B09_Attach_24__Sheet_C1_1_Revision_0003.pdf

PDF 338 KB Posted

Attached to
GATE 225953 - Rehab Well No. 4 Sandy Hook NJ
Solicitation number
140P2022R0044
Issued by

About this file

This document package includes construction drawings and specifications for the rehabilitation of Well No. 4 located at Sandy Hook, New Jersey within the Gateway National Recreation Area. The drawings depict site plans, well structures, utility connections, fencing, access roads and gates for the project. Notes indicate tree protection requirements, soil stabilization and seeding specifications, requirements for water main design calculations and thrust block details, as well as responsibility for electrical and control system design and installation. The related federal contract opportunity is solicitation number 140P2022R0044 issued by the National Park Service for the rehabilitation and replacement of Well No. 4 at Sandy Hook, with an estimated value over $25,000. The work includes well rehabilitation, site work and utility upgrades per the specifications and drawings provided.

View the file

Other files

File Type Posted
B09_Attach_21_Request_for_Information_DRAFT_(1)_0004.pdf PDF
Sol_140P2022R0044_Amd_0004.pdf PDF
B09_Amend_03_RFIs_0003.pdf PDF
B09_Attach_25_Cert_of_Vaccination_Form_Revised_0003.pdf PDF
Sol_140P2022R0044_Amd_0003.pdf PDF
B09_Attach_21_Request_for_Information_DRAFT_0003.docx DOCX document
B09_Attach_21_Request_for_Information_DRAFT_0002.docx DOCX document
B09_Attach_20_Pre-Proposal_Conf__Attendee_List_0002.docx DOCX document
Sol_140P2022R0044_Amd_0002.pdf PDF
B09_Attach_19_GATE_Well_PreProposal_Conf_0002.ppt PPT presentation
B09_Attach_23_Project_Experience_Form_0002.docx DOCX document
B09_Attach_22_Schematic_Design_Plans_Revision_0002.pdf PDF
B09_Amend_02_Attachments_0002.pdf PDF
B09_Amend_01_PreProposal_Conf_0001.pdf PDF
Sol_140P2022R0044_Amd_0001.pdf PDF
B08_Attach_3_Vaccination_Certification_Notification_.pdf PDF
B08_Attach_4_Certification_of_Vaccination_Form.pdf PDF
B08_RFP_140P2022R0044.pdf PDF
B08_Attach_10_Schematic_Design_Tech_Requirements.pdf PDF
B08_Attach_16_NPS_Constructability_Checklist_DRAFT.xlsx XLSX spreadsheet
B08_Attach_8_Discussions_Permitting_Agencies.pdf PDF
B08_Attach_2_Davis_Bacon.pdf PDF
B08_Attach_13_Existing_Photos.pdf PDF
B08_Attach_6_Geologic_Survey___Drilling_Approach.pdf PDF
B08_Attach_9_Schematic_Design_Plans.pdf PDF
Sol_140P2022R0044.pdf PDF
B08_Attach_17_PPQ.docx DOCX document
B08_Attach_14_Existing_System_Drawings.pdf PDF
B08_Attach_18_LmtOnSubconRpt.xlsx XLSX spreadsheet
B08_Attach_15_Well_5A_Raw_Water_Test_Report.pdf PDF
B08_Attach_1_SOS.pdf PDF
B08_Attach_7_Existing_Permit_Authorizations.pdf PDF
B08_Attach_5_Basis_of_Design.pdf PDF
B08_Attach_11_Hazardous_Materials_Survey.pdf PDF
B08_Attach_12_Geotechnical_Report.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROPOSED CLEARING

TIE INTO EX. CHAIN

LINK FENCE

TIE INTO EX. CHAIN

LINK FENCE

WELL #6 BUILDING (SEE

ARCHITECTURAL PLANS FOR

FOUNDATION INFORMATION)

WELL #5A BUILDING

WELL #5 (AUTOMATIC TRANSFER SWITCH) SEE

ELECTRICAL PLANS FOR ADDITIONAL INFORMATION

EXISTING GENERATOR AND FUEL TANK,

SEE NOTE 6 (SEE ELECTRICAL PLANS)

EXISTING TRANSFORMER

TO REMAIN

CONNECT NEW 8" DI

TO WELL #5A OUTLET

(BELOW GRADE)

MATCHLINE SHEET C1.2

6" CONCRETE

BOLLARD (TYP.)

8' CHAIN LINK FENCE

8' WIDE MOW STRIP

CONCRETE

SLAB

UGE TO

WELL #6

PR. 8" DI WL

PR. 8" DI

WL

4' PEDESTRIAN

ACCESS GATE

18' ROLLING

CANTILEVER GATE

18' WIDE ASPHALT

ACCESS DRIVE TIE INTO EXISTING

8" AC WATER MAIN

COMMUNICATION LINE

FROM WELL #6 TO WTP

CUT, CAP AND ABANDON

8" AC PIPE

TWO 3" CONCRETE ENCASED

SCH-80 PVC CONDUITS WITH

FIBER OPTIC CABLE FROM

WELL #6 BUILDING TO WTP

EXISTING 8" AC

WATER MAIN

CONCRETE

SLAB (TYP.)

C2.1

C2.1

C2.1

C2.1

C2.1

C2.1

GV&VB

(TYP.)C2.2

C2.2

C2.1

C2.2

FIVE CONTROL

CONDUITS

(1"Ø MIN.)

CONCRETE SPLASH PAD

AND RIPRAP APRON

REMOVE RTU AND BATTERY

PANELS AND DELIVER TO

THE GOVERNMENT

STABILIZED

CONSTRUCTION

ENTRANCE

C3.1

TREE PROTECTION

(SEE NOTE 1)C3.1

GENERATOR AND BURIED

PROPANE FUEL TANK

(BID OPTION #1)

SEE ELECTRICAL PLANS

TEMPORARY CHAIN LINK

FENCE WITH PRIVACY SLATS

TO PROVIDE SCREENING

DURING CONSTRUCTION

CONSTRUCTION ACCESS

VIA MULTI-USE-PATH IS

PROHIBITED

TWO METAL WINDOWS (37"X37") AT WELL #5

ARE TO BE REMOVED AND REPLACED IN KIND

(BID OPTION #2)

LIMITS OF

CONSTRUCTION

LIMITS OF

CONSTRUCTION

REMOVE EXISTING

CHAIN LINK FENCE

REMOVE

EXISTING

CHAIN LINK

FENCE

EXISTING CHAIN LINK

FENCE TO REMAIN

EX 8" AC

LINE TO BE

ABANDONED

EXISTING 6" CAST IRON

WATERLINE

EXISTING 8" CAST

IRON WATERLINE

EXISTING 10" AC FINISHED

WATER FEED TO POST

EXISTING 8" AC TO

AERATION TANK

FINAL SCHEMATIC DESIGN DOCUMENTS

1. CONTRACTOR SHALL PROTECT EXISTING TREES TO REMAIN PER SECTION 9

(TREE PROTECTION DURING CONSTRUCTION) OF THE STANDARD FOR SOIL

EROSION AND SEDIMENT CONTROL (SSESC) IN NEW JERSEY, LATEST EDITION.

2. ANY DISTURBED AREA NOT RECEIVING IMPERVIOUS COVER SHALL RECEIVE

4" OF TOPSOIL AND SEED PER SECTION 4 (PERMANENT VEGETATIVE COVER

FOR SOIL STABILIZATION) OF SSESC.

3. CONTRACTOR SHALL PREPARE AND SUBMIT WATER MAIN THRUST

CALCULATIONS AND INCLUDE THRUST BLOCK DESIGN DETAILS FOR

CONTRACTING OFFICER'S REVIEW/APPROVAL.

4. DESIGN BUILD CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND

INSTALLATION OF ALL ELECTRICAL AND CONTROL CONDUIT AND WIRING

SYSTEM.

5. STAGING AREA INCLUDING CONTRACTOR TRAILERS TO BE LOCATED WITHIN

LIMITS OF CONSTRUCTION.

6. EXISTING GENERATOR AND FUEL TANK TO REMAIN FOR BASE BID AND

REMOVED IF BID OPTION #1 IS EXECUTED.

7. SEE ELECTRICAL DRAWINGS FOR WORK BEING COMPLETED IN BASE BID AND

BID OPTION #1.

Notes

Sheets and Views
C1.1 FINISH MATERIALS
VIEW