Attachment D - 01 General Drawing Sheets Bldg 72.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24623B0045
About this file
This package includes construction drawings and specifications for a build out of Building 72 at the Fayetteville VA Medical Center to create a Community Living Center. The drawings show the existing conditions of the building, demolition plans, life safety plans, architectural, mechanical, plumbing, fire protection, electrical, low voltage, and interior design plans. Relevant details include constructing a 10-bed healthcare facility totaling 8,857 square feet, with occupancy classifications of healthcare, patient sleeping, incidental storage, and incidental business. Fire protection includes a fully sprinklered NFPA Type II construction building. The related federal contract opportunity is solicitation number 36C24623B0045 for the Z2DZ--Build out Community Living Center Building 72 Project No: 565-21-103, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BLDG 72 CLC
FAYETTEVILLE VA MEDICAL CENTER
PROJECT NO: 565-21-103
BUILD OUT COMMUNITY LIVING CENTER
BUILDING 72
ISSUED FOR CONSTRUCTION
FAYETTEVILLE VA
MEDICAL CENTER PROJECT TEAM
OWNER
ARCHITECTURAL / FIRE PROTECTION / MECHANICAL / PLUMBING / ELECTRICAL
SITE MAP
LOCATION MAP
G001
COVER SHEET
FULLY SPRINKLERED
BUILD OUT BUILDING 72
COMMUNITY LIVING CENTER
FAYETTEVILLE, NC
565-21-103
B72
MCR POD
FAYETTEVILLE, NORTH CAROLINA
ALLIANCE WSP JV
1635 PRINCE STREET
ALEXANDRIA, VA 22314
277 BENDIX ROAD, SUITE 300
VIRGINIA BEACH, VA 23452
VETERANS AFFAIRS MEDICAL CENTER
FAYETTEVILLE, NORTH CAROLINA
2300 RAMSEY ST
FAYETTEVILLE, NC 28301
211B W. 7th Street Richmond, VA, 23224
Cornerstone Architecture & Interior Design Interior Design:
Alliance WSP JV 1635 Prince Street Alexandria, VA 22314 277 Bendix Road, Suite 300 Virginia Beach, VA 23452
