Attachment 20 - Drawings Telecommunications - 3 of 3.pdf
PDF 7 MB Posted
- Solicitation number
- 36C77623B0066
About this file
This document provides construction drawings and specifications for infrastructure upgrades at the Kansas City VA Medical Center. The project involves upgrading telecommunications systems across multiple buildings, including installing new data cabling, fiber backbones, wireless access points, security systems, and related IT infrastructure. Telecommunications rooms will receive new data racks, patch panels, switches, cable trays, and related equipment. Work areas will be upgraded with Category 6A outlets. The opportunity is open to all contractors and has an estimated value over $5 million. The solicitation number is listed and responses are due on June 19, 2023.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
360°
C
W
26.E
26.4a
DATA RACK,
TYP.
FIRE ALARM
SUB PANEL
TELEPHONE
TERMINAL
BOARDS
TELEPHONE
TERMINAL
BOARDS
FIRE ALARM
SUB PANEL 4
TYP.
26.E
26.4a
DATA RACK,
TYP.
ET502
26-VB-715B
26-VB-715A
TR
VB-715A
100 SF
STOCK ROOM
VB-713
149 SF
FIRE ALARM
SUB PANEL
FIRE ALARM
SUB PANEL
TELEPHONE
TERMINAL
BOARDS
TELEPHONE
TERMINAL
BOARDS
SECONDARY
BONDING BUSBAR
(BELOW)
C
26.E
26.4a
DATA RACK,
TYP.
ET501
TYP
TR
VB-715A
100 SF
STOCK ROOM
VB-713
149 SF
ET501 TYP.
VB-711
VB-713
VB-715A
STOCK ROOM
VB-713
164 SF
86 SF
IT CLOSET
VB-711
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
26ET400
BLDG 26 - LEVEL 00 - ENLARGED
TELECOMMUNICATIONS PLANS
LRM/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
KEY PLAN
GENERAL NOTES
KEY NOTES
3/8" = 1'-0"26ET100
1 RM VB-711 & VB-713 - DEMOLITION FLOOR PLAN
3/8" = 1'-0"26ET100
2 RM VB-715A - TELECOMMUNICATIONS PLAN
3/8" = 1'-0"26ET100
4 RM VB-715A - OVERHEAD PLAN
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
1 EXISTING DATA RACKS TO BE SALVAGED TO VA.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
EXISTING EQUIPMENT SHALL BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS SHEET.
RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.
SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL
BONDING DETAILS.
PROJECT
NORTH
NTS26ET100
3 NOT USED
Revisions: Date:
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-
HOOKS AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
388 of 512Page 394 of 518
W
C
1.3d26.3
26.E
26.D.1
TELEPHONE
TERMINAL
BOARD
ACCESS POWER
CONTROLLER
PANEL
ACCESS DOOR
CONTROLLER
DATA RACK, TYP.
TE
V1-685
34 SF
STORAGE
V1-684A
23 SF
1.3d26.3
26.E
26.D.1
DATA RACK,
TYP.
ET502
26-V1-684A
TE
V1-685
34 SF
TR
V1-684
127 SF
ACCESS POWER
CONTROLLER PANEL
ACCESS DOOR
CONTROLLER
TELEPHONE
TERMINAL BOARD STORAGE
V1-684A
23 SF
26-V1-684BSECONDARY
BONDING
BUSBAR
C
V1-684
V1-685
V1-684A
AREA OF WORK
SUPPLY ROOM
V1-684
137 SF
1.3d26.3
26.E
26.D.1
DATA RACK, TYP.
ET501
TYP.
TR
V1-684
127 SF
TE
V1-685
STORAGE
V1-684A
23 SF
ET501
TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
26ET401a
BLDG 26 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLAN
LRL/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
GENERAL NOTES
KEY PLAN
KEY NOTES
1/2" = 1'-0"26ET101
1 RM V1-684 & V1-684A & V1-685 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"26ET101
2 RM V1-684 - TELECOMMUNICATIONS PLAN
NTS26ET101
3 NOT USED
1'0 2' 4'
PROJECT
NORTH
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
EXISTING DATA RACKS TO BE SALVAGED TO VA.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
EXISTING EQUIPMENT SHALL BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS SHEET.
RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.
SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL
BONDING DETAILS.
1/2" = 1'-0"26ET101
4 RM V1-684 - OVERHEAD PLAN
Revisions: Date:
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-
HOOKS AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
389 of 512Page 395 of 518
W W
26.5 1.8
TELEPHONE
TERMINAL BOARDS
DATA RACK
DATA
V1-602
18 SF
ELEC.
V1-604
14 SF
26.5 1.8
TELEPHONE
TERMINAL BOARD
ELEC.
V1-604
14 SF
DATA
V1-602
18 SF
V1-602
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
26ET401b
BLDG 26 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
LRL/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
GENERAL NOTES
KEY PLAN
KEY NOTES
1/2" = 1'-0"26ET101
1 RM V1-602 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"26ET101
2 RM V1-602 - TELECOMMUNICATIONS PLAN
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
EXISTING DATA RACKS TO BE SALVAGED TO VA.1
Revisions: Date:
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-
HOOKS AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
390 of 512Page 396 of 518
26.5
DATA RACK
ELEC
V1-713
15 SF
TELEPHONE
TERMINAL
BOARDS
26.5
ELEC
V1-713
15 SF
TELEPHONE
TERMINAL
BOARD
V1-713
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
26ET401c
BLDG 26 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLAN
LRL/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
GENERAL NOTES
KEY PLAN
KEY NOTES
3/4" = 1'-0"26ET101
1 RM V1-713 - DEMOLITION FLOOR PLAN
3/4" = 1'-0"26ET101
2 RM V1-713 - TELECOMMUNICATIONS PLAN
PROJECT
NORTH
1'0 2' 3'
PROJECT
NORTH
1'0 2' 3'
PROJECT
NORTH
EXISTING DATA RACKS TO BE SALVAGE TO VA. 1
Revisions: Date:
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-
HOOKS AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
391 of 512Page 397 of 518
W
C
26.D
26.D.1 S
26.3
26.D
26.D.1
DATA RACK,
TYP.
ET502
26-V2-749B
26-V2-749A
TR
V2-749
130 SF
SECONDARY
BONDING
BUSBAR
26.3
C
26.D
26.D.1
ET501
TYP.
DATA RACK, TYP.
TR
V2-749
130 SF
ET501
TYP.
26.3
V2-751A
V2-749
AREA OF WORK
TOILET, MALE
V2-751A
55 SF
LOCKERS, FEMALE
V2-749
111 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
26ET402a
BLDG 26 - LEVEL 02 - ENLARGED
TELECOMMUNICATIONS PLANS
LRL/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
GENERAL NOTES
KEY NOTES
1/2" = 1'-0"26ET102
1 RM V2-749 & V2-751A - DEMOLITION FLOOR PLAN
1/2" = 1'-0"26ET102
2 RM V2-749 - TELECOMMUNICATIONS PLAN
1/2" = 1'-0"26ET102
4 RM V2-749 - OVERHEAD PLAN
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
KEY PLAN
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL
BONDING DETAILS.
PROJECT
NORTH
NTS26ET102
3 NOT USED
Revisions: Date:
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE
J-HOOKS AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
392 of 512Page 398 of 518
W W 2
26.G
ACCESS
CONTROL
PANEL
DATA RACK
TELEPHONE
TERMINAL
BOARD
TELECOM.
V2-654
20 SF
26.G
ACCESS
CONTROL
PANEL
TELEPHONE
TERMINAL
BOARD
TELECOM.
V2-654
20 SF
26.H
DATA RACK
TELEPHONE
TERMINAL BOARD
BIOMED NETWORK CLOSET
V2-600
16 SF
26.5
26.H
TELEPHONE
TERMINAL BOARD
BIOMED NETWORK CLOSET
V2-600
16 SF
26.5
V2-600V2-654
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
26ET402b
BLDG 26 - LEVEL 02 - ENLARGED
TELECOMMUNICATIONS PLANS
LRL/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
GENERAL NOTES
KEY NOTES
3/4" = 1'-0"26ET102
1 RM V2-654 - DEMOLITION FLOOR PLAN
3/4" = 1'-0"26ET102
2 RM V2-654 - TELECOMMUNICATIONS PLAN
3/4" = 1'-0"26ET102
3 RM V2-600 - DEMOLITION FLOOR PLAN
3/4" = 1'-0"26ET102
4 RM V2-600 - TELECOMMUNICATIONS PLAN
PROJECT
NORTH
1'0 2' 3'
PROJECT
NORTH
1'0 2' 3'
PROJECT
NORTH
1'0 2' 3'
PROJECT
NORTH
1'0 2' 3'
KEY PLAN
1 EXISTING DATA RACKS TO BE SALVAGED TO VA.
PROJECT
NORTH
Revisions: Date:
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE
J-HOOKS AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
393 of 512Page 399 of 518
26.B
WALL MOUNTED
DATA EQUIPMENT
ACCESS CONTROL
PANEL
TELEPHONE TERMINAL
BOARD
TELECOM. ROOM
V2-780
16 SF
26.B
ACCESS CONTROL
PANEL
TELEPHONE TERMINAL
BOARD
TELECOM. ROOM
V2-780
16 SF
ACCESS CONTROL
PANEL
ACCESS POWER
CONTROLLER PANEL
DATA RACK
TELEPHONE
TERMINAL BLOCK
BIOMED NETWORK
CLOSET
V2-784
16 SF
26.5
ACCESS POWER
CONTROLLER PANEL
TELEPHONE
TERMINAL BOARD
ACCESS CONTROL
PANEL
BIOMED NETWORK
CLOSET
V2-784
16 SF
26.5
V2-784
V2-780
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
26ET402c
BLDG 26 - LEVEL 02 - ENLARGED
TELECOMMUNICATIONS PLANS
LRL/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
GENERAL NOTES
KEY NOTES
3/4" = 1'-0"26ET102
1 RM V2-780 - DEMOLITION FLOOR PLAN
3/4" = 1'-0"26ET102
2 RM V2-780 - TELECOMMUNICATIONS PLAN
3/4" = 1'-0"26ET102
3 RM V2-784 - DEMOLITION FLOOR PLAN
3/4" = 1'-0"26ET102
4 RM V2-784 - TELECOMMUNICATIONS PLAN
PROJECT
NORTH
1'0 2' 3'
PROJECT
NORTH
1'0 2' 3'
PROJECT
NORTH
1'0 2' 3'
PROJECT
NORTH
1'0 2' 3'
KEY PLAN
1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROJECT
NORTH
Revisions: Date:
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE
J-HOOKS AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
394 of 512Page 400 of 518
0°
W
C
1.91.8a
26.D.1
FIRE ALARM SYSTEM
FIRE ALARM PANELS
TELEPHONE
TERMINAL
BOARDS
DATA
RACK,
TYP.
CARD READER
WITH KEYPAD
PANEL
CP-26-3B
PANEL
CP-26-3A
1.91.8a
26.D.1
FIRE ALARM SYSTEM
FIRE ALARM PANELS
TELEPHONE
TERMINAL
BOARDS
DATA RACK,
TYP.
ET502
26-V3-734B
CARD READER
WITH KEYPAD
PANEL
CP-26-3B
PANEL
CP-26-3A
TR
V3-734
95 SF
SECONDARY
BONDING
BUSBAR
C
26-V3-734A
V3-734
DATA
V3-734
95 SF
AREA OF WORK
1.91.8a
26.D.1
DATA RACK, TYP.
TYP.
ET501
TR
V3-734
95 SF
ET501
TYP.
GENERAL NOTES
KEY PLAN
KEY NOTES
1/2" = 1'-0"26ET103
1 RM V3-734 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"26ET103
2 RM V3-734 - TELECOMMUNICATIONS PLAN1'0 2' 4'
PROJECT
NORTH
NTS26ET103
3 NOT USED
1'0 2' 4'
1'0 2' 4'
PROJECT
NORTH
PROJECT
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
26ET403
BLDG 26 - LEVEL 03 - ENLARGED
TELECOMMUNICATIONS PLANS
LRL/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
1 EXISTING DATA RACKS TO BE SALVAGE TO VA.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
EXISTING EQUIPMENT TO BE RELOCATED AS SHOWN IN DETAIL "2" ON THIS SHEET.
RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.
SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL
BONDING DETAILS.
PROJECT
NORTH
1/2" = 1'-0"26ET103
4 RM V3-734 - OVERHEAD PLAN
Revisions: Date:
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLES AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-HOOK AS
REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
395 of 512Page 401 of 518
C
DATA
RACK,
TYP.
TELEPHONE
TERMINAL
BOARDS
PATCH PANEL
ACCESS POWER
CONTROLLER
PANEL
ACCESS CONTROL
PANEL
TELECOM. CLOSET
V5-704
91 SF
EXISTING CARD
READER WITH
KEYPAD
26.4
TELEPHONE
TERMINAL
BOARDS
DATA RACK,
TYP. ET502
26-V5-704-A
26-V5-704-B
PATCH PANEL
ACCESS POWER
CONTROLLER
PANEL
ACCESS CONTROL
PANEL
TR
V5-704
91 SF
SECONDARY
BONDING
BUSBAR
EXISTING CARD
READER WITH
KEYPAD
C
26.4
V5-704
AREA OF WORK
DATA RACK,TYP.
ET501
TYP.
TR
V5-704
91 SF
TYP.
ET501
26.4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
26ET405
BLDG 26 - LEVEL 05 - ENLARGED
TELECOMMUNICATIONS PLANS
LRL/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
GENERAL NOTES
KEY PLAN
KEY NOTES
1/2" = 1'-0"26ET105
1 RM V5-704 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"26ET105
2 RM V5-704 - TELECOMMUNICATIONS PLAN1'0 2' 4' 1'0 2' 4'
PROJECT
NORTH
PROJECT
NORTH
NTS26ET105
3 NOT USED 1'0 2' 4'
PROJECT
NORTH
1 EXISTING DATA RACKS TO BE SALVAGED TO VA.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL
BONDING DETAILS.
EXISTING EQUIPMENT TO BE RELOCATED AS SHOWN IN DETAIL ''2'' ON THIS SHEET.
RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.
PROJECT
NORTH
1/2" = 1'-0"26ET105
4 RM V5-704 - OVERHEAD PLAN
Revisions: Date:
ADDENDUM #1 07/19/2023
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE
J-HOOKS AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
14. ACTIVE OR REQUIRES ICRA CLASS V REQUIREMENTS. ALL EMPLOYEES MUST WEAR
VA PROVIDED COVERALLS AT ENTRY AND EXIT. ALL EQUIPMENT, TOOLS, AND
MATERIALS MUST BE WIPED.
WAP
360°
W
C
WAP
4 5 5.1
A
WORK AREA
(TE)
40-16
420 SF
ICRA CLASS II
WALL MOUNTED
DATA EQUIPMENT
EMERGENCY PANEL
TYP.
4 5 5.1
A
WORK AREA
(TE)
40-16
420 SF
ICRA CLASS II
TELECOMMUNICATIONS
ENCLOSURE
ET502
EMERGENCY PANEL
40-16A
TYP
SECONDARY
BONDING
BUSBAR
C
AREA OF WORK
40-16
4 5 5.1
A
TELECOMMUNICATIONS
ENCLOSURE
WORK AREA
(TE)
40-16
420 SF
ICRA CLASS II
TYP.
ET501
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
40ET401
BLDG 40 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
LRL/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
KEY PLAN
KEY NOTES
GENERAL NOTES
3/8" = 1'-0"40ET101
1 RM 40-16 - DEMOLITION FLOOR PLAN
3/8" = 1'-0"40ET101
2 RM 40-16 - TELECOMMUNICATIONS PLAN2'0 4' 6' 2'0 4' 6'
PROJECT
NORTH
PROJECT
NORTH
3/8" = 1'-0"40ET101
4 RM 40-16 - OVERHEAD PLAN 2'0 4' 6'
PROJECT
NORTH
PROJECT
NORTH
1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. REFERENCE
DETAIL '3' ON SHEET ET501 FOR ADDITIONAL INFORMATION. SIDE 'A' AND SIDE 'B'
SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO
REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT
SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1'
ON SHEET ET501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EQUIPMENT SWINGS AWAY FROM WALL HINGE TO ALLOW BACK-DOOR ACCESS.
SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR
BONDING DETAILS.
EXISTING DATA EQUIPMENT TO SALVAGED TO VA.
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4''-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE
J-HOOKS AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
NTS40ET101
3 NOT USED
Revisions: Date:
397 of 512Page 403 of 518
W
0°
W
C
H1-173
D
BB
R1
FIBER OPTIC
CABINETS
DATA RACK, TYP.
ACCESS POWER
CONTROLLER PANEL
ACCESS DOOR
CONTROLLER
DISC.
EXISTING
CARD READER
FIRE ALARM PANELS
ELUPS
D
BB
R1
TR
H1-173
229 SF
DATA RACK,
TYP.
55-H1-173B
55-H1-173A
ET502
ACCESS POWER
CONTROLLER PANEL
ACCESS DOOR
CONTROLLER
ELUPS
FIRE ALARM PANELS
DISC.
FIBER OPTIC
CABINETS
EXISTING
CARD READER
SECONDARY
BONDING
BUSBAR
C
D
BB
R1
DATA RACK,
TYP.
ET501
TYP.
TR
H1-173
229 SF 3
ET501
TYP.
D
BB
R1
TYP.
TELECOM.
H1-173
229 SF
TELECOM.
H1-173
229 SF
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - KANSAS CITY, MO
Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
589-21-700
55ET401
BLDG 55 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
LRL/SJM RDC/LLT
100% CONSTRUCTION
DOCUMENTS
06/19/2023
KEY PLAN
KEY NOTES
3/8" = 1'-0"55ET101
1 RM H1-173 - DEMOLITION FLOOR PLAN
3/8" = 1'-0"55ET101
2 RM H1-173 - TELECOMMUNICATIONS PLAN
3/8" = 1'-0"55ET101
4 RM H1-173 - OVERHEAD PLAN
3/8" = 1'-0"55ET101
3 RM H1-173 - DEMOLITION OVERHEAD PLAN
2'0 4' 6'
PROJECT
NORTH
1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
EXISTING CABLE TRAY TO BE DEMOLISHED.
SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL
BONDING DETAILS.
EXISTING DATA RACKS TO BE SALVAGED TO VA.
TRUE
NORTH
GENERAL NOTES
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
Revisions: Date:
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE
J-HOOKS AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE…
This is the start of the file's text. The full file is on GovTribe.