Attachment 13 - Drawings Electrical - 8 of 8.pdf
PDF 6 MB Posted
- Solicitation number
- 36C77623B0066
About this file
This document contains mechanical equipment schedules and generator capacity information for an electrical infrastructure upgrade project at the Kansas City VA Medical Center. Key details include specifications for over 100 HVAC and cooling units across 8 buildings, ranging from VRV and ductless split systems to larger air handling and chilled water units. Generator capacity is also scheduled, showing the name, rating, test and peak demand data for 5 generators, along with noting the buildings served by added generator loads. The associated federal contract opportunity is for the construction services for the infrastructure upgrades with an estimated value over $5 million.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
EP701
ELECTRICAL SCHEDULES
SJM/WNM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
Revisions: Date:
ADDENDUM #1 7/19/2023
TAG BUILDING NUMBER DESCRIPTION VOLTAGE PHASE HP AMP CONDUIT & WIRE NOTES
55-AC-01-H1-173 55 VRV UNIT - INDOOR UNIT 208 1 - 0.48
55-AC-02-H2-155 55 VRV UNIT - INDOOR UNIT 208 1 - 0.32
55-AC-03-H2-155 55 VRV UNIT - INDOOR UNIT 208 1 - 0.32
55-CU-01-ROOF 55 VRV UNIT - AIR-COOLED CONDENSING UNIT 208 1 - 23.28
05-AC-01-103 05 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.30 1
05-CU-01-103 05 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 14.64
06-AC-01-137A 06 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.37 1
06-AC-02-E11 06 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.37 1
06-CU-01-6-137A 06 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 13.60
06-CU-02-E11 06 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 13.60
15-AHU-01-F1-000 15 AIR HANDLING UNIT - OUTDOOR UNIT 460 3 - 90.40
15-VAV-01-F1-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2
15-VAV-02-F2-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2
15-VAV-03-F3-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2
15-VAV-04-F4-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2
15-VAV-05-F5-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2
15-VAV-06-F6-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2
15-VAV-07-F7-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2
15-VAV-08-F8-000 15 VAV TERMINAL UNIT - INDOOR UNIT SEE NOTE 2 1 - SEE NOTE 2 2
26-CHWP-01-V4-610 26 CHILLED WATER BOOSTER PUMP - INDOOR UNIT 460 3 3.0 -
26-AC-01-VB-715A 26 CHILLED WATER FAN COIL UNIT - INDOOR UNIT 208 1 - 2.20
26-AC-02-V2-684 26 CHILLED WATER FAN COIL UNIT - INDOOR UNIT 208 1 - 2.20
26-AC-03-V2-749 26 CHILLED WATER FAN COIL UNIT - INDOOR UNIT 208 1 - 2.20
26-AC-04-V3-734 26 CHILLED WATER FAN COIL UNIT - INDOOR UNIT 208 1 - 2.20
26-AC-05-V5-704 26 CHILLED WATER FAN COIL UNIT - INDOOR UNIT 208 1 - 2.20
40-AC-01-16 40 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.30 1
40-CU-01-16 40 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 14.64
56-AC-01-LG-38 56 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.37 1
56-AC-02-L1-56 56 DUCTLESS SPLIT COOLING UNIT - INDOOR UNIT 208 1 - 0.37 1
56-CU-01-ROOF 56 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 13.60
56-CU-02-ROOF 56 DUCTLESS SPLIT COOLING UNIT - OUTDOOR UNIT 208 1 - 13.60
NOTES:
1. INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE CONDUIT AND WIRE FROM CONDENSING UNIT TO ASSOCIATED AC UNIT AS REQUIRED PER MANUFACTURER'S INSTRUCTIONS. COORDINATE WITH
MECHANICAL CONTRACTOR AS REQUIRED.
2. PROVIDE (1) 120V CIRCUIT FROM LOCAL PANELBOARD TO POWER STEP DOWN TRANSFORMER PER MANUFACTURER'S INSTRUCTIONS. COORDINATE WITH MECHANICAL ENGINEERING DRAWINGS AND
MECHANICAL CONTRACTOR AS REQUIRED.
MECHANICAL EQUIPMENT SCHEDULE (2 OF 2)
SEE CONDUIT AND WIRE SCHEDULE
ASSOCIATED WIH EACH BUILDING
TAG BUILDING NUMBER DESCRIPTION VOLTAGE PHASE HP AMP CONDUIT & WIRE NOTES
01-AC-01-MB-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-02-MB-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-03-M1-392 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-04-M1-392 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-05-M2-312 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-06-M2-312 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-07-M3-301A 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-08-M3-301A 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-09-M4-305A 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-10-M4-305A 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-11-M5-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-12-M5-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-13-M6-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-14-M6-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-15-M7-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-16-M7-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-17-M8-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-18-M8-305 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-19-M9-302 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-20-M9-302 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-21-M10-303 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-22-M10-303 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-23-M11-303 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-AC-24-M11-303 01 VRV UNIT - INDOOR UNIT 208 1 - 0.48
01-CU-01-ROOF 01 VRV UNIT - AIR-COOLED CONDENSING UNIT 208 3 - 117.2
01-CU-02-ROOF 01 VRV UNIT - AIR-COOLED CONDENSING UNIT 208 3 - 51.12
02-AC-01-111A 02 VRV UNIT - INDOOR UNIT 208 1 - 0.48
02-AC-02-210 02 VRV UNIT - INDOOR UNIT 208 1 - 0.48
02-CU-01-ROOF 02 VRV UNIT - AIR-COOLED CONDENSING UNIT 208 1 - 23.28
MECHANICAL EQUIPMENT SCHEDULE (1 OF 2)
NOTES:
1. INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE CONDUIT AND WIRE FROM CONDENSING UNIT TO ASSOCIATED AC UNIT AS REQUIRED PER MANUFACTURER'S INSTRUCTIONS. COORDINATE WITH
MECHANICAL CONTRACTOR AS REQUIRED.
