ATTACHMENT 4 - Electrical.pdf

PDF 12 MB Posted

Attached to
Y1DZ--Expand and Renovate B400 for Urgent and Primary Care (Minor) - Tomah
Solicitation number
36C77621B0009
Issued by

About this file

This document provides details for a federal contract opportunity to expand and renovate an existing medical facility. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting bids under solicitation number 36C77621B0009 to completely prepare the site for building operations at the Tomah VA Medical Center in Wisconsin. This includes demolition and removal of existing structures as well as furnishing all labor, materials, and work to expand and renovate the B400 building for urgent and primary care services as outlined in the attached drawings and specifications, specifically the electrical drawings and specifications in Attachment 4. Bidders should reference the provided solicitation number and opportunity details when preparing a response for this contract by the specified response date to expand and upgrade primary care facilities for veterans at the Tomah VA Medical Center.

View the file

Other files

File Type Posted
31 23 19 DEWATERING.pdf PDF
36C77621B0009 0003.pdf PDF
Drawings VF100 - VF101.pdf PDF
Technical Questions - FINAL - Tomah 8-2-21.pdf PDF
36C77621B0009 0002.pdf PDF
ATTACHMENT 17 - Construction Wage Rates - Monroe County - 7-9-21.pdf PDF
Site Visit Sign-in Sheet - Tomah - 9 AM - 7-12-21.pdf PDF
36C77621B0009 0001.pdf PDF
Site Visit Sign-in Sheet - Tomah - 10 AM - 7-13-21.pdf PDF
ATTACHMENT 20 - Site Visit Registration - Map.pdf PDF
36C77621B0009 - 6-29-21.pdf PDF
ATTACHMENT 15 - Fire Alarm.pdf PDF
ATTACHMENT 7 - Fire Protection.pdf PDF
ATTACHMENT 16 - Contractor Core Work Hours.pdf PDF
ATTACHMENT 17 - Construction Wage Rates - Monroe County - 5-14-21.pdf PDF
ATTACHMENT 12 - Furniture.pdf PDF
ATTACHMENT 13 - Civil.pdf PDF
ATTACHMENT 11 - Architectual.pdf PDF
ATTACHMENT 8 - Equipment.pdf PDF
ATTACHMENT 1 - Specifications Final 6-21-21.pdf PDF
ATTACHMENT 6 - Plumbing.pdf PDF
ATTACHMENT 2 - General.pdf PDF
ATTACHMENT 19 - Contractor Safety - Environmental Form.docx DOCX document
ATTACHMENT 10 - Signage.pdf PDF
ATTACHMENT 18 - Limitations on Subcontracting - Construction.docx DOCX document
ATTACHMENT 5 - Mechanical.pdf PDF
ATTACHMENT 9 - Interiors.pdf PDF
ATTACHMENT 3 - Structural.pdf PDF
ATTACHMENT 14 - Hazard.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FF-X

CUH-X

P

C

TC

C

12"x2"

A

A

#X

PT

ML

D

REX

P

C

K

J

J

V

C

S

S

M

M

S

SD

RT

C

F

S

S

H

H

HD

HD

SD

SD

SD

SD

SD

SD

SD

FD

A

M

R

SV

FS

TS

DIZ

DPE

SB

IZ

H

PE

F

F

#X

FA

SD

SBC

SS

PS

R

D

HD

M

C

VFD-X

T

DO

DO

E

T

T

H

TR

D

DF

G

G

TGB

TMGB

A

SI

a

D

A a

A a

A a

A a

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A a

T S

0-10V

P

U

D

MC

P

LV

KMC

L

LTS

LC

K

A V

I

I

I

I

GEN

A

H

S

D N

N

V N

S N

B

E

NC

A

J

E-1

E-1

HEARING AID

VISITOR INTERCOM

NURSE CALL WALL DOUBLE SIDED LIGHT -

1,2 OR 4 LIGHTS

NURSE CALL ANNUNCIATOR PANEL

NURSE CALL WALL LIGHT - 1,2 OR 4 LIGHTS

VISUAL NURSE CALL STATION

GEN-SET ANNUNCIATOR PANEL

INTERCOM HANDSET OUTLET

INTERCOM CALL SWITCH AND SPEAKER

NURSE CALL STATION

NURSE CALL DUTY STATION

NURSE CALL ZONE LIGHT - 1,2 OR 4 LIGHTS

NURSE CALL EMERGENCY STATION

NURSE CALL BATH STATION

NURSE CALL STAFF STATION

INTERCOM CALL SWITCH AND SPEAKER-SECURITY

RELAY

PHOTOCELL

LOWER CASE LETTER INDICATES SWITCH CIRCUIT ID (IF USED), LETTER

INDICATES TYPE, ARROWS INDICATE DIRECTION.

TYPE

SW ID

SINGLE POLE RECEPTACLE

PENDANT FIXTURE

CEILING FAN

(SUBSCRIPT INDICATES TYPE)

NURSE CALL

FIRE/SMOKE DAMPER

0-10V DIMMER SWITCH

3-WAY DIMMER SWITCH

UL924 RELAY

DAYLIGHT SENSOR - DIGITAL

DAYLIGHT SENSOR

POWER PACK (LETTER INDICATES TYPE)

AUTOMATIC LIGHTING CONTROL

CONDUIT IN WALL OR CEILING

CONDUIT IN FLOOR OR UNDERGROUND

HAND DRYER

DROP CORD OUTLET

ISOLATED DUPLEX RECEPTACLE

GFCI DUPLEX RECEPTACLE

MANUAL MOTOR SWITCH

CAR POST HEATER

TAMPER PROOF RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

SPECIAL RECEPTACLE

RECEPTACLE DEVICE ON EMERGENCY CIRCUIT

MOTOR

HALF SWITCH DUPLEX RECEPTACLE

IN-GRADE LIGHT FIXTURE (ARROW INDICATES AIMING DIRECTION)

DIGITAL SWITCH

DIGITAL DIMMER SWITCH

SMOKE DETECTOR- WALL MOUNTED

REMOTE TEST SWITCH

FIRE ALARM CHIME STROBE

SERIAL INTERFACE, ISOLATED RELAY, ETC.)

LIGHTING CONTROL DEVICE (PARTITION SENSOR,

DUAL TECHNOLOGY (CEILING) - DIGITAL

ULTRASONIC (CEILING) - DIGITAL

PIR (CEILING) - DIGITAL

DUAL TECHNOLOGY (CEILING) - STAND ALONE

ULTRASONIC (CEILING) - STAND ALONE

PIR (CEILING) - STAND ALONE

ULTRASONIC (CEILING) - DIGITAL

ULTRASONIC (CEILING) - STAND ALONE

LIGHTING TOUCH SCREEN

ROOM CONTROLLER (LIGHTING / AV EQUIP)

DUAL TECHNOLOGY (WALL) - DIGITAL

DUAL TECHNOLOGY (CEILING) - DIGITAL

ULTRASONIC (WALL) - DIGITAL

ULTRASONIC (CEILING) - DIGITAL

PIR (WALL) - DIGITAL

PIR (CEILING) - DIGITAL

DUAL TECHNOLOGY (WALL) - STAND ALONE

DUAL TECHNOLOGY (CEILING) - STAND ALONE

ULTRASONIC (WALL) - STAND ALONE

ULTRASONIC (CEILING) - STAND ALONE

PIR (WALL) - STAND ALONE

PIR (CEILING) - STAND ALONE

CAST-IN-PLACE FLOOR BOX (LETTER INDICATES TYPE)

ELECTRICAL SYMBOLS

DUCT SMOKE DETECTOR- IONIZATION

DUCT SMOKE DETECTOR- PHOTO ELECTRIC

SMOKE DETECTOR- SOUNDER BASE

SMOKE DETECTOR- IONIZATION

SMOKE DETECTOR- WITH HEAT DETECTOR

SMOKE DETECTOR- PHOTO ELECTRIC

ACCESS

CONTACTOR

RELAY

VARIABLE FREQUENCY DRIVE

EQUIPMENT/CONTROL CABINET

PANELBOARD

COMBINATION STARTER DISCONNECT

TELEPHONE/DATA BACKBOARD

METER SOCKET

LOW VOLTAGE TRANSFORMER

MAGNETIC MOTOR STARTER

DISCONNECT

DISTRIBUTION

FIRE ALARM

AUDIO/VISUAL

MISCELLANEOUS

ELECTRIC HEATING

LIGHTING CONTROL

ELECTRICAL DEVICE

LIGHTING

WIRING AND RACEWAY

SHEET

FIRE ALARM RELAY

FIRE ALARM SPEAKER/STROBE

FIRE ALARM SPEAKER

FLAME DETECTOR

POWER SUPPLY

POWER TRANSFER DEVICE

REQUEST TO EXIT

PROXIMITY READER

PROJECTOR

MOTORIZED DAMPER, INTERLOCK WITH MOTOR #X

MASTER CLOCK STATION

CLOCK SPEAKER

DOOR BELL/CHIME

120V SINGLE STATION SMOKE DETECTOR

INDIVIDUAL ADDRESSABLE MONITOR MODULE

INDIVIDUAL ADDRESSABLE CONTROL MODULE

FIRE/SMOKE DAMPER (MECHANICAL)

DUAL HEAD PARKING LOT LIGHT FIXTURE

CEILING EMERGENCY BATTERY LIGHT FIXTURE

STUB-OUT/TERMINATION

BREAK OR CONTINUATION

GROUND

FAN FORCED HEATER

CEILING RADIANT HEAT PANEL

CARD READER

LOW-VOLTAGE SWITCH

RECESSED LIGHT FIXTURE ON EMERGENCY/LIFE SAFETY

PUSHBUTTON (LETTER(S) INDICATES TYPE)

