Attachment 7 - Drawings Electrical - 2 of 8.pdf

PDF 20 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Kansas City, MO (VA-23-00068037)
Solicitation number
36C77623B0066
Issued by

About this file

This document provides details for a federal contract opportunity for infrastructure upgrades at the Veterans Affairs Medical Center in Kansas City, Missouri. The solicitation number is 36C77623B0066 and is being issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas for construction services to upgrade the EHRM infrastructure at the Kansas City VA facility. The opportunity type is listed as a solicitation and Attachment 7 contains 20MB of drawings related to required electrical work. No other details are included regarding response dates, pricing terms, or incumbent contractors.

View the file

Other files

File Type Posted
Copy of Attachment 1 - Technical Questions - Responses.xlsx XLSX spreadsheet
36C77623B0066 0002.docx DOCX document
Attachment 1 - Site Visit - Sign-In Sheet - 36C77623B0066 EHRM Infra Upgrade - KC.pdf PDF
36C77623B0066 0001.docx DOCX document
Attachment 11 - Drawings Electrical - 6 of 8.pdf PDF
Attachment 19 - Drawings Telecommunications - 2 of 3.pdf PDF
Attachment 1 - Specifications - DIV 1-13.pdf PDF
Attachment 18 - Drawings Telecommunications - 1 of 3.pdf PDF
Attachment 3 - Drawings Architectural - 1 of 2.pdf PDF
Attachment 16 - Drawings Structural.pdf PDF
Attachment 13 - Drawings Electrical - 8 of 8.pdf PDF
Attachment 14 - Drawings Environmental.pdf PDF
Attachment 10 - Drawings Electrical - 5 of 8.pdf PDF
Attachment 12 - Drawings Electrical - 7 of 8.pdf PDF
Attachment 22 - Wage Rates - 6-30-23.pdf PDF
Attachment 21 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 9 - Drawings Electrical - 4 of 8.pdf PDF
Attachment 23 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 6 - Drawings Electrical - 1 of 8.pdf PDF
Attachment 17 - Drawings Technology.pdf PDF
Attachment 2 - Specifications - DIV 21-32.pdf PDF
Attachment 8 - Drawings Electrical - 3 of 8.pdf PDF
36C77623B0066_1.docx DOCX document
Attachment 20 - Drawings Telecommunications - 3 of 3.pdf PDF
Attachment 5 - Drawings Civil.pdf PDF
Attachment 4 - Drawings Architectural - 2 of 2.pdf PDF
Attachment 15 - Drawings Mechanical.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PB PB

Mo a

Mo b

J T J T

PANEL DT4

PULL

BOX

TYP.

ACCESS DOOR

CONTROLLER

ACCESS CONTROL

PANEL

ACCESS POWER

CONTROLLER

PANEL

DATA RACK

TELEPHONE

TERMINAL BOARD

1.9

1.H

1.J

15.M15.N

01-M4-305AB

01-M4-305AA

01-M4-305AA-2 01-M4-305AB-2

01-M4-305AA-2

01-M4-305AA-2

01-M4-305AA-2

01-M4-305AB-2

01-M4-305AB-2

01-M4-305AB-2

DATA RACK,

TYP.

EP502

PANEL DT4

PULL

BOX

RELOCATED

ACCESS

CONTROL PANEL

RELOCATED

ACCESS POWER

CONTROLLER

PANEL TELEPHONE

TERMINAL BOARD

RELOCATED

ACCESS DOOR

CONTROLLER

TR

M4-305A

154 SF

EP504

01-P-09B

01-P-10A

01-P-11A

01-P-12A

01-P-13A

01-P-14A

01-P-15A

01-P-16A

01-P-22

01-P-23

01-P-24

01-P-25

01-P-26

01-P-27

01-P-28

01-P-29

P-TR-2A

P-TR-2B

01-AC-10-M4-305A

01-AC-09-M4-305A

CONTINUE TO 01-CU-01-ROOF

REFERENCE SHEET 01EP412

DISCONNECT

"DISC-TX-01-M4-305AA"

XFMR

"TX-01-TX-01-M4-305AA"

01-P-09A

1.9

1.H

1.J

15.M15.N

EXPOSED

TYP.

1.9

1.H

1.J

15.M15.N

EXPOSED

01-M4-305AB01-M4-305AA

DATA RACK,

TYP.

