Attachment 8 USAFP NFPA 25 Inspection.pdf
PDF 176 KB Posted
- Attached to
- RO Fire Protection Federal contract opportunity
- Solicitation number
- 127EAY26Q0052
About this file
This document is a fire protection system inspections, testing, and maintenance checklist based on NFPA 25 standards, provided by USA Fire Protection as a reference guide for facility owners and managers.
The checklist outlines a comprehensive preventive maintenance schedule for fire sprinkler and suppression systems across multiple time intervals: weekly inspections of control valves, temperature verification, and pressure gauges; monthly examinations of valve exteriors and air compressor conditions; quarterly visualizations of fire department connections and testing of relief valves; semi-annual testing of waterflow switches and nitrogen concentration verification; and annual operational tests of hose valves, control valves, partial trip tests of deluge systems, and lubrication of valve stems. Extended intervals include three-year operational testing of Class II hose valves and full flow trip tests; five-year internal inspections of pipe, deluge valves, and strainers, plus gauge replacement and hydrostatic testing; twenty-year sample testing of dry sprinkler heads and ESFR/CMSA units; twenty-five-year testing of fast-response sprinkler heads; and fifty and seventy-five-year testing protocols for all sprinkler heads with specified retesting intervals. The document includes a disclaimer that the checklist serves as a guide only and does not guarantee code compliance, recommending consultation with a fire and life safety professional and USA Fire Protection for jurisdiction-specific compliance assurance.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions and Answers 10 Sep 26.pdf | ||
| 127EAY26Q0052 Amendment 1.pdf | ||
| Site Visit.pdf | ||
| Attachment 7 Inspection and Testing Emergency Generators.pdf | ||
| 127EAY26Q0052 RO5 Fire Protection.pdf | ||
| Attachment 5 Equipment Photos.pdf | ||
| Attachment 9 Wage Determinaton.pdf | ||
| Attachment 4 Site Map.pdf | ||
| Attachment 6 Fire Pump Inspection Checklist.pdf | ||
| Attachment 2 Schedule of Items.xlsx | XLSX spreadsheet | |
| Attachment 3 Statement of Work.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment: E - Another Example
USAFP’S NFPA 25 INSPECTIONS, TESTING, & MAINTENANCE CHECKLIST
WEEKLY ITEMS
Ensure all control valves are in proper position
Verify temperature >40°F in valve enclosures
Verify RPZ relief is not constantly discharging
Check gauges to ensure the static water supply pressure & air pressure are normal
MONTHLY ITEMS
Examine the exterior of dry, preaction, deluge, & alarm check valves
Inspect the condition of the air compressors, wiring, air lines, & oil level
QUARTERLY ITEMS
Visualize Fire Department Connections (FDC)
Examine electronically supervised control valves
Check sprinkler system pressure reducing & relief valves
Visualize hose valves
Inspect supervisory signal devices & waterflow alarm devices
Main drain test for systems with backflow preventers
Test mechanical water motor gong if present
Test priming water level & quick opening devices on dry systems
SEMI-ANNUAL ITEMS
Test vane type waterflow switches
Test pressure type waterflow switches
Test valve supervisory switches
Verify nitrogen concentration in dry systems equipped with N2 generators
ANNUAL ITEMS
Inspect sprinklers, exposed pipe, & fittings from floor level
Inspect hose, hose cabinets, hose connections, nozzles, storage devices & stapipe piping
Inspect hangers & bracing
Inspect & flow hydrants
Interior inspection of dry valves
Verify proper signage is present
Confirm proper number & type of spare sprinklers & proper wrenches
Clean dry pipe valve internals
Empty low point drains
Operational test of Class I & Class III hose valves
Test control valves
Test any other supervisory signal devices
Partial trip test of dry, preaction, and/or deluge valves
Partial flow test of pressure regulating or pressure reducing valves
Lubricate stems of OS&Y valves
Lubricate hydrant stems, caps, plugs, & threads
3-YEAR ITEMS
Operational test of Class II hose valves
Full flow trip test of dry, preaction, &/or deluge valves
Air leakage test on dry &/or preaction systems
5-YEAR ITEMS
Internal inspection of pipe Internal inspection of non-externally resettable deluge, preaction, & check valves
Internal inspection of strainers, filters, & orifices
Test/Replace gauges Sample testing of extra high temperature heads exposed to maximum allowable temperature
Sample testing of heads in harsh environments
Full flow testing of private main hydrants Hydrostatic test of FDC piping
Hydrostatic test of manual & semiautomatic dry stapipe systems
Full flow of automatic stapipe systems
20-YEAR ITEMS
Sample testing of dry sprinkler heads Sample testing of ESFR & CMSA with fast-response elements (Retest every 10 years)
25-YEAR ITEMS
Sample testing of fast response sprinkler heads except ESFR & CMSA (Retest every 10 years)
50-YEAR ITEMS
Sample testing of all sprinkler heads (Retest every 10 years until the system is 75 years old)
75-YEAR ITEMS
Sample testing of all sprinkler heads (Retest every 5 years)
USA FIRE PROTECTION IS YOUR ALL-INCLUSIVE FIRE AND LIFE SAFETY SOLUTION!
CONTACT US
IL: (847) 816-0050 | SE WI: (262) 782-3311 | NE WI: (920) 836-3344
VISIT US ONLINE
usafireprotectioninc.com
This checklist serves as a guide & reference only. Per applicable NFPA provisions, it may not be comprehensive & cannot guarantee code compliance. Please consult a fire & life safety professional to ensure compliance in your jurisdiction. USA Fire Protection disclaims liability for any losses from reliance on this document & recommends contacting USA Fire Protection for compliance.
File details come from the government source that posted it. Updated .