Attachment D - 01 General Drawing Sheets Bldg 72.pdf

PDF 5 MB Posted

Attached to
Z2DZ--Build out Community Living Center Building 72 Project No: 565-21-103
Solicitation number
36C24623B0045
Issued by

About this file

This package includes construction drawings and specifications for a build out of Building 72 at the Fayetteville VA Medical Center to create a Community Living Center. The drawings show the existing conditions of the building, demolition plans, life safety plans, architectural, mechanical, plumbing, fire protection, electrical, low voltage, and interior design plans. Relevant details include constructing a 10-bed healthcare facility totaling 8,857 square feet, with occupancy classifications of healthcare, patient sleeping, incidental storage, and incidental business. Fire protection includes a fully sprinklered NFPA Type II construction building. The related federal contract opportunity is solicitation number 36C24623B0045 for the Z2DZ--Build out Community Living Center Building 72 Project No: 565-21-103, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6.

View the file

Other files

File Type Posted
36C24623B0045 0008.pdf PDF
Questions and Answers Rev 2.docx DOCX document
09 67 23.60 RESINOUS (EPOXY BASE) WITH VINYL CHIP BROADCAST (RES-2) - IFC.pdf PDF
00 01 10 TABLE OF CONTENTS.pdf PDF
00 01 15 List of Drawing Sheets.pdf PDF
36C24623B0045 0007.docx DOCX document
36C24623B0045 0006.docx DOCX document
36C24623B0045 0005.docx DOCX document
Questions and Answers Rev. 1.docx DOCX document
36C24623B0045 0004.docx DOCX document
Site Visit Attendance.pdf PDF
Drawing ID 701 - Finish Plan 1st Floor - Rev. 1 - 11-09-2023.pdf PDF
36C24623B0045 0003.docx DOCX document
Drawing ID 602 - Room Finishes Legend - Rev. 1 - 11-09-2023.pdf PDF
Specification Section 09 67 23.20 - Dated 11-15-23.pdf PDF
Specification Section 09 91 00 - Dated 11-15-23.pdf PDF
Specification Section 12 36 00 - Dated 11-15-23.pdf PDF
Specification Section 09 65 13 - Dated 11-15-23.pdf PDF
Specification Section 10 21 16 - Dated 11-15-23.pdf PDF
Specification Section 10 26 00 - Dated 11-15-23.pdf PDF
Specification Section 09 65 19 - Dated 11-15-23.pdf PDF
Specification Section 09 72 16 - Dated 11-15-23.pdf PDF
Specification Section 12 34 00 - Dated 11-15-23.pdf PDF
Specification Section 10 13 00 - Dated 11-15-23.pdf PDF
Drawing ID 601 - Room Finishes Schedule - Rev. 1 - 11-09-2023.pdf PDF
Specification Section 09 06 00 - Dated 11-15-23.pdf PDF
Specification Section 09 51 00 - Dated 11-15-23.pdf PDF
36C24623B0045 0002.docx DOCX document
36C24623B0045 0001.docx DOCX document
Attachment I - 06 Plumbing Drawing Sheets Bldg 72.pdf PDF
Attachment B - Wage Determination.pdf PDF
Attachment C - Specifications 565-21-103 Build out Bldg 72.pdf PDF
Attachment G - 04 Fire Protection Drawing Sheets Bldg 72.pdf PDF
36C24623B0045_1.docx DOCX document
Attachment E - 02 Architecture Drawing Sheets Bldg 72.pdf PDF
Attachment J - 07 Electrical Drawing Sheets Bldg 72.pdf PDF
Attachment A - Itemized Schedule of Values Cost Breakdown.xlsx XLSX spreadsheet
Attachment H - 05 Mechanical Drawing Sheets Bldg 72.pdf PDF
Attachment K - 08 Low Voltage Drawing Sheets Bldg 72.pdf PDF
Attachment F - 03 Interior Design Drawing Sheets Bldg 72.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BLDG 72 CLC

