This is a set of technical drawings and geotechnical engineering documentation for electrical transmission and distribution line construction on the Colorado River Indian Reservation in Morgantown, Arizona.
The drawings package includes plan and profile sheets, staking details, structure coordinates, phasing diagrams, stringing charts, transmission line schematics, distribution line details, foundation drawings, and soil boring information. The project involves installation of four new transmission line poles (designated NEW T1 through NEW T4) for a 69kV transmission line with custom steel caisson foundations ranging from 60 to 75 feet in height, along with distribution line modifications at existing and new structures. Key specifications include 4/0 ACSR "Penguin" conductors displayed at 167°F for the transmission line, 3/8" EHS shield wire, and 2 AWG ACSR "Sparrow" conductors for the 12.47kV distribution line. The documentation provides detailed bills of materials specifying equipment from suppliers including Hubbell, AFL, Burndy, Anderson, and others; structural coordinates using PLS-CADD drawings; and conductor tension and sagging calculations across multiple spans. The geotechnical engineering report by Terracon (Project 63235018, dated April 26, 2023) recommends drilled shaft foundations with minimum 10-foot embedment into native soils, documents groundwater encountered at 6 to 13 feet below surface across three boring locations, classifies soil as sandy lean clay and silty materials with medium stiff to loose consistency, and identifies seismic site classification D with minimal liquefaction risk and estimated seismically-induced settlement of 0.37 inches. Corrosivity testing indicates ASTM Type V portland cement is required for concrete in contact with site soils due to soluble sulfate concentrations classified as S2.
View the file
Other files for this federal contract opportunity
Show all 31
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TABLE OF CONTENTS
01 – PLAN AND PROFILE DRAWING
02 – STAKING SHEETS
03 – STRUCTURE COORDINATES
04 – PHASING DIAGRAM
05 – STRINGING CHARTS
06 – TRANSMISSION LINE
07 – DISTRIBUTION LINE
08 –FOUNDATION DRAWINGS
09 – SOIL BORINGS
01 - PLAN AND PROFILE DRAWING
PLS-CADD DRAWING
P I
'0
P I
-1
'2
P I
-4
'5
P I
'5
P I
-0
'5
S
T A
.0
F
T P
IE
R
R V
L
E X
IS
T
IN
G
A
.5
F T
E M
B E
D
X
IS
T
R
M
O V
E E
X
IS
T
IN
G G
U Y
W
IR
E S
T O
N O
R
H
N
W
A
.0
F T
P
IE
R R
W
T L
C
U S
T O
M
C A
IS
S
O
F
-1
W
A
.5
F
T P
IE
R
R
W T
L
S T
O M
C
A
IS
S
-2
W
A
F
T P
IE
R
R
W T
L
S T
O M
S
W
IT
H
A
IS
S
-3
W
A
F
T P
IE
R
R
W T
L
S T
O M
C
A
IS
S
-1
A
F T
E M
B
I
S T
A L
L N
E W
S T
A T
IC
E
Q U
IP
M
E N
T P
E R
B
M
N T
R A
C T
O R
T O
M A
T C
H E
X
IS
T
A N
S M
IS
S
IO
N
T E
N S
IO
N
S U
S
IN
G S
T A
N D
A
P
A C
T
IC
S
T A
L L
L
IN
D S
E Y
/1
W
E
IG
H T
S
C H
C O
N D
I N
S U
L A
T
513, 290 380
426 309
711754
683754
NEW T1
NEW T2
NEW T3
NEW T4
556626 XXXXX
667754
639753
638734
623714
613702 - MOD
NEW D1
NEW D2
NEW T3
DRAWING NUMBER:
CHK BY:
DATE:
DRAWING TITLE:
APPR BY:
REVISION:
PROJ NO:
DATE REV. DESCRIPTION BY CHK
REVISIONS: REVISIONS:
DWG BY:
SITE:
STR/AREA:
FLOOR:
STATUS:
DISCIPLINE:
PROJECT NAME:
INSTALL NEW T3 FENCING
PER DRAWING A69-GR1
AND SPECIFICATION 32 31 10
COND 69KV:
4/0 ACSR "PENGUIN"
DISPLAYED AT 167 DEG F
OHGW:
3/8" EHS
DISPLAYED AT 30 DEG F
COND 13.2KV:
#2 ACSR "SPARROW"
DISPLAYED AT 120 DEG F
NUETRAL :
#2 ACSR "SPARROW"
DISPLAYED AT 120 DEG F
SECONDARY:
1/0 ACSR "RAVEN"
DISPLAYED AT 120 DEG F
MC420
69KV TRANSMISSION LINE
12.47KV DISTRIBUTION LINE
PLAN AND PROFILE
SHEET 1 OF 2
MAIN CANAL 420
TRANS / DIST
ELECT
03/29/2024
31107.01 IFB
CSS (SCLPC)
P&P-001
LDK (SCLPC) LDK (SCLPC)
0 ISSUED FOR BID CSS LDK 03/29/2024
628692
(TO BE REMOVED)
653704
(TO BE REMOVED)
668724
(TO BE REMOVED)
614672
(TO BE REMOVED)
607651
(TO BE REMOVED)
559630
(TO BE REMOVED)
584649
(TO BE REMOVED)
VERT. SCALE
HORIZ. SCALE
20.0 FT.
100.0 FT.
N O
R
TH
FUTURE GROUND ELEVATION
WHEN IT DIFFERS FROM
EXISTING GROUND ELEVATION.
EXISTING WIRE TO BE REMOVED
DURING CONSTRUCTION.
EXISTING STRUCTURES TO BE
REMOVED DURING
CONSTRUCTION.
TRANSMISSION ROW LINE
PLS-CADD DRAWING
P I
'0
P I
'4
P I
-8
'3
P I
'3
P I
'0
P I
'0
P I
-9
'2
P I
'0
A
.0
F
T P
IE
R
R
F
T E
M B
IS
T
A
.2
F T
P
IE
R R
F T
E M
B
IS
T
A
F T
E M
B
IS
T
A
.5
F
T P
IE
R
R
F
T E
M B
IS
T
M
A
F T
E M
B
IS
T
S
T A
L L
O N
E
C
.5
C
.5
S
IN
G
L E
M
W E
S T
S
ID
E O
F B
O T
T O
M C
R O
S S
A
M
M O
V E
W E
S T
E R
N D
O W
N G
U Y
W
A
.2
F
T E
M B
W
D L
-4
IR
E
C T
E M
B
S T
A L
L O
N E
C
.9
G
M
-4
W
A
F
T E
M B
W
D L
-5
IR
E
C T
E M
B
S T
A L
L O
N E
C
.5
C
.5
S
IN
G L
E M
S
T A
L L
O N
E
K
.3
-5
513, 290
171 261
164 117 128
VERT. SCALE
HORIZ. SCALE
20.0 FT.
100.0 FT.
N O
R T H
683754
NEW T1
NEW T2
NEW T3 NEW T4
556626
XXXXX
667754
639753
638734
623714
613702 - MOD
NEW D1
NEW D2
DRAWING NUMBER:
CHK BY:
DATE:
DRAWING TITLE:
APPR BY:
REVISION:
PROJ NO:
DATE REV. DESCRIPTION BY CHK
REVISIONS: REVISIONS:
DWG BY:
SITE:
STR/AREA:
FLOOR:
STATUS:
DISCIPLINE:
PROJECT NAME:
COND 69KV:
4/0 ACSR "PENGUIN"
DISPLAYED AT 167 DEG F
OHGW:
3/8" EHS
DISPLAYED AT 30 DEG F
COND 13.2KV:
#2 ACSR "SPARROW"
DISPLAYED AT 120 DEG F
NUETRAL :
#2 ACSR "SPARROW"
DISPLAYED AT 120 DEG F
SECONDARY:
1/0 ACSR "RAVEN"
DISPLAYED AT 120 DEG F
MC420
69KV TRANSMISSION LINE
12.47KV DISTRIBUTION LINE
PLAN AND PROFILE
SHEET 2 OF 2
MAIN CANAL 420
TRANS / DIST
ELECT
03/29/2023
31107.01 IFB
CSS (SCLPC)
P&P-002
LDK (SCLPC) LDK (SCLPC)
0 ISSUED FOR BID CSS LDK 03/29/2024
FUTURE GROUND ELEVATION
WHEN IT DIFFERS FROM
EXISTING GROUND ELEVATION.
