Attachment 6 Fire Pump Inspection Checklist.pdf
PDF 546 KB Posted
- Attached to
- RO Fire Protection Federal contract opportunity
- Solicitation number
- 127EAY26Q0052
About this file
This document is a Fire Pump Inspection Checklist template based on NFPA 25 standards for inspection, testing, and maintenance (ITM) of water-based fire protection systems. The checklist is designed for weekly inspections of fire pump systems and is sourced from Exhibit 8.21 of the NFPA 25 Handbook.
The checklist covers four primary system categories requiring inspection: Pump House conditions (heating, ventilation, water accumulation, and coupling guards); Pump Systems (valve positions, piping integrity, pressure readings, suction reservoir levels, and waterflow test valve conditions); Electrical Systems (controller and transfer switch indicators, phase rotation, motor oil levels, and jockey pump power status); and Diesel Engine Systems (fuel tank levels, controller settings, battery voltage and charging readings, battery pilot lights, heat maintenance, and engine running time). Additional inspection items address water-jacket heaters, cooling systems, crankcase oil levels, battery terminals, flexible hose conditions, lube oil levels, and fuel tank water contamination. The template includes sections for steam-driven pump systems and exhaust system evaluations. Each inspection item includes Yes/No/Not Applicable response options. The form requires completion of property identification information, inspector details, contract number, date, and contractor credentials including name, address, and license/certification number. A comments section and signature line are provided for documentation purposes. This template is intended as a guide to support compliance with NFPA 25 and does not constitute comprehensive requirements under the standard.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions and Answers 10 Sep 26.pdf | ||
| 127EAY26Q0052 Amendment 1.pdf | ||
| Site Visit.pdf | ||
| Attachment 7 Inspection and Testing Emergency Generators.pdf | ||
| Attachment 9 Wage Determinaton.pdf | ||
| Attachment 4 Site Map.pdf | ||
| Attachment 8 USAFP NFPA 25 Inspection.pdf | ||
| 127EAY26Q0052 RO5 Fire Protection.pdf | ||
| Attachment 5 Equipment Photos.pdf | ||
| Attachment 2 Schedule of Items.xlsx | XLSX spreadsheet | |
| Attachment 3 Statement of Work.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment: C - Example
FIRE PUMP INSPECTION CHECKLIST
Fire pumps are an essential part of many water-based fire protection systems. The right design, installation, and acceptance testing of these pumps will help ensure that they are ready to protect the building on the day of the acceptance test. After that, once “the keys” are handed over to the building owner, there is no guarantee that the pump will remain in a ready state to work as designed unless it undergoes routine inspection, testing, and maintenance (ITM). This checklist from Exhibit 8.21 of the NFPA 25 Handbook: ITM of Water-Based Fire Protection Systems, covers just one aspect of an ITM program in weekly inspections. For more information on fire pumps and other NFPA products and solutions, visit: nfpa.org/fpssolutions.
FIRE PUMP WEEKLY INSPECTION
Property Name: Inspector:
Property Address: Contract No.:
Property Phone Number: Date:
Inspections: Weekly Pump House
❑ Yes
❑ No
❑ N/A
Heat in pump room is not less than 70 F (21 C) for diesel e engine heater
Pump Systems
Pump suction, discharge, and bypass valves are open
❑ Yes ❑ No ❑ N/A No piping or hoses leak
❑ Yes ❑ No ❑ N/A Fire pump leaking one drop of water per second at seals
❑ Yes ❑ No ❑ N/A Suction line pressure is within acceptable range
❑ Yes ❑ No ❑ N/A System line pressure is within acceptable range
❑ Yes ❑ No ❑ N/A Suction reservoir is full
❑ Yes ❑ No ❑ N/A Wet pit suction screens are unobstructed and in place
❑ Yes ❑ No ❑ N/A Waterflow test valves are in closed position, hose connection valve is line to test valves is free of water
Electrical Systems
❑ Yes ❑ No ❑ N/A Controller pilot light (power on) is illuminated
❑ Yes ❑ No ❑ N/A Transfer switch normal power light is illuminated
❑ Yes ❑ No ❑ N/A Isolating switch for standby power is closed
❑ Yes ❑ No ❑ N/A Reverse-phase alarm light is not illuminated
❑ Yes ❑ No ❑ N/A Normal-phase rotation light is illuminated
❑ Yes ❑ No ❑ N/A Oil level in vertical motor sight glass is within acceptable range
❑ Yes ❑ No ❑ N/A Pressure maintenance (jockey) pump has power
Diesel Engine Systems
❑ Yes ❑ No ❑ N/A Diesel fuel tank is at least two-thirds full
❑ Yes ❑ No ❑ N/A Controller selector switch is in “auto” position
❑ Yes ❑ No ❑ N/A Voltage readings for batteries (2) are within acceptable range
❑ Yes ❑ No ❑ N/A Charging current readings are within acceptable range for batteries
Pilot lights for batteries are “on” or battery failure pilot lights are “off” ❑ Yes ❑ No ❑ N/A
❑ Yes ❑ No ❑ N/A Heat in pump room is 40°F (4°C) or higher
❑ Yes ❑ No ❑ N/A Ventilation louvers are free to operate
❑ Yes ❑ No ❑ N/A Excessive water does not appear on the floor
❑ Yes ❑ No ❑ N/A Coupling guard is in place https://www.nfpa.org/News-and-Research/Publications-and-media/Blogs-Landing-Page/NFPA-Today/Blog-Posts/2021/04/02/Fire-Pump-Types http://www.nfpa.org/fpssolutions
FIRE PUMP INSPECTION CHECKLIST (continued)
FIRE PUMP WEEKLY INSPECTION (Continued)
Inspections: Weekly
❑ Yes ❑ No
All alarm pilot lights are “off”
❑ Yes ❑ No ❑ N/A Record engine running time from meter
❑ Yes ❑ No ❑ N/A Oil level is within acceptable range in right angle gear drive pumps
❑ Yes ❑ No ❑ N/A Crankcase oil level is within acceptable range
❑ Yes ❑ No ❑ N/A Cooling water level is within acceptable range
❑ Yes ❑ No ❑ N/A Electrolyte level in batteries is within acceptable range
❑ Yes ❑ No ❑ N/A Battery terminals are free of corrosion
❑ Yes ❑ No ❑ N/A Water-jacket heater is operational
❑ Yes ❑ No ❑ N/A Battery cranking voltage exceeds 9 volts for a 12 volt system system (Alternative ITM A.8.1.1.2)
❑ Yes ❑ No ❑ N/A Water pump(s) is not leaking (Alternative ITM A.8.1.1.2)
❑ Yes ❑ No ❑ N/A Jacket water heater operational (Alternative ITM A.8.1.1.2)
❑ No
❑ No
❑ N/A
❑ N/A
Flexible hose and connections are in good operating condition (Alterna
ITM A.8.1.1.2)
Check lube oil heater for operation (Alternative ITM A.8.1.1.2)
❑ Yes ❑ No ❑ N/A Oil lube level is within acceptable range (Alternative ITM A.8.1.1.2)
❑ Yes ❑ No ❑ N/A Check for water in diesel fuel tank (Alternative ITM A.8.1.1.2)
Steam System
❑ Yes ❑ No ❑ N/A For steam-driven pumps, steam pressure is within acceptable range
Exhaust System
Examine exhaust system for leaks (Alternative ITM A.8.1.1.2)
❑ Yes ❑ No ❑ N/A Drain condensate trap (Alternative ITM A.8.1.1.2)
Comments
Signature: Date:
Contractor Name:
Contractor Address:
License/Certification No.:
This information is provided to help users navigate NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2020 edition. It is not intended to be a comprehensive list of requirements under NFPA 25. Check with the local jurisdictions for specific requirements. This material does not represent the official position of NFPA or its technical committees on any referenced topic, which is represented solely by the NFPA documents in their entirety. For free access to the complete and most current version of all NFPA documents, please go to nfpa.org/docinfo. NFPA disclaims liability for any personal injury, property, or other damages of any nature whatsoever resulting from the use of this information. In using this information, you should rely on your independent judgment, and when appropriate, consult a competent professional.
© 2021 National Fire Protection Association / October 2021 http://www.nfpa.org/docinfo