INTERIOR DESIGN
CORNERSTONE ARCHITECTURE &
INTERIOR DESIGN
211B W. 7th Street Richmond, VA, 23224
SHEET INDEX
SHEET NO. DWG NO. DRAWING TITLE
GENERAL
1 G001 COVER SHEET
LIFE SAFETY
2 CJ101 CONSTRUCTION STAGING PLAN
3 G101 LIFE SAFETY ANALYSIS
4 G201 FIRST FLOOR - LIFE SAFETY PLAN
ARCHITECTURAL
5 A001 ARCH NOTES DETAILS ABBR AND LEGENDS
6 AJ101 EXISTING CONDITIONS FIRST FLOOR PLAN
7 AJ102 EXISTING MECHANICAL PLATFORM PLAN
8 AJ103 EXISTING CONDITIONS ROOF PLAN
9 AE101 FIRST FLOOR PLAN- ANNOTATION
10 AE101A FIRST FLOOR PLAN DIMENSIONS
11 AE102 MECHANICAL PLATFORM PLANS
12 AE301 BUILDING SECTIONS
13 AE401 ENLARGED PLANS
14 AE402 ENLARGED PLANS
15 AE403 INTERIOR ELEVATIONS
16 AE404 INTERIOR ELEVATIONS
17 AE405 INTERIOR ELEVATIONS
18 AE406 INTERIOR ELEVATIONS
19 AE501 CASEWORK DETAILS
20 AE502 CASEWORK DETAILS
21 AE503 INTERIOR PLAN DETAILS
22 AE601 WALL TYPES
23 AE602 DOOR SCHEDULE AND DETAILS
24 AE603 WINDOW SCHEDULE AND DETAILS
25 AE604 EQUIPMENT SCHEDULE
26 AC111 REFLECTED CEILING PLAN
27 AI101 FIRST FLOOR PLAN - SIGNAGE
28 AI102 SIGNAGE DETAILS
INTERIOR DESIGN
29 ID601 ROOM FINISHES SCHEDULE
30 ID602 ROOM FINISHES LEGEND
31 ID701 FINISH PLAN
FIRE PROTECTION
32 FP001 FIRE PROTECTION GENERAL
33 FP002 FIRE ALARM GENERAL
34 FP100 FIRE PROTECTION SITE PLAN (EXIST.)
35 FP101 FIRE SPRINKLER PLAN (EXIST.)
36 FP102 FIRE ALARM SYSTEM (EXIST.)
37 FP200 FIRE PROTECTION PLAN
38 FP300 FIRE ALARM PLAN
MECHANICAL
39 M001 MECHANICAL LEGEND & NOTES
40 MHE101 EXISTING CONDITIONS FIRST FLOOR - HVAC
41 MPE101 EXISTING CONDITIONS - HVAC PIPING
42 MPE102 EXISTING CONDITIONS - HVAC PIPING
43 MHD101 FIRST FLOOR - HVAC DEMOLITION PLAN
44 MPD101 FIRST FLOOR PLAN - HVAC PIPING DEMO
45 MH101 FIRST FLOOR PLAN - HVAC
46 MH102 MEZZANINE PLAN - HVAC
47 MP101 FIRST FLOOR PLAN - HVAC PIPING
48 M501 MECHANICAL DETAILS
49 M502 MECHANICAL DETAILS
50 M601 MECHANICAL SCHEDULES
SHEET NO. DWG NO. DRAWING TITLE
PLUMBING
51 P001 PLUMBING NOTES, ABBR, AND SYMBOLS
52 P002 PLUMBING / MEDICAL GAS SCHEDULE
53 PLE101 EXISTING WASTE AND VENT
54 PLE201 EXISTING WASTE AND VENT RISER
55 PPE101 EXISTING DOMESTIC WATER
56 PPE301 EXISTING DOMESTIC WATER RISER
57 PL101 FIRST FLOOR WASTE AND VENT
58 PL102 MEZZANINE PLAN - PLUMBING
59 PL201 WASTE AND VENT RISER
60 PP101 FIRST FLOOR DOMESTIC WATER
61 PP102 FIRST FLOOR MEDICAL GAS
62 PP301 DOMESTIC WATER RISER
63 PP302 MEDICAL GAS RISER
64 PP401 PLUMBING DETAILS
ELECTRICAL
65 E001 ELECTRICAL NOTES AND LEGENDS
66 EXL101 FIRST FLOOR - LIGHTING - EXISTING
67 EXL102 MEZZANINE PLAN - LIGHTING - EXISTING
68 EXP101 FIRST FLOOR PLAN - POWER - EXISTING
69 EXP102 MEZZANINE PLAN - POWER - EXISTING
70 EL101 FIRST FLOOR PLAN - LIGHTING
71 EL102 MEZZANINE PLAN - LIGHTING
72 EP101 FIRST FLOOR PLAN - POWER
73 EP102 MEZZANINE PLAN - POWER
74 E501 ELECTRICAL RISE R DIAGRAM
75 E601 ELECTRICAL PANEL SCHEDULES
76 E602 ELECTRICAL PANEL SCHEDULES
77 E801 ELECTRICAL LIGHT FIXTURE SCHEDULE
LOW VOLTAGE
78 TY001 LOW VOLTAGE NOTES AND ABBREV
79 TXY101 LOW VOLTAGE PLAN EXISTING
80 TY101 LOW VOLTAGE PLAN
81 TY401 TELECOM ROOM PLAN VIEW AND ELEVATIONS
82 TY501 LOW VOLTAGE STANDARD DETAILS
83 TY502 SECURITY DETAILS
84 TY503 TELECOM DETAILS
85 TY504 NURSE CALL DETAILS
86 TY505 GROUNDING AND BONDING DETAILS
87 TY506 CAMERA MOUNTING DETAILS
88 TY601 TYPICAL DATA TERMINATION DETAIL
89 TY602 PA SYSTEM ONE LINE DIAGRAM
90 TY603 SECURITY PACS-IDS CONNECTION DIAGRAM
91 TY604 VIDEO SURVEILLANCE CONNECTION DETAIL
Project Number
Building Number
Sheet Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
A
B
C
21 4 5 6 7 8
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8
BUILD OUT BUILDING 72
COMMUNITY LIVING CENTER
FAYETTEVILLE, NC
565-21-103
B72 Project Director
OCTOBER 28, 2022Revisions: Date:
D
E
D
E
DWG. ____ OF 91FI
LE
N A
M E:
Z
A W
SP
J
V N
C \2
5.
