Attachment 9 - Drawings Electrical - 4 of 8.pdf

PDF 18 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Kansas City, MO (VA-23-00068037)
Solicitation number
36C77623B0066
Issued by

About this file

This document provides details on a federal contract opportunity for infrastructure upgrades at the Veterans Affairs Medical Center in Kansas City, Missouri. The solicitation number is 36C77623B0066 and is being conducted by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The opportunity involves construction services to upgrade the EHRM infrastructure at the Kansas City VA medical facility, as outlined in Attachment 9 of the solicitation documents which provides electrical drawings for the project. Responses to the solicitation are due by the date listed. The awarded contractor will be expected to complete the infrastructure upgrade work at the medical center.

View the file

Other files

File Type Posted
Copy of Attachment 1 - Technical Questions - Responses.xlsx XLSX spreadsheet
36C77623B0066 0002.docx DOCX document
Attachment 1 - Site Visit - Sign-In Sheet - 36C77623B0066 EHRM Infra Upgrade - KC.pdf PDF
36C77623B0066 0001.docx DOCX document
Attachment 11 - Drawings Electrical - 6 of 8.pdf PDF
Attachment 19 - Drawings Telecommunications - 2 of 3.pdf PDF
Attachment 1 - Specifications - DIV 1-13.pdf PDF
Attachment 18 - Drawings Telecommunications - 1 of 3.pdf PDF
Attachment 3 - Drawings Architectural - 1 of 2.pdf PDF
Attachment 16 - Drawings Structural.pdf PDF
Attachment 7 - Drawings Electrical - 2 of 8.pdf PDF
Attachment 13 - Drawings Electrical - 8 of 8.pdf PDF
Attachment 14 - Drawings Environmental.pdf PDF
Attachment 10 - Drawings Electrical - 5 of 8.pdf PDF
Attachment 12 - Drawings Electrical - 7 of 8.pdf PDF
Attachment 22 - Wage Rates - 6-30-23.pdf PDF
Attachment 21 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 23 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 6 - Drawings Electrical - 1 of 8.pdf PDF
Attachment 17 - Drawings Technology.pdf PDF
Attachment 2 - Specifications - DIV 21-32.pdf PDF
Attachment 8 - Drawings Electrical - 3 of 8.pdf PDF
36C77623B0066_1.docx DOCX document
Attachment 20 - Drawings Telecommunications - 3 of 3.pdf PDF
Attachment 5 - Drawings Civil.pdf PDF
Attachment 4 - Drawings Architectural - 2 of 2.pdf PDF
Attachment 15 - Drawings Mechanical.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY

DISCREPANCIES FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,

AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR

TO IMPLEMENTATION.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-

LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE

PURPOSES.

FUTURE FUTURE

FUTURE

40A2P

10KAIC

FUTURE

H1B

L2A3

POWER

FILTER

L1A3

IG

2" CONDUIT WITH

PULLWIRE FROM MDC

TO ELECTRICAL ROOM

#1095, FOR FUTURE

TO

MAMMOGRAPHY

RE E2.4 FOR

CONTINUATION

1"C. W/

PULLWIRE

2500 AMP

BUS

MFM

T

80/2

ELA

80/2

100/3100A 2P N.F.

ELUPS

500AT

600AF

500/3

SGLB

FIRE PROTECTION

WATER PIPE

(1#3/0)3/4"C.

(1#3/0)3/4"C.

70AT

250AF

100/3

SGLB

(1#6)1/2"C.

100%

RATED

2400AT

2500AF

SS

EMERGENCY

BARRIERS

BONDING

JUMPER

COLD

WATER

PIPE

DRIVEN

ROD

RE:7/E2.3

BLDG

STEEL

G

100AT

250AF

100/3

SGLB

N

110AT

250AF

125/3

SGLB

400AT

400AF

400/3

SGLB

ENCL. CB

100AT

200AF

3P

70/3

EHA

50/3

PASSENGER

ELEV.

