SEMI-ANNUAL NFPA 25 VISUAL AND
FUNCTIONAL INSPECTION
Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems Wet Joey Lindsey:
2022-07-19T22:47:52.343Z job number: 24977158 Hollings Marine Laboratory 331 Fort Johnson Road Charleston, SC 29412
Information on this form covers the minimum requirements of NFPA 25 for fire sprinkler systems.
PART I - OWNER'S SECTION
Is the building occupied? Yes
Has the occupancy classification and hazard of contents remained the same since the last inspection? Yes
Are all fire protection systems in service? Yes
Has the system remained in service without modification since the last inspection? Yes
Was the system free of actuations of devices or alarms since the last inspection? Yes
PART II - INSPECTION AND TESTING
DAILY & WEEKLY
Inspection Items Control valves supervised with seals are accessible and in correct (Open or Closed) position? Yes
MONTHLY
Inspection Items
Control valves with locks or electrical supervision are accessible and in correct (Open or Closed) position? Yes
Sprinkler wrench with spare sprinklers? Yes
Gauges in wet- pipe system in good condition and showing normal water supply pressure? Yes
Alarm valve - exterior:
Gauges show normal supply water pressure is being maintained? Yes
Valves and trim are free from physical damage? Yes
Valves in appropriate open or closed position? Yes
The retarding chamber or alarm drains are not leaking? Yes
QUARTERLY
Inspection Items
Fire Department Connections (If applicable, see FDC List):
Waterflow alarm and supervisory signal initiating devices free from physical damage? Yes
Gauges monitoring water pressure show that normal supply pressure is being maintained? Yes
Testing Items Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes
Post indicating valves opened until spring or torsion is felt in the rod, then closed back one-quarter turn? Yes
Main drain test - if the sole supply is through a backflow preventer or pressure-reducing valve.
Record Static & Residual Pressure:
Please see attached Main Drain List
SEMI-ANNUALLY
Testing Items
Valve supervisory switches indicate movement?
Vane-type and pressure switch-type water flow alarm devices passed tests by opening the inspector's test connection with alarms actuating and flow observed?
Yes
Device Type Frequency QTY Inventoried
QTY Tested QTY Not Tested
QTY Passed QTY Failed
SEMI-ANNUAL INSPECTION, TEST AND MAINTENANCE FOR OUTSIDE STEM AND YOKE-
CONTROL VALVE WITH TAMPER SWITCH
Semi-Annual 3 3 0 3 0
QUARTERLY INSPECTION, TEST AND MAINTENANCE FOR MAIN DRAIN Quarterly 5 5 0 5 0
SEMI-ANNUAL INSPECTION, TEST AND MAINTENANCE FOR INTERNAL BUTTERFLY VALVE-
CONTROL VALVE WITH TAMPER SWITCH
Semi-Annual 1 1 0 1 0
QUARTERLY INSPECTION, TEST AND MAINTENANCE FOR FIRE DEPARTMENT CONNECTION Quarterly 1 1 0 1 0
Semi-Annual Inspection, Test and Maintenance for Internal Butterfly Valve-Control Valve with Tamper Switch
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
BLS3/ Section A, B, C, D, E Internal Butterfly Valve- Control Valve with Tamper Switch
07-19-2022 Joey Lindsey Tested Passed
Valve size (inches): N/A
In the normal open or closed position? Yes
Sealed, locked, or supervised? Yes
Accessible? Yes
Free from external leaks Yes
Provided with applicable identification Yes
Operated through its full range and returned to its normal position? Yes
A distinctive signal indicated movement from the valve’s normal position during either the first two revolutions of the hand wheel or when the stem of the valve moved one-fifth of the distance from its normal position?
Yes
Quarterly Inspection, Test and Maintenance for Main Drain Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
BLS3/ Section A, B, C, D, E Main Drain 07-19-2022 Joey Lindsey Tested Passed
Gauge Year (if applicable): 2017
Static Pressure (PSI): 90
Residual Pressure (PSI): 65
Was pressure within 10% of the previous test? Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Section F Main Drain 07-19-2022 Joey Lindsey Tested Passed
Gauge Year (if applicable): 2017
Static Pressure (PSI): 90
Residual Pressure (PSI): 65
Was pressure within 10% of the previous test? Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Section H 1st fl offices Main Drain 07-19-2022 Joey Lindsey Tested Passed
Gauge Year (if applicable): 2017
Static Pressure (PSI): 90
Residual Pressure (PSI): 65
Was pressure within 10% of the previous test? Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Section H 2nd fl offices Main Drain 07-19-2022 Joey Lindsey Tested Passed
Gauge Year (if applicable): 2017
Static Pressure (PSI): 95
Residual Pressure (PSI): 65
Was pressure within 10% of the previous test? Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Section H 1st fl labs Main Drain 07-19-2022 Joey Lindsey Tested Passed
Gauge Year (if applicable): 2017
Static Pressure (PSI): 90
Residual Pressure (PSI): 65
Was pressure within 10% of the previous test? Yes
Quarterly Inspection, Test and Maintenance for Fire Department Connection Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Fort Johnson rd side of building Fire Department Connection
07-19-2022 Joey Lindsey Tested Passed
Hydrostatic test of the piping from the FDC to the fire department check valve performed at 150 PSI for 2 hours in the last 5 years (if applicable)?
Yes
Year of last 5 year hydrostatic test (if applicable)? N/A
Visible and accessible? Yes
Coupling/swivels in place and operate correctly? Yes
Plugs/caps are in place? Yes
Gaskets are not damaged? Yes
Identification signs are in place? Yes
Check Valve is not leaking? Yes
Automatic drain valve is in place and operating properly? Yes
Clapper(s) operates correctly? Yes
Interior is clear of obstructions? Yes
Visible piping supplying the FDC is undamaged? Yes
Semi-Annual Inspection, Test and Maintenance for Outside Stem and Yoke-Control Valve with Tamper Switch
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Backflow suction control Outside Stem and Yoke- Control Valve with Tamper Switch
07-19-2022 Joey Lindsey Tested Passed
Valve size (inches): N/A
In the normal open or closed position? Yes
Sealed, locked, or supervised? Yes
Accessible? Yes
Free from external leaks Yes
Provided with applicable identification Yes operated through its full range and returned to its normal position? Yes
A distinctive signal indicated movement from the valve’s normal position during either the first two revolutions of the hand wheel or when the stem of the valve moved one-fifth of the distance from its normal position?
Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Backflow discharge control Outside Stem and Yoke- Control Valve with Tamper Switch
07-19-2022 Joey Lindsey Tested Passed
Valve size (inches): N/A
In the normal open or closed position? Yes
Sealed, locked, or supervised? Yes
Accessible? Yes
Free from external leaks Yes
Provided with applicable identification Yes operated through its full range and returned to its normal position? Yes
A distinctive signal indicated movement from the valve’s normal position during either the first two revolutions of the hand wheel or when the stem of the valve moved one-fifth of the distance from its normal position?
Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
A131 Mech room sectional control Outside Stem and Yoke- Control Valve with Tamper Switch
07-19-2022 Joey Lindsey Tested Passed
Valve size (inches): N/A
In the normal open or closed position? Yes
Sealed, locked, or supervised? Yes
Accessible? Yes
Free from external leaks Yes
Provided with applicable identification Yes operated through its full range and returned to its normal position? Yes
A distinctive signal indicated movement from the valve’s normal position during either the first two revolutions of the hand wheel or when the stem of the valve moved one-fifth of the distance from its normal position?
Yes