EXISTING WIRE TO BE REMOVED
DURING CONSTRUCTION
EXISTING STRUCTURES TO BE
REMOVED DURING
CONSTRUCTION
TRANSMISSION ROW LINE
668724
(TO BE REMOVED)
653704
(TO BE REMOVED)
628692
(TO BE REMOVED)
614672
(TO BE REMOVED)
607651
(TO BE REMOVED)
599630
(TO BE REMOVED)
584649
(TO BE REMOVED)
10276 PolyLine
10276 PolyLine
10276 Ellipse
10276 Line
10276 Line
10276 Ellipse
10276 Line
10276 Line
10276 Ellipse
10276 Line
10276 Line
10276 Ellipse
10276 Line
10276 Line
10276 Ellipse
10276 Line
10276 Line
10276 Ellipse
10276 Line
10276 Line
10276 Ellipse
10276 Line
10276 Line
10276 Ellipse
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
10276 Line
02 - STAKING SHEETS
Staking Sheet
Bureau of Indian Affairs
69kV Transmission
POLE
STRUCTURE STATION AHEAD LINE TRANSMISSION DISTRIBUTION HEIGHT FOUNDATION STRUCTURE GUY
NO. SPAN ANGLE CONDUCTOR & QTY CONDUCTOR & QTY (ABOVE GROUND) REVEAL TYPE WIRE COMMENTS
(ft) (ft) (deg) OHGW OHGW (ft) (ft) (FRAMING)
683754 2+96 513 -12.59 1117938.6 526317.7 4/0 PENGUIN ACSR 6/1 STRANDS 3 EX-1 GUY 5 1117959.296 526374.270 SHARED GUY ANCHOR
EXISTING 3/8" HS 7 STRAND 1 GUY 6 1117959.296 526374.270 SHARED GUY ANCHOR
GUY 7 1117957.671 526369.254
GUY 8 1117944.675 526350.177 REMOVE EXISTING GUY WIRES TO NORTH
AFTER WIRE REMOVAL TO STR 668724
NEW T1 8+08 380 -43.88 1117829.3 525817.0 4/0 PENGUIN ACSR 6/1 STRANDS 3 75.0' 3.0' FR-1
3/8" HS 7 STRAND 1
NEW T2 11+88 391 0 1117513.9 525605.8 4/0 PENGUIN ACSR 6/1 STRANDS 3 70.0' 1.5' FR-2
3/8" HS 7 STRAND 1
NEW T3 15+78 426 0 1117189.3 525388.6 4/0 PENGUIN ACSR 6/1 STRANDS 3 60.0' 2.0' FR-3
3/8" HS 7 STRAND 1
NEW T4 20+04 309 19.90 1116835.7 525151.9 4/0 PENGUIN ACSR 6/1 STRANDS 3 60.0' 1.5' FR-1
3/8" HS 7 STRAND 1
INSTALL NEW STATIC EQUIPMENT PER BOM
556626 23+13 1116653.1 524902.5 4/0 PENGUIN ACSR 6/1 STRANDS 3 CONTRACTOR TO MATCH EXISTING TRANSMISSION
EXISTING 3/8" HS 7 STRAND 1 TENSION USING STANDARD PRACTICES
INSTALL LINDSEY 3704/150 WEIGHTS ON EACH COND INSULATOR
INSTALL ONE (1) C6.52, C6.53 SINGLE MOD
613702 - MOD 41+45 117 0.65 1117400.5 525632.6 2 AWG SPARROW ACSR 6/1 STRANDS 3 EX-2 ON WEST SIDE OF BOTTOM CROSSARM
EXISTING 2 AWG SPARROW ACSR 6/1 STRANDS 1 REMOVE TOP CROSS ARM AND JUMPER COND
REMOVE WESTERN DOWN GUYS
NEW D1 42+62 128 -90.29 1117325.6 525542.9 2 AWG SPARROW ACSR 6/1 STRANDS 3 34.0' FR-4 INSTALL ONE (1) C6.91G MOD
2 AWG SPARROW ACSR 6/1 STRANDS 1
NEW D2 43+89 0 0.00 1117228.1 525625.2 2 AWG SPARROW ACSR 6/1 STRANDS 3 43.0' FR-5 INSTALL ONE (1) C6.52, C6.53 SINGLE MOD
2 AWG SPARROW ACSR 6/1 STRANDS 1 INSTALL ONE (1) K4.3G
NORTHING EASTING NORTHING EASTING
7/3/2023 Stanley Consultants Inc. 1
Distribution
POLE
STRUCTURE STATION AHEAD LINE TRANSMISSION DISTRIBUTION HEIGHT STRUCTURE
NO. SPAN ANGLE CONDUCTOR & QTY CONDUCTOR & QTY (ABOVE GROUND) EMBEDMENT TYPE COMMENTS
(ft) (ft) (deg) OHGW OHGW (ft) (ft) (FRAMING)
INSTALL ONE (1) C6.52, C6.53 SINGLE MOD
613702 - MOD 41+45 117 0.65 1117400.5 525632.6 2 AWG SPARROW ACSR 6/1 STRANDS 3 EX-2 ON WEST SIDE OF BOTTOM CROSSARM
EXISTING 2 AWG SPARROW ACSR 6/1 STRANDS 1 REMOVE TOP CROSS ARM AND JUMPER COND
REMOVE WESTERN DOWN GUYS
NEW D1 42+62 128 -90.29 1117325.6 525542.9 2 AWG SPARROW ACSR 6/1 STRANDS 3 34.0' 6.0' FR-4 INSTALL ONE (1) C6.91G MOD
2 AWG SPARROW ACSR 6/1 STRANDS 1
NEW D2 43+89 0 0.00 1117228.1 525625.2 2 AWG SPARROW ACSR 6/1 STRANDS 3 43.0' 7.0' FR-5 INSTALL ONE (1) C6.52, C6.53 SINGLE MOD
2 AWG SPARROW ACSR 6/1 STRANDS 1 INSTALL ONE (1) K4.3G
NORTHING EASTING
6/29/2023 Stanley Consultants Inc. 1
Distribution
POLE
STRUCTURE STATION AHEAD LINE TRANSMISSION DISTRIBUTION HEIGHT FOUNDATION STRUCTURE GUY
NO. SPAN ANGLE CONDUCTOR & QTY CONDUCTOR & QTY (ABOVE GROUND) EMBEDMENT REVEAL TYPE WIRE COMMENTS
(ft) (ft) (deg) OHGW OHGW (ft) (ft) (ft) (FRAMING)
INSTALL ONE (1) C6.52, C6.53 SINGLE MOD
613702 - MOD 41+45 117 0.65 1117400.5 525632.6 2 AWG SPARROW ACSR 6/1 STRANDS 3 EX-2 ON WEST SIDE OF BOTTOM CROSSARM
EXISTING 2 AWG SPARROW ACSR 6/1 STRANDS 1 REMOVE TOP CROSS ARM AND JUMPER COND
REMOVE WESTERN DOWN GUYS
NEW D1 42+62 128 -90.29 1117325.6 525542.9 2 AWG SPARROW ACSR 6/1 STRANDS 3 32.75' 7.25' FR-4 INSTALL ONE (1) C6.91G MOD
2 AWG SPARROW ACSR 6/1 STRANDS 1
NEW D2 43+89 0 0.00 1117228.1 525625.2 2 AWG SPARROW ACSR 6/1 STRANDS 3 43.00' 7.00' FR-5 INSTALL ONE (1) C6.52, C6.53 SINGLE MOD
2 AWG SPARROW ACSR 6/1 STRANDS 1 INSTALL ONE (1) K4.3G
NORTHING EASTING NORTHING EASTING
12/4/2024 Stanley Consultants Inc. 1
03 – STRUCTURE COORDINATES
Stanley
Structure No.
BIA Structure
No. DESCRIPTION Northing Easting Comment
683754 POLE 1117938.626 526317.663
GUY 5 (STATIC) 1117959.296 526374.270 Shared Anchor
GUY 6 (TOP COND) 1117959.296 526374.270 Shared Anchor
GUY 7 (MID COND) 1117957.671 526369.254
GUY 8 (BOT COND) 1117944.675 526350.177
New T1 POLE 1117829.276 525816.982
New T2 POLE 1117513.864 525605.845
New T3 POLE 1117189.323 525388.597
New T4 POLE 1116835.654 525151.850
556626 POLE 1116653.096 524902.504
613702 POLE 1117400.485 525632.591
NEW D1 POLE 1117325.588 525542.918
NEW D2 POLE 1117228.133 525625.155
04 - PHASING DIAGRAM
05 - STRINGING CHARTS
Stanley Consultants, Ins.
