Highlands, New Jersey Terracon Project No. J6215069
September 9, 2021
1.0 INTRODUCTION
Terracon Consultants, Inc. (Terracon) conducted a hazardous materials survey for Well #4 located in the Sandy Hook National Recreation Area near 341 Randolph Drive in Highlands, New Jersey. The hazardous materials survey included an asbestos survey, lead paint testing, and visual observations for universal wastes, polychlorinated biphenyls (PCBs), refrigerants, and chemical storage. The hazmat survey was conducted at the site on August 9, 2021 by a United States Environmental Protection Agency (USEPA)-accredited asbestos inspector and New Jersey-licensed lead inspector in general accordance with Task Order #140P2021F0100, dated June 28, 2021. Terracon collected samples from various accessible, dominant-type interior paints for laboratory analysis to determine lead-content. Accessible interior and exterior building components were surveyed, and homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented for the purpose of subsequent sample collection and laboratory analysis to determine asbestos-content.
Although reasonable effort was made to survey accessible suspect materials, additional suspect materials could be located in walls, in voids, or in other concealed areas.
1.1 Project Objective
We understand our scope of services was requested due to planned replacement of Well #4.
Asbestos surveys are required prior to renovation and demolition activities to satisfy requirements of the USEPA) 40 Code of Federal Regulations (CFR) Part 61, Subpart M, the National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation. The purpose of the lead testing was to provide general information so that contractors who disturb paints with lead can take the appropriate actions to comply with US Occupational Safety and Health Administration (OSHA) regulation 29 CFR 1926.62 – Lead in Construction. The purpose of the visual observation task for other hazardous material items was to create an inventory of such items if they exist, as these would become hazardous waste and would need to be diverted from sanitary landfills by properly collecting/handling and treating/recycling at appropriately accredited/licensed facilities per federal, state, and local regulations.
Sandy Hook Well #4 ■ Highlands, New Jersey September 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable 2
1.2 Reliance
This report is for the exclusive use of VHB Inc. (Client) for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and the Client. Reliance on this report by the Client and all authorized parties will be subject to the terms, conditions, and limitations stated in the task order, this report, and the Master Services Agreement, dated April 22, 2021. The limitations of liability defined in the Master Services Agreement is the aggregate limit of Terracon’s liability to the Client.
2.0 BUILDING DESCRIPTION
The site is a small masonry wellhouse containing one well pump. The well house and pump have been out of service for many years as of the time of this survey.
3.0 FIELD ACTIVITIES
3.1 Asbestos Sampling
The asbestos survey was conducted by Ms. Megan Cruz, a USEPA-accredited asbestos inspector on August 9, 2021. A copy of Ms. Cruz’s asbestos inspector accreditation is attached as Appendix C. The survey was conducted in general accordance with the sample collection protocols established in US EPA 40 CFR Part 763, Subpart E, Section 763.86, known as the Asbestos Hazard Emergency Response Act (AHERA). A summary of survey activities is provided below.
3.1.1 Asbestos Visual Assessment
Survey activities were initiated with visual observation of the accessible interior and exterior areas of the wellhouse structure to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application.
3.1.2 Asbestos Physical Assessment
A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
3.1.3 Asbestos Sample Collection
Based on the results of the visual observation, bulk samples of suspect ACM were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were
September 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable 3 collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.
Terracon collected a total of 12 bulk samples from four (4) homogeneous areas of suspect ACM.
A summary of suspect ACM samples collected during the survey is included as Appendix A.
Bulk samples were submitted under chain of custody to EMSL of Piscataway, New Jersey for analysis. Friable samples were analyzed by Polarized Light Microscopy (PLM) via EPA method 600/R-93/116 and non-friable organically bound (NOB) samples were analyzed by PLM NOB via EPA method 600/R-92/116 with gravimetric reduction. Additionally, NOB samples with inconclusive results (<1% asbestos) via PLM NOB were additionally analyzed by transmission electron microscopy (TEM) via EPA method 600/R-93/116b. EMSL’s Piscataway, New Jersey laboratory is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), accreditation number 101048-2. The laboratory was instructed to analyze samples from each homogeneous area until the first sample containing asbestos was identified. The laboratory analytical data report is attached in Appendix B.