GARAGE DOOR SAFETY SWITCH

SURFACE LIGHT FIXTURE ON EMERGENCY/LIFE SAFETY

STRIP LIGHT

ADA DOOR OPENER

MAGNETIC DOOR LOCK

CAMERA

RESIDENT ROOM NIGHT LIGHT

BELL

HUMIDISTAT

TRIPLE PUSH BUTTON

FIRE ALARM ANNUNCIATOR PANEL

WALL MOUNTED JUNCTION BOX

SINGLE HEAD PARKING LOT LIGHT FIXTURE

LIGHT FIXTURE ON EMERGENCY/LIFE SAFETY

RECESSED MOUNTED LIGHT FIXTURE (2X4 AND 2X2 REPRESENTED)

SHEET NUMBER SHOWN (E-1)

WITH DRAWING NUMBER SHOWN (1) AND

ELEVATION / SECTION NOTE REFERENCE

SHEET NUMBER SHOWN (E-1)

WITH DRAWING NUMBER SHOWN (1) AND

DETAIL NOTE REFERENCE

SHEET NOTE REFERENCE

REVISION NOTE REFERENCE

SURFACE MOUNTED LIGHT FIXTURE

DOOR POSITION SWITCH/DOOR CONTACTOR

SYSTEMS OUTLET (# & LETTER INDICATES QUANTITY & TYPE)

COMBINATION RATE OF RISE HEAT DETECTOR

TAMPER SWITCH

SOLENOID VALVE

FIRE ALARM HORN

DOUBLE PUSH BUTTON

SINGLE PUSH BUTTON

HORN SPEAKER

COMBINATION AUDIO/VISUAL FIRE ALARM

THERMOSTAT BY DIVISION 23

THERMOSTAT BY DIVISION 26

TIME CLOCK

FIRE ALARM STROBE LIGHT

MANUAL PULL STATION

FIXED TEMPERATURE HEAT DETECTOR W/ SETTING

FLOW SWITCH

MAGNETIC DOOR HOLDER

CLOCK - WALL MOUNTED

WALL SPEAKER

(LETTER INDICATES TYPE)

RECESSED CEILING SPEAKER

MICROPHONE OUTLET

VOLUME CONTROL SWITCH

DUAL MICROPHONE OUTLET

KEYPAD

ELECTRIC DOOR STRIKE

CABINET UNIT HEATER (CUH)

EMERGENCY BATTERY LIGHT FIXTURE

WALL MOUNTED LIGHT FIXTURE

RECESSED LIGHT FIXTURE

EMERGENCY LIGHT/REMOTE HEAD

SURFACE LIGHT FIXTURE

BOLLARD TYPE SITE LIGHT FIXTURE

NON-CONTINUOUS CABLE SUPPORTS

CEILING EXIT LIGHT FIXTURE

WALL EXIT LIGHT FIXTURE

DARK DASHED INDICATES ITEMS TO BE REMOVED

SINGLE POLE SWITCH

KEYED SWITCH

FOUR-WAY SWITCH

THREE-WAY SWITCH

SWITCH AND PILOT LIGHT

DIMMER SWITCH

JUNCTION BOX

POKE-THRU FLOOR BOX (LETTER INDICATES TYPE)

ELECTRIC HEAT

CONDUIT STUB-DOWN

CONDUIT STUB-UP

LADDER RACK

CABLE TRAY (NUMBERS INDICATE SIZE)

DUPLEX 20A, 125V,2P,3W RECEPTACLE

KEYED MOMENTARY CONTACT SWITCH

MOMENTARY CONTACT SWITCH

* ALL SYMBOLS AND ABBREVIATIONS DO NOT NECESSARILY APPEAR ON DRAWINGS *

SMOKE DETECTOR- SOUNDER BASE W / CO

HAND OFF-AUTO SWITCH

DUPLEX RECEPTACLE ON DEDICATED CIRCUIT

REMOTE DEAD FRONT GFCI TEST/RESET SWITCH

GROUND BAR (TMGB)

GROUND BAR (TGB)

TIME SWITCH

AV ROUGH-IN / JACKS

S

S

S

D

D

D

S

S

S

S

S

S

S

D

S

S

GFCI DOUBLE DUPLEX RECEPTACLE

MOTOR WITH MOTOR RATED

TOGGLE SWITCH DISCONNECT

S

U DUPLEX RECEPTACLE WITH USB

ELECTRIC BASEBOARD HEAT

OS EXISTING GENERIC OCCUPANCY SENSOR

RB REMOTE BATTERY

CO CARBON DIOXIDE DETECTOR

FSD

S

A

A

DUPLEX RECEPTACLE FLOOR MOUNTED

HORIZONTAL DUPLEX RECEPTACLE

PRV

PNL

PMH

PH

PA

P

NUCC

NO

NL

NIC

NF

NEU

NEMA

NEC

NC

MTS

MTD

MSWBD

MIN

MFS

MFG

MGA

MECH

MDP

M.C.

MCC

XFMR

WP

WH

WG

W/

VA

V

UH

UG

TYP

TV

TSTAT

THRU

TELE

TCR

TCP

SWBD

SUSE

STRUC

SSS

SPC

SE

RS

RNC

RMC

RGP

PVC

ELECTRICAL

ELECTRICAL CONTRACTOR

DRAWING

DOWN

DIRECT BURIED

CABINET UNIT HEATER

CONTRACTOR

COMMUNICATION

COMBINATION

CIRCUIT

CUBIC FEET PER MINUTE

CLOSED CIRCUIT TELEVISION

CRITICAL CARE

CIRCUIT BREAKER

CABINET

CONDUIT

BELOW CABINET

AUTOMATIC TRANSFER SWITCH

APPROXIMATE

AUDIO/ VISUAL

ANNUNCIATOR

ABOVE GRADE

ABOVE FINISHED FLOOR

AIR CONDITIONER

ABOVE COUNTER

AMPERE

AT

ELEC

E.C.

DWG

DN

DB

CUH

CONTR

COMM

COMB

CCT

CFM

CCTV

CC

C.B.

CAB

C.

BC

ATS

APPROX

A/V

ANNUC

AG

AFF

A/C

AC

A

@ POWER ROOF VENTILATOR

PANELBOARD

PULSE START METAL HALIDE

PHASE

PUBLIC ADDRESS

PUMP

CONDUIT WITH CONDUCTORS

NONMETALLIC UNDERGROUND

NORMALLY OPEN

NIGHT LIGHT

NOT IN CONTRACT

NON-FUSED

NEUTRAL

NATIONAL ELEC MFG ASSOCIATION

NATIONAL ELECTRICAL CODE

NORMALLY CLOSED

MANUAL TRANSFER SWITCH

MOUNTED

MAIN SWITCHBOARD

MINIMUM

MAXIMUM FUSE SIZE

MANUFACTURER

MEDICAL GAS ALARM PANEL

MECHANICAL

MAIN DISTRIBUTION PANEL

MECHANICAL CONTRACTOR

MOTOR CONTROL CENTER

KILOVOLT AMPS

LIFE SAFETY

LIQUID TIGHT FLEXIBLE NONMETALLIC CONDUIT

LIQUID TIGHT FLEXIBLE METAL CONDUIT

INTERMEDIATE METAL CONDUIT

HORSEPOWER OR HEAT PUMP

HAND-OFF-AUTO

GROUND

GROUND FAULT CIRCUIT INTERRUPT

GENERAL CONTRACTOR

FEET

FIBER OPTIC

FLEXIBLE METALLIC TUBING

FLEXIBLE METAL CONDUIT

FIRE ALARM CONTROL UNIT

FIRE ALARM ANNUNCIATOR

FIRE ALARM

EXPLOSION PROOF

EXHAUST FAN

EXISTING

EYE WASH/ EMERGENCY SHOWER

ELECTRIC WATER COOLER

EQUIPMENT SUPPLIER

ELECTRICAL NONMETALLIC TUBING

ENCLOSURE

ELECTRICAL METALLIC TUBING

ELEVATION OR ELEVATOR

KVA

LS

LFNC

LFMC

IMC

HP

HOA

GND

GFCI

G.C.

FT

FO

FMT

FMC

FACU

FAA

FA

EXP

EXH

EX

EWS

EWC

E.S.

ENT

ENCL

EMT

ELEV

TRANSFORMER

WEATHERPROOF

WATER HEATER

WIRE GUARD

WITH

VOLT AMPERE

VOLT

UNIT HEATER

UNDERGROUND

TYPICAL

TELEVISION

THERMOSTAT

THROUGH

TELEPHONE

TELECOMMUNICATIONS ROOM

TEMPERATURE CONTROL PANEL

SWITCHBOARD

SUITABLE FOR USE AS SERVICE EQUIP.

STRUCTURAL

SOLID STATE STARTER

SINGLE POINT CONNECTION

SERVICE ENTRANCE

RIGID STEEL (CONDUIT)

RIGID NONMETALLIC CONDUIT

RIGID METAL CONDUIT

REFERENCE GROUND POINT

POLYVINYL-CHLORIDE (CONDUIT)

ELECTRICAL ABBREVIATIONS

NTS NOT TO SCALE

LC-XX LIGHTING CONTROL SCHEDULE NOTE

DEDUCT ALTERNATE #1: REMOVE B407 NORTH SWING SPACE.

DEDUCT ALTERNATE #2: REMOVE B407 SOUTH SWING SPACE, BATHROOM REFRESH, AND IT CLOSET

INFRASTRUCTURE FROM PROJECT.

DEDUCT ALTERNATE #3: REMOVE SEALED BUBBLE WALL FOUNTAIN IN WAITING ROOM 1082 FROM PROJECT.

DEDUCT ALTERNATE #4: REBUILD (E) AHU RATHER THAN INSTALL A NEW ONE.

DEDUCT ALTERNATE #5: REMOVE EXTERIOR ENTRANCE CANOPY AT STAFF LOUNGE 1102.

DEDUCTIVE ALTERNATE:

GFCI RECEPTACLE DEVICE ON EMERGENCY CIRCUIT

GENERAL ELECTRICAL DEMOLITION NOTES:

A. DEMOLISH AND EXTEND EXISTING ELECTRICAL WORK AS INDICATED ON DRAWINGS, UNDER PROVISIONS OF DIVISION 01, AND SPEC SECTION 26 0500.

B. WHERE NOTED, EQUIPMENT REMOVED AND NOT NOTED AS SALVAGE FOR REUSE SHALL BE REMOVED FROM THIS JOB SITE AND LEGALLY DISPOSED OF BY ELECTRICAL CONTRACTOR.

C. MATERIALS AND EQUIPMENT INDICATED TO BE SALVAGED: REMOVE, DEMOUNT, DISCONNECT, AND DELIVER SAME TO A LOCATION DESIGNATED FOR STORAGE. LEAVE IN GOOD CONDITION AND STORE IN ORDERLY MANNER.

D. ALL EQUIPMENT TO BE SALVAGED SHALL BE CHECKED FOR DAMAGE AND CLEANED PRIOR TO REINSTALLATION.

E. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION. CONTRACTOR SHALL REVIEW ALL ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK.

F. REMOVE ALL ABANDONED CONDUIT, UNLESS INDICATED TO REMAIN FOR RE-USE OR FUTURE WORK, INCLUDING ABANDONED CONDUIT EXPOSED DURING DEMOLITION AND LOCATED ABOVE ACCESSIBLE CEILINGS. CUT CONCEALED ABANDONED CONDUIT FLUSH WITH WALLS AND

FLOORS THAT ARE INDICATED TO REMAIN.

G. ALL ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS SHALL BE REMOVED COMPLETE BY THE ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. EQUIPMENT SHALL BE REMOVED COMPLETE WITH ALL ASSOCIATED BACK BOXES, CONDUIT, CIRCUITRY, ETC.

H. PROVIDE APPROPRIATE BLANK COVER FOR ABANDONED BOXES WHICH ARE NOT REMOVED.

I. DISCONNECT AND REMOVE LUMINAIRES COMPLETE INCLUDING BRACKETS, STEMS, HANGERS, AND OTHER ACCESSORIES AS INDICATED. COORDINATE EXTENT OF CEILING DEMOLITION WITH GENERAL CONTRACTOR, AND MECHANICAL CONTRACTOR.

J. NO EXISTING WIRING REMOVED SHALL BE REUSED. PROVIDE ALL NEW CONDUCTORS AS SPECIFIED AND INDICATED ON DRAWINGS.

K. CONDUIT AND BACK BOXES REMOVED DURING DEMOLITION THAT ARE IN GOOD CONDITION MAY BE REUSED. HOWEVER DISCRETION SHOULD BE USED AS THE ENGINEER SHALL MAKE FINAL DETERMINATION AS TO THE CONDITION OF THIS EQUIPMENT. ANY EQUIPMENT NOT DETERMINED

TO BE IN GOOD CONDITION AND REUSED SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE.

L. REPAIR ADJACENT CONSTRUCTION & FINISHES DAMAGED DURING DEMOLITION & EXTENSION WORK. PATCH SURFACES IN ACCORDANCE WITH 26 0500.

M. MAINTAIN ACCESS TO EXISTING ELECTRICAL INSTALLATIONS WHICH REMAIN ACTIVE. MODIFY INSTALLATION OR PROVIDE ACCESS DOOR UNIT AS APPROPRIATE.

N. WHERE WALLS, CEILINGS AND/OR FLOORS ARE TO BE REMOVED. REROUTE FEEDERS AND BRANCH CIRCUITS AS REQUIRED TO MAINTAIN CONTINUITY OF CIRCUITRY TO ALL ELECTRICAL EQUIPMENT NOT REMOVED.

O. EXTEND EXISTING INSTALLATIONS USING MATERIALS AND METHODS COMPATIBLE WITH EXISTING ELECTRICAL INSTALLATIONS, AS SPECIFIED AND IN COMPLIANCE WITH CURRENT CODES.

P. THESE DRAWINGS ARE A REPRESENTATION OF EXISTING CONDITIONS AND DO NOT NECESSARILY INDICATE ALL ELECTRICAL EQUIPMENT TO BE REMOVED OR TO REMAIN INTACT. IT IS THE ELECTRICAL CONTRACTORS RESPONSIBILITY TO EVALUATE ALL CONDITIONS AND PROVIDE

DEMOLITION IN ACCORDANCE WITH THE OWNER.

Q. SEE SPEC SECTION 26 0500.

GENERAL ELECTRICAL NOTES:

A. LABEL ALL RECEPTACLES PLATES AS DESCRIBED IN SPEC. SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS. INCLUDE LABELING ON BACK OF DEVICE PLATE W/ PERMANENT INK.

B. LABEL ALL ADDRESSABLE FIRE ALARM DEVICES AS DESCRIBED IN SPEC. SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS.

C. LABEL ALL PANELBOARDS AS DESCRIBED IN SPEC. SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS.

D. PROVIDE ARC FLASH LABELS AT ALL NEW EQUIPMENT PER SPEC. SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS.

E. RECEPTACLE CIRCUITING: PROVIDE A MINIMUM OF ONE 4" SQUARE 2-1/8" DEEP JUNCTION BOX AT THE ACCESSIBLE CEILING IN EACH ROOM.

F. CONDUIT FITTINGS SHALL BE STEEL WITH SET SCREWS AND INSULATED THROATS. USE WATERTIGHT FITTINGS IN WET LOCATIONS ONLY.

G. ALL DEVICES MOUNTED AT ACCESSIBLE CEILINGS SHALL BE CONNECTED FROM A JUNCTION BOX WITH FLEXIBLE METAL CONDUIT.

H. ALL FIRE ALARM CONDUIT SHALL BE RED.

I. MAKE CONNECTIONS TO VIBRATING EQUIPMENT (INCLUDING MOTORS) USING FLEXIBLE CONDUIT WITH STRANDED CONDUCTORS.

J. MULTI-WIRE BRANCH CIRCUITS SHALL NOT BE ACCEPTABLE. PULL DEDICATED NEUTRAL CONDUCTOR IDENTIFIED WITH TRACER WIRE, COLOR TO MATCH PHASE CONDUCTOR.

K. NEUTRAL CONDUCTOR SIZE SHALL MATCH PHASE CONDUCTORS.

L. PROVIDE GROUND CONDUCTOR IN ALL FEEDERS & BRANCH CIRCUITS. SEE SPEC. SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS.

M. COLOR OF SWITCH LEG CONDUCTORS SHALL MATCH PHASE CONDUCTORS AND BE IDENTIFIED WITH COLORED TAPE. THREE AND FOUR WAY SWITCH "TRAVELERS" SHALL BE PINK OR PURPLE.

N. DO NOT INSTALL FLUSH MOUNTING BOX BACK-TO-BACK IN WALLS; PROVIDE MINIMUM 6 INCHES SEPARATION. PROVIDE MINIMUM 24 INCHES SEPARATION IN ACOUSTIC RATED WALLS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:4

P

M

E-000

ELECTRICAL ABBREVIATIONS AND

SYMBOLS

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.NELSON T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

ELECTRICAL SHEET INDEX

E-000 ELECTRICAL ABBREVIATIONS AND SYMBOLS

ED101 B400 - LEVEL 1 - ELECTRICAL DEMOLITION PLAN

ED102 B400 - LEVEL 2 - ELECTRICAL DEMOLITION PLAN

ED103-407 B407 - LEVEL 3 - ELECTRICAL DEMOLITION PLAN

EF101 B400 - LEVEL 1 - FIRE ALARM DEMOLITION PLAN

EF102 B400 - LEVEL 2 - FIRE ALARM DEMOLITION PLAN

EF103-407 B407 - LEVEL 3 - FIRE ALARM DEMOLITION PLAN

EL101 B400 - LEVEL 1 - LIGHTING PLAN

EL102 B400 - LEVEL 2 - LIGHTING PLAN

EL103-407 B407 - LEVEL 3 - LIGHTING PLAN

EL111 B400 - LEVEL 1 - LIGHTING CALCS

EL112 B400 - LEVEL 2 - LIGHTING CALCS

EL113-407 B407 - LEVEL 3 - LIGHTING CALCS

EP101 B400 - LEVEL 1 - POWER PLAN

EP102 B400 - LEVEL 2 - POWER PLAN

EP103-407 B407 - LEVEL 3 - POWER PLAN

EY101 B400 - LEVEL 1 - SPECIAL SYSTEMS PLAN

EY102 B400 - LEVEL 2 - SPECIAL SYSTEMS PLAN

EY103-407 B407 - LEVEL 3 - SPECIAL SYSTEMS PLAN

EF201 B400 - LEVEL 1 - FIRE ALARM PLAN

EF202 B400 - LEVEL 2 - FIRE ALARM PLAN

EF203-407 B407 - LEVEL 3 - FIRE ALARM PLAN

E-501 ELECTRICAL DETAILS

E-601 B400 ELECTRICAL DIAGRAMS

E-602 B400 ELECTRICAL DIAGRAMS

E-700 ELECTRICAL SCHEDULES

TELECOMMUNICATIONS

ROOMS

286443 TELECOMMUNICATIONS ROOMS 1043, 4010E, AND 3060 1) HAVE NO

GROUNDING FROM IT EQUIPMENT TO BUILDING GROUND, INSTALL

BONDING STRAPS ON IT RACKS, TELEPHONE CABLING HOUSINGS,

AND CABLE TRAYS SUCH THAT THEY ARE GROUNDED TO BUILDING

GROUND.

TELECOMMUNICATIONS

ROOMS

286442 TELECOMMUNICATIONS ROOM 2060 1) HAVE NO GROUNDING FROM

IT EQUIPMENT TO BUILDING GROUND, INSTALL BONDING STRAPS

ON IT RACKS, TELEPHONE CABLING HOUSINGS, AND CABLE TRAYS

SUCH THAT THEY ARE GROUNDED TO BUILDING GROUND. 2) HAVE

ABANDONED CABLING; REMOVE ABANDONED CABLING TO COMPLY

WITH CODE.

TELECOMMUNICATIONS

ROOMS

286441 ALL OF THE TELECOMMUNICATIONS ROOMS ARE TOO SMALL,

EXPAND ROOMS OR RELOCATE TO LOCATIONS THAT CONFORM TO

REQUIREMENTS OUTLINED IN VA SPACE PLANNING CRITERIA

CHAPTER 232 AND OIT DESIGN GUIDE SECTION 4 - 84.

INFORMATION

TECHNOLOGY

REC

NO

DESCRIPTION

SECONDARY DIST. 295171 CORRECT DEFICIENCIES FROM EATON STUDIES REPORT

COMPLETED IN SEPTEMBER 2012. EATON REPORT HAS

RECOMMENDED NEW SETTINGS FOR ADJUSTABLE LOW VOLTAGE

TRIP AND THERMAL MAGNETIC CIRCUIT BREAKERS IN ORDER TO

IMPROVE PROTECTION FOR PERSONNEL AND EQUIPMENT. FOR

DETAIL, REFER TO TABLE 4.4 - TCC PLOTS, PAGES 4-49 TO 4-58.

FIRE ALARM 111163 NEW FIRE ALARM PANEL AND DEVICES WERE INSTALLED IN 1999.

WIRING ON THE 1ST AND 2ND FLOORS HAS EXCEEDED ITS LIFE

EXPECTANCY AND SHOULD BE REPLACED.

PENDING TOTALS: NEW AIR HANDLER SERVING THE LAB AREA IS NOT BACKED UP ON

EMERGENCY POWER AS REQUIRED BY NFPA AND VA

REQUIREMENTS. RE-ROUTE FEEDER FROM NORMAL PANEL TO

EQUIPMENT-BRANCH PANEL.

ELECTRICAL REC

NO

DESCRIPTION

BUILDING 400 FCA REPORT

DISCLAIMER: THESE ITEMS HAVE BEEN DETERMINED TO HAVE REACHED THEIR END OF LIFE

USEFULNESS. THIS SCOPE OF WORK CONTRACT DID NOT ALLOCATE FUNDING FOR THE BELOW

MENTIONED DEFICIENCIES. THE FOLLOWING INFORMATION WAS RECEIVED FROM THE OWNER'S...

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

CCTV

C C

T V

J

NCP

XXX

C C

T V

J C

XX

C C

TV

J

B

J

J

J

E

S

S

S

S

S S

S

S

S

S S

S

S

S S

S

S

S

S

S

S

SS

S

S

S

S S N

N

N

N

N

N

N N N

N

N

N

S

N

N

N

S

N

N

N

N

N

N

N

N

A A

AA

N

N

N

N

N

S

SS

C

S

SM

S

1 2 3 4 5 6 6.1 7 7.8 8 9 9.1 9.9 10 11 11.2 12 13 14 18171615

M.3

M

L

K.3

K

J.4

J.3

J

I.5

I.2

I

H.1

H

G

F.1

F

E

D

C

B

A

ICE

INTERCOMM

PANIC

NC PB

SCL

E C

B -L

S

E C

B -E

Q

ECB-CR

REMOTE

GENERATOR PANEL

DP-CR(480)

DP-CR(208)

T-CR

ATS(208)CR

ATS-LS

ATS(480)CR

T-EQ

DP-208-EQ

ATS-EQ

MSB(208)

LOAD CENTER NP-3-1

CP-4-1

NP-2-1

CP-2-1

CP-3-1

ELEVATOR PANEL

NVP-1

MDP(480)

WIREWAY

PULLBOX PULLBOX

EX NP-1-1

EX CP-6-1EX NP-1-1

EX LS-2-1

EX CP 6-11

EX EF-4

EX EF-2

DATA RACKS

EX EF-3

EX OHD

EX

CIRC

PUMP

EX AHU

EX

EXHAUST

FAN

EX DO (E)UH

EX LS-1-1

EX CP-5-1

EX NP-4-1

EX CP-7-1

EX CP-1-1

EX DP-480-EQ

EXAM

1027 EXAM

EXAM

OFFICE

OFFICE

OFFICE

OFFICE

EXAM

OFFICE

OFFICE

DIRTY

UTILTIY

OFFICE

WAITING

NURSE STATION

OFFICE

1011 EXAM

CONFERENCE

EXAM

EXAM

EXAM

OFFICE

OFFICE

WOMEN VISITOR TOILET

TLT

MECH

IT

OFFICE

1033 OFFICE

1035 OFFICE

EXAM

STAIR

WAITING / CIRCULATION

EXAM

EXAM

EXAM

NURSE STATION

EXAM

EXAM

WOMEN TLT

EXAM

EXAM

OFFICE

STORAGE

1096A

STAFF TOILET

STAFF

TOILET

AMBULANCE GARAGE

IT

1051B

ELECT

1051A

CLEAN STORAGE

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

B400 KEY PLAN

AREA B

AREA

A1

AREA C

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:3

A

M

ED101

B400 - LEVEL 1 - ELECTRICAL

DEMOLITION PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

SCALE: 1/8" = 1'-0"

B400 LEVEL 1 FLOOR PLAN - ELECTRICAL DEMOLITION

A. REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT, BRANCH CIRCUITS

AND FEEDERS IN THEIR ENTIRETY BACK TO THEIR POINT OF ORIGIN UNLESS

OTHERWISE INDICATED. TURN OFF AND LABEL CIRCUIT BREAKERS AS

SPARES FOR NEW WORK.

B. QUANTITY AND LOCATION OF DEVICES SHOWN ON PLANS ARE

APPROXIMATE. FIELD VERIFY DEVICES AND LOCATIONS.

C. PROTECT EXISTING-TO-REMAIN CEILING, FLOORS, WALLS AND PANELS.

D. SELECT DEMOLITION MAY BE REQUIRED FOR NEW CONSTRUCTION AND MAY

NOT BE DELINEATED ON THIS DRAWING. CAREFULLY COORDINATE

DEMOLITION WITH NEW CONSTRUCTION (PARTITION AND REFLECTED

CEILING) PLANS TO VERIFY ACTUAL EXTENT OF DEMOLITION.

E. EXAMINE THE DRAWINGS OF OTHER TRADES AND BE FAMILIAR WITH THE

DEMOLITION REQUIRED BY OTHER TRADES. PERFORM INCIDENTAL

ELECTRICAL DEMOLITION WORK AND/OR RELOCATION REQUIRED TO

FACILITATE THE DEMOLITION WORK OF OTHER TRADES, WHETHER OR NOT

SPECIFICALLY INDICATED

F. RECYCLE OR DISPOSE MATERIALS OFF SITE AND INCLUDE ALL COSTS IN

BID. HANDLE ALL MATERIALS IN ACCORDANCE WITH LEED REQUIREMENTS,

ALL FEDERAL, STATE, AND LOCAL REGULATIONS,

G. PROVIDE BLANK COVER PLATES WHERE DEVICES ARE REMOVED BUT

EXISTING WALLS REMAIN INTACT.

H. WHERE EXISTING BUILDING SERVICES AND/OR EQUIPMENT THAT IS TO

REMAIN IN USE ARE REQUIRED TO BE SHUT DOWN COORDINATE WITH THE

OWNER'S REPRESENTATIVE. , INCLUDE ALL ASSOCIATED OVERTIME COSTS

TO PERFORM THIS WORK DURING WEEKENDS AND EVENINGS. INCLUDE ALL

COSTS FOR PROVIDING TEMPORARY POWER WHERE SHUT DOWN MUST

OCCUR FOR PERIODS LONGER THAN THESE HOURS. COORDINATE

ELECTRICAL SHUT DOWNS WITH THE OWNER ONE WEEK PRIOR TO SHUT

DOWN.

I. PROVIDE NEW TYPED DIRECTORIES FOR PANELS AFFECTED BY THIS

ALTERATION.

J. REMOVE ELECTRICAL EQUIPMENT INDICATED WITH HEAVY WEIGHT DASHED

LINES OR INDICATED WITH KEYNOTES.

K. PROVIDE CODE-COMPLIANT SUPPORT TO EXISTING-TO-REMAIN

UNSUPPORTED CONDUITS AND BOXES WHERE CEILINGS ARE TO BE

REMOVED. RE-ROUTE BRANCH CIRCUITS AND RELOCATE JUNCTION BOXES

AS REQUIRED TO FACILITATE INSTALLATION OF NEW EQUIPMENT AND

SYSTEMS IN CEILING SPACES.

L. MAINTAIN ELECTRICAL SERVICE TO LIGHTING FIXTURES AND DEVICES THAT

ARE TO REMAIN. EXTEND CONDUIT AND WIRE AS REQUIRED WHERE

DEMOLITION WORK AFFECTS ELECTRICAL SERVICE TO DOWNSTREAM

DEVICES THAT ARE TO REMAIN.

M. COORDINATE DEMOLITION AND NEW WORK AS TO NOT REMOVE SYSTEMS,

DEVICES, AND/OR ACCESSORIES NECESSARY FOR AREAS IN LATER

PHASES.

1 EXISTING DOOR ACCESS PANEL FOR URGENT CARE

AND AMBULANCE BAY SHALL BE DISCONNECTED AND

STORED DURING DEMOLITION FOR REINSTALLATION.

2 EXISTING UNDERCABINET LIGHTING TO BE

DEMOLISHED.

3 REMOVE PANELBOARD AND FEEDER TO BELOW

FLOOR, EXISTING FEEDER TO REMAIN AND TO BE

EXTENDED TO NEW LOCATION.

4 REMOVE EXISTING DATA RACK AND ASSOCIATED

DATA CABLES. EXISTING DATA JACKS TO REMAIN

SHALL BE REFED FROM THE MDF.

5 DISCONNECT POWER TO EQUIPMENT BEING

REMOVED, RETAIN BRANCH CIRCUIT FOR USE IN NEW

WORK.

6 DISCONNECT POWER TO EQUIPMENT BEING

REMOVED. REMOVE WIRING BACK TO SOURCE,

REMOVE ACCESSIBLE CONDUIT.

7 EXISTING EXTERIOR WALL PACK SHALL BE

DEMOLISHED. PRESERVE EXISTING WIRING AND

CONTROL CONNECTIONS FOR REROUTING TO NEW

EXTERIOR WALL PACK LOCATION.

8 EXISTING BOGEN GS150D PA AMPLIFIER.

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

Checked

A.NELSON

SS

S S

S

S S

J

A

B

J

SS

S

SS

J

S S

S

SS

J

S

C

S

S

S

S S

J

S

S

1 2 3 4 5 6 6.1 7 7.8 8 9 9.1 9.9 10 11 11.2 12 13 14 18171615

M.3

M

L

K.3

K

J.4

J.3

J

I.5

I.2

I

H.1

H

G

F.1

F

E

D

C

B

A

EX CP-6-2.1

EX CP-6-2

EX 4 CP-2-2

EX CP-2-2 EX CP-1-2

EX NP-1-2

EX LS1-2

EX NC

EX WAP

OFFICE

UNOCCUPIED

CLEAN UTILITY

ELEC.

LAB

MECHANICAL

OFFICE

2015A

TOILET, STAFF

2030A

UTILITY ROOM, SOILED

TOILET

LOCKER ROOM

LAB

TREATMENT ROOM

EXAM/

TREATMENT

ROOM

EXAM/ TREATMENT ROOM

TREATMENT ROOM

EXAM/TREATMENT ROOM

TREATMENT ROOM

STAIR

S9

TELE

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

B400 KEY PLAN

AREA B

AREA

A1

AREA C

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:3

A

M

ED102

B400 - LEVEL 2 - ELECTRICAL

DEMOLITION PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

SCALE: 1/8" = 1'-0"

B400 LEVEL 2 FLOOR PLAN - ELECTRICAL DEMOLITION

A. REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT, BRANCH CIRCUITS

AND FEEDERS IN THEIR ENTIRETY BACK TO THEIR POINT OF ORIGIN UNLESS

OTHERWISE INDICATED. TURN OFF AND LABEL CIRCUIT BREAKERS AS

SPARES FOR NEW WORK.

B. QUANTITY AND LOCATION OF DEVICES SHOWN ON PLANS ARE

APPROXIMATE. FIELD VERIFY DEVICES AND LOCATIONS.

C. PROTECT EXISTING-TO-REMAIN CEILING, FLOORS, WALLS AND PANELS.

D. SELECT DEMOLITION MAY BE REQUIRED FOR NEW CONSTRUCTION AND MAY

NOT BE DELINEATED ON THIS DRAWING. CAREFULLY COORDINATE

DEMOLITION WITH NEW CONSTRUCTION (PARTITION AND REFLECTED

CEILING) PLANS TO VERIFY ACTUAL EXTENT OF DEMOLITION.

E. EXAMINE THE DRAWINGS OF OTHER TRADES AND BE FAMILIAR WITH THE

DEMOLITION REQUIRED BY OTHER TRADES. PERFORM INCIDENTAL

ELECTRICAL DEMOLITION WORK AND/OR RELOCATION REQUIRED TO

FACILITATE THE DEMOLITION WORK OF OTHER TRADES, WHETHER OR NOT

SPECIFICALLY INDICATED

F. RECYCLE OR DISPOSE MATERIALS OFF SITE AND INCLUDE ALL COSTS IN

BID. HANDLE ALL MATERIALS IN ACCORDANCE WITH LEED REQUIREMENTS,

ALL FEDERAL, STATE, AND LOCAL REGULATIONS,

G. PROVIDE BLANK COVER PLATES WHERE DEVICES ARE REMOVED BUT

EXISTING WALLS REMAIN INTACT.

H. WHERE EXISTING BUILDING SERVICES AND/OR EQUIPMENT THAT IS TO

REMAIN IN USE ARE REQUIRED TO BE SHUT DOWN COORDINATE WITH THE

OWNER'S REPRESENTATIVE. , INCLUDE ALL ASSOCIATED OVERTIME COSTS

TO PERFORM THIS WORK DURING WEEKENDS AND EVENINGS. INCLUDE ALL

COSTS FOR PROVIDING TEMPORARY POWER WHERE SHUT DOWN MUST

OCCUR FOR PERIODS LONGER THAN THESE HOURS. COORDINATE

ELECTRICAL SHUT DOWNS WITH THE OWNER ONE WEEK PRIOR TO SHUT

DOWN.

I. PROVIDE NEW TYPED DIRECTORIES FOR PANELS AFFECTED BY THIS

ALTERATION.

J. REMOVE ELECTRICAL EQUIPMENT INDICATED WITH HEAVY WEIGHT DASHED

LINES OR INDICATED WITH KEYNOTES.

K. PROVIDE CODE-COMPLIANT SUPPORT TO EXISTING-TO-REMAIN

UNSUPPORTED CONDUITS AND BOXES WHERE CEILINGS ARE TO BE

REMOVED. RE-ROUTE BRANCH CIRCUITS AND RELOCATE JUNCTION BOXES

AS REQUIRED TO FACILITATE INSTALLATION OF NEW EQUIPMENT AND

SYSTEMS IN CEILING SPACES.

L. MAINTAIN ELECTRICAL SERVICE TO LIGHTING FIXTURES AND DEVICES THAT

ARE TO REMAIN. EXTEND CONDUIT AND WIRE AS REQUIRED WHERE

DEMOLITION WORK AFFECTS ELECTRICAL SERVICE TO DOWNSTREAM

DEVICES THAT ARE TO REMAIN.

1 EXISTING AIR COMPRESSOR TO REMAIN.

2 DISCONNECTED AIR DRYER TO REMAIN.

3 EXISTING AIR HANDLING UNIT TO REMAIN.

4 EXISTING DATA RACK FEEDING SECOND FLOOR.

ADJUST EXISTING PATCH PANEL MOUNTING AS

REQUIRED TO ALLOW FOR NEW PATCH PANELS.

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

J J

J J

J J

J

J

N

N

J

S

VUV-2790

VUV-2776

EX BLANK

EX BLANK EX BLANK

NP2-3

LS-2-3

CP2-3

407.A

407.B1

407.C1

407.D1

407.E

407.F

407.G1

407.H

407.I

407.J

407.K

407.L

407.M

407.N

407.14407.11 407.12.1407.12

407.9407.7

407.41407.4407.3407.21

J.39

J.40

J.41

407.H2

407.H1

407.13.1

EX CP3-3

EX CP1-3

EX LS1-3

EX NP1-3

EX 407 DATA RACK

OPEN OFFICE

ELECTRICAL

DATA CLOSET

3772A

OPEN OFFICE

MECH / ELEC

RESTROOM

RESTROOM

DEDUCT ALT 1:

REMOVE WORK

ASSOCIATED WITH

B407 NORTH.

DEDUCT ALT 2:

REMOVE WORK

ASSOCIATED WITH

B407 SOUTH.

DEDUCT ALT 2:

REMOVE WORK

ASSOCIATED WITH

B407 SOUTH.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

B407 KEY PLAN

AREA A

KEY PLAN

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:3

A

M

ED103-407

B407 - LEVEL 3 - ELECTRICAL

DEMOLITION PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

SCALE: 1/8" = 1'-0"

B407 LEVEL 3 FLOOR PLAN - ELECTRICAL DEMOLITION

A. REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT, BRANCH CIRCUITS

AND FEEDERS IN THEIR ENTIRETY BACK TO THEIR POINT OF ORIGIN UNLESS

OTHERWISE INDICATED. TURN OFF AND LABEL CIRCUIT BREAKERS AS

SPARES FOR NEW WORK.

B. QUANTITY AND LOCATION OF DEVICES SHOWN ON PLANS ARE

APPROXIMATE. FIELD VERIFY DEVICES AND LOCATIONS.

C. PROTECT EXISTING-TO-REMAIN CEILING, FLOORS, WALLS AND PANELS.

D. SELECT DEMOLITION MAY BE REQUIRED FOR NEW CONSTRUCTION AND MAY

NOT BE DELINEATED ON THIS DRAWING. CAREFULLY COORDINATE

DEMOLITION WITH NEW CONSTRUCTION (PARTITION AND REFLECTED

CEILING) PLANS TO VERIFY ACTUAL EXTENT OF DEMOLITION.

E. EXAMINE THE DRAWINGS OF OTHER TRADES AND BE FAMILIAR WITH THE

DEMOLITION REQUIRED BY OTHER TRADES. PERFORM INCIDENTAL

ELECTRICAL DEMOLITION WORK AND/OR RELOCATION REQUIRED TO

FACILITATE THE DEMOLITION WORK OF OTHER TRADES, WHETHER OR NOT

SPECIFICALLY INDICATED

F. RECYCLE OR DISPOSE MATERIALS OFF SITE AND INCLUDE ALL COSTS IN

BID. HANDLE ALL MATERIALS IN ACCORDANCE WITH LEED REQUIREMENTS,

ALL FEDERAL, STATE, AND LOCAL REGULATIONS,

G. PROVIDE BLANK COVER PLATES WHERE DEVICES ARE REMOVED BUT

EXISTING WALLS REMAIN INTACT.

H. WHERE EXISTING BUILDING SERVICES AND/OR EQUIPMENT THAT IS TO

REMAIN IN USE ARE REQUIRED TO BE SHUT DOWN COORDINATE WITH THE

OWNER'S REPRESENTATIVE. , INCLUDE ALL ASSOCIATED OVERTIME COSTS

TO PERFORM THIS WORK DURING WEEKENDS AND EVENINGS. INCLUDE ALL

COSTS FOR PROVIDING TEMPORARY POWER WHERE SHUT DOWN MUST

OCCUR FOR PERIODS LONGER THAN THESE HOURS. COORDINATE

ELECTRICAL SHUT DOWNS WITH THE OWNER ONE WEEK PRIOR TO SHUT

DOWN.

I. PROVIDE NEW TYPED DIRECTORIES FOR PANELS AFFECTED BY THIS

ALTERATION.

