Attachment 13 - Drawings Electrical - 8 of 8.pdf

PDF 6 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Kansas City, MO (VA-23-00068037)
Solicitation number
36C77623B0066
Issued by

About this file

This document contains mechanical equipment schedules and generator capacity information for an electrical infrastructure upgrade project at the Kansas City VA Medical Center. Key details include specifications for over 100 HVAC and cooling units across 8 buildings, ranging from VRV and ductless split systems to larger air handling and chilled water units. Generator capacity is also scheduled, showing the name, rating, test and peak demand data for 5 generators, along with noting the buildings served by added generator loads. The associated federal contract opportunity is for the construction services for the infrastructure upgrades with an estimated value over $5 million.

View the file

Other files

File Type Posted
Copy of Attachment 1 - Technical Questions - Responses.xlsx XLSX spreadsheet
36C77623B0066 0002.docx DOCX document
Attachment 1 - Site Visit - Sign-In Sheet - 36C77623B0066 EHRM Infra Upgrade - KC.pdf PDF
36C77623B0066 0001.docx DOCX document
Attachment 11 - Drawings Electrical - 6 of 8.pdf PDF
Attachment 19 - Drawings Telecommunications - 2 of 3.pdf PDF
Attachment 1 - Specifications - DIV 1-13.pdf PDF
Attachment 18 - Drawings Telecommunications - 1 of 3.pdf PDF
Attachment 3 - Drawings Architectural - 1 of 2.pdf PDF
Attachment 16 - Drawings Structural.pdf PDF
Attachment 7 - Drawings Electrical - 2 of 8.pdf PDF
Attachment 14 - Drawings Environmental.pdf PDF
Attachment 10 - Drawings Electrical - 5 of 8.pdf PDF
Attachment 12 - Drawings Electrical - 7 of 8.pdf PDF
Attachment 22 - Wage Rates - 6-30-23.pdf PDF
Attachment 21 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 9 - Drawings Electrical - 4 of 8.pdf PDF
Attachment 23 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 6 - Drawings Electrical - 1 of 8.pdf PDF
Attachment 17 - Drawings Technology.pdf PDF
Attachment 2 - Specifications - DIV 21-32.pdf PDF
Attachment 8 - Drawings Electrical - 3 of 8.pdf PDF
36C77623B0066_1.docx DOCX document
Attachment 20 - Drawings Telecommunications - 3 of 3.pdf PDF
Attachment 5 - Drawings Civil.pdf PDF
Attachment 4 - Drawings Architectural - 2 of 2.pdf PDF
Attachment 15 - Drawings Mechanical.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

EP701

ELECTRICAL SCHEDULES

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

Revisions: Date:

ADDENDUM #1 7/19/2023

TAG BUILDING NUMBER DESCRIPTION VOLTAGE PHASE HP AMP CONDUIT & WIRE NOTES

55-AC-01-H1-173 55 VRV UNIT - INDOOR UNIT 208 1 - 0.48

55-AC-02-H2-155 55 VRV UNIT - INDOOR UNIT 208 1 - 0.32

55-AC-03-H2-155 55 VRV UNIT - INDOOR UNIT 208 1 - 0.32

55-CU-01-ROOF 55 VRV UNIT - AIR-COOLED CONDENSING UNIT 208 1 - 23.28

05-AC-01-103 05 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.30 1

05-CU-01-103 05 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 14.64

06-AC-01-137A 06 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.37 1

06-AC-02-E11 06 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.37 1

06-CU-01-6-137A 06 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 13.60

06-CU-02-E11 06 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 13.60

15-AHU-01-F1-000 15 AIR HANDLING UNIT - OUTDOOR UNIT 460 3 - 90.40

15-VAV-01-F1-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2

15-VAV-02-F2-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2

15-VAV-03-F3-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2

15-VAV-04-F4-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2

15-VAV-05-F5-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2

15-VAV-06-F6-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2

15-VAV-07-F7-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2

15-VAV-08-F8-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2

26-CHWP-01-V4-610 26 CHILLED WATER BOOSTER PUMP - INDOOR UNIT 460 3 3.0 -

26-AC-01-VB-715A 26 CHILLED WATER FAN COIL UNIT - INDOOR UNIT 208 1 - 2.20

26-AC-02-V2-684 26 CHILLED WATER FAN COIL UNIT - INDOOR UNIT 208 1 - 2.20

26-AC-03-V2-749 26 CHILLED WATER FAN COIL UNIT - INDOOR UNIT 208 1 - 2.20

26-AC-04-V3-734 26 CHILLED WATER FAN COIL UNIT - INDOOR UNIT 208 1 - 2.20

26-AC-05-V5-704 26 CHILLED WATER FAN COIL UNIT - INDOOR UNIT 208 1 - 2.20

40-AC-01-16 40 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.30 1

40-CU-01-16 40 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 14.64

56-AC-01-LG-38 56 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.37 1

56-AC-02-L1-56 56 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.37 1

56-CU-01-ROOF 56 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 13.60

56-CU-02-ROOF 56 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 13.60

NOTES:

1. INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE CONDUIT AND WIRE FROM CONDENSING UNIT TO ASSOCIATED AC UNIT AS REQUIRED PER MANUFACTURER'S INSTRUCTIONS. COORDINATE WITH

MECHANICAL CONTRACTOR AS REQUIRED.

2. PROVIDE (1) 120V CIRCUIT FROM LOCAL PANELBOARD TO POWER STEP DOWN TRANSFORMER PER MANUFACTURER'S INSTRUCTIONS. COORDINATE WITH MECHANICAL ENGINEERING DRAWINGS AND

MECHANICAL CONTRACTOR AS REQUIRED.

MECHANICAL EQUIPMENT SCHEDULE (2 OF 2)

SEE CONDUIT AND WIRE SCHEDULE

ASSOCIATED WIH EACH BUILDING

TAG BUILDING NUMBER DESCRIPTION VOLTAGE PHASE HP AMP CONDUIT & WIRE NOTES

01-AC-01-MB-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-02-MB-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-03-M1-392 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-04-M1-392 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-05-M2-312 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-06-M2-312 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-07-M3-301A 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-08-M3-301A 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-09-M4-305A 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-10-M4-305A 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-11-M5-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-12-M5-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-13-M6-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-14-M6-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-15-M7-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-16-M7-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-17-M8-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-18-M8-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-19-M9-302 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-20-M9-302 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-21-M10-303 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-22-M10-303 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-23-M11-303 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-AC-24-M11-303 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48

01-CU-01-ROOF 01 VRV UNIT - AIR-COOLED CONDENSING UNIT 208 3 - 117.2

01-CU-02-ROOF 01 VRV UNIT - AIR-COOLED CONDENSING UNIT 208 3 - 51.12

02-AC-01-111A 02 VRV UNIT - INDOOR UNIT 208 1 - 0.48

02-AC-02-210 02 VRV UNIT - INDOOR UNIT 208 1 - 0.48

02-CU-01-ROOF 02 VRV UNIT - AIR-COOLED CONDENSING UNIT 208 1 - 23.28

MECHANICAL EQUIPMENT SCHEDULE (1 OF 2)

NOTES:

1. INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE CONDUIT AND WIRE FROM CONDENSING UNIT TO ASSOCIATED AC UNIT AS REQUIRED PER MANUFACTURER'S INSTRUCTIONS. COORDINATE WITH

MECHANICAL CONTRACTOR AS REQUIRED.

SEE CONDUIT AND WIRE SCHEDULE

ASSOCIATED WIH EACH BUILDING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

EP702

ELECTRICAL SCHEDULES

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

Revisions: Date:

ADDENDUM #1 7/19/2023

GENERATOR

NAME

GENERATOR

RATING (KW)

TEST REPORT

DATE

PEAK

RECORDED

DEMAND (kW)

SEASONAL

ADJUSTMENT

FACTOR

NEC

DEMAND

FACTOR

DEMAND

Kw

(w/ NEC

FACTOR)

ADDED

LOAD

(kW)

TOTAL

DEMAND

LOAD (kW)