SEE CONDUIT AND WIRE SCHEDULE
ASSOCIATED WIH EACH BUILDING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
EP702
ELECTRICAL SCHEDULES
SJM/WNM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
Revisions: Date:
ADDENDUM #1 7/19/2023
GENERATOR
NAME
GENERATOR
RATING (KW)
TEST REPORT
DATE
PEAK
RECORDED
DEMAND (kW)
SEASONAL
ADJUSTMENT
FACTOR
NEC
DEMAND
FACTOR
DEMAND
Kw
(w/ NEC
FACTOR)
ADDED
LOAD
(kW)
TOTAL
DEMAND
LOAD (kW)
ESTIMATED GENERATOR
PERCENT LOADING (%) NOTES
Generator 2 175 Mar-22 74.34 1 1.25 92.93 13.4 106.33 60.8% 1
Generator 19 2250 Jun-22 567.00 1 1.25 708.75 19.3 728.05 32.4% 2
Generator 26A 250 Mar-22 77.49 1 1.25 96.86 138.3 235.16 94.1% 3
Generator 26B 400 Sep-22 200.36 1 1.25 250.45 42.9 293.35 73.3% 4
Generator 28 1000 Jul-22 469.91 1 1.25 587.39 143.3 730.69 73.1% 5
4. ADDED LOAD IS COMPRISED OF BUILDINGS: 26
5. ADDED LOAD IS COMPRISED OF BUILDINGS: 1
GENERATOR CAPACITY AND LOAD INFORMATION SCHEDULE
NOTES:
1. ADDED LOAD IS COMPRISED OF BUILDINGS: 2
2. ADDED LOAD IS COMPRISED OF BUILDINGS: 4, 5, 40
3. ADDED LOAD IS COMPRISED OF BUILDINGS: 6, 15
BUILDING EQUIPMENT NAME
EQUIPMENT
VOLTAGE (V) EQUIPMENT PHASE
EQUIPMENT AMP
RATING (A) METERING DATE
METERED
DEMAND (kW) PF ADJUST
METERED
DEMAND
(kVA)
SEASONAL
ADJUSTMENT
FACTOR
NEC DEMAND
FACTOR
DEMAND Kva
(w/ NEC
FACTOR)
ADDED
LOAD
(kVA)
TOTAL
DEMAND
LOAD (kVA)
TOTAL LOAD <= 80% OF
EQUIPMENT RATING NOTES
SWBD T8 208 3PH 4000 TBD - 0.9 - 1 1.25 - 125.7 - - -
SWBD T9 208 3PH 4000 TBD - 0.9 - 1 1.25 - 85.5 - - -
2 MP 208 3PH 1200 TBD - 0.9 - 1 1.25 - 13.4 - - -
BOILER MCC, MAIN 480 3PH 600 JULY 13 2023 91.64 0.788 116.30 1 1.25 145.4 7.2 152.6 YES -
BOILER MCC, BRANCH CIRCUIT CONDUCTOR
FEEDING BUILDING 5
480 3PH -
TBD - 0.9 - 1 1.25 - 4.3 - - -
BOISCIENCE MDP 208 3PH 1000 JULY 13 2023 77.76 0.906 84.9 1 1.25 106.1 29.2 135.3 YES -
EDP BIOSCIENCE 208 3PH 400 JULY 13 2023 53.37 0.877 59.54 1 1.25 74.4 - - YES -
T-B6 (T7), PRIMARY 13200 3PH 9.84 MAY 16 2023 106.3 0.9 118.1 1 1.25 147.6 29.2 176.8 YES 1
15 MSB 480 3PH 3200 MAY 16 2023 - - 871 1 1.25 1088.8 54.6 1143.4 YES 1
26 MSB-26A 208 3PH 1600 MAY 16 2023 162 0.96 168.8 1 1.25 210.9 89.2 300.1 YES 1
40 TRANSFORMER T17, PRIMARY 13200 3PH 3.28 MAY 16 2023 72.9 0.98 74.4 1 1.25 93.0 7.8 100.8 NO 1, 2
55 MDC 480 3PH 2400 MAY 16 2023 - - 427 1 1.25 533.8 28.0 561.8 YES 1
56 MSB 480 3PH 800 MAY 16 2023 158.5 0.9 176 1 1.25 220.1 25.3 245.4 YES 1
1. DATA OBTAINED FROM EQUIPMENT INTEGRAL OR EXTERNAL METER.
2. TRANSFORMER T17 IS A 75kVA TRANSFORMER FEEDING BUILDING 40 AND PANEL GRP. PANEL GRP IS LOADED TO 124% OF IT'S NAMEPLATE RATING. DUE TO OVERLOADING, ELECTRICAL DISTRIBUTION UPSIZED FOR ADDED LOAD. REFER TO SHEET 40EP601 AND 40EP611 FOR ADDITIONAL INFORMATION.
EQUIPMENT METERING AND LOAD INFORMATION SCHEDULE
NOTES:
File details come from the government source that posted it. Updated .