3.2 Limited Lead Paint Sampling
Terracon visually assessed the interior and exterior of the wellhouse structure on August 9, 2021 and collected paint chip samples from dominant-type, representative painted components for laboratory analysis. The paint chip samples were submitted to EMSL of Cinnaminson, New Jersey, a laboratory participating in the Environmental Lead Laboratory Accreditation Program (ELLAP), accreditation number 100194, for lead-content analysis. A total of seven (7) paint chip samples were collected from accessible dominant-type painted surface coatings and analyzed for lead-content via EPA Method SW846 3050B/7000B using flame atomic absorption spectrophotometry (Flame AAS).
3.3 Hazardous Materials Observations
Terracon visually observed the interior of the wellhouse structure and the area immediately surrounding it for the following items:
n Universal wastes (mercury-containing equipment, batteries, and waste lamps), n Polychlorinated biphenyls (PCBs), n Refrigerants, and n Chemical Storage.
September 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable 4
This task did include sampling and analysis; this task was only a visual observation for such items, if accessible and present.
4.0 REGULATORY OVERVIEW
4.1 Asbestos
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACM is considered regulated asbestos containing material (RACM).
The asbestos NESHAP regulation classifies material subject to demolition or renovation as either RACM, Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM (pre-disturbance), along with Category I non-friable ACM that becomes friable (during disturbance), and Category I non-friable ACM subject to sanding, grinding, cutting, or abrading, or Category II non-friable ACM with a high probability of becoming crumbled, pulverized, or reduced to powder by forces expected to act on the material during disturbance. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials (other than Category I non-friable ACM) that contain more than 1% asbestos. Category II non-friable ACM generally includes (but is not limited to) cementitious material such as: cement pipes, cement siding, cement panels, glazing, mortar, and grouts.
Asbestos activities are regulated by the New Jersey Department of Labor (NJDL) and the New Jersey Department of Health and Senior Services (NJDHSS) under the NJDL Asbestos Control and Licensing Act (N.J.S.A. 34:5A-32). The regulations require that any asbestos-related activity conducted in a public building be performed by personnel licensed by the NJDL. The owner or operator must provide the NJ Department of Environmental Protection, NJDL, NJDHSS, and the NJ Department of Community Affairs with written notification of planned removal activities at least 10 working days prior to the commencement of asbestos abatement activities that will disturb RACM in amounts greater than or equal to 3 square feet 3 linear feet.
The Public Employee Occupational Safety and Health Program (PEOSH), by authority established under the PEOSH Act of 1995 (N.J.S.A 34:6A-25 et seq., enacted in 1984 and amended on July 25, 1995) is responsible for promoting the health and safety for government employees in the State of New Jersey. The federal Occupational Safety and Health Administration (OSHA) maintains jurisdiction over all workplaces. The OSHA standards at 29 CFR 1910.1001 and 29 CFR 1926.1101, regulates employee exposure to asbestos. The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained at or below 0.1 fibers per cubic
September 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable 5 centimeter of air (0.1 f/cc) as an eight-hour time weighted average (TWA) and not exceed 1.0 fibers per cubic centimeter of air (1.0 f/cc) over a 30-minute time period known as an excursion limit (EL). The TWA and EL are known as OSHA’s permissible exposure limits (PELs). The OSHA standard classifies construction and maintenance activities which could disturb ACM, and specifies work practices and precautions which employers must follow when engaging in each class of regulated work.
4.2 Lead Paint
Lead paint is regulated by the EPA, New Jersey Department of Health (NJDH), and OSHA. The EPA and NJDH regulate lead use, removal, disposal, and OSHA regulates lead exposure to workers. The EPA defines “lead-based paint” (LBP) as paint, varnish, stain, or other applied coating that contains lead equal to or greater than 1.0 mg/cm2, 5,000 mg/Kg, or 0.5% by dry weight as determined by laboratory analysis. EPA and NJDH regulations only apply to residential housing and child-occupied facilities. For the purpose of the OSHA lead standard, “lead” includes metallic lead, all inorganic lead compounds, and organic lead soaps. A synopsis of the OSHA regulations (29 CFR 1926.62) and the applicability are as follows:
The OSHA Lead Standard for Construction (29 CFR 1926.62) applies to all construction work where an employee may be occupationally exposed to lead. All work related to construction, alteration, or repair (including painting and decorating) is included. The lead-in-construction standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon on the method of removal and other workplace conditions. Under this standard, construction includes, but is not limited to, the following:
n Demolition or salvage of structures where lead or materials containing lead are present n Removal or encapsulation of materials containing lead n New construction, alteration, repair, or renovation of structures, substrates, or portions containing lead, or materials containing lead n Installation of products containing lead n Lead contamination/emergency clean-up n Transportation, disposal, storage, or containment of lead or materials containing lead on the site or location at which construction activities are performed n Maintenance operations associated with construction activities described above
September 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable 6
5.0 FINDINGS AND RECOMMENDATIONS
5.1 Asbestos
Based on the analytical results for the collected samples, ACM was not identified.
An asbestos sample and results summary is included in Appendix A, the laboratory analytical report is included in Appendix B, and a photo log is included in Appendix D
5.2 Lead Paint
Laboratory analysis identified the presence of lead in all nine (9) paint samples collected. The table below summarizes the paints which were identified to contain lead above the analytical method’s reporting limit.
Lead-Containing Paint (LCP)
Paint Color Component Lead Content (% Lead by Weight)
Orange Wooden Door 0.36%
White Wooden Door 0.39%
Green Wooden Door Frame 6.2%
Red Brown Metal Hatch 0.049%
Green Masonry Wall 7.1%
White Masonry Wall 0.48%
Gray Metal Duct 0.24%
Gray Metal Pipe 0.38%
White Metal Pipe 0.27%
Contractors should be made aware of LCP so that they can take the appropriate actions to comply with OSHA regulation 29 CFR 1926.62 – Lead in Construction, as well as any Client or Owner project specifications involving the disturbance of LCP.
A paint sample and results summary is included in Appendix A and the laboratory analytical report is included in Appendix B.
September 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable 7
5.3 Hazardous Material Items Observation Summary
Universal Wastes
Universal wastes (UW) are specific hazardous waste streams that a generator can choose to manage in an alternative manner in place of the more complex hazardous waste requirements.
These wastes are generated by numerous businesses, typically in small quantities. The Universal Waste Rules (UWR) are intended to promote recycling as well as proper disposal by easing certain regulatory requirements. New Jersey’s UWRs are located in New Jersey Administrative Code (NJAC) 7:26A and the federal UWRs are located in 40 code of federal regulations (CFR)
261. A waste must be a hazardous waste before it can be a universal waste. If a hazardous waste stream is not managed as a universal waste, then the waste must be managed as a hazardous waste under the applicable hazardous waste regulations.
It should be noted that any materials resulting from the release or clean-up of spills or breakage of any universal waste is not itself universal waste. It must be determined whether or not such materials are a hazardous waste as identified in 40 CFR 261, and the material must then be managed and disposed in accordance with applicable hazardous or solid waste regulations.
Lamps This category includes hazardous waste lamps that meet the definition in NJAC 7:26A. The universal waste lamp category is slightly broader in that it includes lamps that are hazardous for any characteristic, not just for mercury. However, fluorescent light bulbs remain the most common item in this category of universal waste. This category does not include associated light fixture components such as ballasts. Hazardous waste lamps become subject to this rule if they are hazardous waste under 40 CFR 261, and when they are permanently removed from a fixture or determined to be discarded. A note about crushing: crushing of hazardous waste bulbs is considered treatment, which is explicitly prohibited under the Universal Waste Rule (40 CFR 273.11(b) and 273.31(b)). The only circumstance where hazardous waste lamps may be allowed to be crushed is when they are managed as fully regulated hazardous waste (rather than as universal waste) which is treated (i.e., crushed) in tanks or containers by the generator of the waste under the implied generator treatment allowance in 40 CFR 262.34, and in conformance with all applicable hazardous waste management standards.
Lamps were not readily identified at the site.
Potential Mercury-Containing Equipment
This category, added to the Federal Rule at 40 CFR 273 on August 5, 2005. It includes devices, items, or articles which contain elemental mercury that is integral to their functions and which would otherwise be regulated as a hazardous waste when discarded by virtue of exhibiting the toxicity characteristic (TC) for mercury (hazardous waste code D009). Some examples of such items include mercury-containing thermostats (formerly a separate universal waste category in
September 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable 8 the original rule), thermometers, barometers, mercury switches, and certain types of meters, regulators, and gauges, in which elemental mercury is contained in ampules or otherwise enclosed and can be managed intact. This category does not include cathode ray tubes or other types of electronic equipment in which elemental mercury is not integral to function, nor does it include mercury waste that is generated as a by-product through the process of manufacturing or treatment.