ESTIMATED GENERATOR

PERCENT LOADING (%) NOTES

Generator 2 175 Mar-22 74.34 1 1.25 92.93 13.4 106.33 60.8% 1

Generator 19 2250 Jun-22 567.00 1 1.25 708.75 19.3 728.05 32.4% 2

Generator 26A 250 Mar-22 77.49 1 1.25 96.86 138.3 235.16 94.1% 3

Generator 26B 400 Sep-22 200.36 1 1.25 250.45 42.9 293.35 73.3% 4

Generator 28 1000 Jul-22 469.91 1 1.25 587.39 143.3 730.69 73.1% 5

4. ADDED LOAD IS COMPRISED OF BUILDINGS: 26

5. ADDED LOAD IS COMPRISED OF BUILDINGS: 1

GENERATOR CAPACITY AND LOAD INFORMATION SCHEDULE

NOTES:

1. ADDED LOAD IS COMPRISED OF BUILDINGS: 2

2. ADDED LOAD IS COMPRISED OF BUILDINGS: 4, 5, 40

3. ADDED LOAD IS COMPRISED OF BUILDINGS: 6, 15

BUILDING EQUIPMENT NAME

EQUIPMENT

VOLTAGE (V) EQUIPMENT PHASE

EQUIPMENT AMP

RATING (A) METERING DATE

METERED

DEMAND (kW) PF ADJUST

METERED

DEMAND

(kVA)

SEASONAL

ADJUSTMENT

FACTOR

NEC DEMAND

FACTOR

DEMAND Kva

(w/ NEC

FACTOR)

ADDED

LOAD

(kVA)

TOTAL

DEMAND

LOAD (kVA)

TOTAL LOAD <= 80% OF

EQUIPMENT RATING NOTES

SWBD T8 208 3PH 4000 TBD - 0.9 - 1 1.25 - 125.7 - - -

SWBD T9 208 3PH 4000 TBD - 0.9 - 1 1.25 - 85.5 - - -

2 MP 208 3PH 1200 TBD - 0.9 - 1 1.25 - 13.4 - - -

BOILER MCC, MAIN 480 3PH 600 JULY 13 2023 91.64 0.788 116.30 1 1.25 145.4 7.2 152.6 YES -

BOILER MCC, BRANCH CIRCUIT CONDUCTOR

FEEDING BUILDING 5

480 3PH -

TBD - 0.9 - 1 1.25 - 4.3 - - -

BOISCIENCE MDP 208 3PH 1000 JULY 13 2023 77.76 0.906 84.9 1 1.25 106.1 29.2 135.3 YES -

EDP BIOSCIENCE 208 3PH 400 JULY 13 2023 53.37 0.877 59.54 1 1.25 74.4 - - YES -

T-B6 (T7), PRIMARY 13200 3PH 9.84 MAY 16 2023 106.3 0.9 118.1 1 1.25 147.6 29.2 176.8 YES 1

15 MSB 480 3PH 3200 MAY 16 2023 - - 871 1 1.25 1088.8 54.6 1143.4 YES 1

26 MSB-26A 208 3PH 1600 MAY 16 2023 162 0.96 168.8 1 1.25 210.9 89.2 300.1 YES 1

40 TRANSFORMER T17, PRIMARY 13200 3PH 3.28 MAY 16 2023 72.9 0.98 74.4 1 1.25 93.0 7.8 100.8 NO 1, 2

55 MDC 480 3PH 2400 MAY 16 2023 - - 427 1 1.25 533.8 28.0 561.8 YES 1

56 MSB 480 3PH 800 MAY 16 2023 158.5 0.9 176 1 1.25 220.1 25.3 245.4 YES 1

1. DATA OBTAINED FROM EQUIPMENT INTEGRAL OR EXTERNAL METER.

2. TRANSFORMER T17 IS A 75kVA TRANSFORMER FEEDING BUILDING 40 AND PANEL GRP. PANEL GRP IS LOADED TO 124% OF IT'S NAMEPLATE RATING. DUE TO OVERLOADING, ELECTRICAL DISTRIBUTION UPSIZED FOR ADDED LOAD. REFER TO SHEET 40EP601 AND 40EP611 FOR ADDITIONAL INFORMATION.

EQUIPMENT METERING AND LOAD INFORMATION SCHEDULE

NOTES: