SEMI-ANNUAL NFPA 2001 INSPECTION TEST AND
MAINTENANCE
NFPA 2001: Standard on Clean Agent Fire Extinguishing Systems Clean Agent Suppression Phillip Hair: FAC 3359 2022-07-13T13:50:19.220Z job number: 24977158 Hollings Marine Laboratory 331 Fort Johnson Road Charleston, SC 29412
This standard contains requirements for total flooding and local application clean agent fire extinguishing systems.
Monitoring Entity Name: All American Monitoring
Phone Number: (800)318-9486
Account Number: LR1218
Approving Agency Name: James Island Fire Dept
Phone Number: (843)795-2345
Control Unit Information Manufacturer: Fire Lite
Model: MRP-2002
Panel/Node Identifier:
Software Revision:
Type of Communicator: DACT - Digital Alarm Communicator Txr
Circuit Style: 4,Y
Number of SLC Circuits (if Applicable):
Number of NAC Circuits (if Applicable): 2
Number of Zones (if Applicable): 4
Integrated with bldg FACP: Yes
System Information Agent Common Name: FM200 (HFC 227)
Agent Type: Halocarbon
Integrated with sprinkler system? No-Stand Alone
System location: HFC 227
Releasing Mechanism type: Electric
Manufacturer Date (if applicable)
Time Delay (Yes,No) Yes
Time delay (seconds): 30
Notification Sequence 1st Alarm: 60 PPM
2nd Alarm: 120 PPM
Discharge: Steady
PART I - OWNER'S SECTION
Is the building occupied? Yes
Has the occupancy classification and hazard of contents remained the same since the last inspection? Yes
Are all fire protection systems in service? Yes
Has the system remained in service without modification since the last inspection? Yes
Was the system free of actuations of devices or alarms since the last inspection? Yes
Are design drawings available and on site? Yes
PART II - INSPECTION AND TESTING
MONTHLY
Releasing panel is powered and is free of supervisory, trouble, or alarm conditions? Yes
Manual controls are unobstructed? Yes
System shows no physical damage or condition that could prevent operation? Yes
Pressure gauges are in the operable range. Yes
Protected equipment and/or hazard has not been changed or modified. Yes
Any previously noted deficiencies have been corrected. Yes
ANNUALLY
Protected Enclosure:
Integrity and dimensions of the protected enclosure have remaind the same since last inspection? Yes
Walls are free of unsealed penetrations? Yes
Subfloor is free of unsealed penetrations and gaps? Yes
Door seals and closures appear to be functioning as designed? Yes
System Hoses:
All system hoses free of damage?
All system hoses have been hydro tested or replaced within the last 5 years? See cylinder details for dates. Yes
Agent Cylinders (Applies to Halocarbon & Inert Gas):
Cylinder brackets are secure? Yes
Cylinders have had an external visual inspection within the past 5 years? See cylinder details for dates. Yes
Discharge Piping:
Nozzles are clear and free of obstruction? Yes
All hangers are secure? Yes
Signage:
Warning and instruction sign present at entrance? Yes
Warning and instruction sign present inside protected environment? Yes
Control Panel & Power Supplies:
Control unit and power supplies are free of physical damage? Yes
All lamps, LEDs, and/or LCDs are functional? Yes
All fuses are functional? Yes
All disconnect switches and buttons are functional? Yes
Ground-fault monitoring is functional? Yes
Circuits properly monitored for integrity (Class A or Class B)? Yes
Local & Remote Annunciators:
All annunciators pass visual inspection? N/A
All annunciators pass functional test? N/A
Supervisory Devices:
All devices pass visual inspection? Yes
All devices pass functional test? Yes
Initiating Devices:
All devices pass visual inspection? Yes
All devices pass functional test? Yes
Notification Devices:
All devices pass visual inspection? Yes
All devices pass functional test? Yes
Notification devices operated in correct alarm sequence? Yes
Releasing mechanism:
Energized/activated as designed? Yes
For systems installed in 2016 and newer, actuator position is supervised? Yes
Abort switches operate as designed? Yes
Mode 1: Engaging pauses the countdown for as long as switch remains engaged. The countdown resumes when the switch is released.
Mode 2: Engaging resets timer to a predetermined value and pauses countdown for as long as switch remains engaged. The countdown restarts when the switch is released.
Mode 3: Engaging permits the timer to continue counting down untl it reaches predetermined value, then pauses for as long as the switch remains engaged. The countdown resumes from the predetermined value when the switch is released.
Bypass/disconnect swithes operate as designed? Yes
Pneumatic devices operate as designed? Yes
Manual releasing devices operate as designed? Yes
Time delays operate as designed? Yes
HVAC shutdowns operate as designed or bypassed for testing? If bypassed, explain reason in comments. N/A
Dampers operate as designed or bypassed for testing? If bypassed, explain reason in comments. N/A
EPO operates as designed or bypassed for testing? If bypassed, explain reason in comments. Yes
PART III - SYSTEM RESTORAL
All control heads and cylinders re-enabled? Tech Initials. PH
Date system was restored to normal: 7/13/22
Time system was restored to normal: 9:15
Device Type Frequency QTY Inventoried QTY Tested QTY Not Tested QTY Passed QTY Failed ANNUAL INSPECTION, TEST AND MAINTENANCE FOR PHOTOELECTRIC SMOKE DETECTOR Annual 2 2 0 2 0 ANNUAL INSPECTION, TEST AND MAINTENANCE FOR ION SMOKE DETECTOR Annual 2 2 0 2 0 ANNUAL INSPECTION, TEST AND MAINTENANCE FOR BELL Annual 1 1 0 1 0 ANNUAL INSPECTION, TEST AND MAINTENANCE FOR HORN/STROBE Annual 1 1 0 1 0 SEMI-ANNUAL INSPECTION, TEST AND MAINTENANCE FOR BATTERIES Semi-Annual 1 1 0 0 1
SEMI-ANNUAL INSPECTION, TEST AND MAINTENANCE FOR CLEAN AGENT HALOCARBON
CYLINDER
Semi-Annual 2 2 0 0 2
Device Type Frequency QTY Inventoried QTY Tested QTY Not Tested QTY Passed QTY Failed SEMI-ANNUAL INSPECTION, TEST AND MAINTENANCE FOR ABORT SWITCH Semi-Annual 2 2 0 2 0 ANNUAL INSPECTION, TEST AND MAINTENANCE FOR AGENT RELEASE MANUAL STATION Annual 2 2 0 2 0
Semi-Annual Inspection, Test and Maintenance for Batteries Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Inside alarm panel Batteries 07-13-2022 Phillip Hair Tested Failed
Panel Make: N/A
Panel Model: N/A
Breaker Panel Location: N/A
Breaker Panel: N/A
Circuit Breaker: N/A
Amp Hour Rating (AH): 7
Charger Test Voltage (VDC): 25.3
Load Voltage: 12V
Load Amperage: 7A
Discharge Voltage: 13.2
Load Voltage: 12V
Load Amperage: 7A
Discharge Voltage: 13.1
Was the charger voltage within parameters? Yes
Was the load voltage of both batteries within required parameters? Yes
Was the load amperage of both batteries within required parameters? Yes
Was the discharge voltage of both batteries within required parameters? Yes
Install Date (MM/YY) 12/13
Can the batteries remain in service considering manufacturers recommendations (such as date of manufacture, service temperature, and integrity of the casing)?
No
Semi-Annual Inspection, Test and Maintenance for Clean Agent Halocarbon Cylinder Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Server rm H223 Clean Agent Halocarbon Cylinder
07-13-2022 Phillip Hair Tested Failed
Record tag is present on all cylinders with the following information? Yes
Container pressure and temp. is appropriate per the given ambient room temp. according to manufacturer? Yes
Cylinders have not had a loss in agent quantity greater than 5%, and/or a loss in pressure of more than 10%. Yes
Manufacturer: Pyro Chem
Room Temp (in Fahrenheit): 70
Serial Number: 373027
Liquid Level (if applicable): N/A
Pressure (PSI): N/A
Scale Weight (lbs) if no Liquid Level: N/A
Full Weight (lbs): N/A
Agent Weight (lbs): N/A
Cylinder Hydro Date (if applicable): 2008
Cylinder Visual 5 Year Date: N/A
Hose Hydro Date (If applicable): 2008
Initiator Date (if applicable): N/A
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Server rm H223 Clean Agent Halocarbon Cylinder
07-13-2022 Phillip Hair Tested Failed
Record tag is present on all cylinders with the following information? Yes
Container pressure and temp. is appropriate per the given ambient room temp. according to manufacturer? Yes
Cylinders have not had a loss in agent quantity greater than 5%, and/or a loss in pressure of more than 10%. Yes
Manufacturer: Pyro Chem
Room Temp (in Fahrenheit): 70
Serial Number: 373024
Liquid Level (if applicable): N/A
Pressure (PSI): N/A
Scale Weight (lbs) if no Liquid Level: N/A
Full Weight (lbs): N/A
Agent Weight (lbs): N/A
Cylinder Hydro Date (if applicable): 2008
Cylinder Visual 5 Year Date: N/A
Hose Hydro Date (If applicable): N/A
Initiator Date (if applicable): N/A
Annual Inspection, Test and Maintenance for Ion Smoke Detector
Inside Server RM H223 Ion Smoke Detector 07-13-2022 Phillip Hair Tested Passed
Was smoke detector tested in place to ensure smoke entry into the sensing chamber? Yes
Did the detector activate an alarm reponse? Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Inside Server RM H223 Ion Smoke Detector 07-13-2022 Phillip Hair Tested Passed
Was smoke detector tested in place to ensure smoke entry into the sensing chamber? Yes
Did the detector activate an alarm reponse? Yes
Annual Inspection, Test and Maintenance for Photoelectric Smoke Detector Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Inside server Rm H223 Photoelectric Smoke Detector
07-13-2022 Phillip Hair Tested Passed
Was smoke detector tested in place to ensure smoke entry into the sensing chamber? Yes
Did the detector activate an alarm reponse? Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Inside Server RM H223 Photoelectric Smoke Detector
07-13-2022 Phillip Hair Tested Passed
Was smoke detector tested in place to ensure smoke entry into the sensing chamber? Yes
Did the detector activate an alarm reponse? Yes
Annual Inspection, Test and Maintenance for Agent Release Manual Station Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Inside Server RM H223 Agent Release Manual Station
07-13-2022 Phillip Hair Tested Passed
Did the manual station operate as per the manufacturer's published instructions? Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Inside Server RM H223 Agent Release Manual Station
07-13-2022 Phillip Hair Tested Passed
Did the manual station operate as per the manufacturer's published instructions? Yes
Semi-Annual Inspection, Test and Maintenance for Abort Switch Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Inside Server RM H223 Abort Switch 07-13-2022 Phillip Hair Tested Passed
Please select Mode Type Mode 3
Abort switches operate as designed? Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Inside Server RM H223 Abort Switch 07-13-2022 Phillip Hair Tested Passed
Please select Mode Type Mode 3
Abort switches operate as designed? Yes
Annual Inspection, Test and Maintenance for Bell
Outside Server RM Bell 07-13-2022 Phillip Hair Tested Passed
Did the notification appliance operate audibly? Yes
Annual Inspection, Test and Maintenance for Horn/Strobe Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Inside Server RM H223 Horn/Strobe 07-13-2022 Phillip Hair Tested Passed
Did the notification appliance operate audibly? Yes
Did the notification appliance operate visibly? Yes
Deficiencies
Identifier Address Location Description Device Type Date of Failure
N/A Inside alarm panel Batteries 07-13-2022
Reason for Failure Non-Addressable Batteries, Inside alarm panel
Recommended Fix Action Batteries are outdated and will need to be replaced
Code Reference NFPA 72 2013 Table 14.4.3.2 (9) (c) (1)
Identifier Address Location Description Device Type Date of Failure
N/A Server rm H223 Clean Agent Halocarbon Cylinder
07-13-2022
Reason for Failure Non-Addressable Clean Agent Halocarbon Cylinder, Server rm H223
Recommended Fix Action Needs to be hydro
Code Reference N/A
Identifier Address Location Description Device Type Date of Failure
N/A Server rm H223 Clean Agent Halocarbon Cylinder
07-13-2022
Reason for Failure Non-Addressable Clean Agent Halocarbon Cylinder, Server rm H223
Recommended Fix Action Needs to be hydro
Code Reference N/A
Comments
Panel is normal upon departure