While no readily visible indication of equipment with potential mercury was observed, please be aware that mercury seal in water pumps may be present. Water pumps are comprised of a motor, moving parts that pump the water, and a water intake area. Dynamic seals create a barrier between the electrical parts of the motor and the water intake area. Seals prevent water from entering the motor casing and damaging the electrical components of the motor. The seal must stop water from entering the motor enclosure but must allow for movement of parts that extend from the motor into the intake area. A seal typically includes a main barrier, made of metal or other material. However, where moving parts extend from the motor to the intake area or at the edges of the main barrier, gaps will exist. Because of its high surface tension, mercury’s physical properties make it useful as a seal material to fill in these gaps. The mercury also acts as a lubricant, keeping the moving parts moving and preventing friction from overheating the unit.
Mercury quantities in submersible pump seals can be as high as 12 pounds (U.S. EPA, 2001).
Mercury seals have been identified in submersible well pumps at public water systems. While most manufacturers currently report using alternative sealing technologies, mercury sealing technology may have been common as recent as the 1990s.
Please note that well pumps and motor parts may also contain lubricating oils which have PCBs.
PCBs and the site’s well pumps are discussed on the following page with photos. It is recommended that any water pumps at the site be assumed to have mercury seals if the pump is ten years or older, and/or information on the sealing technology cannot be determined. If to be discarded, such equipment should be carefully removed, handled and treated/recycled at a facility such as manufacturer or hazardous waste treatment/recycling facility which is accredited/licensed to properly address lubricating oils, PCBs, and mercury in accordance with federal, state, and local regulations, and any Client or Owner project specifications.
Batteries
This category includes discarded primary (non-rechargeable) and secondary (rechargeable) batteries that contain elements such as cadmium, lead, or mercury, which would render them as Resource Conservation and Recovery Act (RCRA) hazardous wastes. Examples are nickel-cadmium (Ni-Cad), sealed lead-acid, or mercury-oxide batteries. UW batteries are defined as devices consisting of one or more electrically connected electrochemical cells that are designed to receive, store and deliver electric energy. Lead-acid batteries (such as automotive batteries) that are generated, transported, or collected to be reclaimed, or regenerated, but not reclaimed where stored, under provisions of 40 CFR 266, Subpart G, “Spent Lead-Acid Batteries Being Reclaimed,” do not need to be managed as UW. However, waste lead-acid batteries not
September 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable 9 managed, or eligible for management, under 40 CFR 266, Subpart G, are subject to the UW Rule requirements. Lead-acid batteries that are stored at facilities that reclaim them are subject to RCRA regulation as specified in 40 CFR 266.80(b). Many commonly generated waste batteries, such as dry cell zinc-carbon and alkaline (“long life”) batteries, typically do not contain appreciable amounts of the hazardous elements of concern, and hence would not be required to be managed as UW. However, they may be managed along with UW batteries, and this is encouraged in the interest of diverting them from less desirable disposal destinies such as incineration or disposal in solid waste landfills.
Equipment assumed to contain batteries was not readily identified at the site.
Potential PCB-Containing Equipment
The potential exists for polychlorinated biphenyls (PCBs)-containing ballasts to be present in fluorescent light fixtures throughout the subject building. If ballasts are not marked "No PCB", they must be treated as containing PCBs. In 1978, the U.S. Environmental Protection Agency (EPA) issued a ban on manufacturing equipment using PCBs, which most ballasts manufactured before 1978 contained, due to it being hazardous to both human health and the environment.
PCBs are regulated under the Toxic Substance Control Act (TSCA) through U.S. EPA. The U.S.
EPA Region 2 regulates the specifics on proper management of PCBs. If the generator determines that the ballasts do not contain hazardous constituents and do not contain PCBs then they can be disposed of as solid waste; however, they must first be evaluated in accordance with NJAC 7:26A to determine if they are hazardous. If they are hazardous and will be disposed, they must be managed as a hazardous waste and cannot be disposed of in a solid waste dumpster or landfill. The U.S. EPA and state recommendations for management of non-leaking ballasts is recycling. Ballasts that are leaking and are determined or assumed to contain PCBs must be disposed properly at an EPA-approved facility.