MC420 Transmission Line
Sheet 1 6/30/2023 Sheet 1 of 10
3/8” 7 strand HS Steel Shield Wire – Str. 683754 to Str. New T1
Section #2 from structure #683754 to structure #New T1, start set #1 'sw', end set #1 ''
Cable 'C:\projects\CRIP Canal\PLS\Cable\3_8-7_ehs_steel.wir', Ruling span (ft) 510.635
Sagging data: Catenary (ft) 8127.64, Horiz. Tension (lbs) 2218.85 Condition I Temperature (deg F) 60
Results below for condition 'Initial RS'
Calculations done using actual span lengths and vertical projections
Span Mid Mid Mid Mid Mid Mid Mid Mid Mid Left Span
Length Span Span Span Span Span Span Span Span Span Struct Vertical
Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
(ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft)
511.1 3.71 3.86 4.03 4.19 4.37 4.56 4.76 4.97 5.18 683754 21.44
Span 3 3 3 3 3 3 3 3 3 Left Span
Length Wave Wave Wave Wave Wave Wave Wave Wave Wave Struct Vertical
Time Time Time Time Time Time Time Time Time Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
(ft) Sec. Sec. Sec. Sec. Sec. Sec. Sec. Sec. Sec. (ft)
511.1 5.76 5.88 6.00 6.12 6.25 6.39 6.53 6.67 6.81 683754 21.44
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz
Tension Tension Tension Tension Tension Tension Tension Tension Tension
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
(lbs) (lbs) (lbs) (lbs) (lbs) (lbs) (lbs) (lbs) (lbs)
2408 2310 2216 2128 2040 1955 1873 1795 1722
Sheet 2 6/30/2023 Sheet 2 of 10
4/0 AWG 6/1 Strand “Penguin” ACSR – Str. 683754 to Str. New T1
Section #5 from structure #683754 to structure #New T1, start set #3 'cond', end set #3 ''
Cable 'C:\projects\CRIP Canal\PLS\Cable\penguin_acsr.wir', Ruling span (ft) 510.532
Sagging data: Catenary (ft) 6483.34, Horiz. Tension (lbs) 1887.3 Condition I Temperature (deg F) 60
Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
510.8 4.47 4.74 5.03 5.35 5.69 6.05 6.43 6.82 7.23 683754 15.94
Time Time Time Time Time Time Time Time Time Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
510.8 6.33 6.51 6.71 6.92 7.13 7.36 7.58 7.81 8.04 683754 15.94
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
2123 2003 1887 1775 1670 1571 1478 1392 1315
Sheet 3 6/30/2023 Sheet 3 of 10
3/8” 7 strand HS Steel Shield Wire – Str. New T1 to Str. New T3
Section #17 from structure #New T1 to structure #New T3, start set #11 '', end set #1 ''
Cable 'C:\projects\CRIP Canal\PLS\Cable\3_8-7_ehs_steel.wir', Ruling span (ft) 384.296
Sagging data: Catenary (ft) 7994.45, Horiz. Tension (lbs) 2182.48 Condition I Temperature (deg F) 60
Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
(ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft)
378.7 2.05 2.14 2.24 2.35 2.46 2.58 2.72 2.85 3.01 New T1 -7.42
389.8 2.17 2.27 2.38 2.49 2.61 2.74 2.88 3.02 3.18 New T2 -9.63
Time Time Time Time Time Time Time Time Time Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
(ft) Sec. Sec. Sec. Sec. Sec. Sec. Sec. Sec. Sec. (ft)
378.7 4.28 4.38 4.48 4.59 4.69 4.81 4.93 5.05 5.18 New T1 -7.42
389.8 4.41 4.51 4.61 4.72 4.83 4.95 5.07 5.20 5.34 New T2 -9.63
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
2388 2285 2183 2083 1987 1894 1802 1715 1629
Sheet 4 6/30/2023 Sheet 4 of 10
4/0 AWG 6/1 Strand “Penguin” ACSR – Str. New T1 to Str. New T3
Section #21 from structure #New T1 to structure #New T3, start set #13 '', end set #3 ''
Cable 'C:\projects\CRIP Canal\PLS\Cable\penguin_acsr.wir', Ruling span (ft) 384.071
Sagging data: Catenary (ft) 6222.6, Horiz. Tension (lbs) 1811.4 Condition I Temperature (deg F) 60
Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
(ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft)
378.5 2.51 2.69 2.88 3.10 3.34 3.60 3.89 4.19 4.52 New T1 -8.19
389.6 2.66 2.85 3.05 3.28 3.54 3.82 4.12 4.44 4.78 New T2 -7.85
Time Time Time Time Time Time Time Time Time Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
(ft) Sec. Sec. Sec. Sec. Sec. Sec. Sec. Sec. Sec. (ft)
378.5 4.74 4.90 5.08 5.27 5.47 5.68 5.90 6.12 6.35 New T1 -8.19
389.6 4.88 5.05 5.22 5.42 5.63 5.84 6.07 6.30 6.54 New T2 -7.85
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
2075 1941 1810 1682 1561 1448 1341 1244 1155
Sheet 5 6/30/2023 Sheet 5 of 10
3/8” 7 strand HS Steel Shield Wire – Str. New T3 to Str. New T4
Section #18 from structure #New T3 to structure #New T4, start set #11 '', end set #1 ''
Cable 'C:\projects\CRIP Canal\PLS\Cable\3_8-7_ehs_steel.wir', Ruling span (ft) 424.155
Sagging data: Catenary (ft) 7911.78, Horiz. Tension (lbs) 2159.92 Condition I Temperature (deg F) 60
Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
424.2 2.61 2.72 2.84 2.98 3.12 3.27 3.42 3.59 3.76 New T3 2.92
Time Time Time Time Time Time Time Time Time Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
424.2 4.83 4.93 5.04 5.16 5.28 5.40 5.53 5.67 5.80 New T3 2.92
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
2357 2257 2160 2064 1970 1880 1793 1710 1632
Sheet 6 6/30/2023 Sheet 6 of 10
4/0 AWG 6/1 Strand “Penguin” ACSR – Str. New T3 to Str. New T4
Section #22 from structure #New T3 to structure #New T4, start set #13 '', end set #3 ''
Cable 'C:\projects\CRIP Canal\PLS\Cable\penguin_acsr.wir', Ruling span (ft) 423.697
Sagging data: Catenary (ft) 6321.88, Horiz. Tension (lbs) 1840.3 Condition I Temperature (deg F) 60
Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
423.7 3.11 3.32 3.55 3.80 4.08 4.38 4.70 5.04 5.39 New T3 2.92
Time Time Time Time Time Time Time Time Time Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
423.7 5.28 5.45 5.64 5.83 6.04 6.26 6.48 6.71 6.94 New T3 2.92
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
2098 1967 1840 1719 1601 1492 1391 1297 1212
Sheet 7 6/30/2023 Sheet 7 of 10
3/8” 7 strand HS Steel Shield Wire – Str. New T4 to Str. 556626
CONTRACTOR TO MATCH EXISTING STATIC TENSIONS USING STANDARD PRACTICES
Sheet 8 6/30/2023 Sheet 8 of 10
4/0 AWG 6/1 Strand “Penguin” ACSR – Str. New T4 to Str. 556626
CONTRACTOR TO MATCH EXISTING CONDUCTOR TENSIONS USING STANDARD PRACTICES
Sheet 9 6/30/2023 Sheet 9 of 10
3/8” 7 strand HS Steel Shield Wire – Str. 556626 Ahead Span
CONTRACTOR TO MATCH EXISTING STATIC TENSIONS USING STANDARD PRACTICES
Sheet 10 6/30/2023 Sheet 10 of 10
2 AWG 6/1 Strand “Sparrow” ACSR – Str. 613702 to Str. NEW D1
Section #15 from structure #613702 - MOD to structure #NEW D1, start set #10 '', end set #10 ''
Cable 'C:\projects\CRIP Canal\PLS\Cable\sparrow_acsr - 200.wir', Ruling span (ft) 113.769
Sagging data: Catenary (ft) 328.587, Horiz. Tension (lbs) 30 Condition I Temperature (deg F) 60
Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
115.0 4.98 5.03 5.10 5.14 5.17 5.20 5.23 5.27 5.30 613702 - MOD -17.18
Time Time Time Time Time Time Time Time Time Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
115.0 6.67 6.71 6.76 6.78 6.80 6.82 6.84 6.86 6.88 613702 - MOD -17.18
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
31 30 30 30 30 29 29 29 29
Sheet 11 6/30/2023 Sheet 11 of 10
2 AWG 6/1 Strand “Sparrow” ACSR – Str. 613702 to Str. NEW D1
Section #9 from structure #613702 - MOD to structure #NEW D1, start set #8 '', end set #8 ''
Cable 'C:\projects\CRIP Canal\PLS\Cable\sparrow_acsr - 200.wir', Ruling span (ft) 113.777
Sagging data: Catenary (ft) 328.587, Horiz. Tension (lbs) 30 Condition I Temperature (deg F) 60
Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
115.0 4.98 5.03 5.11 5.14 5.17 5.20 5.24 5.27 5.30 613702 - MOD -17.18
Time Time Time Time Time Time Time Time Time Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
115.0 6.67 6.71 6.76 6.78 6.80 6.82 6.84 6.86 6.89 613702 - MOD -17.18
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
31 30 30 30 30 29 29 29 29
Sheet 12 6/30/2023 Sheet 12 of 10
2 AWG 6/1 Strand “Sparrow” ACSR – Str. New D1 to Str. NEW D2
Section #19 from structure #NEW D1 to structure #NEW D2, start set #11 '', end set #10 ''
Cable 'C:\projects\CRIP Canal\PLS\Cable\sparrow_acsr - 200.wir', Ruling span (ft) 126.499
Sagging data: Catenary (ft) 427.163, Horiz. Tension (lbs) 39 Condition I Temperature (deg F) 60
Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
127.5 4.67 4.74 4.81 4.87 4.93 4.97 5.01 5.05 5.09 NEW D1 16.18
Time Time Time Time Time Time Time Time Time Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
127.5 6.46 6.51 6.56 6.60 6.64 6.67 6.69 6.72 6.74 NEW D1 16.18
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
40 40 39 38 38 38 37 37 37
Sheet 13 6/30/2023 Sheet 13 of 10
2 AWG 6/1 Strand “Sparrow” ACSR – Str. New D1 to Str. NEW D2
Section #11 from structure #NEW D1 to structure #NEW D2, start set #9 '', end set #9 ''
Cable 'C:\projects\CRIP Canal\PLS\Cable\sparrow_acsr - 200.wir', Ruling span (ft) 126.499
Sagging data: Catenary (ft) 427.163, Horiz. Tension (lbs) 39 Condition I Temperature (deg F) 60
Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
127.5 4.67 4.74 4.81 4.87 4.93 4.97 5.01 5.05 5.09 NEW D1 16.18
Time Time Time Time Time Time Time Time Time Number Projection
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
127.5 6.46 6.51 6.56 6.60 6.64 6.67 6.69 6.72 6.74 NEW D1 16.18
40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F
40 40 39 38 38 38 37 37 37
06 – TRANSMISSION LINE
3'-0" 20'-0" 3'-0"
3' -0
3'
-0
3' -0
4'-6"7'-6"
GROUND GRID
PLAN ELEVATION
G18B
G18B
G16B
G16C
6"
6" G16B
G16C
DETAIL GB
TYPICAL GROUND MAT
GROUNDED SWITCH MAT
(1 REQ'D)
SCALE:NONE
G10B
DETAIL GC
G16A
G10D
G10E G11
TYPICAL MAN GATE
(2 REQ'D)
SCALE:NONE
TYP.
G16A
G12B
BARBED WIRE
DETAIL GEDETAIL GD
G16A
TYPICAL CORNER POST CONNECTION
(4 REQ'D)
SCALE:NONE
G12A
G12A
CONNECTED WIRE TO RAZOR WIRE
(8 REQ'D)
SCALE:NONE
G13A
G16A
G12A
4'-6" 7'-6"
3' -0
3 NO.7 CW.
GROUND
CLAMP
GROUND
CLAMP
1.900"O.D. GATE FRAME
7#8 CCS TO
GROUND GRID GROUND CLAMP FOR 2.875"O.D. POST
INSTALL CLAMP ABOVE GRADE
7#8 CCS TO
GROUND GRID
CU. CRIMPIT FOR
7#8 CCS TO 3 NO. 7 CW.
3 NO. 7 CW.
USE 3 SPLIT BOLTS TO
CONNECT 3 NO.7 CW.
TO FABRIC.
CONTINUE TO RAZOR WIRE
SEE DETAIL GE, THIS SHEET
GATE POST SIZE
2.875" O.D.
BRAID
CONTINUE TO RAZOR WIRE
SEE DETAIL GE, THIS SHEET
FENCE CORNER POST
CONTINUE TO RAZOR WIRE
SEE DETAIL GE, THIS SHEET
USE 3 SPLIT BOLTS TO
CONNECT 3 NO.7 CW.
TO FABRIC.
3 NO. 7 CW.
CU. CRIMPIT FOR
7#8 CCS TO 3 NO. 7 CW.
USE 3 SPLIT BOLTS TO
CONNECT 3 NO.7 CW.
TO FABRIC.
7#8 CCS TO
GROUND GRID
G10B
GROUND CLAMP FOR 2.875"O.D. POST
INSTALL CLAMP ABOVE GRADE
UNRAVEL 3 NO.7 CW.
STRANDING TO ATTACH
TO BARBED WIRE
COPPER CRIMPIT
GROUNDING PLAN
SCALE: 1/4" = 1'-0"
'-0
FLEX
BRAID
7#8 CCS
GROUNDING PIGTAIL
7#8 CCS GROUNDING
PIGTAIL
STRUCTURE
FLEX BRAID
MANUAL OPERATED
SWITCH MECHANISM
4'-0"X4'-0"
GROUND MAT
40% CONDUCTIVITY
#6 AWG COPPERWELD
GROUND MAT ON
EARTH GRADE
ROCK GRADE
EARTH GRADE
4'-0"
4'-0"
DETAIL GD
DETAIL GD
DETAIL GD
DETAIL GD
DETAIL GC
DETAIL GC
DETAIL GB
DETAIL GA
3' -0
M
IN
3' -0
M
IN
10'-0"
MIN
10'-0"
MIN
DETAIL GA
STEEL POLE GROUND
(1 REQ'D)
SCALE:NONE
G18AGROUND CLAMP @
5'-0" SPACING (TYP.)
TO TOP OF POLE
FRONT AND BACK
G13A
G16A
G12A
CU. CRIMPIT FOR
7#8 CCS TO 3 NO. 7 CW.
3 NO. 7 CW.
USE 3 SPLIT BOLTS TO
CONNECT 3 NO.7 CW.
TO FABRIC.
CONTINUE TO RAZOR WIRE
SEE DETAIL GE, THIS SHEET
USE 3 SPLIT BOLTS TO
CONNECT 3 NO.7 CW.
TO FABRIC.
CONTINUE TO RAZOR WIRE
SEE DETAIL GE, THIS SHEET
GATE POST SIZE
2.875" O.D.
G12A
G17A
G17B
GROUND ROD
(TYP. 9 PLACES) G17A G17B
G13A
COMPRESSION
CONNECTOR
(TYP. 32 PLACES)
G13A
COMPRESSION
CONNECTOR G13A
COMPRESSION
CONNECTOR G13A
G18BGROUND CLAMP
G18A
G18BG18B
7#8 CCS G16B
G16B G16B G16B
G18BGROUND CLAMPG18B GROUND CLAMP
7#8 CCS TO
SWITCH MAT
G16B
GROUND ROD 3/4" X 10'-0"
COMPRESSION CONNECTOR
7#8 CCS GROUND WIRE
LEGEND
69kV T-Line
Supplier Catalog # Description Units Required
Qty.
CONTRACTOR SUPPLIED #4 CU #4 AWG, Copper Conductor, bare, Solid, Soft Drawn FT AS REQ'D
CONTRACTOR SUPPLIED Screw 1/2" DIA X 3/4" 1/2"-13 X 3/4" Grade 18-8 Stainless Steel Hex Cap Screw EA 14
LINDSEY 3704/150 150LB Weight, Suspension clamp style with eye EA 3
CONTRACTOR SUPPLIED Washer, Lock, 3/4" 3/4" Lock Washer EA 2
CONTRACTOR SUPPLIED Nut, 3/4" 3/4" Nut EA 2
Hubbell S025023S2010 69kV Insulator, Polymer, Y-Clevis-Ball End Fittings EA 21
Hubbell SD112C Aluminum Bolted Strain Clamp, Deadend, 4/0 "Penguin" ACSR EA 21
Hubbell TSC106 Aluminum Trunnion Clamp, range 0.50"-1.06", 0°-15° EA 12
Hubbell AS25BNK Anchor Shackle, 30k EA 31
AFL SAR088 Armor Rod, 3/8" HS EA 1
AFL AAR140 Armor Rod, 4/0 "Penguin", Individual Rods EA 12
HUBBELL 89_ Bolt, 3/4" Machine EA 8
CONTRACTOR SUPPLIED Bolt, Machine, 3/4" BOLT, MACHINE, 3/4" X REQ'D LENGTH EA 2
Hubbell PSSE3412CW Bolt, Shoulder Eye, 3/4" x 12in EA 4
Hubbell MS60N Clamp, Suspension, Cushioned, AGS 3/8" HS EA 1
Hubbell CCEL15506 Clevis Eye Extension Link EA 6
Burndy GRC34 Connector, Ground Rod Clamp, 3/4" EA 17
ACA COPPERWELD Copper Clad Steel, 7#8, 40% Conductivity (NO SUBSTITUTIONS) FT AS REQ'D
Burndy YA4CN Copper Compression Lug, #4 AWG, for 1/2" Stud EA 8
Burndy YA26N Copper Compression Lug, 2/0 AWG, for 1/2" Stud EA 6
PLP GDE-1108 Dead-end Guy Grip, 7/16" EA 16
Hughes Brothers 2817R4.5-13-15 Deadend Tee, Cuved Back EA 2
Hubbell SWDE55N Deadend, Bolted 3/8" HS Steel EA 9
Hughes Brothers RW2-80 Flat Washer, Round 7/8" DIA, Galvanized EA 40
Southern C341013 Ground Rod, 3/4" X 10' Solid Steel with Copper Jacket EA 17
PLP PG-5518 Guard, Guy 8' yellow EA 4
HUBBELL GEP6N Guy Attachment Pole Eye Plate EA 4
Hubbell 522006-1102 Insulator, 69kV Horizontal Line Post, Polymer, W/ Gain Base EA 12
HUBBELL 31506 Insulator, guy strain EA 4
Burndy UC8W26L Parallel Clamp, #4 Cu to 3/8" HS Steel EA 17
Hubbell PTR40 Partial Tension Overhead Line Splice EA 9
HUBBELL 12334P ROD, 1" 7', 23,000 LBS EA 4
Hubbell SYC-30 Socket Y-Clevis EA 21
Hughes Brothers B8XX-6 Square Head Bolt, w/ Nut 7/8" X Required Length, Galvanized EA 26
Hughes Brothers MF80 Square Nut, Lock, 7/8" DIA, Galvanized EA 26
CONTRACTOR SUPPLIED Washer, Lock, 1/2" Stainless Steel Lock Washer, For 1/2" Screw EA 14
Hughes Brothers C4484-C14 Steel Davit Arm, Static Support Arm, Transmission EA 1
SOUTHWIRE N/A Strand, 7/16" Galvanized FT As REQ
Cleveland Price Unitized, C26A038-G05 Unitized, Group Operated "V" Switch 69kV, 350kV BIL, 1200A EA 1
HUGHES BROS SW3-70 Washer, Flat, 3" X 3", 3/4" EA 4
Hughes Brothers SLW80 Washer, Split Lock, 7/8" DIA, Galvanized EA 26
Hubbell YCS06 Y-Clevis Eye EA 1
03-01530 or DOUBLE HELIX, 10" or
03-01556 MULI HELIX, 10" X 8"
GS21078CC1 or Insulator, 78" FIBERLASS, STRAIN or
GS21144CC1 INSULATOR, 144", FIBERGLASS, STRAIN