C om m un ity
L iv in g
C en te r B
\D
ES
IG
N \C ov er
S he et \C
D
C ov er S he et
8.
d w g L
A
YO
UT
N
A M
E:
L ay ou t1 P
LO
TT
ED
: T ue sd ay , O ct ob er
5,
- 1 1:
am
U
SE
R:
p od on ov an
Rev 0 10/28/2022 mrobinson Stamp
LEGEND
TEMPORARY CONSTRUCTION
FENCE/LIMIT OF DISTRUBANCE
B72
EXISTING CONCRETE
AVOID AREA
SILT FENCE
TEMPORARY DIVERSION
STORM INLET PROTECTION
DF DF DF DF
SF SF SF SF
DF DF DF DF
DF DF DF DF DF DF DF
DF DF DF DF DF DF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
B72
MCR BMD
CJ101
CONSTRUCTION
STAGING PLAN
Feet 0 30 60
SCALE: 1" = 30'
CONSTRUCTION STAGING PLAN
GENERAL NOTES:
1. TEMPORARY 8' TALL CHAIN LINK CONSTRUCTION FENCE SHALL BE
SECURED WITH POSTS THAT EXTEND INTO THE GROUND. A PERMANENT
FENCE MAY BE INSTALLED AND THEN REMOVED AT THE END OF THE
CONSTRUCTION PERIOD. SEE SPECIFICATIONS FOR FURTHER DETAIL.
2. CONTRUCTION FENCE SHALL VISIBLY OBSCURE CONSTRUCTION
ACTIVITY FROM VA MEDICAL FACILITY STAFF, PATIENTS, AND VISITORS.
3. LOCATION OF TEMPORARY CONSTRUCTION FENCE SHOWN IS
SCHEMATIC. CONTRACTOR TO CONFIRM FINAL PLACEMENT LOCATION
OF TEMPORARY CONSTRUCTION FENCE WITH VA COR 7 DAYS BEFORE
INSTALLATION.
4. CONTRACTOR SHALL RESTORE THE LANDSCAPING WITHIN THE LOD TO
THE SAME CONDITION PRIOR TO CONSTRUCTION.
5. CONTRACTOR MAY UTILIZE ALL AREA INSIDE THE TEMPORARY
CONSTRUCTION FENCE FOR MATERIAL LAYDOWN. CONTRACTOR WILL
CONTACT VA COR IF MORE AREA IS REQUIRED. FOLLOW NCDOT
CONSTRUCTION ENTRANCE STND. 1607.01. CONTRACTOR SHALL
COORDINATE WITH VA COR FOR LOCATION AND PLACEMENT OF
CONSTRUCTION ENTRANCE.
6. SILT FENCE SHALL FOLLOW NCDOT TEMPORARY SILT FENCE STND.
1605.01
7. TEMPORARY DIVERSION BERM SHALL FOLLOW NCDOT STND.
TEMPORARY DIVERSION 1630.05
8. CONTRACTOR SHALL ADD ROCK INLET SEDIMENT TRAP TYPE C FROM
NCDOT STND. 1632.03 ON INLETS SHOWN ON PLAN AS WELL AS ANY
DOWNSTREAM INLETS NOT SHOWN ON THIS PLAN.
9. CONSTRUCTION DUMPSTER SHALL BE PLACED WITHIN THE LIMIT OF
DISTURBANCE AND CONSTRUCTION FENCE. CONTRACTOR SHALL
COORDINATE WITH VA COR FOR CONSTRUCTION DUMPSTER
LOCATION.
Alliance WSP JV 1635 Prince Street Alexandria, VA 22314 277 Bendix Road, Suite 300 Virginia Beach, VA 23452
Interior Design:
Cornerstone Architecture & Interior Design 211B W. 7th Street Richmond, VA, 23224
EXISTING FLOWER BED
EXISTING FLOWER BED SEE NOTE 8
Project Number
Building Number
Sheet Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
A
B
C
21 4 5 6 7 8
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8
BUILD OUT BUILDING 72
COMMUNITY LIVING CENTER
FAYETTEVILLE, NC
565-21-103
B72 Project Director
OCTOBER 28, 2022Revisions: Date:
D
E
D
E
DWG. ____ OF 91FI
LE
N A
M E:
Z
A W
SP
J
V N
C \2
5.
C om m un ity
L iv in g
C en te r B
\D
ES
IG
N \C
IV
IL
\C J1
.d w g
L A
YO
UT
N A
M E:
L ay ou t1
P
LO
TT
ED
: T hu rs d ay , O ct ob er
7,
- 4 :2
1p m
U
SE
R:
p od on ov an
Rev 0 10/28/2022
Alliance WSP JV 1635 Prince Street Alexandria, VA 22314 277 Bendix Road, Suite 300 Virginia Beach, VA 23452
Interior Design:
Cornerstone Architecture & Interior Design 211B W. 7th Street Richmond, VA, 23224
MCR
INTERIOR FINISHES
CODE / REGULATION
ITEM NFPA 101 CHAPTER 18
WALL AND CEILING
FINISHES - 18.3.3.2 CLASS A
OCCUPANCY TYPE(S) NEW HEALTHCARE
SPRINKLED OR
NON-SPRINKLED FULLY SPRINKLED
CORRIDORS CLASS B OR C
ROOMS AND SPACES CLASS B OR C
OCCUPANCY CLASSIFICATION: NEW HEALTHCARE
10 BED HOME OCCUPANCY LOADING TABLE
OCCUPANCY
CLASSIFICATION
AREA
(S.F.)
OCCUPANCY
LOAD
FACTOR
OCCUPANCY
LOAD
CAPACITY EXIT
DOOR
WIDTH/PERSON
MIN. EGRESS
WIDTH
REQUIRED
(INCH)
HEALTHCARE
0.2 17
PATIENT SLEEPING 5,626 120 47
INCIDENTAL STORAGE 572 500 2
INCIDENTAL BUSINESS 378 100 4
PATIENT ASSEMBLY 1,025 50 23
MECHINICAL 807 100 9
TOTAL 8,408 85
PLUMBING FIXTURE REQUIREMENTS
CODE 2018 INTERNATIONAL
BUILDING CODE
TOTAL
UR
TOTAL
WC
TOTAL
LAV
TOTAL
FOUNTAIN
TOTAL SERV.
SINK
FIRST FLOOR:
MEN'S REQUIRED NA 11 11
1 1
WOMEN'S REQUIRED NA 11 11
*NOTE: PROVIDED FIXTURE REQUIREMENTS ARE BASED ON FIRST FLOOR OCCUPANT LOAD
ONLY (85)
PLUMBING OCCUPANT LOADS
MEN 43
WOMEN 43
TOTAL 86
PROJECT DATA
PROJECT: BUILD OUT BUILDING 72 COMMUNITY LIVING CENTER
DESCRIPTION: COMMUNITY LIVING CENTER
BUILDING AREA: 8,857 S.F.
G101
LIFE SAFETY
ANALYSIS
MCR BMD 3
Project Number
Building Number
Sheet Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
A
B
C
21 4 5 6 7 8
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8
BUILD OUT BUILDING 72
COMMUNITY LIVING CENTER
FAYETTEVILLE, NC
565-21-103
B72 Project Director
OCTOBER 28, 2022Revisions: Date:
D
E
D
E
DWG. ____ OF 91FI
LE
N A
M E:
Z
A W
SP
J
V N
C \2
5.