Fluorescent light ballasts were not observed to be associated with the subject site building.
However, please note that lubricating oils may also be a source of PCBs. A well pump was observed within the wellhouse and several motor parts were observed surrounding the structure.
The age of the pump and associated equipment is unknown to Terracon. Terracon did not disassemble equipment but rather assumed that such items contain lubricating oils with potential PCBs; additional quantities may be present.
September 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable 10
Equipment Description Approximate locations
Approximate quantities Photo Example(s)
Well Pump Wellhouse 1
Motor Parts Surrounding Wellhouse ~2 (+/-)
As noted above, well pumps may contain mercury seals as well as lubricating oils with potential PCBs. The age of any pumps and motors with lubricating oils was unknown to Terracon. It is recommended that any water pumps and motor equipment at the site be assumed to contain lubricating oils with PCBs and mercury seals. If to be discarded, such equipment should be carefully removed, handled and treated/recycled at a facility such as manufacturer or hazardous waste treatment/recycling facility which is accredited/licensed to properly address lubricating oils, PCBs, and mercury in accordance with federal, state, and local regulations and any Client or Owner project specifications.
Refrigerants
Under Section 608 of the Clean Air Act (CAA), U.S. EPA has established regulations (40 CFR Part 82, Subpart F) concerning refrigerants. The highlights of these regulations include:
· Require service practices that maximize recovery and recycling of ozone-depleting substances (both chlorofluorocarbons [CFCs] and hydrochlorofluorocarbons [HCFCs] and their blends) during the servicing and disposal of air-conditioning and refrigeration equipment.
· Set certification requirements for refrigerant recycling and recovery equipment, technicians, and refrigerant reclaimers.
· Restrict the sale of refrigerant to certified technicians.
· Require persons servicing or disposing of air-conditioning and refrigeration equipment to certify to EPA that they have acquired refrigerant recovery and/or recycling equipment and are complying with the requirements of the rule.
· Require the repair of substantial leaks in air-conditioning and refrigeration equipment with a refrigerant charge greater than 50 pounds.
· Establish safe disposal requirements to ensure removal of refrigerants from goods that enter the waste stream with the charge intact.
http://www.epa.gov/air/caa/title6.html http://ecfr.gpoaccess.gov/cgi/t/text/text-idx?c=ecfr&sid=3089adbc4a6a5f8b61a0c6ce34a56f13&rgn=div6&view=text&node=40:17.0.1.1.2.6&idno=40 http://ecfr.gpoaccess.gov/cgi/t/text/text-idx?c=ecfr&sid=3089adbc4a6a5f8b61a0c6ce34a56f13&rgn=div6&view=text&node=40:17.0.1.1.2.6&idno=40 http://www.epa.gov/ozone/title6/608/608defns.html#recycle http://www.epa.gov/ozone/title6/608/608defns.html#recover http://www.epa.gov/ozone/title6/608/608defns.html#technician http://www.epa.gov/ozone/title6/608/608defns.html#reclaim
September 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable 11
Equipment likely to have associated refrigerants was not observed on the site.
Chemical Storage
No chemical storage was observed in or adjacent to the subject wellhouse.
6.0 LIMITATIONS/GENERAL COMMENTS
This hazardous materials survey scope of services was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our site visit.
The information contained in this report is relevant to the date on which this survey was performed and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by VHB Inc. for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding actual quantities present and any further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third-parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.
APPENDIX A
Sandy Hook Well #4
341 Randolph Drive, Highlands, New Jersey Summary of Asbestos Samples and Analytical Results
HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)
01 Wire Insulation – Woven
Electrical Panel
ND
02 ND
03 ND
02 Wire Insulation - Paper
Electrical Panel
ND
05 ND
06 ND
03 Black Sealant
Mechanical Equipment
ND
08 ND
09 ND
04 Cement Pipe Gasket
Pipe Elbow
ND
11 ND
12 ND
ND = None Detected
Responsive ■ Resourceful ■ Reliable 13
Summary of Paint Chip Samples for Lead and Results
Sample ID Color Substrate Component Sample Location Lab Results (% lead by weight)*
P-1 Orange Wood Door Well House for Well #4 0.36% P-2 White Wood Door Well House for Well #4 0.39% P-3 Green Wood Door Frame Well House for Well #4 6.2% P-4 Red Brown Metal Hatch Well House for Well #4 0.049% P-5 Green Masonry Wall Well House for Well #4 7.1% P-6 White Masonry Wall Well House for Well #4 0.48% P-7 Gray Metal Duct Well House for Well #4 0.24% P-8 Gray Metal Pipe Well House for Well #4 0.38% P-9 White Metal Pipe Well House for Well #4 0.27%
APPENDIX B
ASBESTOS & LEAD PAINT ANALYTICAL LABORATORY DATA
EMSL Analytical, Inc.
1056 Stelton Road Piscataway, NJ 08854
Phone/Fax: (732) 981-0550 / (732) 981-0551 http://www.EMSL.com / piscatawaylab@emsl.com
TERC42
052103686
J6215069
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Attn:
Proj: J6215069 / Well #4
Phone: (908) 546-6187
Fax:
Collected: 8/ 9/2021
Received: 8/09/2021
Analyzed: 8/13/2021
Megan E. Cruz
Terracon Consultants, Inc.
4081 Hadley Road, Unit B
South Plainfield, NJ 07080
Summary Test Report for Asbestos Analysis in Accordance with N.J.A.C. 8:60 and 12:120 via EPA 600/R-93/116
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-000101-WP6-01
Electrical Panel/Wire Insulation - Woven
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/12/2021 90.0% 10.0%PLM Black None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-000201-WP6-02
Electrical Panel/Wire Insulation - Woven
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/12/2021 90.0% 10.0%PLM Black None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-000301-WP6-03
Electrical Panel/Wire Insulation - Woven
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/12/2021 90.0% 10.0%PLM Black None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-000402-WP6-04
Electrical Panel/Wire Insulation - Paper
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/12/2021 90.0% 10.0%PLM Brown None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-000502-WP6-05
Electrical Panel/Wire Insulation - Paper
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/12/2021 85.0% 15.0%PLM Brown None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-000602-WP6-06
Electrical Panel/Wire Insulation - Paper
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/13/2021 90.0% 10.0%PLM Brown None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-000703-MS5-07
Mechanical Equipment/Black Sealant
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/12/2021 <0.25% 100%PLM Grav. Reduction None DetectedBlack
8/12/2021 0.0% 100.0%TEM Grav. Reduction None DetectedBlack
Test Report:EPAMultiTests-7.32.2.D Printed: 8/14/2021 03:18PM Page 1 of 3
Phone/Fax: (732) 981-0550 / (732) 981-0551 http://www.EMSL.com / piscatawaylab@emsl.com
TERC42
052103686
J6215069
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis in Accordance with N.J.A.C. 8:60 and 12:120 via EPA 600/R-93/116
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-000803-MS5-08
Mechanical Equipment/Black Sealant
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/12/2021 0.0% 100%PLM Grav. Reduction None DetectedBlack
8/12/2021 0.0% 100.0%TEM Grav. Reduction None DetectedBlack
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-000903-MS5-09
Mechanical Equipment/Black Sealant
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/12/2021 0.0% 100%PLM Grav. Reduction None DetectedBlack
8/12/2021 0.0% 100.0%TEM Grav. Reduction None DetectedBlack
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-001004-CP5-10
Pipe Elbow/Cement Pipe Gasket
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/12/2021 0.0% 100.0%PLM Gray None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-001104-CP5-11
Pipe Elbow/Cement Pipe Gasket
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/12/2021 0.0% 100.0%PLM Gray None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 052103686-001204-CP5-12
Pipe Elbow/Cement Pipe Gasket
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/13/2021 0.0% 100.0%PLM Gray None Detected
Test Report:EPAMultiTests-7.32.2.D Printed: 8/14/2021 03:18PM Page 2 of 3
Phone/Fax: (732) 981-0550 / (732) 981-0551 http://www.EMSL.com / piscatawaylab@emsl.com
TERC42
052103686
J6215069
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis in Accordance with N.J.A.C. 8:60 and 12:120 via EPA 600/R-93/116
Analyst(s):
PLM (4)Danielle Hurst
PLM (5)
PLM Grav. Reduction (3)
TEM Grav. Reduction (3)
Susan Pollack
Chaiyut Sae Lao, Laboratory Manager or Other Approved Signatory
Reviewed and approved by:
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody.
Samples are within quality control criteria and met method specifications unless otherwise noted. Estimation of uncertainty available upon request. This report is a summary of multiple methods of analysis, fully compliant reports are available upon request. A combination of PLM and TEM analysis may be necessary to ensure consistently reliable detection of asbestos. This report must not be used to claim product endorsement by NVLAP of any agency or the U.S. Government.
Samples analyzed by EMSL Analytical, Inc. Piscataway, NJ NYS ELAP 11423, NVLAP Lab Code 101048-2, NJ NELAC 12037, Philadelphia
289, CT PH-0266
Initial report from: 08/14/202115:18:16
Test Report:EPAMultiTests-7.32.2.D Printed: 8/14/2021 03:18PM Page 3 of 3
OrderID: 052103686
OrderID: 052103686
Client Sample Description ConcentrationLab ID Analyzed Weight Lead
Collected
EMSL Analytical, Inc.
200 Route 130 North, Cinnaminson, NJ 08077 Phone/Fax: (856) 303-2500 / (856) 786-5974 http://www.EMSL.com cinnaminsonleadlab@emsl.com
Attn: Megan E. Cruz Terracon Consultants, Inc.
4081 Hadley Road, Unit B South Plainfield, NJ 07080
Received: 08/10/21 9:00 AM
J6215069 / Well #4
Fax:
Phone: (908) 546-6187
Project:
8/9/2021Collected:
Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*
202106133 CustomerID: TERC42 CustomerPO: J6215069 ProjectID:
EMSL Order:
0.2707 Site: Door - Wood Desc: Orange
202106133-0001P-1 0.36 % wt8/12/2021 g8/9/2021
0.2729 Site: Door - Wood Desc: White
202106133-0002P-2 0.39 % wt8/12/2021 g8/9/2021
0.1008 Site: Door Frame - Wood Desc: Green
202106133-0003P-3 6.2 % wt8/12/2021 g8/9/2021
0.1405 Site: Hatch - Metal Desc: Red-Brown
202106133-0004P-4 0.049 % wt8/12/2021 g8/9/2021
0.2429 Site: Wall - Masonry Desc: Green
202106133-0005P-5 7.1 % wt8/12/2021 g8/9/2021
0.1948 Site: Wall - Masonry Desc: White
202106133-0006P-6 0.48 % wt8/12/2021 g8/9/2021
0.2582 Site: Duct - Metal Desc: Gray
202106133-0007P-7 0.24 % wt8/12/2021 g8/9/2021
0.1772 Site: Pipe - Metal Desc: Gray
202106133-0008P-8 0.38 % wt8/12/2021 g8/9/2021
0.1105 Site: Pipe - Metal Desc: White
202106133-0009P-9 0.27 % wt8/12/2021 g8/9/2021
The sample duplicate RSD for samples -0001 through -0009 fell outside control limits. All other QC results met criteria.
Phillip Worby, Lead Laboratory Manager or other approved signatory
Test Report ChmSnglePrm/nQC-7.32.3 Printed: 8/17/2021 11:32:28 AM
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.
Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.008% wt based on the minimum sample weight per our SOP. "<" (less than) result signifies the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. Definitions of modifications are available upon request.
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NELAP Certifications: NJ 03036, NY 10872, PA 68-00367, AIHA-LAP, LLC ELLAP 100194, A2LA 2845.01
Initial report from 08/17/2021 11:32:28
OrderID: 202106133
OrderID: 202106133
APPENDIX C
LICENSES AND CERTIFICATIONS
APPENDIX D
PHOTOGRAPHS
Date Pictures Taken: August 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable
Photo 1 Exterior of wellhouse Photo 2 Exterior of wellhouse
Photo 3 Terracotta pipes with cementitious gaskets (Asbestos HA #4)
Photo 4 Debris surrounding the well house
Photo 5 Wellhouse interior Photo 6 Pump in the well house
Date Pictures Taken: August 9, 2021 ■ Terracon Project No. J6215069
Responsive ■ Resourceful ■ Reliable
Photo 7 Electrical panel Photo 8 Wire insulation – woven (Asbestos HA #1)
Photo 9 Wire insulation – paper (Asbestos HA #2) Photo 10 Black sealant (Asbestos HA #3)
Photo 11 Well #4 cover Photo 12 Various paints containing lead
| GATE 225953 - DB RFP PART 5 - ATTACHMENTS |
| Attachment G - Hazardous Materials Survey - Well #4 |
File details come from the government source that posted it. Updated .