J. REMOVE ELECTRICAL EQUIPMENT INDICATED WITH HEAVY WEIGHT DASHED

LINES OR INDICATED WITH KEYNOTES.

K. PROVIDE CODE-COMPLIANT SUPPORT TO EXISTING-TO-REMAIN

UNSUPPORTED CONDUITS AND BOXES WHERE CEILINGS ARE TO BE

REMOVED. RE-ROUTE BRANCH CIRCUITS AND RELOCATE JUNCTION BOXES

AS REQUIRED TO FACILITATE INSTALLATION OF NEW EQUIPMENT AND

SYSTEMS IN CEILING SPACES.

L. MAINTAIN ELECTRICAL SERVICE TO LIGHTING FIXTURES AND DEVICES THAT

ARE TO REMAIN. EXTEND CONDUIT AND WIRE AS REQUIRED WHERE

DEMOLITION WORK AFFECTS ELECTRICAL SERVICE TO DOWNSTREAM

DEVICES THAT ARE TO REMAIN.

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

D

D

S

D

D

S

D

S

D

D

D

D

S D

S

S

D

S

D

D

D

DD

D

S

D

D

D

D

S

D

D

D

J

J

S

U

S

S

D

D

D

D

D

D

LC

LC

D

D

D

D

D

D D

D

D

D

D

D

D

D

D D

D

D

D D

A. ALIGN DEVICES VERTICALLY WHERE LIGHTING, POWER, AND SYSTEM

DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE INDICATED CLOSE TO

OTHER DEVICES.

B. REFER TO THE ARCHITECTURAL ELEVATION, DETAIL, AND REFLECTED

CEILING PLAN DRAWINGS FOR COORDINATION OF ELECTRICAL DEVICES.

C. CUTTING, DRILLING, AND/OR BORING THROUGH STRUCTURAL MEMBERS IS

NOT ACCEPTABLE.

D. PROVIDE FIRE RATED SEALS ON PENETRATIONS IN FIRE RATED FLOORS

AND WALLS. COORDINATE RATED LOCATIONS WITH LIFE SAFETY CODE

PLAN DRAWINGS.

E. PROVIDE INSULATED BUSHINGS FOR ROUGH-IN AND CONDUIT SLEEVE

LOCATIONS PRIOR TO INSTALLATION OF ANY CABLING.

F. BRANCH CIRCUITS CONDUCTOR LENGTHS FROM PANEL LONGER THAN 100’

FOR 120V AND 200' FOR 277V SHALL BE #10 OR LARGER FOR ENTIRE

LENGTH OF CIRCUIT FOR LINE, NEUTRAL, AND GROUND WIRES.

G. PROVIDE DEDICATED NEUTRAL FOR EACH MULTIWIRE BRANCH CIRCUIT

PHASE CONDUCTOR. PROVIDE DEDICATED NEUTRAL FOR EACH DIMMING

CIRCUIT.

H. DEVICES IN FINISHED AREAS ARE TO BE RECESSED WITHIN WALLS EXCEPT

WHERE REQUIRED TO BE SURFACE MOUNTED. IN UNFINISHED AREAS

(PLUMBING CHASES, JANITORS CLOSETS, ELECTRICAL ROOMS, AND

MECHANICAL ROOMS) DEVICES AND CONDUIT MAY BE SURFACE MOUNTED.

I. LIGHT SWITCHES SHALL BE MOUNTED ON LATCH SIDE OF DOOR, WITHIN 12"

OF DOOR/SIDELIGHT FRAMING, UNLESS NOTED OTHERWISE. LIGHT

SWITCHES INSTALLED ADJACENT TO DOOR SWINGS SHALL BE MOUNTED

CLEAR OF DOOR SWING AND WITHIN 12" OF DOOR IN OPEN POSITION.

COORDINATE LOCATION WITH OTHER WALL DEVICES.

J. COORDINATE LUMINAIRE LOCATIONS WITH STRUCTURAL AND MECHANICAL

TRADES PRIOR TO INSTALLATION. COORDINATE MOUNTING HEIGHTS AND

LOCATIONS OF LUMINAIRES IN MECHANICAL ROOMS WITH DUCTS, PIPES,

AND EQUIPMENT. MOUNT LUMINAIRES BELOW DUCTS AND PIPES AND AVOID

MOUNTING LUMINAIRES OVER EQUIPMENT. SUPPORT LUMINAIRES

INDEPENDENTLY OF DUCTS, PIPES, AND EQUIPMENT.

K. VERIFY OCCUPANCY SENSOR DEVICE LAYOUT AND QUANTITIES FOR

COMPLETE AREA/ROOM COVERAGE WITH SENSOR MANUFACTURER PRIOR

TO ROUGH-IN.

L. COORDINATE CEILING TYPES, RECESS CONDITIONS, AND MOUNTING

HARDWARE REQUIRED PRIOR TO PURCHASE OF LUMINAIRES.

M. WIRING SHALL NOT FEED THROUGH FIXTURES EXCEPT TO SERVE

CONTINUOUS ROWS OF SIMILAR TYPE OF LUMINAIRES.

N. FOR EXISTING PANELS, CIRCUIT NUMBERS ARE FOR REFERENCE ONLY.

COORDINATE EXISTING PANEL CONFIGURATION. UTILIZE EXISTING DEMOED

CIRCUITS FEEDING THIS AREA. PROVIDE NEW, UPDATED, TYPED PANEL

INDEX FOR MODIFIED PANELS. UNUSED CIRCUIT BREAKERS SHALL BE

LISTED AS SPARE.

O. COORDINATE DEMOLITION AND NEW WORK AS TO NOT REMOVE SYSTEMS,

DEVICES, AND/OR ACCESSORIES NECESSARY FOR AREAS IN LATER

PHASES.

P. PROVIDE NON-METALLIC SURFACE RACEWAY FOR DEVICES MOUNTED ON

EXISTING SOLID WALLS. EXPOSED/SURFACE CONDUIT IS NOT ALLOWED.

1 2 3 4 5 6 6.1 7 7.8 8 9 9.1 9.9 10 11 11.2 12 13 14 18171615

M.3

M

L

K.3

K

J.4

J.3

J

I.5

I.2

I

H.1

H

G

F.1

F

E

D

C

B

A

LIGHTING CONTROL ZONE

LIGHTING CONTROL ZONE

LIGHTING CONTROL ZONE

LIGHTING CONTROL ZONE

CONF

CONSULT ROOM 2

CONSULT ROOM 1

CLEAN UTILITY

EXAM 10

CHAIR EXAM

1085b

EXAM 6

1083 ANTE ROOM

1108A

OFFICE

EXAM 8

ALCOVE

WHEELCHAIR ALCOVE

EQ. ALCOVE

EXAM 13 / CONSULT RM 3

EXAM 2

TEAM

WORK

STATIONS

WAITING

1032B

TEAM AREA

1101A

TEAM AREA

1086A

PATIENT TLT

TLT

1022B

STAFF TLT

1019B

MECH

STAFF

TOILET

1100B

BARIATRIC/

WOMENS

HEALTH

TLT

TLT

1104B

TLT/SHWR

EXAM 2 - NEGATIVE PRESS

1104A

MEDS

EXAM 4

EXAM 5 BARIATRIC/ WOMENS HEALTH

1100A

RECEPT CHECK IN/OUT

1032A

WEIGH AREA

MEDS

CORRIDOR

OC11

EXAM 12

FAMILY TLT

NURSE

MANAGER

OFFICE

OFFICE

CLEAN

SUPPLY

EXAM 7

SOILED UTILITY / SPD

CORRIDOR

OC13

EXAM 1

TLT

1108C

LOGISTICS STORAGE

AMBULANCE BAY

TELEHEALTH

TRIAGE

RECEPTION

1080C

TELEHEALTH

STOR

EXAM 7

CLEAN UTLITY

VESTIBULE

EXAM 9

STAFF LOUNGE

EXAM 1- NEGATIVE PRESS

1108B

WAITING

CORRIDOR

OC20

SOILED UTILITY

1099A

MENTAL

HEALTH

CORRIDOR

OC21

CORRIDOR

OC19

CORRIDOR

OC22

HALLWAY

OC14

EXAM 8

EXAM 11

LACTATION

IT

1051B

ELECT

1051A

HAC

LC-11

LC-10

LC-10

LC-5

LC-10

LC-9

LC-9

LC-6

LC-4

LC-9

LC-10

LC-10

LC-7

LC-8LC-8

LC-3

LC-3

LC-3

LC-3

LC-3

LC-3

LC-10

LC-5

LC-9

LC-10

LC-2

LC-5

LC-6

LC-10

LC-3

LC-11

LC-4

LC-5

LC-10

LC-5

LC-6

LC-10

LC-3

LC-5

LC-11

LC-9

LC-1

LC-11

LC-9

LC-10

LC-4

LC-10

LC-1

LC-6

LC-5

LC-9

LC-6

LC-6

LC-6

LC-2

LC-10

LC-10

LC-9

LC-5

EX ECB-EQ

EX REMOTE

GENERATOR PANEL

EX ATS-LS

EX ATS(480)CR

EX ATS-EQEX DP-LS

EX ATS(208)CR EX DP-LQ

EX DP-CR(480)

EX T-CR

EX DP-CR(208)

EX DP-208-EQ

EX T-EQ

EX ECB-LS

EX ECB-CR

EX LOAD CENTER

EX NP-3-1

EX MSB(208)

EX CP-3-1

EX ELEVATOR

PANEL

EX NVP-1

EX MDP(480)

EX CP-2-1

EX NP-2-1

EX CP-4-1

EX DP-480-EQ

EX CP-6-1 EX NP-1-1

EX LS-2-1

B1

B1

B1

B1

B1B1B1

A1

A1

B1 B1

A1

C1

B1

A1 A3

B1

A1 A1

A1

A1

B1 B1

A1

B1

A3

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

E1

E1

A1 A1

B1 B1

B1

B1

B1 B1

B1

A3

A1

A1

A3

A1

A3

B1

B1 B1

B1

A1

A3

A3

A1

A1

A1

B1 B1 B1 B1

B1 B1 B1

B1

D1

D1

D1

A1

A3

A1

A3

A1

A3

A3

A1

A1

A1

A2 A4

A1

B1B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1 B1

B1B1

B1 B1

B1

B1

A2 A4

A1

A3

A1

B1

A1

A1 A3

A3

A1

A1 A3

A3

D1

DP

DP

F1

F1

F1

H1

B1

D1

DT

D1

B1

B1

D1

D1

D2

D2

D2

B1 B1 z1 z1 z1

D1 D1

D1

B1

E1

E1

E1

D2

A1

A3

E1

E1

E2

B1

D1 D1

D1

E1

H1 H1

A5

A5

B2 B2

D2

D2

A5

DT

CP-8-1-36

CP-8-1-36

CP-8-1-36

CP-8-1-36

CP-8-1-34

CP-8-1-34 CP-8-1-34

CP-8-1-34

CP-8-1-34

CP-8-1-34

CP-8-1-34

CP-8-1-34 LS-2-1-1

CP-8-1-34CP-8-1-34CP-8-1-34

CP-8-1-34

CP-8-1-34

CP-8-1-34

CP-8-1-34

CP-8-1-34

CP-8-1-35

CP-8-1-35 CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-35

CP-8-1-37CP-8-1-37 LS-2-1-1

LS-2-1-1

LS-2-1-1

LS-2-1-1

LS-2-1-1

LS-2-1-1

LS-2-1-1

LS-2-1-1

LS-2-1-1

LS-2-1-1

LS-2-1-1

CP-8-1-37

LS-2-1-1

CP-8-1-37 CP-8-1-37

CP-8-1-37

CP-8-1-37

CP-8-1-37

CP-8-1-37

CP-8-1-37

CP-8-1-37

CP-8-1-37

LS-2-1-3

LS-2-1-3

LS-2-1-3

LS-2-1-3

LS-2-1-3

LS-2-1-3

LS-2-1-3

LS-2-1-3

LS-2-1-3

LS-2-1-3

CP-1-1-40

CP-1-1-40 CP-1-1-40

CP-1-1-40

CP-1-1-40

CP-1-1-40

CP-1-1-40

CP-1-1-40

CP-1-1-40

CP-1-1-40

CP-1-1-40

CP-1-1-40 CP-1-1-40

CP-1-1-40

CP-1-1-40 CP-1-1-40

CP-1-1-40 CP-1-1-40

CP-1-1-40CP-1-1-40

CP-1-1-40CP-1-1-40

CP-1-1-40

CP-1-1-40

CP-1-1-40CP-1-1-40

CP-1-1-40 CP-1-1-40

CP-1-1-40CP-1-1-40

LS-2-1-3

LS-2-1-3

CP-1-1-41

CP-1-1-41

CP-1-1-41 CP-1-1-41

CP-1-1-41

CP-1-1-41CP-1-1-41

CP-1-1-41 CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-42

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-41

CP-1-1-42

CP-1-1-42

CP-1-1-42CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

LS-2-1-3

CP-1-1-42 CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

CP-1-1-42

NL

NL

NL

NL

NL

NL

NL

NL

NL

NL

NL

NL

NL

NL

SL SL

SL SL

SL SL

CP-8-1-37

CP-8-1-37

CP-8-1-37 CP-8-1-37

CP-8-1-37

CP-8-1-37

b b ba a a

NL

a b

H1

CP-1-1-42

B2

CP-1-1-42

D2

CP-1-1-40

S1

CP-1-1-40

LC-5

S1

CP-1-1-40

S1

CP-1-1-40

CP-1-1

LC-2

S1

CP-1-1-42

S1

CP-8-1-35

LC-5

S1

CP-8-1-35

S1

CP-8-1-35

CP-8-1 NP-5-1

EX CP-5-1

CP-8-1-37

S2

CP-8-1-34

S1

CP-8-1-34

EX

EX

EX

EX

NP-1-1

A5

CP-8-1-34

LC-3

1099B

TLT

MENTAL

HEALTH

D2

CP-8-1-34

D1

CP-8-1-35

A3

A3

CP-8-1-34

CP-8-1-34

z2 z2 z2 z2 z2

CP-8-1-37

z3

F1

F1

CP-8-1-37

CP-8-1-37

z3 z3

C1

CP-8-1-34

EX NP-4-1

EX CP-7-1

E2

LS-2-1-1

LS-1-1

NL

E1

LS-2-1-1

DEDUCT

ALTERNATE #5:

EXTERIOR

EXTRANCE CANOPY.

z1 z2 z3 z1 z1 z1 z1z1z3 z3 z3 z2 z2 z2 z2 z2 z2 z2 z2z2 z2 z2

D1

LS-2-1-3

NL

ALTERNATE #5: REMOVE EXTERIOR ENTRANCE CANOPY

AT STAFF LOUNGE 1100.

A. PROVIDE CONNECTIONS FROM LIGHTING CIRCUITING

ROUGH-INS TO INTEGRAL CANOPY LIGHTING.

Z1

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

B400 KEY PLAN

AREA B

AREA

A1

AREA C

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:1

A

M

EL101

B400 - LEVEL 1 - LIGHTING PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

1 COORDINATE MOUNTING OF LUMINAIRES WITH

MECHANICAL DUCTWORK AND EQUIPMENT IN THIS

SPACE.

2 PROVIDE POWER AND CONTROLS ROUGH-IN TO

CANOPY UNDER BASE BID. EXTEND EXISTING

EXTERIOR LIGHTING CIRCUIT TO CANOPY ROUGH-IN

LOCATION. COORDINATE CONNECTION WITH CANOPY

INSTALLER.

3 PROVIDE 3-WAY DIMMER SWITCH FOR LOCAL

OVERRIDE OF LIGHTING CONTROL ZONE.

4 PROVIDE ROOM CONTROLLER EQUAL TO STEINEL DCS

CONTROLLER. ROOM CONTROLLER SHALL BE

PROGRAMMED WITH OWNER'S BAS DUSK-TO-DAWN

TIME SETTINGS. LOCAL PIR OCCUPANCY SENSORS

AND DIMMER WALL STATIONS SHALL BE WIRED

THROUGH ROOM CONTROLLER.

5 EXTEND/REFEED EXISTING WIRING FROM

DEMOLISHED EXTERIOR WALL PACK TO NEW

EXTERIOR WALL PACK LOCATION. FIXTURE MOUNTED

IDEALLY 8'-0" TO CENTER OF ROUGH-IN. CONCEAL

CONDUIT AS MUCH AS POSSIBLE. COORDINATE

MOUNTING WITH OWNER.

SCALE: 1/8" = 1'-0"

B400 LEVEL 1 FLOOR PLAN - LIGHTING

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

D

D

D

D D

S

D

D

D

D S

D

DDD

D

D

D

LC

1 2 3 4 5 6 6.1 7 7.8 8 9 9.1 9.9 10 11 11.2 12 13 14 18171615

M.3

M

L

K.3

K

J.4

J.3

J

I.5

I.2

I

H.1

H

G

F.1

F

E

D

C

B

A

MECH

INFUSION ROOM

MECH

EXAM 1

CLEAN UTILITY - LOGISTICS

TLT

TEAM

WORK

AREA

MED EQUIPMENT STORAGE

EXAM 5

EXAM 3

EXAM 2

EXAM 4

CORRIDOR

OC22

CLEAN LINENS

SOILED UTILITY

A1

A3 A3

A1

B1

B1

B1

B1

B1

B1

B1

B1

A3

A1

A1

A3

B1

A1 A1

A3

A3

A1

D1 D1

B1

B1

B1 B1

B1

B1 B1

A1 A1

LIGHTING CONTROL ZONE

A3

E1 a b a a b b b

CP-1-2-17

CP-1-2-17CP-1-2-17

CP-1-2-17

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16 CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-16

CP-1-2-17

CP-1-2-16

LS1-2-1

LS1-2-1

LS1-2-1

LS1-2-1

LS1-2-1

CP-1-2-18

CP-1-2-18

CP-1-2-18

CP-1-2-18

B1

B1

CP-1-2-17

CP-1-2-17

NL

NL

NL

NL

d c b a a a d c b

B2

CP-1-2-18

EX

LC-7

LC-3

S1

CP-1-2-16LC-3

LC-10

LC-5

LC-10

LC-10

LC-9

LC-6

LC-9

LC-9

EX CP-2-2

EX CP-1-2

EX NP-1-2

EX CP-6-2.1

EX CP-6-2

EX 4 CP-2-2

SOILED

UTILITY

LC-5

A1

CP-1-2-18

LC-5

a,b,c,d

A. ALIGN DEVICES VERTICALLY WHERE LIGHTING, POWER, AND SYSTEM

DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE INDICATED CLOSE TO

OTHER DEVICES.

B. REFER TO THE ARCHITECTURAL ELEVATION, DETAIL, AND REFLECTED

CEILING PLAN DRAWINGS FOR COORDINATION OF ELECTRICAL DEVICES.

C. CUTTING, DRILLING, AND/OR BORING THROUGH STRUCTURAL MEMBERS IS

NOT ACCEPTABLE.

D. PROVIDE FIRE RATED SEALS ON PENETRATIONS IN FIRE RATED FLOORS

AND WALLS. COORDINATE RATED LOCATIONS WITH LIFE SAFETY CODE

PLAN DRAWINGS.

E. PROVIDE INSULATED BUSHINGS FOR ROUGH-IN AND CONDUIT SLEEVE

LOCATIONS PRIOR TO INSTALLATION OF ANY CABLING.

F. BRANCH CIRCUITS CONDUCTOR LENGTHS FROM PANEL LONGER THAN 100’

FOR 120V AND 200' FOR 277V SHALL BE #10 OR LARGER FOR ENTIRE

LENGTH OF CIRCUIT FOR LINE, NEUTRAL, AND GROUND WIRES.

G. PROVIDE DEDICATED NEUTRAL FOR EACH MULTIWIRE BRANCH CIRCUIT

PHASE CONDUCTOR. PROVIDE DEDICATED NEUTRAL FOR EACH DIMMING

CIRCUIT.

H. DEVICES IN FINISHED AREAS ARE TO BE RECESSED WITHIN WALLS EXCEPT

WHERE REQUIRED TO BE SURFACE MOUNTED. IN UNFINISHED AREAS

(PLUMBING CHASES, JANITORS CLOSETS, ELECTRICAL ROOMS, AND

MECHANICAL ROOMS) DEVICES AND CONDUIT MAY BE SURFACE MOUNTED.

I. LIGHT SWITCHES SHALL BE MOUNTED ON LATCH SIDE OF DOOR, WITHIN 12"

OF DOOR/SIDELIGHT FRAMING, UNLESS NOTED OTHERWISE. LIGHT

SWITCHES INSTALLED ADJACENT TO DOOR SWINGS SHALL BE MOUNTED

CLEAR OF DOOR SWING AND WITHIN 12" OF DOOR IN OPEN POSITION.

COORDINATE LOCATION WITH OTHER WALL DEVICES.

J. COORDINATE LUMINAIRE LOCATIONS WITH STRUCTURAL AND MECHANICAL

TRADES PRIOR TO INSTALLATION. COORDINATE MOUNTING HEIGHTS AND

LOCATIONS OF LUMINAIRES IN MECHANICAL ROOMS WITH DUCTS, PIPES,

AND EQUIPMENT. MOUNT LUMINAIRES BELOW DUCTS AND PIPES AND AVOID

MOUNTING LUMINAIRES OVER EQUIPMENT. SUPPORT LUMINAIRES

INDEPENDENTLY OF DUCTS, PIPES, AND EQUIPMENT.

K. VERIFY OCCUPANCY SENSOR DEVICE LAYOUT AND QUANTITIES FOR

COMPLETE AREA/ROOM COVERAGE WITH SENSOR MANUFACTURER PRIOR

TO ROUGH-IN.

L. COORDINATE CEILING TYPES, RECESS CONDITIONS, AND MOUNTING

HARDWARE REQUIRED PRIOR TO PURCHASE OF LUMINAIRES.

M. WIRING SHALL NOT FEED THROUGH FIXTURES EXCEPT TO SERVE

CONTINUOUS ROWS OF SIMILAR TYPE OF LUMINAIRES.

N. FOR EXISTING PANELS, CIRCUIT NUMBERS ARE FOR REFERENCE ONLY.

COORDINATE EXISTING PANEL CONFIGURATION. UTILIZE EXISTING DEMOED

CIRCUITS FEEDING THIS AREA. PROVIDE NEW, UPDATED, TYPED PANEL

INDEX FOR MODIFIED PANELS. UNUSED CIRCUIT BREAKERS SHALL BE

LISTED AS SPARE.

O. COORDINATE DEMOLITION AND NEW WORK AS TO NOT REMOVE SYSTEMS,

DEVICES, AND/OR ACCESSORIES NECESSARY FOR AREAS IN LATER

PHASES.

P. PROVIDE NON-METALLIC SURFACE RACEWAY FOR DEVICES MOUNTED ON

EXISTING SOLID WALLS. EXPOSED/SURFACE CONDUIT IS NOT ALLOWED.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

B400 KEY PLAN

AREA B

AREA

A1

AREA C

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:1

A

M

EL102

B400 - LEVEL 2 - LIGHTING PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

SCALE: 1/8" = 1'-0"

B400 LEVEL 2 FLOOR PLAN - LIGHTING

1 PROVIDE 3-WAY DIMMER SWITCH FOR LOCAL

OVERRIDE OF LIGHTING CONTROL ZONE.

2 PROVIDE ROOM CONTROLLER EQUAL TO STEINEL DCS

CONTROLLER. ROOM CONTROLLER SHALL BE

PROGRAMMED WITH OWNER'S BAS DUSK-TO-DAWN

TIME SETTINGS. LOCAL PIR OCCUPANCY SENSORS

AND DIMMER WALL STATIONS SHALL BE WIRED

THROUGH ROOM CONTROLLER.

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

DD

S

D

D

D

D

D

B2 B2

B1 B1

B2 B2

B2 B2

B2B2B2B2

B2 B2 B2 B2

B2 B2 B2 B2

A5 H1 H1

OFFICE

3790A

MECH / ELECT

3790C

OFFICE

3775B

OPEN OFFICE

OFFICE

3790B

BEDROOM

BEDROOM

MECHANICAL ROOM

3780A

MECH / ELEC

MECHANICAL ROOM

BEDROOM

MEDS

3711A

BEDROOM

STORAGE

DINING

3749A

BREAK

3765 BEDROOM

WARD

READING

BEDROOM

TREATMENT

CT CLINIC

TOILET

3744A

CLOSET

RESTROOM

RESTROOM

SHOWERS

3784A

DRESSING

DRESSING

SHOWERS

3715A

Room

DAY ROOM

TOILET

CLOSET

3750A

CORRIDOR

7C36

CORRIDOR

7C31

DATA CLOSET

3772A

ELECTRICAL

CORRIDOR

7C38

CORRIDOR

7C39

OFFICE

STAIR

S4

CORRIDOR

7C37

CORRIDOR

7C32

HAC

3736A

NURSES

BEDROOM

BEDROOM

READING

UTILITY

WARD

STAIR

S6

DINING

LOCKERS

WARD

BEDROOM

BEDROOM

CLEAN LINENS

Room

CLOSET

ELEVATOR LOBBY

7C35

ELEVATOR

CORRIDOR

CORRIDOR

7C33

BEDROOM

LAUNDRY

OPEN OFFICE

B1 B1 B2

H1 H1

B2 B2 B2 B2

B2B2B2B2

B2

B2 B2

B2 B2

B2 B2

B2

407.A

407.B1

407.C1

407.D1

407.E

407.F

407.G1

407.H

407.I

407.J

407.K

407.L

407.M

407.N

407.14407.11 407.12.1407.12

407.9407.7

407.41407.4407.3407.21

J.39

J.40

J.41

407.H2

407.H1

407.13.1

E1

B1 B1

E1

CP3-3-1 CP3-3-1 CP3-3-1 CP3-3-1

CP3-3-1CP3-3-1LS1-3-17CP3-3-1

CP3-3-1 CP3-3-1 CP3-3-1 CP3-3-1

CP3-3-1CP3-3-1CP3-3-1CP3-3-1

CP3-3-1 CP3-3-1

LS1-3-17 CP3-3-1 CP3-3-1

CP3-3-2CP3-3-2

CP3-3-2 CP3-3-2

CP3-3-2CP3-3-2

CP3-3-2

CP3-3-2

CP3-3-2 CP3-3-2 CP3-3-2 CP3-3-2

CP3-3-2CP3-3-2CP3-3-2CP3-3-2

CP3-3-2 CP3-3-2 CP3-3-2 CP3-3-2

CP3-3-2 CP3-3-2

CP3-3-2CP3-3-2

LS1-3-17

LS1-3-17

LS1-3-17

EX CP3-3

EX CP1-3

EX LS1-3

EX NP1-3

EX BLANK

EX BLANK EX BLANK

LC-11

LC-7

LC-11

LC-3

LC-7

LC-11 LC-3

EX LS-2-3

EX NP2-3

EX CP4-3

NL

NL

DEDUCT ALT 1:

REMOVE WORK

ASSOCIATED WITH

B407 NORTH.

DEDUCT ALT 2:

REMOVE WORK

ASSOCIATED WITH

B407 SOUTH.

DEDUCT ALT 2:

REMOVE WORK

ASSOCIATED WITH

B407 SOUTH.

A. ALIGN DEVICES VERTICALLY WHERE LIGHTING, POWER, AND SYSTEM

DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE INDICATED CLOSE TO

OTHER DEVICES.

B. REFER TO THE ARCHITECTURAL ELEVATION, DETAIL, AND REFLECTED

CEILING PLAN DRAWINGS FOR COORDINATION OF ELECTRICAL DEVICES.

C. CUTTING, DRILLING, AND/OR BORING THROUGH STRUCTURAL MEMBERS IS

NOT ACCEPTABLE.

D. PROVIDE FIRE RATED SEALS ON PENETRATIONS IN FIRE RATED FLOORS

AND WALLS. COORDINATE RATED LOCATIONS WITH LIFE SAFETY CODE

PLAN DRAWINGS.

E. PROVIDE INSULATED BUSHINGS FOR ROUGH-IN AND CONDUIT SLEEVE

LOCATIONS PRIOR TO INSTALLATION OF ANY CABLING.

F. BRANCH CIRCUITS CONDUCTOR LENGTHS FROM PANEL LONGER THAN 100’

FOR 120V AND 200' FOR 277V SHALL BE #10 OR LARGER FOR ENTIRE

LENGTH OF CIRCUIT FOR LINE, NEUTRAL, AND GROUND WIRES.

G. PROVIDE DEDICATED NEUTRAL FOR EACH MULTIWIRE BRANCH CIRCUIT

PHASE CONDUCTOR. PROVIDE DEDICATED NEUTRAL FOR EACH DIMMING

CIRCUIT.

H. DEVICES IN FINISHED AREAS ARE TO BE RECESSED WITHIN WALLS EXCEPT

WHERE REQUIRED TO BE SURFACE MOUNTED. IN UNFINISHED AREAS

(PLUMBING CHASES, JANITORS CLOSETS, ELECTRICAL ROOMS, AND

MECHANICAL ROOMS) DEVICES AND CONDUIT MAY BE SURFACE MOUNTED.

I. LIGHT SWITCHES SHALL BE MOUNTED ON LATCH SIDE OF DOOR, WITHIN 12"

OF DOOR/SIDELIGHT FRAMING, UNLESS NOTED OTHERWISE. LIGHT

SWITCHES INSTALLED ADJACENT…

This is the start of the file's text. The full file is on GovTribe.