C om m un ity
L iv in g
C en te r B
\D
ES
IG
N \C
IV
IL
\G
1_
LI
FE
S
A
FE
TY
A
N A
LY
SI
S.
d w g
L A
YO
UT
N A
M E:
L ay ou t1
P
LO
TT
ED
: M on d ay
, O ct ob er
4,
- 3
:5 0p m U
SE
R:
p od on ov an
Rev 0 10/28/2022
CODES & REGULATIONS
AUTHORITY HAVING JURISDICTION CODES AND REGULATIONS
DEPARTMENT OF VETERANS
AFFAIRS 2022 NFPA 10
2022 NFPA 13
2022 NFPA 70
2022 NFPA 72
2022 NFPA 80
2021 NFPA 90A
2021 NFPA 96
2021 NFPA 99
2021 NFPA 101
2021 NFPA 220
2021 NFPA 291
2021 NFPA - LIFE SAFETY CODE
VA FIRE PROTECTION DESIGN MANUAL, 8TH EDITION, JUNE,
UL 300, 1999 EDITION
FIXTURES REQUIREMENTS
PLUMBING FIXTURE RATIOS - STAFF
1 WC PER 25 FOR FIRST 50 OCCUPANTS
1 PER 50 FOR THE REMAINDER
1 LAV PER 40 THE FIRST 80 OCCUPANTS
1 PER 80 FOR THE REMAINDER
1 DRINKING FOUNTAIN PER 100 100 OCCUPANTS
1 SERVICE SINK
PLUMBING FIXTURE RATIOS - PATIENTS
1 WC PER ROOM
1 LAV PER ROOM
1 BATHTUB/SHOWER PER ROOM
1 DRINKING FOUNTAIN PER 100 OCCUPANTS
1 SERVICE SINK
FIRE RESISTIVE RATINGS
CODE/REGULATION ITEM INTERNATIONAL BUILDING CODE - TABLE 601
FIRE RESISTIVE RATING FOR
BUILDING ELEMENTS:
NON-BEARING WALLS:
INTERIOR 2 HOURS OR LESS
OCCUPANCY CLASSIFICATION
NFPA 101 NEW HEALTHCARE (SEE NFPA 101 CHAPTER 18 FOR
REQUIREMENTS
USE SLEEPING DEPARTMETNS, LIMITED CARE FACILITY
SF/PERSON 120
BUILDING DATA
CONSTRUCTION TYPE NFPA TYPE II (000)
SPRINKLERS YES
BUILDING HEIGHT 28'-0"
TOTAL NUMBER OF STORIES 1 (ACCEPTABLE)
EXTERIOR WALL RATING BASED ON
FIRE SEPARATION DISTANCE GREATER THAN 10'
ALLOWABLE BUILDING HEIGHT AND
AREA BASED ON CONSTRUCTION
TYPE / OCCUPANCY
MAX HEIGHT 28' (PROJECT NOT ALTERING EXISTING BLDG
HEIGHT)
PROTECTION REQUIREMENTS - NFPA
CORRIDORS 0-HOUR (SMOKE RESISTANT)
STORAGE 1-HOUR (100 SF AND MORE)
SOILED UTILITY 1-HOUR (64 GAL OR MORE VOLUME)
LAUNDRIES 1-HOUR (GREATER THAN 100SF)
EGRESS / EXIT REQUIREMENTS - NFPA
MAXIMUM TRAVEL DISTANCE HEALTHCARE - 200' SPRINKLERED
MAXIMUM DEAD END HEALTHCARE - 30'
MAXIMUM COMMON PATH OF
TRAVEL
HEALTHCARE - 100' SPRINKLERED (NFPA 101 - 18.2.5.3)
MINIMUM EGRESS DOOR WIDTH 32 INCHES OF CLEAR WIDTH
EXTERIOR WALL RATING BASED ON
FIRE SEPARATION DISTANCE
6' (72 INCHES) (UNLESS OTHERWISE SPECIFIED IN NFPA 101 -
18.2.3.5
FE
C
FE
C
FD
FD
FD
64' TRAVEL DIST.
' T
R
AV
EL
D
IS
T.