FAYETTEVILLE VA MEDICAL CENTER

PROJECT NO: 565-21-103

BUILD OUT COMMUNITY LIVING CENTER

BUILDING 72

ISSUED FOR CONSTRUCTION

FAYETTEVILLE VA

MEDICAL CENTER PROJECT TEAM

OWNER

ARCHITECTURAL / FIRE PROTECTION / MECHANICAL / PLUMBING / ELECTRICAL

SITE MAP

LOCATION MAP

G001

COVER SHEET

FULLY SPRINKLERED

BUILD OUT BUILDING 72

COMMUNITY LIVING CENTER

FAYETTEVILLE, NC

565-21-103

B72

MCR POD

FAYETTEVILLE, NORTH CAROLINA

ALLIANCE WSP JV

1635 PRINCE STREET

ALEXANDRIA, VA 22314

277 BENDIX ROAD, SUITE 300

VIRGINIA BEACH, VA 23452

VETERANS AFFAIRS MEDICAL CENTER

FAYETTEVILLE, NORTH CAROLINA

2300 RAMSEY ST

FAYETTEVILLE, NC 28301

211B W. 7th Street Richmond, VA, 23224

Cornerstone Architecture & Interior Design Interior Design:

Alliance WSP JV 1635 Prince Street Alexandria, VA 22314 277 Bendix Road, Suite 300 Virginia Beach, VA 23452

INTERIOR DESIGN

CORNERSTONE ARCHITECTURE &

INTERIOR DESIGN

211B W. 7th Street Richmond, VA, 23224

SHEET INDEX

SHEET NO. DWG NO. DRAWING TITLE

GENERAL

1 G001 COVER SHEET

LIFE SAFETY

2 CJ101 CONSTRUCTION STAGING PLAN

3 G101 LIFE SAFETY ANALYSIS

4 G201 FIRST FLOOR - LIFE SAFETY PLAN

ARCHITECTURAL

5 A001 ARCH NOTES DETAILS ABBR AND LEGENDS

6 AJ101 EXISTING CONDITIONS FIRST FLOOR PLAN

7 AJ102 EXISTING MECHANICAL PLATFORM PLAN

8 AJ103 EXISTING CONDITIONS ROOF PLAN

9 AE101 FIRST FLOOR PLAN- ANNOTATION

10 AE101A FIRST FLOOR PLAN DIMENSIONS

11 AE102 MECHANICAL PLATFORM PLANS

12 AE301 BUILDING SECTIONS

13 AE401 ENLARGED PLANS

14 AE402 ENLARGED PLANS

15 AE403 INTERIOR ELEVATIONS

16 AE404 INTERIOR ELEVATIONS

17 AE405 INTERIOR ELEVATIONS

18 AE406 INTERIOR ELEVATIONS

19 AE501 CASEWORK DETAILS

20 AE502 CASEWORK DETAILS

21 AE503 INTERIOR PLAN DETAILS

22 AE601 WALL TYPES

23 AE602 DOOR SCHEDULE AND DETAILS

24 AE603 WINDOW SCHEDULE AND DETAILS

25 AE604 EQUIPMENT SCHEDULE

26 AC111 REFLECTED CEILING PLAN

27 AI101 FIRST FLOOR PLAN - SIGNAGE

28 AI102 SIGNAGE DETAILS

INTERIOR DESIGN

29 ID601 ROOM FINISHES SCHEDULE

30 ID602 ROOM FINISHES LEGEND

31 ID701 FINISH PLAN

FIRE PROTECTION

32 FP001 FIRE PROTECTION GENERAL

33 FP002 FIRE ALARM GENERAL

34 FP100 FIRE PROTECTION SITE PLAN (EXIST.)

35 FP101 FIRE SPRINKLER PLAN (EXIST.)

36 FP102 FIRE ALARM SYSTEM (EXIST.)

37 FP200 FIRE PROTECTION PLAN

38 FP300 FIRE ALARM PLAN

MECHANICAL

39 M001 MECHANICAL LEGEND & NOTES

40 MHE101 EXISTING CONDITIONS FIRST FLOOR - HVAC

41 MPE101 EXISTING CONDITIONS - HVAC PIPING

42 MPE102 EXISTING CONDITIONS - HVAC PIPING

43 MHD101 FIRST FLOOR - HVAC DEMOLITION PLAN

44 MPD101 FIRST FLOOR PLAN - HVAC PIPING DEMO

45 MH101 FIRST FLOOR PLAN - HVAC

46 MH102 MEZZANINE PLAN - HVAC

47 MP101 FIRST FLOOR PLAN - HVAC PIPING

48 M501 MECHANICAL DETAILS

49 M502 MECHANICAL DETAILS

50 M601 MECHANICAL SCHEDULES

SHEET NO. DWG NO. DRAWING TITLE

PLUMBING

51 P001 PLUMBING NOTES, ABBR, AND SYMBOLS

52 P002 PLUMBING / MEDICAL GAS SCHEDULE

53 PLE101 EXISTING WASTE AND VENT

54 PLE201 EXISTING WASTE AND VENT RISER

55 PPE101 EXISTING DOMESTIC WATER

56 PPE301 EXISTING DOMESTIC WATER RISER

57 PL101 FIRST FLOOR WASTE AND VENT

58 PL102 MEZZANINE PLAN - PLUMBING

59 PL201 WASTE AND VENT RISER

60 PP101 FIRST FLOOR DOMESTIC WATER

61 PP102 FIRST FLOOR MEDICAL GAS

62 PP301 DOMESTIC WATER RISER

63 PP302 MEDICAL GAS RISER

64 PP401 PLUMBING DETAILS

ELECTRICAL

65 E001 ELECTRICAL NOTES AND LEGENDS

66 EXL101 FIRST FLOOR - LIGHTING - EXISTING

67 EXL102 MEZZANINE PLAN - LIGHTING - EXISTING

68 EXP101 FIRST FLOOR PLAN - POWER - EXISTING

69 EXP102 MEZZANINE PLAN - POWER - EXISTING

70 EL101 FIRST FLOOR PLAN - LIGHTING

71 EL102 MEZZANINE PLAN - LIGHTING

72 EP101 FIRST FLOOR PLAN - POWER

73 EP102 MEZZANINE PLAN - POWER

74 E501 ELECTRICAL RISE R DIAGRAM

75 E601 ELECTRICAL PANEL SCHEDULES

76 E602 ELECTRICAL PANEL SCHEDULES

77 E801 ELECTRICAL LIGHT FIXTURE SCHEDULE

LOW VOLTAGE

78 TY001 LOW VOLTAGE NOTES AND ABBREV

79 TXY101 LOW VOLTAGE PLAN EXISTING

80 TY101 LOW VOLTAGE PLAN

81 TY401 TELECOM ROOM PLAN VIEW AND ELEVATIONS

82 TY501 LOW VOLTAGE STANDARD DETAILS

83 TY502 SECURITY DETAILS

84 TY503 TELECOM DETAILS

85 TY504 NURSE CALL DETAILS

86 TY505 GROUNDING AND BONDING DETAILS

87 TY506 CAMERA MOUNTING DETAILS

88 TY601 TYPICAL DATA TERMINATION DETAIL

89 TY602 PA SYSTEM ONE LINE DIAGRAM

90 TY603 SECURITY PACS-IDS CONNECTION DIAGRAM

91 TY604 VIDEO SURVEILLANCE CONNECTION DETAIL

Project Number

Building Number

Sheet Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

A

B

C

21 4 5 6 7 8

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8

BUILD OUT BUILDING 72

COMMUNITY LIVING CENTER

FAYETTEVILLE, NC

565-21-103

B72 Project Director

OCTOBER 28, 2022Revisions: Date:

D

E

D

E

DWG. ____ OF 91FI

LE

N A

M E:

Z

A W

SP

J

V N

C \2

5.

C om m un ity

L iv in g

C en te r B

\D

ES

IG

N \C ov er

S he et \C

D

C ov er S he et

8.

d w g L

A

YO

UT

N

A M

E:

L ay ou t1 P

LO

TT

ED

: T ue sd ay , O ct ob er

5,

- 1 1:

am

U

SE

R:

p od on ov an

Rev 0 10/28/2022 mrobinson Stamp

LEGEND

TEMPORARY CONSTRUCTION

FENCE/LIMIT OF DISTRUBANCE

B72

EXISTING CONCRETE

AVOID AREA

SILT FENCE

TEMPORARY DIVERSION

STORM INLET PROTECTION

DF DF DF DF

SF SF SF SF

DF DF DF DF

DF DF DF DF DF DF DF

DF DF DF DF DF DF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

SF

B72

MCR BMD

CJ101

CONSTRUCTION

STAGING PLAN

Feet 0 30 60

SCALE: 1" = 30'

CONSTRUCTION STAGING PLAN

GENERAL NOTES:

1. TEMPORARY 8' TALL CHAIN LINK CONSTRUCTION FENCE SHALL BE

SECURED WITH POSTS THAT EXTEND INTO THE GROUND. A PERMANENT

FENCE MAY BE INSTALLED AND THEN REMOVED AT THE END OF THE

CONSTRUCTION PERIOD. SEE SPECIFICATIONS FOR FURTHER DETAIL.

2. CONTRUCTION FENCE SHALL VISIBLY OBSCURE CONSTRUCTION

ACTIVITY FROM VA MEDICAL FACILITY STAFF, PATIENTS, AND VISITORS.

3. LOCATION OF TEMPORARY CONSTRUCTION FENCE SHOWN IS

SCHEMATIC. CONTRACTOR TO CONFIRM FINAL PLACEMENT LOCATION

OF TEMPORARY CONSTRUCTION FENCE WITH VA COR 7 DAYS BEFORE

INSTALLATION.

4. CONTRACTOR SHALL RESTORE THE LANDSCAPING WITHIN THE LOD TO

THE SAME CONDITION PRIOR TO CONSTRUCTION.

5. CONTRACTOR MAY UTILIZE ALL AREA INSIDE THE TEMPORARY

CONSTRUCTION FENCE FOR MATERIAL LAYDOWN. CONTRACTOR WILL

CONTACT VA COR IF MORE AREA IS REQUIRED. FOLLOW NCDOT

CONSTRUCTION ENTRANCE STND. 1607.01. CONTRACTOR SHALL

COORDINATE WITH VA COR FOR LOCATION AND PLACEMENT OF

CONSTRUCTION ENTRANCE.

6. SILT FENCE SHALL FOLLOW NCDOT TEMPORARY SILT FENCE STND.

1605.01

7. TEMPORARY DIVERSION BERM SHALL FOLLOW NCDOT STND.

TEMPORARY DIVERSION 1630.05

8. CONTRACTOR SHALL ADD ROCK INLET SEDIMENT TRAP TYPE C FROM

NCDOT STND. 1632.03 ON INLETS SHOWN ON PLAN AS WELL AS ANY

DOWNSTREAM INLETS NOT SHOWN ON THIS PLAN.

9. CONSTRUCTION DUMPSTER SHALL BE PLACED WITHIN THE LIMIT OF

DISTURBANCE AND CONSTRUCTION FENCE. CONTRACTOR SHALL

COORDINATE WITH VA COR FOR CONSTRUCTION DUMPSTER

LOCATION.

Alliance WSP JV 1635 Prince Street Alexandria, VA 22314 277 Bendix Road, Suite 300 Virginia Beach, VA 23452

Interior Design:

Cornerstone Architecture & Interior Design 211B W. 7th Street Richmond, VA, 23224

EXISTING FLOWER BED

EXISTING FLOWER BED SEE NOTE 8

Project Number

Building Number

Sheet Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

A

B

C

21 4 5 6 7 8

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8

BUILD OUT BUILDING 72

COMMUNITY LIVING CENTER

FAYETTEVILLE, NC

565-21-103

B72 Project Director

OCTOBER 28, 2022Revisions: Date:

D

E

D

E

DWG. ____ OF 91FI

LE

N A

M E:

Z

A W

SP

J

V N

C \2

5.

C om m un ity

L iv in g

C en te r B

\D

ES

IG

N \C

IV

IL

\C J1

.d w g

L A

YO

UT

N A

M E:

L ay ou t1

P

LO

TT

ED

: T hu rs d ay , O ct ob er

7,

- 4 :2

1p m

U

SE

R:

p od on ov an

Rev 0 10/28/2022

Alliance WSP JV 1635 Prince Street Alexandria, VA 22314 277 Bendix Road, Suite 300 Virginia Beach, VA 23452

Interior Design:

Cornerstone Architecture & Interior Design 211B W. 7th Street Richmond, VA, 23224

MCR

INTERIOR FINISHES

CODE / REGULATION

ITEM NFPA 101 CHAPTER 18

WALL AND CEILING

FINISHES - 18.3.3.2 CLASS A

OCCUPANCY TYPE(S) NEW HEALTHCARE

SPRINKLED OR

NON-SPRINKLED FULLY SPRINKLED

CORRIDORS CLASS B OR C

ROOMS AND SPACES CLASS B OR C

OCCUPANCY CLASSIFICATION: NEW HEALTHCARE

10 BED HOME OCCUPANCY LOADING TABLE

OCCUPANCY

CLASSIFICATION

AREA

(S.F.)

OCCUPANCY

LOAD

FACTOR

OCCUPANCY

LOAD

CAPACITY EXIT

DOOR

WIDTH/PERSON

MIN. EGRESS

WIDTH

REQUIRED

(INCH)

HEALTHCARE

0.2 17

PATIENT SLEEPING 5,626 120 47

INCIDENTAL STORAGE 572 500 2

INCIDENTAL BUSINESS 378 100 4

PATIENT ASSEMBLY 1,025 50 23

MECHINICAL 807 100 9

TOTAL 8,408 85

PLUMBING FIXTURE REQUIREMENTS

CODE 2018 INTERNATIONAL

BUILDING CODE

TOTAL

UR

TOTAL

WC

TOTAL

LAV

TOTAL

FOUNTAIN

TOTAL SERV.

SINK

FIRST FLOOR:

MEN'S REQUIRED NA 11 11

1 1

WOMEN'S REQUIRED NA 11 11

*NOTE: PROVIDED FIXTURE REQUIREMENTS ARE BASED ON FIRST FLOOR OCCUPANT LOAD

ONLY (85)

PLUMBING OCCUPANT LOADS

MEN 43

WOMEN 43

TOTAL 86

PROJECT DATA

PROJECT: BUILD OUT BUILDING 72 COMMUNITY LIVING CENTER

DESCRIPTION: COMMUNITY LIVING CENTER

BUILDING AREA: 8,857 S.F.

G101

LIFE SAFETY

ANALYSIS

MCR BMD 3

Project Number

Building Number

Sheet Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

A

B

C

21 4 5 6 7 8

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8

BUILD OUT BUILDING 72

COMMUNITY LIVING CENTER

FAYETTEVILLE, NC

565-21-103

B72 Project Director

OCTOBER 28, 2022Revisions: Date:

D

E

D

E

DWG. ____ OF 91FI

LE

N A

M E:

Z

A W

SP

J

V N

C \2

5.

C om m un ity

L iv in g

C en te r B

\D

ES

IG

N \C

IV

IL

\G

1_

LI

FE

S

A

FE

TY

A

N A

LY

SI

S.

d w g

L A

YO

UT

N A

M E:

L ay ou t1

P

LO

TT

ED

: M on d ay

, O ct ob er

4,

- 3

:5 0p m U

SE

R:

p od on ov an

Rev 0 10/28/2022

CODES & REGULATIONS

AUTHORITY HAVING JURISDICTION CODES AND REGULATIONS

DEPARTMENT OF VETERANS

AFFAIRS 2022 NFPA 10

2022 NFPA 13

2022 NFPA 70

2022 NFPA 72

2022 NFPA 80

2021 NFPA 90A

2021 NFPA 96

2021 NFPA 99

2021 NFPA 101

2021 NFPA 220

2021 NFPA 291

2021 NFPA - LIFE SAFETY CODE

VA FIRE PROTECTION DESIGN MANUAL, 8TH EDITION, JUNE,

UL 300, 1999 EDITION

FIXTURES REQUIREMENTS

PLUMBING FIXTURE RATIOS - STAFF

1 WC PER 25 FOR FIRST 50 OCCUPANTS

1 PER 50 FOR THE REMAINDER

1 LAV PER 40 THE FIRST 80 OCCUPANTS

1 PER 80 FOR THE REMAINDER

1 DRINKING FOUNTAIN PER 100 100 OCCUPANTS

1 SERVICE SINK

PLUMBING FIXTURE RATIOS - PATIENTS

1 WC PER ROOM

1 LAV PER ROOM

1 BATHTUB/SHOWER PER ROOM

1 DRINKING FOUNTAIN PER 100 OCCUPANTS

1 SERVICE SINK

FIRE RESISTIVE RATINGS

CODE/REGULATION ITEM INTERNATIONAL BUILDING CODE - TABLE 601

FIRE RESISTIVE RATING FOR

BUILDING ELEMENTS:

NON-BEARING WALLS:

INTERIOR 2 HOURS OR LESS

OCCUPANCY CLASSIFICATION

NFPA 101 NEW HEALTHCARE (SEE NFPA 101 CHAPTER 18 FOR

REQUIREMENTS

USE SLEEPING DEPARTMETNS, LIMITED CARE FACILITY

SF/PERSON 120

BUILDING DATA

CONSTRUCTION TYPE NFPA TYPE II (000)

SPRINKLERS YES

BUILDING HEIGHT 28'-0"

TOTAL NUMBER OF STORIES 1 (ACCEPTABLE)

EXTERIOR WALL RATING BASED ON

FIRE SEPARATION DISTANCE GREATER THAN 10'

ALLOWABLE BUILDING HEIGHT AND

AREA BASED ON CONSTRUCTION

TYPE / OCCUPANCY

MAX HEIGHT 28' (PROJECT NOT ALTERING EXISTING BLDG

HEIGHT)

PROTECTION REQUIREMENTS - NFPA

CORRIDORS 0-HOUR (SMOKE RESISTANT)

STORAGE 1-HOUR (100 SF AND MORE)

SOILED UTILITY 1-HOUR (64 GAL OR MORE VOLUME)

LAUNDRIES 1-HOUR (GREATER THAN 100SF)

EGRESS / EXIT REQUIREMENTS - NFPA

MAXIMUM TRAVEL DISTANCE HEALTHCARE - 200' SPRINKLERED

MAXIMUM DEAD END HEALTHCARE - 30'

MAXIMUM COMMON PATH OF

TRAVEL

HEALTHCARE - 100' SPRINKLERED (NFPA 101 - 18.2.5.3)

MINIMUM EGRESS DOOR WIDTH 32 INCHES OF CLEAR WIDTH

EXTERIOR WALL RATING BASED ON

FIRE SEPARATION DISTANCE

6' (72 INCHES) (UNLESS OTHERWISE SPECIFIED IN NFPA 101 -

18.2.3.5

FE

C

FE

C

FD

FD

FD

64' TRAVEL DIST.

' T

R

AV

EL

D

IS

T.

36"

42"

72"

34"

' T

O F

EC53' TO FEC

FE

C

' T

O F

EC

SMOKE

COMPARTMENT - 2

2617 SF

FDFD FD FD

FD

FD

FD

FD

FD

FD

FD

COVERED

PORCH

PORCH

PORCH

CO

CO

CO

BEDROOM

BEDROOM

ELEC

146 SOILED

HVAC

LAUNDRY

MECH

IT

CLOSET

MED

SUPPLIES

LIVING

ROOM

DINING

KITCHEN

SUPPLIES

MED

GAS

LINEN

CLOS

ELEC

CLOS

TLT

TLT

123 BEDROOM

BEDROOM

BEDROOM

BARIATRIC

CORRIDOR

BEDROOM

BEDROOM

112ADMIN

VESTIBULE

BREAK

ROOM

BEDROOM

132BEDROOM

COMM

130LINENS

CORRIDOR

ENTRY

FOYER

SOILED

127PANTRY

STOR

TLT

TLT

113STAFF

TLT

TLT

TLT

TLT

TLT

LADDER

TLT

TLT

72"

SMOKE

COMPARTMENT - 1

5064 SF

FE

C

72"

42"

72"

LIFE SAFETY PLAN LEGEND

1-HOUR FIRE RATED BARRIER

W/ 45 MIN 'C' LABEL DOOR

1-HOUR FIRE RATED SMOKE BARRIER

W/ 20 MIN. CORRIDOR DOORS

HEALTHCARE/ DINING -

ASSEMBLY OCCUPANCY

FIRE EXTINGUISHER CABINET

SMOKE RESISTANT

PARTITION NON-RATED

MECHANICAL

TRAVEL DISTANCE TO

AN EXIT

BUILDING EXIT EGRESS

WIDTH (INCHES)

EXIT SIGN

HEALTHCARE OCCUPANCY -

PATIENT SLEEPING

INCIDENTAL STORAGE

INCIDENTAL BUSINESS

TRAVEL DISTANCE TO A

FEC

FEC

50' TRAVEL

DISTANCE

34"

50' TRAVEL

DISTANCE

Alliance WSP JV 1635 Prince Street Alexandria, VA 22314 277 Bendix Road, Suite 300 Virginia Beach, VA 23452

Interior Design:

Cornerstone Architecture & Interior Design 211B W. 7th Street Richmond, VA, 23224

G201

FIRST FLOOR - LIFE SAFETY PLAN

SCALE: 18"=1'-0"

G201

FIRST FLOOR -

LIFE SAFETY PLAN

MCR BMD 4

Notes:

1. CONTRACTOR TO PROVIDE A CLASS K EXTINGUISHER IN THE FEC

2. CONTRACTOR TO PROVIDE AN ABC EXTINGUISHER IN THE FEC

SEE NOTE 2

SEE NOTE 1

Project Number

Building Number

Sheet Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

A

B

C

21 4 5 6 7 8

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8

BUILD OUT BUILDING 72

COMMUNITY LIVING CENTER

FAYETTEVILLE, NC

565-21-103

B72 Project Director

OCTOBER 28, 2022Revisions: Date:

D

E

D

E

DWG. ____ OF 91FI

LE

N A

M E:

Z

A W

SP

J

V N

C \2

5.

C om m un ity

L iv in g

C en te r B

\D

ES

IG

N \C

IV

IL

\G

1_

LI

FE

S

A

FE

TY

P

LA

N

.d w g L

A

YO

UT

N

A M

E:

L ay ou t1 P

LO

TT

ED

: M on d ay , O ct ob er

4,

- 3 :4

9p m

U

SE

R:

p od on ov an

Rev 0 10/28/2022

OCCUPANCY CLASSIFICATION: NEW HEALTHCARE

10 BED HOME OCCUPANCY LOADING TABLE

OCCUPANCY

CLASSIFICATION

AREA

(S.F.)

OCCUPANCY

LOAD

FACTOR

OCCUPANCY

LOAD

CAPACITY EXIT

DOOR

WIDTH/PERSON

MIN. EGRESS

WIDTH

REQUIRED

(INCH)

HEALTHCARE

0.2 17

PATIENT SLEEPING 5,626 120 47

INCIDENTAL STORAGE 572 500 2

INCIDENTAL BUSINESS 378 100 4

PATIENT ASSEMBLY 1,025 50 23

MECHINICAL 807 100 9

TOTAL 8,408 85

01 BLDG 72 G001_COVER SHEET
Layout1
02 BLDG 72 CJ101_CONSTRUCTION STAGING PLAN
Layout1
03 BLDG 72 G101_LIFE SAFETY ANALYSIS
Layout1
04 BLDG 72 G201_LIFE SAFETY PLAN
Layout1

File details come from the government source that posted it. Updated .