ML1

100/3

100/3 125/3

SERVICE

ELEV.

FUTURE

ELEV.

30HP

60/3 60A

FRS-R

MH1A1

50/30

LOW

VOLTAGE

RELAY

PANEL

"T1A"

150 KVA

480-120/208V.

3PHASE, 4W.

H1A 40/2 500/3

R1A 60/3

POWER

FILTER

200/3

L1A1 225/3

L1A2

ML2

100/3 MH2A1

R2A

LOW

VOLTAGE

RELAY

PANEL

H2A 110/3

L2A1 60/3

250/3

PWR

SIFTOR #1

CB1

45AT,100AF

10KAIC

TOMO ROOM

RE: 2/E3.2

FOR CONTINUATION

(1#1/0 CU IG)3/4"C.

200/3

SPARE

200/3

SPARES

(3)

L1A4 100/3

L1A5

H2B 110/3

POWER

FILTER

L2A1 100/3

L2B1 60/3

250/3

L2B2

R2B

LOW

VOLTAGE

RELAY

PANEL

RTU 1 RTU 2 RTU 3

M

M M M

"TM2"

30 KVA

480-120/208V/.

3PHASE, 4W.

FUTURE

480 - 120/208V.

3PHASE, 4W. FUTURE

FUTURE

480-120/208V.

3PHASE, 4W.

"T2A"

75KVA

480-120/208V.

3PHASE, 4W.

"T2A"

75KVA

480-120/208V.

3PHASE, 4W.

FUTURE

480-120/208V.

3PHASE, 4W.

50/3

FUTURE

480-120/208V.

3PHASE, 4W.

FUTURE

R1B

LOW

VOLTAGE

RELAY

PANEL

"TMAM"15KVA

480V, 1PHASE PRI.

240V 1PHASE SEC.

PP1

600A, 120/208V, 3PHASE, 4W

10K AIC, FULL NEUTRAL BUS,

FULL LENGTH GROUND BUS

"TXR"

75 KVA

480-480/277V.

3PHASE, 4W.

REFERENCE ELECTRICAL

SITE PLAN FOR LOCATION

UTILITY COMPANY

PAD MOUNTED

TRANSFORMER

480/277V

SECONDARY

"TM1"

30KVA

480-120/208V.

3PHASE, 4W.

"TEA"

30KVA

480-120/208V.

3PHASE, 4W.

120/208V, 1PHASE, 3W.

REFERENCE E3.0

FOR ADDITIONAL

INFORMATION.

10/12

KVA

UPS

MAIN DISTRIBUTION CENTER MDC

277/480V 3PHASE, 4WIRE 2500A,

50kA SYMMETRICAL BRACING WITH 42kA SYMMETRICAL LOWEST

AIC OF INSTALLED DEVICES

7SETS (4-500MCM

IN 3 1/2"C.)

4#1/0, 1#8G

IN 2"C.

4#1/0, 1#6G

IN 2"C.

2 SETS

(4#250

KCMIL,

1#2G IN

3"C.)

2 SETS

(4#3/0, 1#3G IN

2"C.)

400AT

400AF

400/3

SGLB

2500 AMP

BUS

4#2, 1#8 IN

1 1/4"C.

4#2, 1#8 IN

1 1/4"C. 3#8 IN

3/4"C.

3#4 1#4G

IN 1"C.

30HP

60/3 60A

FRS-R

40HP

100/3 90A

FRS-R

3#4, 1#8G

IN 1 1/4"C. 3#2,

1#6G

IN

1 1/4"C.

4#2, 1#8 IN

1 1/4"C. 3#8 IN

3/4"C.

200AT

250AF

200/3

SGLB

400AT

600AF

400/3

SGLB

4#3/0, 1#6G

IN 2"C.

2 SETS

(4#3/0, 1#3G IN

2"C.)

225AT

250AF

225/3

SGLB

110AT

250AF

110/3

SGLB

60AT

250AF

60/3

SGLB

200AT

250AF

200/3

SGLB

400AT

400AF

400/3

SGLB

225AT

250AF

225/3

SGLB

225AT

250AF

225/3

SGLB

225AT

250AF

225/3

SGLB

3P SPACE

(X23)

4#1/0, 1#6G

IN 2"C.

3#2, 1#6G

IN 1 1/4"C.

4#1/0, 1#8G

IN 2"C.

2#8, 1#10G

IN 3/4"C.

2#3, 1#8G

IN 1"C.

4#3/0, 1#6G IN

2"C.

4#2/0, 1#2/0G IN

2"C.

3#2, 1#8G IN

1 1/4"C.

4#250KCMIL, 1#4G

IN 3"C.

4#3, 1#8G

IN 1 1/4"C.4#6, 1#6G

IN 1"C.

4#6, 1#6G

IN 1"C.

3#2, 1#8G IN

1 1/4"C.

4#250KCMIL, 1#4G

IN 3"C.

FUTURE FUTURE

FUTURE FUTURE

REFER TO

MECHANICAL

SCHEDULE

150A/3P 150A/3P

1 1

XFMR "TX-55-TRB"

75kVA Pri: 480/277V Sec: 208/120V

XFMR "TX-55-TRA"

75kVA Pri: 480/277V Sec: 208/120V

PANEL

55-TRB

225A BUS

225A MCB

208/120V

3PH

PANEL

55-TRA

225A BUS

225A MCB

208/120V

3PH

PANEL

55-H2-155B

100A BUS

100A MCB

208/120V

3PH

PANEL

55-H1-173B

100A BUS

100A MCB

208/120V

3PH

PANEL

55-H2-155A

100A BUS

100A MCB

208/120V

3PH

PANEL

55-H1-173A

100A BUS

100A MCB

208/120V

3PH

BLDG 55 BLDG 55 BLDG 55 BLDG 55

55-P-05

55-P-04

AFC = 2,494 A

VD = 2.5%

AFC = 2,687 A

VD = 2.2%

AFC = 2,587 A

VD = 2.3%

AFC = 2,794 A

VD = 2.1%

AFC = 5,689 A

VD = 0.2%55-P-03

AFC = 5,689 A

VD = 0.2%

55-P-0255-P-01

55-P-06 55-P-07 55-P-08

2 2 2 2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

55EP611

BLDG 55 - ONE-LINE DIAGRAM -

REVISED

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY NOTES

- NTS

1 BLDG 55 - ONE-LINE DIAGRAM - REVISED

1 EXISTING PANEL TO BE MODIFIED; PROVIDE CIRCUIT BREAKER TO SUPPLY LOAD AS

SHOWN.

PROVIDE PANEL WITH OVERSIZED LUGS TO ACCOMODATE OVERSIZED FEEDER.

METERING NOTES

Revisions: Date:

ADDENDUM #1 7/19/2023

METERING POINT: REFERENCE ''METERING AND LOAD INFORMATION SCHEDULE

ON SHEET EP702 FOR ADDITIONAL INFORMATION.

5. PROVIDE PULLBOXES AS REQUIRED FOR FEEDER RUNS EXCEEDING 200' OR WHERE

RACEWAY TURNS EXCEED 360-DEGREES; PULLBOXES SHALL BE SIZED PER NEC.

M

K

K

M

PROVIDE KIRK KEY INTERLOCK

BETWEEN UTILITY AND PORTABLE TAP

BOX CIRCUIT BREAKERS.

MAIN DISTRIBUTION

SWITCHBOARD "MSB"

480Y/277V, 3PH, 4W

800A MAIN BUSSING

42,000 AIC

UTILITY

SECTION

MAIN

SECTION0

3P, LSIG

100%

GFR

TVSS

KANSAS CITY POWER &

LIGHT UTILITY METER

UTILITY CO. PAD MOUNTED

TRANSFORMER

500-kVA, 480Y/277V SECONDARY

41,949 AIC FROM UTILITY

F1

REFER TO ELECTRICAL

SITE PLAN

TO BE LOCATED JUST

OUTSIDE MAIN

ELECTRICAL ROOM.

PORTABLE TAP BOX

800A BUSSING

277/480Y, 3PH,4W

NEMA 3R

FIRST FLOOR DATA

ROOM GROUND BUS

WATER

PIPEBUILDING

STEEL

GROUND FLOOR DATA

ROOM GROUND BUS

UFER

GROUND

RODS

"HEQ-1"

F3 F4

TRANSFORMER

TEQ,

112.5-kVA

PRI:480V

SEC:208Y/120

F5

F6

"LEQ-1" F7 "LEQ-2"

F14

"L1"

F15

"L2"

F16

"L3"

F17

"L4"

"LDP"

I-LINE

400 AMP

208/120, 3PH,

4W

"H1"

"HDP-2" "HDP-1"

F2 F8

800A 3P

600A 3P

100A 3P

225A 3P

100A 3P

F11

F9

INVERTER

TRANSFORMER

TLDP, 112.5-kVA

PRI:480V

SEC:208Y/120

F12

F18 BUSSMAN

POWER

MODULE

100 AMP

(FUTURE)

ELEVATOR

30HP

F10 F13

N

G

#2/0 BARE COPPER GRD IN 1"C.

2 SETS OF 4-500KCMIL EACH IN 3 1/2"C.

3 SETS OF 4-300KCMIL, 1#1/0 GRD

EACH IN 3"C.

(4)#1, (1)#8G, 1-1/2"C.

#2/0 BARE COPPER GRD IN 1"C.

#2/0 BARE COPPER GRD IN 1"C.

#1/0 INSULATED COPPER GRD IN 1"C.

#1/0 INSULATED COPPER GRD IN 1"C.

2 SETS OF

4-350KCMIL, 1#1 GRD

EACH IN 3"C. (4)#1, (1)#8G, 1-1/2"C.

(3)#4/0, (1)#4G, 2"C.

2 SETS OF 4#3/0, 1#2 GRD EACH IN 2"C.

#2 BARE COPPER GRD IN 3/4" C.

(4)#4, (1)#10G, 1"C

(2)#12, (1)#12G, 1/2"C.

(3)#4/0, (1)#4G, 2"C.

(4)#1, (1)#8G, 1-1/2"C.

2 SETS OF 4#3/0, 1#2 GRD

EACH IN 2"C.

#2 BARE COPPER

GRD IN 3/4" C.

(4)#1, (1)#8G, 1-1/2"C.

(4)#1/0, (1)#6G, 1-1/2"C

(4)#1, (1)#8G, 1-1/2"C. (4)#1, (1)#8G, 1-1/2"C.

(3)#1, (1)#8G, 1-1/4"C.

20A 3P

UNKNOWN

3P SPACE

(X3)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

56EP601

BLDG 56 - ONE-LINE DIAGRAM -

EXISTING

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY NOTES

- NTS

1 BLDG 56 - ONE-LINE DIAGRAM - EXISTING

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,

AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30-DAYS PRIOR

TO IMPLEMENTATION.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-

LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE

PURPOSES.

1 EXISTING EQUIPMENT TO BE MODIFIED; REFERENCE ASSOCIATED REVISED ONE-LINE

DIAGRAM FOR ADDITIONAL INFORMATION.

METERING NOTES

Revisions: Date: 287 of 512Page 293 of 518

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY

DISCREPANCIES FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,

AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR

TO IMPLEMENTATION.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-

LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE

PURPOSES.

M

K

K

M

PROVIDE KIRK KEY INTERLOCK

BETWEEN UTILITY AND PORTABLE TAP

BOX CIRCUIT BREAKERS.

MAIN DISTRIBUTION

SWITCHBOARD "MSB"

480Y/277V, 3PH, 4W

800A MAIN BUSSING

42,000 AIC

UTILITY

SECTION

MAIN

SECTION0

3P, LSIG

100%

GFR

TVSS

KANSAS CITY POWER &

LIGHT UTILITY METER

UTILITY CO. PAD MOUNTED

TRANSFORMER

500-kVA, 480Y/277V SECONDARY

41,949 AIC FROM UTILITY

F1

TO BE LOCATED JUST

OUTSIDE MAIN

ELECTRICAL ROOM.

PORTABLE TAP BOX

800A BUSSING

277/480Y, 3PH,4W

NEMA 3R

FIRST FLOOR DATA

ROOM GROUND BUS

WATER

PIPEBUILDING

STEEL

GROUND FLOOR DATA

ROOM GROUND BUS

UFER

GROUND

RODS

"HEQ-1"

F3 F4

TRANSFORMER

TEQ,

112.5-kVA

PRI:480V

SEC:208Y/120

F5

F6

"LEQ-1" F7 "LEQ-2"

F14

"L1"

F15

"L2"

F16

"L3"

F17

"L4"

"LDP"

I-LINE

400 AMP

208/120, 3PH,

4W

"H1"

"HDP-2" "HDP-1"

F2 F8

800A 3P

600A 3P

100A 3P

225A 3P

100A 3P

F11

F9

INVERTER

TRANSFORMER

TLDP, 112.5-kVA

PRI:480V

SEC:208Y/120

F12

F18 BUSSMAN

POWER

MODULE

100 AMP

(FUTURE)

F10 F13

N

G

#2/0 BARE COPPER GRD IN 1"C.

2 SETS OF 4-500KCMIL EACH IN 3 1/2"C.

3 SETS OF 4-300KCMIL, 1#1/0 GRD

EACH IN 3"C.

(4)#1, (1)#8G, 1-1/2"C.

#2/0 BARE COPPER GRD IN 1"C.

#2/0 BARE COPPER GRD IN 1"C.

#1/0 INSULATED COPPER GRD IN 1"C.

#1/0 INSULATED COPPER GRD IN 1"C.

2 SETS OF

4-350KCMIL, 1#1 GRD

EACH IN 3"C.

(4)#1, (1)#8G, 1-1/2"C.

(3)#4/0, (1)#4G, 2"C.

2 SETS OF 4#

3/0, 1#2 GRD

EACH IN 2"C.

#2 BARE COPPER GRD IN 3/4" C.

(4)#4, (1)#10G, 1"C

(2)#12, (1)#12G, 1/2"C.

(3)#4/0, (1)#4G, 2"C.

(4)#1, (1)#8G, 1-1/2"C.

2 SETS OF 4#3/0, 1#2 GRD

EACH IN 2"C.

#2 BARE COPPER

GRD IN 3/4" C.

(4)#1, (1)#8G, 1-1/2"C.

(4)#1/0, (1)#6G, 1-1/2"C

(4)#1, (1)#8G, 1-1/2"C.

(4)#1, (1)#8G, 1-1/2"C.

(3)#1, (1)#8G, 1-1/4"C.

REFER TO ELECTRICAL

SITE PLAN

150A/3P 150A/3P

1 1

PANEL

56-TRB

225A BUS

225A MCB

208/120V

3PH

PANEL

56-LG-38A

100A BUS

100A MCB

208/120V

3PH

BLDG 56 BLDG 56 BLDG 56 BLDG 56

PANEL

56-L1-56A

100A BUS

100A MCB

208/120V

3PH

PANEL

56-LG-38B

100A BUS

100A MCB

208/120V

3PH

PANEL

56-L1-56B

100A BUS

100A MCB

208/120V

3PH

PANEL

56-TRA

225A BUS

225A MCB

208/120V

3PH

TRANSFORMER

TX-56-TRB

480-208/120V 75kVA

TRANSFORMER

TX-56-TRA

480-208/120V 75kVA

AFC = 5,156 A

VD = 0.6%

AFC = 5,156 A

VD = 0.6%

AFC = 2,224 A

VD = 3.1%

AFC = 2,121 A

VD = 3.3%

AFC = 2,215 A

VD = 3.1%

AFC = 2,357 A

VD = 2.9%

20A 3P

UNKNOWN

3P SPACE

56-P-01

56-P-02

56-P-03 56-P-04

56-P-05 56-P-06 56-P-07 56-P-08

2 2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

56EP611

BLDG 56 - ONE-LINE DIAGRAM -

REVISED

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY NOTES

1 EXISTING PANEL TO BE MODIFIED; PROVIDE CIRCUIT BREAKER TO SUPPLY LOAD AS

SHOWN.

PROVIDE PANEL WITH OVERSIZED LUGS TO ACCOMODATE OVERSIZED FEEDER.

- NTS

1 BLDG 56 - ONE-LINE DIAGRAM - REVISED

METERING NOTES

Revisions: Date:

ADDENDUM #1 7/19/2023

METERING POINT: REFERENCE ''METERING AND LOAD INFORMATION SCHEDULE

ON SHEET EP702 FOR ADDITIONAL INFORMATION.

2.3% 2.4% 1.8% 2.0%

5. PROVIDE PULLBOXES AS REQUIRED FOR FEEDER RUNS EXCEEDING 200' OR WHERE

RACEWAY TURNS EXCEED 360-DEGREES; PULLBOXES SHALL BE SIZED PER NEC.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP701

BLDG 01 - ELECTRICAL

SCHEDULES

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY NOTES

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN

ANY AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE

TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

3. VOLTAGE DROP INDICATES TOTAL VOLTAGE DROP FROM SOURCE PANEL TO

EQUIPMENT BEING FED.

Revisions: Date:

ADDENDUM #1 7/19/2023

FROM TO QTY SIZE (QTY) & SIZE

GROUND

SIZE

01-P-01A TRANSFORMER "TX-01-ATS5-N" SWITCHBOARD "T8" TRANSFORMER "TX-01-ATS5-N" 3 4" (4) 400 Kcmil 2/0 AWG 1, 2

01-P-01B NORMAL POWER, TRANSFER SWITCH "ATS-5" TRANSFORMER "TX-01-ATS5-N" TRANSFER SWITCH "ATS5" 3 3" (4) 350 Kcmil 1 AWG 1

01-P-02A TRANSFORMER "TX-01-ATS5-E" SWITCHBOARD "28" TRANSFORMER "TX-01-ATS5-E" 2 3" (4) 500 Kcmil 2/0 AWG 1, 2

01-P-02B EMERGENCY POWER, TRANSFER SWITCH "ATS-5" TRANSFORMER "TX-01-ATS5-E" TRANSFER SWITCH "ATS-5" 2 3" (4) 350 Kcmil 1 AWG 1

01-P-03A TRANSFORMER "TX-01-ATS5-LV" TRANSFER SWITCH "ATS-5" TRANSFORMER "TX-01-ATS5-LV" 2 3" (4) 350 Kcmil 1 AWG 1

01-P-03B DISTRIBUTION PANEL "B-B1W-ATS5-LV" TRANSFORMER "TX-01-ATS5-LV" DISTRIBUTION PANEL "B-B1W-ATS5-LV" 2 3" (4) 350 Kcmil 1 AWG -

01-P-04 DISTRIBUTION PANEL "01-DP-TRA" TRANSFER SWITCH "ATS-5" DISTRIBUTION PANEL "01-DP-TRA" 2 2" (4) 3/0 AWG 3 AWG 1

01-P-05A TRANSFORMER "TX-01-MB-305A" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-MB-305A" 1 1-1/4" (4) 4 AWG 6 AWG 1, 2

01-P-05B PANELBOARD "01-MB-305A" TRANSFORMER "TX-01-MB-305A" PANELBOARD "01-MB-305A" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-06A TRANSFORMER "TX-01-M1-392A" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M1-392A" 1 1-1/4" (4) 4 AWG 6 AWG 1, 2

01-P-06A PANELBOARD "01-M1-392A" TRANSFORMER "TX-01-M1-392A" PANELBOARD "01-M1-392A" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-07B TRANSFORMER "TX-01-M2-312A" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M2-312A" 1 1-1/4" (4) 3 AWG 4 AWG 1, 2

01-P-07C PANELBOARD "01-M2-312A" TRANSFORMER "TX-01-M2-312A" PANELBOARD "01-M2-312A" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-08A TRANSFORMER "TX-01-M3-301AA" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M3-301AA" 1 1-1/4" (4) 3 AWG 4 AWG 1, 2

01-P-08B PANELBOARD "01-M3-301AA" TRANSFORMER "TX-01-M3-301AA" PANELBOARD "01-M3-301AA" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-09A TRANSFORMER "TX-01-M4-305AA" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M4-305AA" 1 1-1/4" (4) 2 AWG 3 AWG 1, 2

01-P-09B PANELBOARD "01-M4-305AA" TRANSFORMER "TX-01-M4-305AA" PANELBOARD "01-M4-305AA" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-10A TRANSFORMER "TX-01-M5-305A" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M5-305A" 1 1-1/4" (4) 2 AWG 3 AWG 1, 2

01-P-10B PANELBOARD "01-M5-305A" TRANSFORMER "TX-01-M5-305A" PANELBOARD "01-M5-305A" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-11A TRANSFORMER "TX-01-M6-305A" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M6-305A" 1 1-1/4" (4) 2 AWG 3 AWG 1, 2

01-P-11B PANELBOARD "01-M6-305A" TRANSFORMER "TX-01-M6-305A" PANELBOARD "01-M6-305A" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-12A TRANSFORMER "TX-01-M7-305A" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M7-305A" 1 1-1/2" (4) 1 AWG 2 AWG 1, 2

01-P-12B PANELBOARD "01-M7-305A" TRANSFORMER "TX-01-M7-305A" PANELBOARD "01-M7-305A" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-13A TRANSFORMER "TX-01-M8-305A" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M8-305A" 1 2-1/2" (4) 1/0 AWG 1 AWG 1, 2

01-P-13B PANELBOARD "01-M8-305A" TRANSFORMER "TX-01-M8-305A" PANELBOARD "01-M8-305A" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-14A TRANSFORMER "TX-01-M9-302A" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M9-302A" 1 2-1/2" (4) 1/0 AWG 1 AWG 1, 2

01-P-14B PANELBOARD "01-M9-302A" TRANSFORMER "TX-01-M9-302A" PANELBOARD "01-M9-302A" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-15A TRANSFORMER "TX-01-M10-303A" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M10-303A" 1 2-1/2" (4) 1/0 AWG 1 AWG 1, 2

01-P-15B PANELBOARD "01-M10-303A" TRANSFORMER "TX-01-M10-303A" PANELBOARD "01-M10-303A" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-16A TRANSFORMER "TX-01-M11-303A" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-01-M11-303A" 1 2-1/2" (4) 1/0 AWG 1 AWG 1, 2

01-P-16B PANELBOARD "01-M11-303A" TRANSFORMER "TX-01-M11-303A" PANELBOARD "01-M11-303A" 1 1-1/4" (4) 3 AWG 4 AWG -

01-P-17 DISTRIBUTION PANEL "01-DP-TRB" SWITCHBOARD "T9" DISTRIBUTION PANEL "01-DP-TRB" 3 3" (4) 500 Kcmil 2/0 AWG 1

01-P-18 PANELBOARD "01-MB-305B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-MB-305B" 1 1-1/4" (4) 3 AWG 8 AWG -

01-P-19 PANELBOARD "01-M1-392B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M1-392B" 1 1-1/4" (4) 3 AWG 8 AWG -

01-P-20 PANELBOARD "01-M2-312B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M2-312B" 1 1-1/4" (4) 2 AWG 6 AWG 1

01-P-21 PANELBOARD "01-M3-301AB" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M3-301AB" 1 1-1/4" (4) 2 AWG 6 AWG 1

01-P-22 PANELBOARD "01-M4-305AB" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M4-306AB" 1 2" (4) 2 AWG 6 AWG 1

01-P-23 PANELBOARD "01-M5-305B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M5-305B" 1 2" (4) 1 AWG 4 AWG 1

01-P-24 PANELBOARD "01-M6-305B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M6-305B" 1 2" (4) 1 AWG 4 AWG 1

01-P-25 PANELBOARD "01-M7-305B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M7-305B" 1 2" (4) 1/0 AWG 4 AWG 1

01-P-26 PANELBOARD "01-M8-305B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M8-305B" 1 2" (4) 1/0 AWG 4 AWG 1

01-P-27 PANELBOARD "01-M9-302B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M9-302B" 1 2" (4) 1/0 AWG 4 AWG 1

01-P-28 PANELBOARD "01-M10-303B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M10-303B" 1 2" (4) 1/0 AWG 4 AWG 1

01-P-29 PANELBOARD "01-M11-303B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-M11-303B" 1 2" (4) 1/0 AWG 4 AWG 1

01-P-30A TRANSFORMER "TX-CU-01" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-CU-01" 1 2" (4) 1/0 AWG 6 AWG -

01-P-30B CONDENSING UNIT "01-CU-01-ROOF" TRANSFORMER "TX-CU-01" CONDENSING UNIT "01-CU-01-ROOF" ELECTRICAL PANEL 1 2-1/2" (4) 4/0 AWG 3 AWG 1

01-P-31A TRANSFORMER "TX-CU-02" DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "TX-CU-02" 1 3/4" (3) 8 AWG 10 AWG -

01-P-31B CONDENSING UNIT "01-CU-02-ROOF" TRANSFORMER "TX-CU-02" CONDENSING UNIT "01-CU-02-ROOF" 1 1-1/2" (3) 1 AWG 4 AWG 1

P-TR-1A TYPICAL TELECOM ROOM DATA RACK POWER FEED (1-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG -

P-TR-2A TYPICAL TELECOM ROOM DATA RACK POWER FEED (2-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG -

P-TR-3A TYPICAL TELECOM ROOM DATA RACK POWER FEED (3-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A JUNCTION BOX 1 1" (4) 6 AWG 8 AWG -

P-TR-1B TYPICAL TELECOM ROOM DATA RACK POWER FEED (1-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG -

P-TR-2B TYPICAL TELECOM ROOM DATA RACK POWER FEED (2-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG -

P-TR-3B TYPICAL TELECOM ROOM DATA RACK POWER FEED (3-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B JUNCTION BOX 1 1" (4) 6 AWG 8 AWG -

NOTES

NOTE(S):

2. CONDUIT CONNECTION VIA DISCONNECT.

BLDG 1 - CONDUIT AND WIRE SCHEDULE - VA MO KANSAS CITY EHRM UPGRADES

CONDUIT

TAG

SERVICE

ROUTING CONDUIT CONDUCTORS

1. FEEDER OVERSIZED TO ACCOUNT FOR VOLTAGE DROP.

ELECTRICAL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP702

BLDG 01 - ELECTRICAL

SCHEDULES

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/23

Revisions: Date:

ADDENDUM #1 7/19/2023

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP702

BLDG 01 - ELECTRICAL

SCHEDULES

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/23

GENERAL NOTES

KEY NOTES

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN

ANY AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE

TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Revisions: Date:

ADDENDUM #1 7/19/2023

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP703

BLDG 01 - ELECTRICAL

SCHEDULES

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/23

Revisions: Date:

ADDENDUM #1 7/19/2023

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP703

BLDG 01 - ELECTRICAL

SCHEDULES

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/23

GENERAL NOTES

KEY NOTES

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN

ANY AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE

TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Revisions: Date:

ADDENDUM #1 7/19/2023

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP704

BLDG 01 - ELECTRICAL

SCHEDULES

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/23

Revisions: Date:

ADDENDUM #1 7/19/2023

GENERAL NOTES

KEY NOTES

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN

ANY AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE

TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.