36"
42"
72"
34"
' T
O F
EC53' TO FEC
FE
C
' T
O F
EC
SMOKE
COMPARTMENT - 2
2617 SF
FDFD FD FD
FD
FD
FD
FD
FD
FD
FD
COVERED
PORCH
PORCH
PORCH
CO
CO
CO
BEDROOM
BEDROOM
ELEC
146 SOILED
HVAC
LAUNDRY
MECH
IT
CLOSET
MED
SUPPLIES
LIVING
ROOM
DINING
KITCHEN
SUPPLIES
MED
GAS
LINEN
CLOS
ELEC
CLOS
TLT
TLT
123 BEDROOM
BEDROOM
BEDROOM
BARIATRIC
CORRIDOR
BEDROOM
BEDROOM
112ADMIN
VESTIBULE
BREAK
ROOM
BEDROOM
132BEDROOM
COMM
130LINENS
CORRIDOR
ENTRY
FOYER
SOILED
127PANTRY
STOR
TLT
TLT
113STAFF
TLT
TLT
TLT
TLT
TLT
LADDER
TLT
TLT
72"
SMOKE
COMPARTMENT - 1
5064 SF
FE
C
72"
42"
72"
LIFE SAFETY PLAN LEGEND
1-HOUR FIRE RATED BARRIER
W/ 45 MIN 'C' LABEL DOOR
1-HOUR FIRE RATED SMOKE BARRIER
W/ 20 MIN. CORRIDOR DOORS
HEALTHCARE/ DINING -
ASSEMBLY OCCUPANCY
FIRE EXTINGUISHER CABINET
SMOKE RESISTANT
PARTITION NON-RATED
MECHANICAL
TRAVEL DISTANCE TO
AN EXIT
BUILDING EXIT EGRESS
WIDTH (INCHES)
EXIT SIGN
HEALTHCARE OCCUPANCY -
PATIENT SLEEPING
INCIDENTAL STORAGE
INCIDENTAL BUSINESS
TRAVEL DISTANCE TO A
FEC
FEC
50' TRAVEL
DISTANCE
34"
50' TRAVEL
DISTANCE
Alliance WSP JV 1635 Prince Street Alexandria, VA 22314 277 Bendix Road, Suite 300 Virginia Beach, VA 23452
Interior Design:
Cornerstone Architecture & Interior Design 211B W. 7th Street Richmond, VA, 23224
G201
FIRST FLOOR - LIFE SAFETY PLAN
SCALE: 18"=1'-0"
G201
FIRST FLOOR -
LIFE SAFETY PLAN
MCR BMD 4
Notes:
1. CONTRACTOR TO PROVIDE A CLASS K EXTINGUISHER IN THE FEC
2. CONTRACTOR TO PROVIDE AN ABC EXTINGUISHER IN THE FEC
SEE NOTE 2
SEE NOTE 1
Project Number
Building Number
Sheet Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
A
B
C
21 4 5 6 7 8
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8
BUILD OUT BUILDING 72
COMMUNITY LIVING CENTER
FAYETTEVILLE, NC
565-21-103
B72 Project Director
OCTOBER 28, 2022Revisions: Date:
D
E
D
E
DWG. ____ OF 91FI
LE
N A
M E:
Z
A W
SP
J
V N
C \2
5.
C om m un ity
L iv in g
C en te r B
\D
ES
IG
N \C
IV
IL
\G
1_
LI
FE
S
A
FE
TY
P
LA
N
.d w g L
A
YO
UT
N
A M
E:
L ay ou t1 P
LO
TT
ED
: M on d ay , O ct ob er
4,
- 3 :4
9p m
U
SE
R:
p od on ov an
Rev 0 10/28/2022
OCCUPANCY CLASSIFICATION: NEW HEALTHCARE
10 BED HOME OCCUPANCY LOADING TABLE
OCCUPANCY
CLASSIFICATION
AREA
(S.F.)
OCCUPANCY
LOAD
FACTOR
OCCUPANCY
LOAD
CAPACITY EXIT
DOOR
WIDTH/PERSON
MIN. EGRESS
WIDTH
REQUIRED
(INCH)
HEALTHCARE
0.2 17
PATIENT SLEEPING 5,626 120 47
INCIDENTAL STORAGE 572 500 2
INCIDENTAL BUSINESS 378 100 4
PATIENT ASSEMBLY 1,025 50 23
MECHINICAL 807 100 9
TOTAL 8,408 85
| 01 BLDG 72 G001_COVER SHEET |
| Layout1 |
| 02 BLDG 72 CJ101_CONSTRUCTION STAGING PLAN |
| Layout1 |
| 03 BLDG 72 G101_LIFE SAFETY ANALYSIS |
| Layout1 |
| 04 BLDG 72 G201_LIFE SAFETY PLAN |
| Layout1 |