L2E a

01-M4-305AA-4

L2 b

01-M4-305AB-4

TR

M4-305A

154 SF

L2E a

01-M4-305AA-4

L2 b

01-M4-305AB-4

1.9

1.H

1.J

15.M15.N

M4-305A

M4-305

HALLWAY

M4-305

67 SF

DATA

M4-305A

79 SF

DATA

M4-305A

79 SF

HALLWAY

M4-305

67 SF

AREA OF WORK

A SIDE POWER

B SIDE POWER

SHEET SHALL BE PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP404

BLDG 01 - LEVEL 04 - ENLARGED

ELECTRICAL PLANS

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

KEY PLAN

GENERAL NOTES

KEY NOTES

- 1/2" = 1'-0"

1 RM M4-305 & M4-305A - DEMOLITION ELECTRICAL PLAN

- 1/2" = 1'-0"

2 RM M4-305A - ELECTRICAL PLAN

- 1/2" = 1'-0"

3 RM M4-305 & M4-305A - DEMOLITION LIGHTING PLAN

- 1/2" = 1'-0"

4 RM M4-305A - LIGHTING PLAN

1'0 2' 4'

1'0 2' 4' 1'0 2' 4'

1'0 2' 4'

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING

SHALL BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "01-M4-305AA".

SOURCE B POWER PANELBOARD "01-M4-305AB".

SECONDARY BONDING BUSBAR.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

01-AC-09-M4-305A AND 01-AC-10-M4-305A POWERED FROM 01-CU-01-ROOF, PROVIDE

CONDUCTORS AND WIRE PER MANUFACTURER'S REQUIREMENTS. COORDINATE

WITH MECHANICAL CONTRACTOR AS REQUIRED.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING

TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.

COORDINATE WITH VA AS REQUIRED.

12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT

LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".

REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

PROJECT

NORTH

Revisions: Date:

ADDENDUM #1 07/19/2023

a

Mo b

PANEL DT5

PULL BOX

TYP

FIRE ALARM

SUBPANEL

FACP

POWER

SUPPLY

PANEL

ACCESS DOOR

CONTROLLER

UNLABELED

PANEL

TELEPHONE

TERMINAL

BOARD

DATA

RACK,

TYP.

1.91.8a

DATA RACK

EP502

01-M5-305A

01-M5-305B01-M5-305A-2

01-M5-305A-2

01-M5-305A-2

01-M5-305A-2

01-M5-305B-2

01-M5-305B-2

01-M5-305B-2

01-M5-305B-2

PULL BOX

PANEL DT5

ACCESS DOOR

CONTROLLER

UNLABELED

PANEL

RELOCATED FIRE

ALARM SUBPANEL

RELOCATED FACP

POWER SUPPLY

PANEL

TELEPHONE

TERMINAL

BOARD

01-AC-11-M5-305

TR

M5-305

164 SF

CONTINUE TO 01-CU-1-ROOF

REFERENCE SHEET 01EP412

EP504

01-P-29

01-P-28

01-P-27

01-P-26

01-P-25

01-P-24

01-P-23

01-P-11A

01-P-12A

01-P-13A

01-P-14A

01-P-15A

01-P-16A

P-TR-2BP-TR-2A

DISCONNECT

"DISC-TX-01-M5-305A"

XFMR "TX-01-M5-305A"

01-P-10C

01-P-10B

1.91.8a

01-AC-12-M5-305

M5-303

M5-305

TYP.

1.9

DATA RACK

01-M5-305A 01-M5-305B

TR

M5-305

164 SF

L2 b

01-M5-305B-4

L2 b

01-M5-305B-4

L2E a

01-M5-305A-4

L2E a

01-M5-305A-4

1.9

Room

M5-303

EMS CLOSET

M5-305

Room

M5-303

EMS CLOSET

M5-305

AREA OF WORK

A SIDE POWER

B SIDE POWER

SHEET SHALL BE PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP405

BLDG 01 - LEVEL 05 - ENLARGED

ELECTRICAL PLANS

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY PLAN

KEY NOTES

- 3/8" = 1'-0"

1 RM M5-303 & M5-305 - DEMOLITION ELECTRICAL PLAN

- 3/8" = 1'-0"

2 RM M5-305 - ELECTRICAL PLAN2'0 4' 6' 2'0 4' 6'

- 3/8" = 1'-0"

3 RM M5-303 & M5-305 - DEMOLITION LIGHTING PLAN

- 3/8" = 1'-0"

4 RM M5-305 - LIGHTING PLAN2'0 4' 6' 2'0 4' 6'

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE SHALL

BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "01-M5-305A".

SOURCE B POWER PANELBOARD "01-M5-305B".

SECONDARY BONDING BUSBAR.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

01-AC-11-M5-305 POWERED FROM 01-CU-1-ROOF, PROVIDE CONDUCTORS AND WIRE

PER MANUFACTURER'S REQUIREMENTS. COORDINATE WITH MECHANICAL

CONTRACTOR AS REQUIRED.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING

TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.

COORDINATE WITH VA AS REQUIRED.

12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT

LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".

REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

PROJECT

NORTH

Revisions: Date:

ADDENDUM #1 07/19/2023

PB

SM

S M

S M

Mo a

Mo b

PB

FIRE ALARM

SUB PANEL

DATA RACK

TYP.

PANEL DT6

ACCESS DOOR

CONTROLLER

FIBER OPTIC

PANEL

TELEPHONE

TERMINAL BOARDS

PULL BOX

1.9

1.H

1.J

15.M15.N

M6-305

M6-311

1 TYP

1.9

1.H

1.J

15.M15.N

DATA RACK,

TYP.

01-M6-305B

01-M6-305A

L2 b

01-M6-305B-4

L2E a

01-M6-305A-4

L2E a

01-M6-305A-4

L2E b

01-M6-305B-4

TR

M6-305

140 SF

1.9

1.H

1.J

15.M15.N

01-M6-305A

01-AC-13-M6-305

DATA RACK,

TYP.

01-M6-305A- 2

01-M6-305A- 2

01-M6-305A- 2

01-M6-305A- 2

01-M6-305B- 2

01-M6-305B- 2

01-M6-305B- 2

01-M6-305B- 2

EP502

PANEL DT6

RELOCATED

FIRE ALARM

SUBPANELS

TELEPHONE

TERMINAL BLOCKS

RELOCATED

ACCESS DOOR

CONTROLLER

PULL BOX

FIBER OPTIC

PANEL

EP504

TR

M6-305

140 SF

01-P-29

01-P-28

01-P-27

01-P-26

01-P-25

01-P-24

01-P-12A

01-P-13A

01-P-14A

01-P-15A

01-P-16A

01-AC-14-M6-305

01-M6-305B

CONTINUE TO 01-CU-01-ROOF

REFERENCE SHEET 01EP412

P-TR-2A

P-TR-2B

DISCONNECT

''DISC-TX-01-M6-305A''

01-P-11B

01-P-11A

1.9

1.H

1.J

15.M15.N

CLOSET IRM

M6-305

122 SF

M6-311

108 SF

CLOSET IRM

M6-305

122 SF

M6-311

108 SF

AREA OF WORK

A SIDE POWER

B SIDE POWER

SHEET SHALL PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP406

BLDG 01 - LEVEL 06 - ENLARGED

ELECTRICAL PLANS

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY PLAN

KEY NOTES

- 3/8" = 1'-0"

1 RM M6-305 & M6-311 - DEMOLITION ELECTRICAL PLAN 2'0 4' 6'

- 3/8" = 1'-0"

3 RM M6-305 & M6-311- DEMOLITION LIGHTING PLAN

- 3/8" = 1'-0"

4 RM M6-305 - LIGHTING PLAN

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

- 3/8" = 1'-0"

2 RM M6-305 - ELECTRICAL PLAN

1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING

SHALL BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "01-M6-305A".

SOURCE B POWER PANELBOARD "01-M6-305B".

SECONDARY BONDING BUSBAR.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

EXISTING EQUIPMENT TO BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS SHEET.

RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.

01-AC-12-M6-305 AND 01-AC-13-M6-305 POWERED FROM 01-CU-1-ROOF, PROVIDE

CONDUCTORS AND WIRE PER MANUFACTURER'S REQUIREMENTS. COORDINATE

WITH MECHANICAL CONTRACTOR AS REQUIRED.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING

TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.

COORDINATE WITH VA AS REQUIRED.

12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT

LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".

REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

Revisions: Date:

PB

a

Mo b

Mo a

Mo b

PANEL

DT7

TELEPHONE

TERMINAL BOARD,

TYP.

TYP.

PULL BOX

DATA RACK,

TYP.

EXISTING FIRE

ALARM PANEL

UNLABELED

PANELS

DOOR ACCESS

CONTROLLER

EXISTING POWER

SUPPLY, FAP

TEMPERATURE

CONTROL PANELS

TEMPERATURE

CONTROL PANELS

1.9

1.H

1.J

1.8a 15.M15.N

01-M7-305A2

DATA RACK,

TYP.

EP502

PULL BOX

PANEL DT7

01-M7-305B-201-M7-305A-2

TELEPHONE

TERMINAL BOARD,

TYP.

DOOR ACCESS

CONTROLLER

ACCESS CONTROL

PANEL

RELOCATED FIRE

ALARM PANEL

RELOCATED

POWER SUPPLY,

FAP

01-M7-305B-2

01-M7-305B-2

01-M7-305B-2

01-M7-305A-2

01-M7-305A-2

01-M7-305A-2

01-M7-305B

RELOCATED

TEMPERATURE

CONTROL PANELS

TR

M7-305

155 SF

CONTINUE TO 01-CU-01-ROOF

REFERENCE SHEET 01EP412

EP504

01-P-26

01-P-27

01-P-29

01-P-28

01-P-25

01-P-13A

01-P-14A

01-P-15A

01-P-16A

01-AC-15-M7-305

01-AC-16-M7-305

P-TR-2A

P-TR-2B

UNLABELED PANEL

XFMR "TX-01-M7-305A"

DISCONNECT

"DISC-TX-01-M7-305A"

1.9

1.H

1.J

1.8a 15.M15.N

01-P-12B

01-P-12A

M7-305

01-M7-305B01-M7-305A

DATA RACK,

TYP.

L2E a

01-M7-305A-4

L2 b

01-M7-305B-4

155 SF

IT

M7-305

L2E a

01-M7-305A-4

L2 b

01-M7-305B-4

1.9

1.H

1.J

1.8a 15.M15.N

1TYP

1.9

1.H

1.J

1.8a 15.M15.N

AREA OF WORK

A SIDE POWER

B SIDE POWER

SHEET SHALL PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP407

BLDG 01 - LEVEL 07 - ENLARGED

ELECTRICAL PLANS

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

- 1/2" = 1'-0"

1 RM M7-305 - DEMOLITION ELECTRICAL PLAN

- 1/2" = 1'-0"

2 RM M7-305 - ELECTRICAL PLAN

GENERAL NOTES

KEY PLAN

KEY NOTES

1'0 2' 4'

PROJECT

NORTH

- 1/2" = 1'-0"

4 RM M7-305 - LIGHTING PLAN

- 1/2" = 1'-0"

3 RM M7-305 - DEMOLITION LIGHTING PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE SHALL

BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "01-M7-305A".

SOURCE B POWER PANELBOARD "01-M7-305B".

SECONDARY BONDING BUSBAR.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

EXISTING EQUIPMENT TO BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS SHEET.

RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.

01-AC-14-M7-305 AND 01-AC-15-M7-305 POWERED FROM 01-CU-01-ROOF, PROVIDE

CONDUCTORS AND WIRE PER MANUFACTURER'S REQUIREMENTS. COORDINATE

WITH MECHANICAL CONTRACTOR AS REQUIRED.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING

TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.

COORDINATE WITH VA AS REQUIRED.

12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT

LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".

REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

PROJECT

NORTH

Revisions: Date: Page 203 of 518

Mo a

Mo b

PANEL DT8

TYP.

FIRE ALARM

CONTROL PANEL

ACCESS

CONTROL PANEL

TELEPHONE

TERMINAL BOARD

ACCESS DOOR

CONTROL PANEL

DATA RACK

1.9

1.H

1.J

1.9c

DATA RACK,

TYP.

EP502

01-M8-305A-2

2 01-M8-305A

301-M8-305B

01-M8-305B-2

PANEL DT8

FIRE ALARM

CONTROL

PANEL

TELEPHONE

TERMINAL BOARD

ACCESS

CONTROL PANEL

01-AC-18-M8-305

ACCESS DOOR

CONTROL PANEL

TR

M8-305

151 SF

01-M8-305B-2

01-M8-305B-2

01-M8-305B-2

01-M8-305A-2

01-M8-305A-2

01-M8-305A-2

01-P-26

01-P-14A

01-P-15A

01-P-16A

01-P-29

01-P-28

01-P-27

01-AC-17-M8-305

CONTINUE TO 01-CU-01-ROOF

REFERENCE SHEET 01EP412

P-TR-2A

P-TR-2B

DISCONNECT

''DISC-TX-01-M8-305A''

XFMR ''TX-01-M8-305A

EP504

TELEPHONE

TERMINAL BOARD

01-P-13B

01-P-13A

1.9

1.H

1.J

1.9c

M8-305

TYP.

1.9

1.H

1.J

1.9c

DATA RACK,

TYP.

01-M8-305A

01-M8-305B

TR

M8-305

151 SF

L2E a

01-M8-305A-4

L2 b

01-M8-305B-4

L2 b

01-M8-305B-4

L2E a

01-M8-305A-4

1.9

1.H

1.J

1.9c

IT

M8-305

151 SF

IT

M8-305

151 SF

AREA OF WORK

A SIDE POWER

B SIDE POWER

SHEET SHALL PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP408

BLDG 01 - LEVEL 08 - ENLARGED

ELECTRICAL PLANS

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY PLAN

KEY NOTES

- 1/2" = 1'-0"

1 RM M8-305 - DEMOLITION ELECTRICAL PLAN

- 1/2" = 1'-0"

2 RM M8-305 - ELECTRICAL PLAN1'0 2' 4' 1'0 2' 4'

- 1/2" = 1'-0"

3 RM M8-305 - DEMOLITION LIGHTING PLAN

- 1/2" = 1'-0"

4 RM M8-305 - LIGHTING PLAN1'0 2' 4' 1'0 2' 4'

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE SHALL

BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "01-M8-305A".

SOURCE B POWER PANELBOARD "01-M8-305B".

SECONDARY BONDING BUSBAR.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

01-AC-16-M8-305 AND 01-AC-17-M8-305 POWERED FROM 01-CU-01-ROOF, PROVIDE

CONDUCTORS AND WIRE PER MANUFACTURER'S REQUIREMENTS. COORDINATE

WITH MECHANICAL CONTRACTOR AS REQUIRED.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING

TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.

COORDINATE WITH VA AS REQUIRED.

12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT

LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".

REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

PROJECT

NORTH

Revisions: Date:

a b

OS

OS

PANEL DT9

PULL BOX

TYP.

DATA RACK, TYP.

TELEPHONE

TERMINAL BOARD

ACCESS POWER

CONTROLLER

PANEL

FIRE ALARM

SUBPANEL

ACCESS DOOR

CONTROL PANEL

CONTROL J-BOXES

1.9

1.H 1.H

1.J

TR

M9-302

165 SF

01-M9-302B-2

01-M9-302A-2

01-M9-302A-2

01-M9-302A-2

01-M9-302B-2

01-M9-302A-2

01-M9-302A

01-M9-302B

PANEL DT9

01-M9-302B-2

01-M9-302B-2

PULL BOX

RELOCATED

FIRE ALARM

SUBPANEL

ACCESS POWER

CONTROLLER

PANEL

TELEPHONE

TERMINAL BOARD

DATA RACK,

TYP.

EP502

ACCESS DOOR

CONTROL PANEL

01-AC-20-M9-302

CONTROL J-BOXES

CONTINUE TO 01-CU-01-ROOF

REFERENCE SHEET 01EP412

01-AC-19-M9-302

EP504

01-P-16A

01-P-15A

01-P-28

01-P-29

01-P-27

P-TR-2A

P-TR-2B

DISCONNECT

"DISC-TX-01-M9-302A"

XFMR "TX01-M9-302A"

01-P-14A

1.9

1.H

1.J

01-P-14A

AREA OF WORK

M9-302

M9-307

TYP.

1.9

1.H

1.J

TR

M9-302

165 SF

01-M9-302A

01-M9-302B

DATA RACK,

TYP.

L2 b

01-M9-302B-4

L2E a

01-M9-302A-4

L2 b

01-M9-302B-4

L2E a

01-M9-302A-4

1.9

1.H

1.J a, b a, b

A SIDE POWER

B SIDE POWER

SHEET SHALL PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP409

BLDG 01 - LEVEL 09 - ENLARGED

ELECTRICAL PLANS

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

- 1/2" = 1'-0"

1 RM M9-307 & M9-302 - DEMOLITION ELECTRICAL PLAN

- 1/2" = 1'-0"

2 RM M9-302 - ELECTRICAL PLAN

KEY PLAN

KEY NOTES

GENERAL NOTES

- 1/2" = 1'-0"

3 RM M9-307 & M9-302 - DEMOLITION LIGHTING PLAN

- 1/2" = 1'-0"

4 RM M9-302 - LIGHTING PLAN

1'0 2' 4'

1'0 2' 4'1'0 2' 4'

1'0 2' 4'

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE SHALL

BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "01-M9-302A".

SOURCE B POWER PANELBOARD "01-M9-302B".

SECONDARY BONDING BUSBAR.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

01-AC-18-M9-302 & 01-AC-19-M9-302, POWERED FROM 01-CU-01-ROOF, PROVIDE

CONDUCTORS AND WIRE PER MANUFACTURER'S REQUIREMENTS. COORDINATE

WITH MECHANICAL CONTRACTOR AS REQUIRED.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING

TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.

COORDINATE WITH VA AS REQUIRED.

12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT

LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".

REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

Revisions: Date:

a

Mo b

DT-10

DATA RACK, TYP.

PULL BOX

ACCESS CONTROL

PANELS

FIRE ACCESS

CONTROL PANEL ACCESS DOOR

CONTROLLER

PANEL

FIRE ALARM

SYSTEM

FIRE ALARM

SYSTEM POWER

PANEL

TELEPHONE TERMINAL

BOARD

TYP.

FIRE ALARM

POWER SUPPLY

1.8 1.9

1.H

1.J

1.8a 15.M15.N

DATA RACK

01-M10-303A

01-M10-303B 3

01-M10-303B-2

EP502

TR

M10-303

158 SF

EQUIP. STO.

M10-312

100 SF

01-M10-303A-2

01-M10-303A-2

01-M10-303B-2

01-M10-303B-2

01-M10-303B-2 01-M10-303A-2

01-M10-303A-2

DT-10

RELOCATED ACCESS

CONTROL PANELS

DOOR ACCESS

CONTROL PANEL

RELOCATED ACCESS

CONTROL PANELS

PULL BOX

RELOCATED

FIRE ALARM

SYSTEM POWER

PANEL

RELOCATED

FIRE ALARM SYSTEM

TELEPHONE

TERMINAL BOARD

01-AC-21-M10-303

CONTINUE TO 01-CU-2-ROOF

REFERENCE SHEET 01EP412

01TN1000

01-P-16A

01-P-29

01-P-28

P-TR-2A

DISCONNECT

"DISC-TX-01-M10-303A"

XFMR "TX-01-M10-303A"

01-P-15A

01-P-15B

1.8 1.9

1.H

1.J

1.8a 15.M15.N

01-AC-22-M10-303

M10-303

M10-312

AREA OF WORK

L2E a

01-M10-303A-4

01-M10-303A

01-M10-303B

DATA RACK

TR

M10-303

158 SF

EQUIP. STO.

M10-312

100 SF

L2E a

01-M10-303A-4

L2 b

01-M10-303B-4

L2 b

01-M10-303B-4

1.8 1.9

1.H

1.J

1.8a 15.M15.N

TYP.

1.8 1.9

1.H

1.J

1.8a 15.M15.N

155 SF

EQUIPMENT

STO.

M10-312

97 SF

IT

M10-303

155 SF

EQUIPMENT

STO.

M10-312

97 SF

IT

M10-303

A SIDE POWER

B SIDE POWER

SHEET SHALL PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP410

BLDG 01 - LEVEL 10 - ENLARGED

ELECTRICAL PLANS

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

KEY PLAN

GENERAL NOTES

KEY NOTES

3/8" = 1'-0"*01EP110

1 RM M10-312 & M10-303 - DEMOLITION ELECTRICAL PLAN

3/8" = 1'-0"*01EP110

2 RM M10-303 - ELECTRICAL PLAN

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

3/8" = 1'-0"*01EP110

4 RM M10-303 - LIGHTING PLAN

PROJECT

NORTH

PROJECT

NORTH

22'0 4' 6' 2'0 4' 6'

2'0 4' 6' 2'0 4' 6'

3/8" = 1'-0"*01EP110

3 RM M10-312 & M10-303 - DEMOLITION LIGHTING PLAN

1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING

SHALL BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "01-M10-303A". PROVIDE STRUT, MOUNTING

SUPPORTS, AND FASTENING HARDWARE AS REQUIRED TO INSTALL PANELBOARD

ABOVE TRANSFORMER. PANELBOARD AND TRANSFORMER FACES SHALL BE EVEN

WITH ONE ANOTHER.

SOURCE B POWER PANELBOARD "01-M10-303B".

SECONDARY BONDING BUSBAR.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

EXISTING EQUIPMENT TO BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS SHEET.

RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.

01-AC-21-M10-303 AND 01-AC-22-M10-303 POWERED FROM 01-CU-2-ROOF, PROVIDE

CONDUCTORS AND WIRE PER MANUFACTURER'S REQUIREMENTS. COORDINATE

WITH MECHANICAL CONTRACTOR AS REQUIRED.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING

TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.

COORDINATE WITH VA AS REQUIRED.

12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT

LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".

REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

Revisions: Date:

ADDENDUM #1 07/19/2023

SMSM

a b

OS

OS

AREA OF WORK

M11-303

M11-305

PANEL

DT11

1TYP.

DATA RACK, TYP.

FIRE ALARM

PANEL

PULL BOX

TELEPHONE

TERMINAL BOARD

FIBER OPTIC CABINET

ACCESS POWER

CONTROLLER

PANEL

ACCESS DOOR CONTROLLER

1.9 1.10

1.H

1.J

1.8a

1.H.1

15.M15.N

DATA RACK, TYP.

01-M11-303B-2

01-M11-303A-2

01-M11-303B-2

01-M11-303A-2

01-M11-303A-2

01-M11-303A-2 01-M11-303B-2

01-M11-303A

PANEL

DT11

01-M11-303B-2

EP502

FIRE ALARM

PANEL

FIRE ALARM

PANEL

RELOCATED

TELEPHONE

TERMINAL BOARD

FIBER OPTIC

CABINET

RELOCATED

ACCESS POWER

CONTROLLER

PANEL

01-AC-24-M11-303

ACCESS DOOR

CONTROLLER

01-AC-23-M11-303

TR

M11-303

253 SF

PULL BOX

CONTINUE TO 01-CU-02-ROOF

REFERENCE SHEET 01EP412

EP504

01-P-2901-P-16B

P-TR-2A

XFMR "TX-01-M11-303A"

DISCONNECT

"DISC-TX-01-M11-303A"

01-P-16A

1.9 1.10

1.H

1.J

1.8a

1.H.1

15.M15.N

301-M11-303B

P-TR-2B

TYP.

CLOSET IRM

M11-303

134 SF

OFFICE

M11-305

112 SF

1.9 1.10

1.H

1.J

1.8a

1.H.1

15.M15.N

DATA RACK, TYP.

01-M11-303A

TR

M11-303

253 SF

L2 b

01-M11-303B-4

L2E a

01-M11-303A-4

L2E a

01-M11-303A-4

L2E a

01-M11-303A-4 L2 b

01-M11-303B-4

1.9 1.10

1.H

1.J

1.8a

1.H.1

15.M15.N

01-M11-303Ba,b a,b

OFFICE

M11-305

112 SF

CLOSET IRM

M11-303

134 SF

SHEET SHALL PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

A SIDE POWER

B SIDE POWER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP411

BLDG 01 - LEVEL 11 - ENLARGED

ELECTRICAL PLANS

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY PLAN

KEY NOTES2'0 4' 8'

PROJECT

NORTH

- 1/4" = 1'-0"

1 RM M11-303 & M11-305 - DEMOLITION ELECTRICAL PLAN

- 1/4" = 1'-0"

2 RM M11-303 - ELECTRICAL PLAN

- 1/4" = 1'-0"

3 RM M11-303 & M11-305 - DEMOLITION LIGHTING PLAN

- 1/4" = 1'-0"

4 RM M11-303 - LIGHTING PLAN

2'0 4' 8'

PROJECT

NORTH

2'0 4' 8'

PROJECT

NORTH

2'0 4' 8'

PROJECT

NORTH

PROJECT

NORTH

EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING

SHALL BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "01-M11-303A".

SOURCE B POWER PANELBOARD "01-M11-303B".

SECONDARY BONDING BUSBAR.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

EXISTING EQUIPMENT TO BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS SHEET.

RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.

01-AC-23-M11-303 & 01-AC-24-M11-303 POWERED FROM 01-CU-02-ROOF, PROVIDE

CONDUCTORS AND WIRE PER MANUFACTURER'S REQUIREMENTS. COORDINATE

WITH MECHANICAL CONTRACTOR AS REQUIRED.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING

TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.

COORDINATE WITH VA AS REQUIRED.

12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT

LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".

REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

Revisions: Date:

1.10

1.G

1.J.1

1.H.1

MECH. ROOM

MP-202

SERVICE

ELEVATOR

MECH. ROOM

MP-203

ELEVATOR NO.

E1

ELEVATOR NO.

E2

PUMP ROOM

MP-204

ELEVATOR NO.

E3

ELEVATOR NO.

E4

MECH. ROOM

MP-205

01-CU-01-ROOF

01-CU-02-ROOF

01-DP-TRA-16

01-DP-TRA-15

CONTINUE TO

01-AC-20-M10-303, 01-AC-22-M10-303,

01-AC-21-M11-303, 01-AC-22-M11-303

REFERENCE SHEETS

01EP410 AND 01EP411

CONTINUE TO

01-AC-01-MB-305, 01-AC-02-MB-305,

01-AC-03-M1-392, 01-AC-04-M1-392,

01-AC-05-M2-312, 01-AC-06-M2-312,

01-AC-07-M3-301A, 01-AC-08-M3-301A,

01-AC-09-M4-305A, 01-AC-10-M4-305A,

01-AC-11-M5-305,

01-AC-12-M6-305, 01-AC-13-M6-305,

01-AC-14-M7-305, 01-AC-15-M7-305,

01-AC-16-M8-305, 01-AC-17-M8-305,

01-AC-18-M9-302, 01-AC-19-M9-302

REFERENCE SHEETS 01EP400 TO 01EP409

AREA OF WORK

A SIDE POWER

B SIDE POWER

SHEET SHALL PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

01EP412

BLDG 01 - ENLARGED ROOF PLAN

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

- 3/16" = 1'-0"

1 BLDG 01 - ENLARGED ROOF PLAN

KEY PLAN

GENERAL NOTES

KEY NOTES

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING

TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.

COORDINATE WITH VA AS REQUIRED.

12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT

LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".

REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

PROJECT

NORTH

4'0 8' 12'

PROJECT

NORTH

PROVIDE CONDUIT AND WIRE FROM CONDENSING UNIT TO ASSOCIATED AC UNIT AS

REQUIRED PER MANUFACTURER'S INSTRUCTIONS. COORDINATE WITH MECHANICAL

CONTRACTOR AS REQUIRED.

HVAC MANUFACTURER PROVIDED PANEL, WITH INTEGRAL DISCONNECT, FOR

SINGLE POINT ELECTRICAL CONNECTION.

Revisions: Date:

202 of 512Page 208 of 518 a

Mo b

J

AREA OF WORK

2-111A

10 11

E

F

TYP

10 11

E

F

TYP.

