Attachment 20 - Drawings Telecommunications - 3 of 3.pdf

PDF 7 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Kansas City, MO (VA-23-00068037)
Solicitation number
36C77623B0066
Issued by

About this file

This document provides construction drawings and specifications for infrastructure upgrades at the Kansas City VA Medical Center. The project involves upgrading telecommunications systems across multiple buildings, including installing new data cabling, fiber backbones, wireless access points, security systems, and related IT infrastructure. Telecommunications rooms will receive new data racks, patch panels, switches, cable trays, and related equipment. Work areas will be upgraded with Category 6A outlets. The opportunity is open to all contractors and has an estimated value over $5 million. The solicitation number is listed and responses are due on June 19, 2023.

View the file

Other files

File Type Posted
Copy of Attachment 1 - Technical Questions - Responses.xlsx XLSX spreadsheet
36C77623B0066 0002.docx DOCX document
Attachment 1 - Site Visit - Sign-In Sheet - 36C77623B0066 EHRM Infra Upgrade - KC.pdf PDF
36C77623B0066 0001.docx DOCX document
Attachment 11 - Drawings Electrical - 6 of 8.pdf PDF
Attachment 19 - Drawings Telecommunications - 2 of 3.pdf PDF
Attachment 1 - Specifications - DIV 1-13.pdf PDF
Attachment 18 - Drawings Telecommunications - 1 of 3.pdf PDF
Attachment 3 - Drawings Architectural - 1 of 2.pdf PDF
Attachment 16 - Drawings Structural.pdf PDF
Attachment 7 - Drawings Electrical - 2 of 8.pdf PDF
Attachment 13 - Drawings Electrical - 8 of 8.pdf PDF
Attachment 14 - Drawings Environmental.pdf PDF
Attachment 10 - Drawings Electrical - 5 of 8.pdf PDF
Attachment 12 - Drawings Electrical - 7 of 8.pdf PDF
Attachment 22 - Wage Rates - 6-30-23.pdf PDF
Attachment 21 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 9 - Drawings Electrical - 4 of 8.pdf PDF
Attachment 23 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 6 - Drawings Electrical - 1 of 8.pdf PDF
Attachment 17 - Drawings Technology.pdf PDF
Attachment 2 - Specifications - DIV 21-32.pdf PDF
Attachment 8 - Drawings Electrical - 3 of 8.pdf PDF
36C77623B0066_1.docx DOCX document
Attachment 5 - Drawings Civil.pdf PDF
Attachment 4 - Drawings Architectural - 2 of 2.pdf PDF
Attachment 15 - Drawings Mechanical.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

360°

C

W

26.E

26.4a

DATA RACK,

TYP.

FIRE ALARM

SUB PANEL

TELEPHONE

TERMINAL

BOARDS

TELEPHONE

TERMINAL

BOARDS

FIRE ALARM

SUB PANEL 4

TYP.

26.E

26.4a

DATA RACK,

TYP.

ET502

26-VB-715B

26-VB-715A

TR

VB-715A

100 SF

STOCK ROOM

VB-713

149 SF

FIRE ALARM

SUB PANEL

FIRE ALARM

SUB PANEL

TELEPHONE

TERMINAL

BOARDS

TELEPHONE

TERMINAL

BOARDS

SECONDARY

BONDING BUSBAR

(BELOW)

C

26.E

26.4a

DATA RACK,

TYP.

ET501

TYP

TR

VB-715A

100 SF

STOCK ROOM

VB-713

149 SF

ET501 TYP.

VB-711

VB-713

VB-715A

STOCK ROOM

VB-713

164 SF

86 SF

IT CLOSET

VB-711

AREA OF WORK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

26ET400

BLDG 26 - LEVEL 00 - ENLARGED

TELECOMMUNICATIONS PLANS

LRM/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

KEY PLAN

GENERAL NOTES

KEY NOTES

3/8" = 1'-0"26ET100

1 RM VB-711 & VB-713 - DEMOLITION FLOOR PLAN

3/8" = 1'-0"26ET100

2 RM VB-715A - TELECOMMUNICATIONS PLAN

3/8" = 1'-0"26ET100

4 RM VB-715A - OVERHEAD PLAN

2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

1 EXISTING DATA RACKS TO BE SALVAGED TO VA.

PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND

SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

EXISTING EQUIPMENT SHALL BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS SHEET.

RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.

SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL

BONDING DETAILS.

PROJECT

NORTH

NTS26ET100

3 NOT USED

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE

BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING

FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-

HOOKS AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED

PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE

DRAWINGS AS REQUIRED.

13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

388 of 512Page 394 of 518

W

C

1.3d26.3

26.E

26.D.1

TELEPHONE

TERMINAL

BOARD

ACCESS POWER

CONTROLLER

PANEL

ACCESS DOOR

CONTROLLER

DATA RACK, TYP.

TE

V1-685

34 SF

STORAGE

V1-684A

23 SF

1.3d26.3

26.E

26.D.1

DATA RACK,

TYP.

ET502

26-V1-684A

TE

V1-685

34 SF

TR

V1-684

127 SF

ACCESS POWER

CONTROLLER PANEL

ACCESS DOOR

CONTROLLER

TELEPHONE

TERMINAL BOARD STORAGE

V1-684A

23 SF

26-V1-684BSECONDARY

BONDING

BUSBAR

C

V1-684

V1-685

V1-684A

AREA OF WORK

SUPPLY ROOM

V1-684

137 SF

1.3d26.3

26.E

26.D.1

DATA RACK, TYP.

ET501

TYP.

TR

V1-684

127 SF

TE

V1-685

STORAGE

V1-684A

23 SF

ET501

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

26ET401a

BLDG 26 - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLAN

LRL/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY PLAN

KEY NOTES

1/2" = 1'-0"26ET101

1 RM V1-684 & V1-684A & V1-685 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"26ET101

2 RM V1-684 - TELECOMMUNICATIONS PLAN

NTS26ET101

3 NOT USED

1'0 2' 4'

PROJECT

NORTH

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

EXISTING DATA RACKS TO BE SALVAGED TO VA.

PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND

SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

EXISTING EQUIPMENT SHALL BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS SHEET.

RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.

SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL

BONDING DETAILS.

1/2" = 1'-0"26ET101

4 RM V1-684 - OVERHEAD PLAN

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE

BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING

FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-

HOOKS AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED

PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE

DRAWINGS AS REQUIRED.

13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

389 of 512Page 395 of 518

W W

26.5 1.8

TELEPHONE

TERMINAL BOARDS

DATA RACK

DATA

V1-602

18 SF

ELEC.

V1-604

14 SF

26.5 1.8

TELEPHONE

TERMINAL BOARD

ELEC.

V1-604

14 SF

DATA

V1-602

18 SF

V1-602

AREA OF WORK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

26ET401b

BLDG 26 - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

LRL/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY PLAN

KEY NOTES

1/2" = 1'-0"26ET101

1 RM V1-602 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"26ET101

2 RM V1-602 - TELECOMMUNICATIONS PLAN

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

EXISTING DATA RACKS TO BE SALVAGED TO VA.1

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE

BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING

FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-

HOOKS AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED

PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE

DRAWINGS AS REQUIRED.

13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

390 of 512Page 396 of 518

26.5

DATA RACK

ELEC

V1-713

15 SF

TELEPHONE

TERMINAL

BOARDS

26.5

ELEC

V1-713

15 SF

TELEPHONE

TERMINAL

BOARD

V1-713

AREA OF WORK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

26ET401c

BLDG 26 - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLAN

LRL/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY PLAN

KEY NOTES

3/4" = 1'-0"26ET101

1 RM V1-713 - DEMOLITION FLOOR PLAN

3/4" = 1'-0"26ET101

2 RM V1-713 - TELECOMMUNICATIONS PLAN

PROJECT

NORTH

1'0 2' 3'

PROJECT

NORTH

1'0 2' 3'

PROJECT

NORTH

EXISTING DATA RACKS TO BE SALVAGE TO VA. 1

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE

BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING

FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-

HOOKS AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED

PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE

DRAWINGS AS REQUIRED.

13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

391 of 512Page 397 of 518

W

C

26.D

26.D.1 S

26.3

26.D

26.D.1

DATA RACK,

TYP.

ET502

26-V2-749B

26-V2-749A

TR

V2-749

130 SF

SECONDARY

BONDING

BUSBAR

26.3

C

26.D

26.D.1

ET501

TYP.

DATA RACK, TYP.

TR

V2-749

130 SF

ET501

TYP.