6562 or TWINEYE NUT, 23,000 LBS or
C102-0025 TRIPLEYE ATTACHMENT, 36,000 LBS
12251 or EXTENSION, 1" X 3 1/2', 23,000 LBS Or
12655 EXTENSION, 1 1/2" X 3 1/2', 36,000 LBS
- - 60' CUSTOM STEEL EA 2
- - 70' CUSTOM STEEL EA 1
- - 75' CUSTOM STEEL EA 1
ANDERSON GC-111-8C GROUND CLAMP FOR 2.875" O.D. FENCE POST TO 7#8 STR. CCS. WIRE EA 8
ANDERSON GC-111-6B GROUND CLAMP FOR 1.875" O.D. GATE FRAME TO 3 NO. 7 COPPERWELD EA 2
ANDERSON GC-109-06 GROUND CLAMP FOR 1.875" O.D. GATE FRAME TO FLAT BRAID EA 2
ANDERSON GC-109-08 GROUND CLAMP FOR 2.875" O.D. FENCE POST TO FLAT BRAID EA 2
ANDERSON GB-200-5B FLEXIBLE COPPER BRAID, 24" LONG EA 2
BURNDY FFGC8 SPLIT BOLT FOR CONNECTING 3 NO. 7 COPPERWELD TO #9 GA FENCE FABRIC EA 42
BURNDY KSU17 SPLIT BOLT FOR CONNECTING ONE STRAND OF 3 NO. 7 COPPERWELD TO BARB WIRE EA 42
BURNDY YGHC26C26 COMPRESSION CONNECTOR, COPPER, 1-2/0 AWG(STR), (RUN) & 1-2/0 AWG(STR) (TAP) EA 45
ACA COPPERWELD 3 NO. 7 COPPERWELD WIRE (0.1747 LB/FT) FT 100
ACA COPPERWELD COPPER CLAD STEEL, 7#8, 40% CONDUCTIVITY (NO SUBSTITUTIONS) FT 200
ERICO MT-2-C-48-D-48-A PREFABRICATED SWITCH OPERATOR MAT, 4' X 4' MANUFACTURED FROM #6-40% COPPERWELD ON 6"X6" CENTERS EA 1
TRAVIS 17-159-SS BRONZE GROUND CLAMP FOR ONE CABLE (#4 - 300KCMIL) TO FLAT, WITH STAINLESS STEEL HARDWARE EA 21
TRAVIS 17-164-SS BRONZE GROUND CLAMP FOR TWO CABLES (#4 - 300KCMIL) TO FLAT, WITH STAINLESS STEEL HARDWARE EA 5
HUBBELL EA 4
HUBBELL EA As REQ
Bill of Material-Summary
HUBBELL EA 4
HUBBELL EA 4
2:32 PM
7/7/2023 Stanley Consultants, Inc. 1
Supplier Catalog # Description Units Required Qty.
AFL SAR088 Armor Rod, 3/8" HS EA 1
Hughes Brothers MF80 Square Nut, Lock, 7/8" DIA, Galvanized EA 8
Hughes Brothers SLW80 Washer, Split Lock, 7/8" DIA, Galvanized EA 8
Hughes Brothers RW2-80 Flat Washer, Round 7/8" DIA, Galvanized EA 16
Hughes Brothers B8XX-6 Square Head Bolt, w/ Nut 7/8" X Required Length, Galvanized EA 8
CONTRACTOR SUPPLIED Screw 1/2" DIA X 3/4" 1/2"-13 X 3/4" Grade 18-8 Stainless Steel Hex Cap Screw EA 1
CONTRACTOR SUPPLIED Washer, Lock, 1/2" Stainless Steel Lock Washer, For 1/2" Screw EA 1
Burndy YA4CN Copper Compression Lug, #4 AWG, for 1/2" Stud EA 1
CONTRACTOR SUPPLIED #4 CU #4 AWG, Copper Conductor, bare, Solid, Soft Drawn FT AS REQ'D
Hubbell MS60N Clamp, Suspension, Cushioned, AGS 3/8" HS EA 1
Hubbell YCS06 Y-Clevis Eye EA 1
Hubbell AS25BNK Anchor Shackle, 30k EA 1
Hughes Brothers C4484-C14 Steel Davit Arm, Static Support Arm, Transmission EA 1
Burndy UC8W26L Parallel Clamp, #4 Cu to 3/8" HS Steel EA 1
AFL AAR140 Armor Rod, 4/0 "Penguin", Individual Rods EA 3
Hubbell TSC106 Aluminum Trunnion Clamp, range 0.50"-1.06", 0°-15° EA 3
Hubbell 522006-1102 Insulator, 69kV Horizontal Line Post, Polymer, W/ Gain Base EA 3
Southern C341013 Ground Rod, 3/4" X 10' Solid Steel with Copper Jacket EA 2
Burndy GRC34 Connector, Ground Rod Clamp, 3/4" EA 2
ACA COPPERWELD Copper Clad Steel, 7#8, 40% Conductivity (NO SUBSTITUTIONS) FT AS REQ'D
CONTRACTOR SUPPLIED Screw 1/2" DIA X 3/4" 1/2"-13 X 3/4" Grade 18-8 Stainless Steel Hex Cap Screw EA 2
CONTRACTOR SUPPLIED Washer, Lock, 1/2" Stainless Steel Lock Washer, For 1/2" Screw EA 2
Burndy YA26N Copper Compression Lug, 2/0 AWG, for 1/2" Stud EA 2
- - 70' CUSTOM STEEL EA 1
Bill of Materials for Structures
New T2
Supplier Catalog # Description Units Required
Qty.
CONTRACTOR SUPPLIED Screw 1/2" DIA X 3/4" 1/2"-13 X 3/4" Grade 18-8 Stainless Steel Hex Cap Screw EA 8
CONTRACTOR SUPPLIED Washer, Lock, 1/2" Stainless Steel Lock Washer, For 1/2" Screw EA 8
Burndy YA4CN Copper Compression Lug, #4 AWG, for 1/2" Stud EA 4
CONTRACTOR SUPPLIED #4 CU #4 AWG, Copper Conductor, bare, Solid, Soft Drawn FT AS REQ'D
Hubbell AS25BNK Anchor Shackle, 30k EA 8
Burndy UC8W26L Parallel Clamp, #4 Cu to 3/8" HS Steel EA 6
Hubbell SWDE55N Deadend, Bolted 3/8" HS Steel EA 4
Hubbell PTR40 Partial Tension Overhead Line Splice EA 6
Hubbell SD112C Aluminum Bolted Strain Clamp, Deadend, 4/0 "Penguin" ACSR EA 12
Hubbell SYC-30 Socket Y-Clevis EA 12
Hubbell S025023S2010 69kV Insulator, Polymer, Y-Clevis-Ball End Fittings EA 12
AFL AAR140 Armor Rod, 4/0 "Penguin", Individual Rods EA 6
Hughes Brothers RW2-80 Flat Washer, Round 7/8" DIA, Galvanized EA 24
Hughes Brothers SLW80 Washer, Split Lock, 7/8" DIA, Galvanized EA 12
Hughes Brothers MF80 Square Nut, Lock, 7/8" DIA, Galvanized EA 12
Hughes Brothers B8XX-6 Square Head Bolt, w/ Nut 7/8" X Required Length, Galvanized EA 12
Hubbell TSC106 Aluminum Trunnion Clamp, range 0.50"-1.06", 0°-15° EA 6
Hubbell 522006-1102 Insulator, 69kV Horizontal Line Post, Polymer, W/ Gain Base EA 6
Southern C341013 Ground Rod, 3/4" X 10' Solid Steel with Copper Jacket EA 4
Burndy GRC34 Connector, Ground Rod Clamp, 3/4" EA 4
ACA COPPERWELD Copper Clad Steel, 7#8, 40% Conductivity (NO SUBSTITUTIONS) FT AS REQ'D
Burndy YA26N Copper Compression Lug, 2/0 AWG, for 1/2" Stud EA 4
- - 75' CUSTOM STEEL EA 1
- - 60' CUSTOM STEEL EA 1
NEW T1 and 4
Supplier Catalog # Description Units Required
Qty.
CONTRACTOR SUPPLIED Screw 1/2" DIA X 3/4" 1/2"-13 X 3/4" Grade 18-8 Stainless Steel Hex Cap Screw EA 2
CONTRACTOR SUPPLIED Washer, Lock, 1/2" Stainless Steel Lock Washer, For 1/2" Screw EA 2
Burndy YA4CN Copper Compression Lug, #4 AWG, for 1/2" Stud EA 2
CONTRACTOR SUPPLIED #4 CU #4 AWG, Copper Conductor, bare, Solid, Soft Drawn FT AS REQ'D
Hubbell AS25BNK Anchor Shackle, 30k EA 8
Burndy UC8W26L Parallel Clamp, #4 Cu to 3/8" HS Steel EA 3
Hubbell SWDE55N Deadend, Bolted 3/8" HS Steel EA 2
Hubbell SD112C Aluminum Bolted Strain Clamp, Deadend, 4/0 "Penguin" ACSR EA 6
Hubbell SYC-30 Socket Y-Clevis EA 6
Hubbell S025023S2010 69kV Insulator, Polymer, Y-Clevis-Ball End Fittings EA 6
Cleveland Price Unitized, C26A038-G05 Unitized, Group Operated "V" Switch 69kV, 350kV BIL, 1200A EA 1
- - 60' CUSTOM STEEL EA 1
ANDERSON GC-111-8C GROUND CLAMP FOR 2.875" O.D. FENCE POST TO 7#8 STR. CCS. WIRE EA 8
ANDERSON GC-111-6B GROUND CLAMP FOR 1.875" O.D. GATE FRAME TO 3 NO. 7 COPPERWELD EA 2
ANDERSON GC-109-06 GROUND CLAMP FOR 1.875" O.D. GATE FRAME TO FLAT BRAID EA 2
ANDERSON GC-109-08 GROUND CLAMP FOR 2.875" O.D. FENCE POST TO FLAT BRAID EA 2
ANDERSON GB-200-5B FLEXIBLE COPPER BRAID, 24" LONG EA 2
BURNDY FFGC8 SPLIT BOLT FOR CONNECTING 3 NO. 7 COPPERWELD TO #9 GA FENCE FABRIC EA 42
BURNDY KSU17 SPLIT BOLT FOR CONNECTING ONE STRAND OF 3 NO. 7 COPPERWELD TO BARB WIRE EA 42
BURNDY YGHC26C26 COMPRESSION CONNECTOR, COPPER, 1-2/0 AWG(STR), (RUN) & 1-2/0 AWG(STR) (TAP) EA 45
ACA COPPERWELD 3 NO. 7 COPPERWELD WIRE (0.1747 LB/FT) FT 100
ACA COPPERWELD COPPER CLAD STEEL, 7#8, 40% CONDUCTIVITY (NO SUBSTITUTIONS) FT 200
ERICO MT-2-C-48-D-48-A PREFABRICATED SWITCH OPERATOR MAT, 4' X 4' MANUFACTURED FROM #6-40% COPPERWELD ON 6"X6" CENTERS EA 1
BURNDY GRC34 CONNECTOR, GROUND ROD CLAMP, 3/4" EA 9
SOUTHERN C341013 GROUND ROD, 3/4" X 10'-0" SOLID STEEL W/COPPER JACKET EA 9
TRAVIS 17-159-SS BRONZE GROUND CLAMP FOR ONE CABLE (#4 - 300KCMIL) TO FLAT, WITH STAINLESS STEEL HARDWARE EA 21
TRAVIS 17-164-SS BRONZE GROUND CLAMP FOR TWO CABLES (#4 - 300KCMIL) TO FLAT, WITH STAINLESS STEEL HARDWARE EA 5
NEW T3
CONTRACTOR SUPPLIED Screw 1/2" DIA X 3/4" 1/2"-13 X 3/4" Grade 18-8 Stainless Steel Hex Cap Screw EA 1
CONTRACTOR SUPPLIED Washer, Lock, 1/2" Stainless Steel Lock Washer, For 1/2" Screw EA 1
Burndy YA4CN Copper Compression Lug, #4 AWG, for 1/2" Stud EA 1
CONTRACTOR SUPPLIED #4 CU #4 AWG, Copper Conductor, bare, Solid, Soft Drawn FT AS REQ'D
Hubbell AS25BNK Anchor Shackle, 30k EA 4
Burndy UC8W26L Parallel Clamp, #4 Cu to 3/8" HS Steel EA 2
Hubbell SWDE55N Deadend, Bolted 3/8" HS Steel EA 1
Hubbell PTR40 Partial Tension Overhead Line Splice EA 3
Hubbell SD112C Aluminum Bolted Strain Clamp, Deadend, 4/0 "Penguin" ACSR EA 3
Hubbell SYC-30 Socket Y-Clevis EA 3
Hubbell S025023S2010 69kV Insulator, Polymer, Y-Clevis-Ball End Fittings EA 3
AFL AAR140 Armor Rod, 4/0 "Penguin", Individual Rods EA 3
Hubbell TSC106 Aluminum Trunnion Clamp, range 0.50"-1.06", 0°-15° EA 3
Hubbell 522006-1102 Insulator, 69kV Horizontal Line Post, Polymer, W/ Gain Base EA 3
Hughes Brothers SLW80 Washer, Split Lock, 7/8" DIA, Galvanized EA 6
Hughes Brothers MF80 Square Nut, Lock, 7/8" DIA, Galvanized EA 6
Hughes Brothers B8XX-6 Square Head Bolt, w/ Nut 7/8" X Required Length, Galvanized EA 6
Hubbell PSSE3412CW Bolt, Shoulder Eye, 3/4" x 12in EA 4
Hubbell CCEL15506 Clevis Eye Extension Link EA 6
HUBBELL GEP6N Guy Attachment Pole Eye Plate EA 4
HUBBELL 89_ Bolt, 3/4" Machine EA 8
HUGHES BROS SW3-70 Washer, Flat, 3" X 3", 3/4" EA 4
GS21078CC1 Insulator, 78" FIBERLASS, STRAIN
GS21144CC1 INSULATOR, 144", FIBERGLASS, STRAIN
HUBBELL 31506 Insulator, guy strain EA 4
SOUTHWIRE N/A Strand, 7/16" Galvanized FT As REQ
PLP GDE-1108 Dead-end Guy Grip, 7/16" EA 16
PLP PG-5518 Guard, Guy 8' yellow EA 4
6562 TWINEYE NUT, 23,000 LBS
C102-0025 TRIPLEYE ATTACHMENT, 36,000 LBS
12251 EXTENSION, 1" X 3 1/2', 23,000 LBS OR
12655 EXTENSION, 1 1/2" X 3 1/2', 36,000 LBS
HUBBELL 12334P ROD, 1" 7', 23,000 LBS EA 4
03-01530 DOUBLE HELIX, 10"
03-01556 MULI HELIX, 10" X 8"
HUBBELL EA 4
HUBBELL EA 4
HUBBELL EA As REQ
Bill of Materials for Structures
683754
HUBBELL EA 4
LINDSEY 3704/150 150LB Weight, Suspension clamp style with eye EA 3
CONTRACTOR SUPPLIED #4 CU #4 AWG, Copper Conductor, bare, Solid, Soft Drawn FT AS REQ'D
Hubbell AS25BNK Anchor Shackle, 30k EA 2
Burndy UC8W26L Parallel Clamp, #4 Cu to 3/8" HS Steel EA 5
Hubbell SWDE55N Deadend, Bolted 3/8" HS Steel EA 2
Hughes Brothers 2817R4.5-13-15 Deadend Tee, Curved Back EA 2
CONTRACTOR SUPPLIED Bolt, Machine, 3/4" BOLT, MACHINE, 3/4" X REQ'D LENGTH EA 2
CONTRACTOR SUPPLIED Washer, Lock, 3/4" 3/4" Lock Washer EA 2
CONTRACTOR SUPPLIED Nut, 3/4" 3/4" Nut EA 2
556626
07 – DISTRIBUTION LINE
EX-2
(613702)
SINGLE
SINGLE MOD
FR-4
(NEW D1)
C6.52 SINGLE MOD
10' CROSSARM
NUETRAL UP MOD
MOD
USE C6.52 MOD
FR-5
(NEW D2)
NOTE: STANLEY POINT OF
DELINEATION OCCURS AT TOP
OF STRUCTURE WITH
INSTALLING NEUTRAL AND
CONDUCTOR DEADEND
ATTACHMENTS. DETAIL
PROVIDED FOR INFORMAITON
ONLY
69kV T-Line
Supplier Catalog # Description Units Required
Qty.
BOLT, MACHINE, 1/2" X REQ'D LENGTH EA 16
BOLT, MACHINE, 5/8" X REQ'D LENGTH EA 8
WASHER, ROUND, 1 3/8" EA 16
WASHER, SQUARE, 2 1/4" EA 76
CROSS ARM, 3 5/8" X 4 5/8" X 10'-0" EA 8
INSULATOR, SUSPENSION, 4 1/4" EA 24
BOLT, DOUBLE ARM, 5/8" X REQ'D LENGTH EA 16
BOLT, EYE, 5/8" X REQ'D LENGTH EA 8
CONNECTORS, AS REQ'D EA AS REQ'D
NUT, EYE, 5/8" EA 40
JUMPERS, AS REQ'D EA AS REQ'D
SHACKLE, ANCHOR EA 8
BRACE, WOOD, 60" SPAN EA 8
LOCKNUTS EA 116
INSULATOR, PIN TYPE (12.47kV) EA 2
PIN, CROSSARM STEEL, CLAMP TYPE EA 2
LINK, EXTENSION, INSULATED, 12" MIN EA 2
40ft Class 2 Southern Yellow Pine EA 1
50ft Class 2 Southern Yellow Pine EA 1
Bill of Material-Summary
2:11 PM
12/4/2024 Stanley Consultants, Inc. 1
BOLT, MACHINE, 1/2" X REQ'D LENGTH EA 8
BOLT, MACHINE, 5/8" X REQ'D LENGTH EA 4
WASHER, ROUND, 1 3/8" EA 8
WASHER, SQUARE, 2 1/4" EA 38
CROSS ARM, 3 5/8" X 4 5/8" X 10'-0" EA 4
INSULATOR, SUSPENSION, 4 1/4" EA 12
BOLT, DOUBLE ARM, 5/8" X REQ'D LENGTH EA 8
BOLT, EYE, 5/8" X REQ'D LENGTH EA 4
CONNECTORS, AS REQ'D EA AS REQ'D
NUT, EYE, 5/8" EA 20
JUMPERS, AS REQ'D EA AS REQ'D
SHACKLE, ANCHOR EA 4
BRACE, WOOD, 60" SPAN EA 4
LOCKNUTS EA 58
INSULATOR, PIN TYPE (12.47kV) EA 2
PIN, CROSSARM STEEL, CLAMP TYPE EA 2
LINK, EXTENSION, INSULATED, 12" MIN EA 2
40ft Class 2 Southern Yellow Pine EA 1
New D1
BOLT, MACHINE, 1/2" X REQ'D LENGTH EA 4
BOLT, MACHINE, 5/8" X REQ'D LENGTH EA 2
WASHER, ROUND, 1 3/8" EA 4
WASHER, SQUARE, 2 1/4" EA 19
CROSS ARM, 3 5/8" X 4 5/8" X 10'-0" EA 2
INSULATOR, SUSPENSION, 4 1/4" EA 6
BOLT, DOUBLE ARM, 5/8" X REQ'D LENGTH EA 4
BOLT, EYE, 5/8" X REQ'D LENGTH EA 2
CONNECTORS, AS REQ'D EA AS REQ'D
NUT, EYE, 5/8" EA 10
JUMPERS, AS REQ'D EA AS REQ'D
SHACKLE, ANCHOR EA 2
BRACE, WOOD, 60" SPAN EA 2
LOCKNUTS EA 29
50ft Class 2 Southern Yellow Pine EA 1
New D2
BOLT, MACHINE, 1/2" X REQ'D LENGTH EA 4
BOLT, MACHINE, 5/8" X REQ'D LENGTH EA 2
WASHER, ROUND, 1 3/8" EA 4
WASHER, SQUARE, 2 1/4" EA 19
CROSS ARM, 3 5/8" X 4 5/8" X 10'-0" EA 2
INSULATOR, SUSPENSION, 4 1/4" EA 6
BOLT, DOUBLE ARM, 5/8" X REQ'D LENGTH EA 4
BOLT, EYE, 5/8" X REQ'D LENGTH EA 2
NUT, EYE, 5/8" EA 10
SHACKLE, ANCHOR EA 2
BRACE, WOOD, 60" SPAN EA 2
LOCKNUTS EA 29
Existing 613702
08 - FOUNDATION DRAWINGS
09 – SOIL BORINGS
Report Cover Page
Parker Transmission
Line
Geotechnical Engineering Report
April 26, 2023 | Terracon Project No. 63235018
Prepared for:
Stanley Consultants, Inc.
8501 West Higgins Road, Suite 704
Chicago, Illinois 85705
355 S Euclid Ave, Ste. 107
Tucson, Arizona 85719
P (520) 770-1789
Terracon.com
Facilities | Environmental | Geotechnical | Materials
Report Cover Letter to Sign
April 26, 2023
Stanley Consultants, Inc.
8501 West Higgins Road, Suite 704
Chicago, Illinois 85705
Attn: Ms. Kym Chudomel, PE
P: (773) 714-2031
E: ChudomelKym@stanleygroup.com
Re: Geotechnical Engineering Report
Parker Transmission Line
Colorado River Indian Reservation
Indian School Road
Morgantown, Arizona
Terracon Project No. 63235018
Dear Ms. Chudomel:
We have completed the scope of Geotechnical Engineering services for the above referenced project in general accordance with Terracon Proposal No. P63235018 dated
February 27, 2023. This report presents the findings of the subsurface exploration and provides geotechnical engineering recommendations concerning the design and construction of foundations for the proposed project.
We appreciate the opportunity to be of service to you on this project. Please contact us if you have any questions concerning this report or if we may be of further service.
Sincerely, Terracon
Louis D. Braun, P.E. Donald R. Clark, P.E.
Geotechnical Group Manager Sr. Consultant/Sr. Principal
Geotechnical Engineering Report
Parker Transmission Line | Morgantown, Arizona
Table of Contents Page Number
Introduction
Project Description
Site Conditions
Geotechnical Characterization
Geology
Subsurface Conditions
Groundwater Conditions
Seismic Site Class
Seismic Considerations and Liquefaction
Corrosivity
Geotechnical Overview
Deep Foundations
Design Recommendations
Drilled Shaft Construction Recommendations
General Comments
Figures
Attachments
Exploration and Testing Procedures Site Location and Exploration Plans
Exploration and Laboratory Results
Supporting Information
Note: This report was originally delivered in a web-based format. Blue Bold text in the report indicates a referenced section heading. The PDF version also includes hyperlinks which direct the reader to that section and clicking on the logo will bring you back to this page. For more interactive features, please view your project online at client.terracon.com. Refer to each individual Attachment for a listing of contents.
http://client.terracon.com/
Facilities | Environmental | Geotechnical | Materials 1
Introduction
This report presents the results of our subsurface exploration and Geotechnical
Engineering services performed for the proposed Parker Transmission Line project located on the Colorado River Indian Reservation in Morgantown, Arizona. The approximate location of the project is shown on the attached Site Location map. The purpose of these services was to provide information and geotechnical engineering recommendations relative to:
■ Subsurface soil conditions
■ Groundwater conditions
■ Seismic site classification per IBC
■ Site preparation and earthwork
■ Foundation design and construction
■ Excavation considerations
The geotechnical engineering Scope of Services for this project included the advancement of three borings (Borings B-1 thru B-3) to depths ranging from approximately 25 to 35 feet below existing site grades, laboratory testing of samples collected from our field exploration, engineering analyses and the preparation of this geotechnical engineering report.
A map showing the boring locations is shown on the attached Exploration Plan. Logs of the borings are included in the Exploration Results section of this report. The results of the laboratory testing performed on soil samples obtained from the site during the field exploration are summarized in part on the boring logs and are provided in graphical and tabular form in the Exploration Results section of this report.
Facilities | Environmental | Geotechnical | Materials 2
Project Description
Our initial understanding of the project was provided in our proposal and our final understanding of the project conditions is as follows:
Item Description
Project
Description
Based on the information provided, we understand the proposed project will include four new transmission line poles for a 69kV
Transmission Line. We understand the poles are planned as steel monopoles to be supported on drilled shaft foundations.
Maximum Loads
(provided)
• Moment = 1,228 ft-k
• Shear = 20 kips
• Axial = 1.2 kips
Grading/Slopes We understand the structures are planned to be at current grade.
Terracon should be notified if any of the above information is inconsistent with the planned construction, especially the grading limits, as modifications to our recommendations may be necessary.
Site Conditions
The following description of site conditions is derived from our site visit in association with the field exploration and our review of publicly available topographic maps.
Item Description
Location
Information
The project alignment is on Colorado River Indian Reservation land and extends from Indian School Road south approximately
1,300 feet southeast on the west side of the Main Canal in
Morgantown, Arizona.
See Site Location for additional site information.
Existing
Improvements
The area along the majority of the alignment is undeveloped, although there are a few areas of cleared and graded roadways, and the Main Canal is located to the west of the alignment.
Current Ground
Cover
The majority of the ground cover along the proposed alignment consists of cleared and graded areas with some areas of moderately dense vegetation.
Existing
Topography
The site is relatively flat, although the site slopes slightly upward nearing the Main Canal.
Facilities | Environmental | Geotechnical | Materials 3
Geotechnical Characterization
Geology
The project area is located in the Basin and Range physiographic province (1Cooley, 1967) of the North American Cordillera (2Stern, et al, 1979) of the southwestern United
States. The Basin and Range Province is defined by wide alluvial valleys and varied topography and is split into five distinct sections; the topography is defined by the features found in the Mexican Highlands and Sonoran Desert sections (3Demsey, 1988).
The southern portion of the Basin and Range province is situated along the southwestern flank of the Colorado Plateau and is bounded by the Sierra Nevada Mountains to the west. Formed during middle and late Tertiary time (100 to 15 million years ago), the
Basin and Range province is dominated by fault-controlled topography. The topography consists of mountain ranges and relatively flat alluvial valleys. Typically, the ranges in this area are of a small areal extent but protrude significantly above adjacent wide alluvial plains and valleys. These mountain ranges and valleys have evolved from generally complex movements and associated erosional and depositional processes.
Dominant features in the province consist of:
Feature Description
Pediments Gently dipping slopes formed due to an underlying rock erosional surface
Alluvial fans Sediments deposited in outwash plains at areas of low water velocity
Bajadas Alluvial fans which combine at the base of mountains
Inselbergs Isolated hills or mountains, usually that maintain their relief after erosion of surrounding rock
Based on review of U.S. Geological Survey (USGS) geological maps, surficial geologic conditions mapped at the site consist of Holocene river alluvium deposits. This is described as unconsolidated to weakly consolidated sand and gravel in river channels and sand, silt, and clay on floodplains. Also includes young terrace deposits fringing floodplains. (0-10 ka).
1 Cooley, M.E., 1967, Arizona Highway Geologic Map, Arizona Geological Society.
2 Stern, C.W., et al, 1979, Geological Evolution of North America, John Wiley & Sons, Santa Barbara, California.
3 Demsey, K, 1988, Geologic map of Quaternary and Upper Tertiary alluvium in the Phoenix North 30’x60’
Quadrangle, Arizona. Arizona Geological Survey, Open File Report 88-17, Map Scale 1:100,000, revised 1990.
Facilities | Environmental | Geotechnical | Materials 4
Subsurface Conditions
We have developed a general characterization of the subsurface conditions based upon our review of the subsurface exploration, laboratory data, geologic setting and our understanding of the project. This characterization, termed GeoModel, forms the basis of our geotechnical engineering calculations and evaluation of the site. Conditions observed at each exploration point are indicated on the individual logs. The individual logs can be found in the Exploration Results and the GeoModel can be found in the Figures attachment of this report.
As part of our analyses, we identified the following model layers within the subsurface profile. For a more detailed view of the model layer depths at each boring location, refer to the GeoModel.
Model
Layer Layer Name General Description
Medium Stiff to Stiff
Clays
Clay soils with variable amounts of silt, sand, and gravel with medium stiff to stiff consistency
Medium Stiff to Stiff
Silts
Silt soils with variable amounts of sand with generally medium stiff to stiff consistency
3 Loose Silty Sand Silty sand soils with variable amounts of gravel with generally loose relative density
Laboratory tests were conducted on selected soil samples and the test results are presented in the Exploration Results section of this report. The results of the laboratory testing indicate the soils across the alignment consist of sandy lean clay with gravel, silty clay with sand, silt with variable amounts of sand, and silty sand with gravel with Unified Soil Classifications of CL, CL-ML, ML, and SM. Laboratory test results indicate the fines within these soils exhibit non-plastic to medium plasticity characteristics.
Two unconfined compressive strength tests were performed on selected soil samples.
The unconfined compression strengths of the fine-grained soils ranged between 539 to
998 psf.
Groundwater Conditions
Groundwater was encountered at each boring location at the time of the field exploration at depths ranging from approximately 6 to 13 feet below the existing ground surface.
These observations represent groundwater conditions at the time of the field exploration and may not be indicative of other times, or at other locations. Groundwater conditions can change with varying seasonal and weather conditions, and other factors
Facilities | Environmental | Geotechnical | Materials 5
Fluctuations in groundwater levels can best be determined by implementation of a groundwater monitoring plan. Such a plan would include installation of groundwater monitoring wells, and periodic measurement of groundwater levels over a sufficient period of time. The possibility of groundwater fluctuations should be considered when developing design and construction plans for the project.
Seismic Site Class
The seismic design requirements for buildings and other structures are based on Seismic
Design Category. Site Classification is required to determine the Seismic Design
Category for a structure. The Site Classification is based on the upper 100 feet of the site profile defined by a weighted average value of either shear wave velocity, standard penetration resistance, or undrained shear strength in accordance with Section 20.4 of
ASCE 7 and the International Building Code (IBC). Based on the soil properties observed at the site and as described on the exploration logs and results, our professional opinion is that a Seismic Site Classification of D be considered for the project. Subsurface explorations at this site were extended to a maximum depth of approximately 35 feet.
The site properties below the boring depth to 100 feet were estimated based on our experience and knowledge of geologic conditions of the general area. Additional deeper borings or geophysical testing may be performed to confirm the conditions below the current boring depth.
Seismic Considerations and Liquefaction
The transmission line alignment is located near Southern California, which is a seismically active area. The type and magnitude of seismic hazards affecting the site are dependent on the distance to causative faults, the intensity, and the magnitude of the seismic event. The distance of the fault zones and the associated maximum credible earthquake that can be produced by nearby seismic events, is calculated using the USGS
Earthquake Hazard Program. Based on this source, the mean Rictor magnitude of any potential earthquake affecting the project site with a return period of 2475 years is on the order of 6.72. The SAF (San Andreas Fault) - Coachella segment, which is located approximately 152 kilometers from the site, is considered to have the most significant effect at the site from a design standpoint with a maximum credible earthquake magnitude of 8.1.
Liquefaction is a mode of ground failure that results from the generation of high pore water pressures during earthquake ground shaking, causing loss of shear strength.
Liquefaction is typically a hazard where loose sandy soils exist below groundwater in an area with significant ground shaking potential during a seismic event.
Facilities | Environmental | Geotechnical | Materials 6
Based on the materials encountered at the project site, subsurface materials encountered at Boring B-1 predominantly consist of non-liquefiable fine-grained soils in the upper 17 to 18 feet and layers of loose to medium dense silty sand to the maximum depth explored at 35 feet below the ground surface (bgs). Groundwater was encountered in the borings during drilling and sampling at a depth of 6 to 13 feet bgs.
Based on groundwater data, the depth to groundwater of 6 feet was used in the analysis for liquefaction. A peak ground acceleration 0.145g and mean earthquake magnitude of
6.72 were used in the analysis for liquefaction at the location of this project.
Liquefaction analysis at Boring B-1 was performed by utilizing the software “LiquefyPro” by CivilTech Software for calculated liquefaction potential and estimated seismically induced settlement. This analysis was based on the soils data from the boring log and laboratory test results. Maximum acceleration was calculated using the Peak Ground
Acceleration (PGAM) as per ASCE 7-10 (Equation 11.8-1).
Liquefaction potential was calculated from the ground surface to a depth of 50 feet bgs extrapolating the information from the final sample. Based on calculation results, seismically-induced settlement of saturated and dry sands is estimated to be between ¼ to ½ inch. Liquefaction potential analysis results can be found in the Figures attachment of this report
Corrosivity
The following table lists the corrosivity test results obtained from samples collected from the boring location. These values may be used to estimate potential corrosive characteristics of the on-site soils with respect to contact with the various underground materials which will be used for project construction. The results of the corrosion testing are presented in Laboratory Results section.
Corrosivity Test Results Summary
Location
Sample
Depth
(feet)
Soil
Description
Soluble
Sulfate
(mg/kg)
Soluble
Chloride
(mg/kg)
Electrical
Resistivity
(Ω-cm) pH
B-1 0 – 5 Sandy Lean Clay with Gravel 2,500 1,700 170 7.9
B-3 0 - 5 Silt with Sand 3,300 4,800 38 7.8
Results of soluble sulfate testing indicate that samples of the on-site soils tested classify as S2 according to Table 19.3.1.1 of Section 318 of the American Concrete Institute
(ACI) Building Code Requirements…