10 11

E

F

TR

2-111A

110 SF

L1E a

02-2-111AA-4

02-2-111AA

DATA RACK

02-2-111AB

L1E a

02-2-111AA-4

L1 b

02-2-111BB-4

L1 b

02-2-111BB-4

10 11

E

F

02-2-111AA

02-2-111AB

02-2-111AA-2

02-2-111AB-2

02-2-111AB-2

02-2-111AB-2

02-2-111AA-2

02-2-111AA-2

02-2-111AB-2

TR

2-111A

110 SF

02-AC-01-111A

CONTINUATION TO 02-CU-01-ROOF

REFERENCE SHEET 02EP403

DATA

RACK

EP502

02-2-111AB-2

EP504

02-P-03

02-P-04

02-P-05

02-P-06

P-TR-1B

P-TR-1A

A SIDE POWER

B SIDE POWER

SHEET SHALL PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

02EP401

BLDG 02 - LEVEL 01 - ENLARGED

ELECTRICAL PLANS

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY PLAN

KEY NOTES

PROJECT

NORTH

- 1/2" = 1'-0"

1 RM 2-111A & 2-111B - DEMOLITION ELECTRICAL PLAN

- 1/2" = 1'-0"

3 RM 2-111A & 2-111B - DEMOLITION LIGHTING PLAN

- 1/2" = 1'-0"

4 RM 2-111A - LIGHTING PLAN

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

- 1/2" = 1'-0"

2 RM 2-111A - ELECTRICAL PLAN

EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING

SHALL BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "02-111AA".

SOURCE B POWER PANELBOARD "02-111AB".

SECONDARY BONDING BUSBAR.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

FURNISH AND INSTALL BOXED POWER SUPPLIES AS INDICATED ABOVE ACCESSIBLE

CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER SUPPLY FOR

EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATE SERVE DOORS WITH

ELECTRIFIED DOOR HARDWARE AND MAKE CONNECTIONS AS REQUIRED. SEE

REQUIREMENTS IN 087100 - DOOR HARDWARE. COORDINATE WITH ARCHITECT AND

DOOR INSTALLER.

02-AC-01-111A POWERED FROM 02-CU-01-ROOF, PROVIDE CONDUCTORS AND WIRE

PER MANUFACTURER'S REQUIREMENTS. COORDINATE WITH MECHANICAL

CONTRACTOR AS REQUIRED.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING

TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.

COORDINATE WITH VA AS REQUIRED.

12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT

LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".

REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

Revisions: Date: 203 of 512Page 209 of 518

J a

Mo b

2-210

10 11

E

ROOF ACCESS

2-224

17 SF

10 11

E 02-2-210A-2

02-2-210A-2

02-2-210A-2 02-2-210A-2

02-2-210B-2

02-2-210B-2 02-2-210B-2

02-2-210B-2

ROOF ACCESS

2-224

17 SF

02-AC-02-210

93 SF

TR

2-210

CONTINUATION TO 02-CU-01-ROOF

REFERENCE SHEET 02EP403

DATA

RACK

EP502

02-2-210A

02-2-210B

EP504

02-P-04

02-P-06

P-TR-1B

P-TR-1A

10 11

E

1 TYP

ROOF ACCESS

2-224

17 SF

10 11

E

ROOF ACCESS

2-224

17 SF

93 SF

TR

2-210

DATA RACK

02-2-210A

L2E a 02-2-210A-4

L2E a 02-2-210A-4

02-2-210B

L2 b 02-2-210B-4

L2 b 02-2-210B-4

AREA OF WORK

A SIDE POWER

B SIDE POWER

SHEET SHALL PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

1285 SF

OFFICE

2-210

1285 SF

OFFICE

2-210

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

02EP402

BLDG 02 - LEVEL 02 - ENLARGED

ELECTRICAL PLANS

SJM/WNM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY PLAN

KEY NOTES

- 1/2" = 1'-0"

1 RM 2-210 - DEMOLITION ELECTRICAL PLAN

- 1/2" = 1'-0"

2 RM 2-210 - ELECTRICAL PLAN1'0 2' 4' 1'0 2' 4'

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

- 1/2" = 1'-0"

3 RM 2-210 - DEMOLITION LIGHTING PLAN

- 1/2" = 1'-0"

4 RM 2-210 - LIGHTING PLAN1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE SHALL

BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "02-2-210A".

SOURCE B POWER PANELBOARD "02-2-210B".

SECONDARY BONDING BUSBAR.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

FURNISH AND INSTALL BOXED POWER SUPPLIES AS INDICATED ABOVE ACCESSIBLE

CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER SUPPLY FOR

EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATE SERVE DOORS WITH

ELECTRIFIED DOOR HARDWARE AND MAKE CONNECTIONS AS REQUIRED. SEE

REQUIREMENTS IN 087100 - DOOR HARDWARE. COORDINATE WITH ARCHITECT AND

DOOR INSTALLER.

02-AC-02-210 POWERED FROM 02-CU-01-ROOF, PROVIDE CONDUCTORS AND WIRE

PER MANUFACTURER'S REQUIREMENTS. COORDINATE WITH MECHANICAL

CONTRACTOR AS REQUIRED.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES…

This is the start of the file's text. The full file is on GovTribe.