26.3

V2-751A

V2-749

AREA OF WORK

TOILET, MALE

V2-751A

55 SF

LOCKERS, FEMALE

V2-749

111 SF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

26ET402a

BLDG 26 - LEVEL 02 - ENLARGED

TELECOMMUNICATIONS PLANS

LRL/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY NOTES

1/2" = 1'-0"26ET102

1 RM V2-749 & V2-751A - DEMOLITION FLOOR PLAN

1/2" = 1'-0"26ET102

2 RM V2-749 - TELECOMMUNICATIONS PLAN

1/2" = 1'-0"26ET102

4 RM V2-749 - OVERHEAD PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

KEY PLAN

EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING

SHALL BE DEMOLISHED BACK TO SOURCE.

PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND

SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL

BONDING DETAILS.

PROJECT

NORTH

NTS26ET102

3 NOT USED

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE

BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING

FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE

J-HOOKS AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED

PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE

DRAWINGS AS REQUIRED.

13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

392 of 512Page 398 of 518

W W 2

26.G

ACCESS

CONTROL

PANEL

DATA RACK

TELEPHONE

TERMINAL

BOARD

TELECOM.

V2-654

20 SF

26.G

ACCESS

CONTROL

PANEL

TELEPHONE

TERMINAL

BOARD

TELECOM.

V2-654

20 SF

26.H

DATA RACK

TELEPHONE

TERMINAL BOARD

BIOMED NETWORK CLOSET

V2-600

16 SF

26.5

26.H

TELEPHONE

TERMINAL BOARD

BIOMED NETWORK CLOSET

V2-600

16 SF

26.5

V2-600V2-654

AREA OF WORK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

26ET402b

BLDG 26 - LEVEL 02 - ENLARGED

TELECOMMUNICATIONS PLANS

LRL/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY NOTES

3/4" = 1'-0"26ET102

1 RM V2-654 - DEMOLITION FLOOR PLAN

3/4" = 1'-0"26ET102

2 RM V2-654 - TELECOMMUNICATIONS PLAN

3/4" = 1'-0"26ET102

3 RM V2-600 - DEMOLITION FLOOR PLAN

3/4" = 1'-0"26ET102

4 RM V2-600 - TELECOMMUNICATIONS PLAN

PROJECT

NORTH

1'0 2' 3'

PROJECT

NORTH

1'0 2' 3'

PROJECT

NORTH

1'0 2' 3'

PROJECT

NORTH

1'0 2' 3'

KEY PLAN

1 EXISTING DATA RACKS TO BE SALVAGED TO VA.

PROJECT

NORTH

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE

BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING

FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE

J-HOOKS AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED

PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE

DRAWINGS AS REQUIRED.

13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

393 of 512Page 399 of 518

26.B

WALL MOUNTED

DATA EQUIPMENT

ACCESS CONTROL

PANEL

TELEPHONE TERMINAL

BOARD

TELECOM. ROOM

V2-780

16 SF

26.B

ACCESS CONTROL

PANEL

TELEPHONE TERMINAL

BOARD

TELECOM. ROOM

V2-780

16 SF

ACCESS CONTROL

PANEL

ACCESS POWER

CONTROLLER PANEL

DATA RACK

TELEPHONE

TERMINAL BLOCK

BIOMED NETWORK

CLOSET

V2-784

16 SF

26.5

ACCESS POWER

CONTROLLER PANEL

TELEPHONE

TERMINAL BOARD

ACCESS CONTROL

PANEL

BIOMED NETWORK

CLOSET

V2-784

16 SF

26.5

V2-784

V2-780

AREA OF WORK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

26ET402c

BLDG 26 - LEVEL 02 - ENLARGED

TELECOMMUNICATIONS PLANS

LRL/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY NOTES

3/4" = 1'-0"26ET102

1 RM V2-780 - DEMOLITION FLOOR PLAN

3/4" = 1'-0"26ET102

2 RM V2-780 - TELECOMMUNICATIONS PLAN

3/4" = 1'-0"26ET102

3 RM V2-784 - DEMOLITION FLOOR PLAN

3/4" = 1'-0"26ET102

4 RM V2-784 - TELECOMMUNICATIONS PLAN

PROJECT

NORTH

1'0 2' 3'

PROJECT

NORTH

1'0 2' 3'

PROJECT

NORTH

1'0 2' 3'

PROJECT

NORTH

1'0 2' 3'

KEY PLAN

1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING

SHALL BE DEMOLISHED BACK TO SOURCE.

PROJECT

NORTH

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE

BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING

FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE

J-HOOKS AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED

PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE

DRAWINGS AS REQUIRED.

13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

394 of 512Page 400 of 518

0°

W

C

1.91.8a

26.D.1

FIRE ALARM SYSTEM

FIRE ALARM PANELS

TELEPHONE

TERMINAL

BOARDS

DATA

RACK,

TYP.

CARD READER

WITH KEYPAD

PANEL

CP-26-3B

PANEL

CP-26-3A

1.91.8a

26.D.1

FIRE ALARM SYSTEM

FIRE ALARM PANELS

TELEPHONE

TERMINAL

BOARDS

DATA RACK,

TYP.

ET502

26-V3-734B

CARD READER

WITH KEYPAD

PANEL

CP-26-3B

PANEL

CP-26-3A

TR

V3-734

95 SF

SECONDARY

BONDING

BUSBAR

C

26-V3-734A

V3-734

DATA

V3-734

95 SF

AREA OF WORK

1.91.8a

26.D.1

DATA RACK, TYP.

TYP.

ET501

TR

V3-734

95 SF

ET501

TYP.

GENERAL NOTES

KEY PLAN

KEY NOTES

1/2" = 1'-0"26ET103

1 RM V3-734 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"26ET103

2 RM V3-734 - TELECOMMUNICATIONS PLAN1'0 2' 4'

PROJECT

NORTH

NTS26ET103

3 NOT USED

1'0 2' 4'

1'0 2' 4'

PROJECT

NORTH

PROJECT

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

26ET403

BLDG 26 - LEVEL 03 - ENLARGED

TELECOMMUNICATIONS PLANS

LRL/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

1 EXISTING DATA RACKS TO BE SALVAGE TO VA.

PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND

SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

EXISTING EQUIPMENT TO BE RELOCATED AS SHOWN IN DETAIL "2" ON THIS SHEET.

RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.

SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL

BONDING DETAILS.

PROJECT

NORTH

1/2" = 1'-0"26ET103

4 RM V3-734 - OVERHEAD PLAN

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLES AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO

ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO

TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-HOOK AS

REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED

PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE

DRAWINGS AS REQUIRED.

13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

395 of 512Page 401 of 518

C

DATA

RACK,

TYP.

TELEPHONE

TERMINAL

BOARDS

PATCH PANEL

ACCESS POWER

CONTROLLER

PANEL

ACCESS CONTROL

PANEL

TELECOM. CLOSET

V5-704

91 SF

EXISTING CARD

READER WITH

KEYPAD

26.4

TELEPHONE

TERMINAL

BOARDS

DATA RACK,

TYP. ET502

26-V5-704-A

26-V5-704-B

PATCH PANEL

ACCESS POWER

CONTROLLER

PANEL

ACCESS CONTROL

PANEL

TR

V5-704

91 SF

SECONDARY

BONDING

BUSBAR

EXISTING CARD

READER WITH

KEYPAD

C

26.4

V5-704

AREA OF WORK

DATA RACK,TYP.

ET501

TYP.

TR

V5-704

91 SF

TYP.

ET501

26.4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

26ET405

BLDG 26 - LEVEL 05 - ENLARGED

TELECOMMUNICATIONS PLANS

LRL/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

GENERAL NOTES

KEY PLAN

KEY NOTES

1/2" = 1'-0"26ET105

1 RM V5-704 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"26ET105

2 RM V5-704 - TELECOMMUNICATIONS PLAN1'0 2' 4' 1'0 2' 4'

PROJECT

NORTH

PROJECT

NORTH

NTS26ET105

3 NOT USED 1'0 2' 4'

PROJECT

NORTH

1 EXISTING DATA RACKS TO BE SALVAGED TO VA.

PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND

SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL

BONDING DETAILS.

EXISTING EQUIPMENT TO BE RELOCATED AS SHOWN IN DETAIL ''2'' ON THIS SHEET.

RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.

PROJECT

NORTH

1/2" = 1'-0"26ET105

4 RM V5-704 - OVERHEAD PLAN

Revisions: Date:

ADDENDUM #1 07/19/2023

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE

BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING

FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE

J-HOOKS AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED

PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE

DRAWINGS AS REQUIRED.

13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

14. ACTIVE OR REQUIRES ICRA CLASS V REQUIREMENTS. ALL EMPLOYEES MUST WEAR

VA PROVIDED COVERALLS AT ENTRY AND EXIT. ALL EQUIPMENT, TOOLS, AND

MATERIALS MUST BE WIPED.

WAP

360°

W

C

WAP

4 5 5.1

A

WORK AREA

(TE)

40-16

420 SF

ICRA CLASS II

WALL MOUNTED

DATA EQUIPMENT

EMERGENCY PANEL

TYP.

4 5 5.1

A

WORK AREA

(TE)

40-16

420 SF

ICRA CLASS II

TELECOMMUNICATIONS

ENCLOSURE

ET502

EMERGENCY PANEL

40-16A

TYP

SECONDARY

BONDING

BUSBAR

C

AREA OF WORK

40-16

4 5 5.1

A

TELECOMMUNICATIONS

ENCLOSURE

WORK AREA

(TE)

40-16

420 SF

ICRA CLASS II

TYP.

ET501

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

40ET401

BLDG 40 - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

LRL/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

KEY PLAN

KEY NOTES

GENERAL NOTES

3/8" = 1'-0"40ET101

1 RM 40-16 - DEMOLITION FLOOR PLAN

3/8" = 1'-0"40ET101

2 RM 40-16 - TELECOMMUNICATIONS PLAN2'0 4' 6' 2'0 4' 6'

PROJECT

NORTH

PROJECT

NORTH

3/8" = 1'-0"40ET101

4 RM 40-16 - OVERHEAD PLAN 2'0 4' 6'

PROJECT

NORTH

PROJECT

NORTH

1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING

SHALL BE DEMOLISHED BACK TO SOURCE.

PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. REFERENCE

DETAIL '3' ON SHEET ET501 FOR ADDITIONAL INFORMATION. SIDE 'A' AND SIDE 'B'

SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.

PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO

REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT

SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1'

ON SHEET ET501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL

INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.

EQUIPMENT SWINGS AWAY FROM WALL HINGE TO ALLOW BACK-DOOR ACCESS.

SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR

BONDING DETAILS.

EXISTING DATA EQUIPMENT TO SALVAGED TO VA.

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4''-SQUARE

BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING

FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE

J-HOOKS AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED

PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE

DRAWINGS AS REQUIRED.

13. CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

NTS40ET101

3 NOT USED

Revisions: Date:

397 of 512Page 403 of 518

W

0°

W

C

H1-173

D

BB

R1

FIBER OPTIC

CABINETS

DATA RACK, TYP.

ACCESS POWER

CONTROLLER PANEL

ACCESS DOOR

CONTROLLER

DISC.

EXISTING

CARD READER

FIRE ALARM PANELS

ELUPS

D

BB

R1

TR

H1-173

229 SF

DATA RACK,

TYP.

55-H1-173B

55-H1-173A

ET502

ACCESS POWER

CONTROLLER PANEL

ACCESS DOOR

CONTROLLER

ELUPS

FIRE ALARM PANELS

DISC.

FIBER OPTIC

CABINETS

EXISTING

CARD READER

SECONDARY

BONDING

BUSBAR

C

D

BB

R1

DATA RACK,

TYP.

ET501

TYP.

TR

H1-173

229 SF 3

ET501

TYP.

D

BB

R1

TYP.

TELECOM.

H1-173

229 SF

TELECOM.

H1-173

229 SF

AREA OF WORK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES - KANSAS CITY, MO

Kansas City VAMC 4801 Linwood Blvd Kansas City, MO 64128

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

589-21-700

55ET401

BLDG 55 - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

LRL/SJM RDC/LLT

100% CONSTRUCTION

DOCUMENTS

06/19/2023

KEY PLAN

KEY NOTES

3/8" = 1'-0"55ET101

1 RM H1-173 - DEMOLITION FLOOR PLAN

3/8" = 1'-0"55ET101

2 RM H1-173 - TELECOMMUNICATIONS PLAN

3/8" = 1'-0"55ET101

4 RM H1-173 - OVERHEAD PLAN

3/8" = 1'-0"55ET101

3 RM H1-173 - DEMOLITION OVERHEAD PLAN

2'0 4' 6'

PROJECT

NORTH

1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING

SHALL BE DEMOLISHED BACK TO SOURCE.

PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND

SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

EXISTING CABLE TRAY TO BE DEMOLISHED.

SECONDARY BONDING BUSBAR. REFERENCE ELECTRICAL DETAIL SHEETS FOR ALL

BONDING DETAILS.

EXISTING DATA RACKS TO BE SALVAGED TO VA.

TRUE

NORTH

GENERAL NOTES

2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW 4"-SQUARE

BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING

FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE

J-HOOKS AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE…